Addressable Fire Alarm Control Panel

Model No: LF-6100A/1

Description
The LF-6100A/1 is a distributed intelligent fire alarm control
panel with a microprocessor based advanced detection and
protection system. With its flexibility, unique design and ability
to utilize both intelligent and conventional devices, makes it a
very reliable system for life safety use. It adopts the use of a
multi-line LCD screen for ease of viewing of events and controls,
RTOS (Real time operating system), for real time monitoring and
display of events, and a graphical display for user-friendly menu
and control operation as well as ease of identifying information
being sent by field devices to the fire alarm controller.

The LF-6100A/1 design widely applies to all kinds of industrial


and commercial constructions with its high resistance to humidi-
ty, wide operating temperature range, high reliability and ease of
installation and configuration.

Features With its user-friendly interface, the controller also adopts easy
• 1 Intelligent detection circuits to identify function switches and status LED's that even
• Closed loop design (Class A wiring) untrained operators can understand and properly respond to
• Microprocessor based system the event that occurred.
• Intelligent distributed system structure
• Quick response time - fire alarm in <1 second History recording is also an integral part of the system. All data
• Up to 127 devices per loop is stored inside the system's flash memory and can be viewed or
• Dynamic supervision printed at any time using the event browser, A stored history
• Fully field programmable event adopts the circular type storage wherein the oldest data
• 5" LCD Display - 320x240dpi resolution gets deleted in replacement of new incoming data when
• 21 key user-friendly control switches memory buffer is full. Maximum capacity of history memory is
• 15 LED status indicators approximated at 999 events.
• Menu driven functions
• RS485 communication for fire repeater display panel The controller can accommodate which is adequate enough for
• Laptop programing small to medium sized life safety applications. Each device has a
• 3 Level system password protection code that is to be set using the LF-DP-6190 device programmer.
• Logic controlled output functions
• Circular history event flash memory storage An auto-learn feature for devices is also present in the system.
• Data transfer speed and reliability The controller analyzes the environment on which the detection
• High performance at low cost devices are installed and adjust the detector's actuation level
• Well mount enclosures accordingly.
• Monitoring and reporting of fire events in up to 254 zones
• Duplicate Address detection It also utilizes a specialized loop circuit design, in which the
device's transmitted data is sorted out based on its priority. The
information with the highest priority would transfer first. Other
information from the field devices up to the controller shall be
processed accordingly which ensured a rapid and efficient
response of the system. Fire alarm from a field device is trans-
mitted in less than 1 second.
Wiring Details

24V KA2 Fire Voltage-Free Output Contact


24V DC Output (0.5A)
GND KA1 (30V DC, 5A)
T+ YA2
LOOP1 OUT

Fire Voltage-Free Output Contact


Loop Alarm Bus 1 Out
T- YA1 (30V DC, 5A)
T+ FB
LOOP1 IN

Loop Alarm Bus 1 In Repeater Panel RS485 Communication Line


T- FA
T+ MB
LOOP2 OUT

Not Use COMM Port


T- MA
T+ CL
LOOP2 IN

Not Use CAN Bus


T- CH
NAC+
Notification Alarm Current
NAC-

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.
Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] www.lifeco-uk.com 1
Addressable Fire Alarm Control Panel
Model No: LF-6100A/1

Technical Specifications

220V AC 50Hz/60Hz +10%-15%


Main Power Supply
(≤10WattConsumption)
Back-up Power Supply DC 24V,7AH(built-in)
Battery Maximum Output Current (Amps) 0.8 Amps
Operating Voltage (DC) 19v -26v DC (-2%)
Maximum Ripple Current (Peak-Peak) 400mV
Output Current Load (1 min) 10mA
Output Current Load (1 max a) 168mA
Output Current Load (1 max b) 536mA
Fuse Size, Rating and Locations See Annex C Fuse Replacement in user manual
Basic supervise capacity 1 loops, 127 addressable points per loop
≤10 seconds (single point continuous searching in
Polling cycle
abnormal situation)
Transmission distance ≤1000m (RVS-2×1.5mm2); ≤1500m (RVS-2×2.0mm2);
Line wiring method 2-wire bus
Alarm Bus Loop
Output Voltage 18V~26V
Max Current 87.5mA (Per Loop)
Transmission distance ≤1000m (RVS-2×1.5mm2);
Repeat panel
communication loop Output Signal RS485
(FA,FB)
Maximum Quantity ≤2 Repeater Panels
Transmission distance ≤2000m (RVS-2×1.5mm2);
FACPs communication
Output Signal CAN bus
loop (CH/CL)
Maximum Quantity ≤16 FACPs
Fire Alarm Output Output Voltage 19V~27V
(NAC+, NAC-) Max Current 50mA
Fire alarm output Contact Capacity 30VDC/5.0A, Voltage Free Contact
(KA1,KA2) In fire alarm state Contacts Closed in Fire Alarm Condition
Contact Capacity 30VDC/5.0A, Voltage Free Contact
Fault output (YA1,YA2)
In fault state Contacts Open in Fault Condition
Operation temperature 0℃~55℃
Working environment indoor use
Relative humidity ≤95%
Is able to store 999 records, including opening machine,
Memory Capacity close machine, reset, fire alarm, supervising, associated
operation and fault alarm).
Associated operation programmable number 100 pieces, including OR1, OR2 & AND logic.
1×127 addressable device positions each can have 20
Location conversion capacity English characters. A maximum of 254 zone positions
can be used each can have up to 20 English.

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.
Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] www.lifeco-uk.com 2
Addressable Fire Alarm Control Panel
Model No: LF-6100A/2

Description
The LF-6100A/2 is a distributed intelligent fire alarm control
panel with a microprocessor based advanced detection and
protection system. With its flexibility, unique design and ability
to utilize both intelligent and conventional devices, makes it a
very reliable system for life safety use. It adopts the use of a
multi-line LCD screen for ease of viewing of events and controls,
RTOS (Real time operating system), for real time monitoring and
display of events, and a graphical display for user-friendly menu
and control operation as well as ease of identifying information
being sent by field devices to the fire alarm controller.

The LF-6100A/2 design widely applies to all kinds of industrial


and commercial constructions with its high resistance to humidi-
ty, wide operating temperature range, high reliability and ease of
installation and configuration.

Features With its user-friendly interface, the controller also adopts easy
• 2 Intelligent detection circuits to identify function switches and status LED's that even
• Closed loop design (Class A wiring) untrained operators can understand and properly respond to
• Microprocessor based system the event that occurred
• Intelligent distributed system structure History recording is also an integral part of the system. All data
• Quick response time - fire alarm in <1 second is stored inside the system's flash memory and can be viewed or
• Up to 127 devices per loop printed at any time using the event browser, A stored history
• Dynamic supervision event adopts the circular type storage wherein the oldest data
• Fully field programmable gets deleted in replacement of new incoming data when
• 5" LCD Display - 320x240dpi resolution memory buffer is full. Maximum capacity of history memory is
• 21 key user-friendly control switches approximated at 999 events.
• 15 LED status indicators
• Menu driven functions The controller can accommodate which is adequate enough for
• RS485 communication for fire repeater display panel small to medium sized life safety applications. Each device has a
• Laptop programming code that is to be set using the LF-DP-6190 device programmer.
• 3 Level system password protection
• Logic controlled output functions An auto-learn feature for devices is also present in the system.
• Circular history event flash memory storage The controller analyses the environment on which the detection
• Data transfer speed and reliability devices are installed and adjust the detector's actuation level
• High performance at low cost accordingly.
• Well mount enclosures
• Monitoring and reporting of fire events in up to 254 zones It also utilizes a specialized loop circuit design, in which the
• Duplicate Address detection device's transmitted data is sorted out based on its priority. The
information with the highest priority would transfer first. Other
information from the field devices up to the controller shall be
processed accordingly which ensured a rapid and efficient
response of the system. Fire alarm from a field device is trans-
Wiring Details mitted in less than 1 second.

24V KA2 Fire Voltage-Free Output Contact


24V DC Output (0.5A)
GND KA1 (30V DC, 5A)
LOOP2 IN LOOP2 OUT LOOP1 IN LOOP1 OUT

T+ YA2 Fire Voltage-Free Output Contact


Loop Alarm Bus 1 Out
T- YA1 (30V DC, 5A)
T+ FB
Loop Alarm Bus 1 In Repeater Panel RS485 Communication Line
T- FA
T+ MB
Loop Alarm Bus 2 Out COMM Port
T- MA
T+ CL
Loop Alarm Bus 2 In CAN Bus
T- CH
NAC+
Notification Alarm Current
NAC-

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.
Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] www.lifeco-uk.com 1
Addressable Fire Alarm Control Panel
Model No: LF-6100A/2

Technical Specifications

220V AC 50Hz/60Hz +10%-15%


Main Power Supply
(≤10WattConsumption)
Back-up Power Supply DC 24V,7AH(built-in)
Battery Maximum Output Current (Amps) 0.8 Amps
Operating Voltage (DC) 19v -26v DC (-2%)
Maximum Ripple Current (Peak-Peak) 400mV
Output Current Load (1 min) 10mA
Output Current Load (1 max a) 217mA
Output Current Load (1 max b) 622mA
Fuse Size, Rating and Locations See Annex C Fuse Replacement in user manual
Basic supervise capacity 2 loops, 127 addressable points per loop
≤10 seconds (single point continuous searching in
Polling cycle
abnormal situation)
Transmission distance ≤1000m (RVS-2×1.5mm2); ≤1500m (RVS-2×2.0mm2);
Line wiring method 2-wire bus
Alarm Bus Loop
Output Voltage 18V~26V
Max Current 87.5mA (Per Loop)
Transmission distance ≤1000m (RVS-2×1.5mm2);
Repeat panel
communication loop Output Signal RS485
(FA,FB)
Maximum Quantity ≤2 Repeater Panels
Transmission distance ≤2000m (RVS-2×1.5mm2);
FACPs communication
Output Signal CAN bus
loop (CH/CL)
Maximum Quantity ≤16 FACPs
Fire Alarm Output Output Voltage 19V~27V
(NAC+, NAC-) Max Current 50mA
Fire alarm output Contact Capacity 30VDC/5.0A, Voltage Free Contact
(KA1,KA2) In fire alarm state Contacts Closed in Fire Alarm Condition
Contact Capacity 30VDC/5.0A, Voltage Free Contact
Fault output (YA1,YA2)
In fault state Contacts Open in Fault Condition
Operation temperature 0℃~55℃
Working environment indoor use
Relative humidity ≤95%
Is able to store 999 records, including opening machine,
Memory Capacity close machine, reset, fire alarm, supervising, associated
operation and fault alarm).
Associated operation programmable number 100 pieces, including OR1, OR2 & AND logic.
2×127 addressable device positions each can have 20
Location conversion capacity English characters. A maximum of 254 zone positions can
be used each can have up to 20 English characters.

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.
Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] www.lifeco-uk.com 2
Addressable Fire Alarm Control Panel
Model No: LF-6100A/4

Description
The LF-6100A/4 is a distributed intelligent fire alarm control
panel with a microprocessor based advanced detection and
protection system. With its flexibility, unique design and ability
to utilize both intelligent and conventional devices, makes it a
very reliable system for life safety use. It adopts the use of a
multi-line LCD screen for ease of viewing of events and controls,
RTOS (Real time operating system), for real time monitoring and
display of events, and a graphical display for user-friendly menu
and control operation as well as ease of identifying information
being sent by field devices to the fire alarm controller.

The LF-6100A/4 design widely applies to all kinds of industrial


and commercial constructions with its high resistance to humidi-
ty, wide operating temperature range, high reliability and ease of
installation and configuration. With its user-friendly interface,
the controller also adopts easy to indentify function switches
Features and status LED's that even untrained operators can understand
• 4 Intelligent detection circuits and properly respond to the event that occurred.
• Closed loop design (Class A wiring)
• Microprocessor based system History recording is also an integral part of the system. All data
• Intelligent distributed system structure is stored inside the system's flash memory and can be viewed or
• Quick response time - fire alarm in <1 second printed at any time using the event browser, A stored history
• Up to 127 devices per loop event adopts the circular type storage wherein the oldest data
• Dynamic supervision gets deleted in replacement of new incoming data when
• Fully field programmable memory buffer is full. Maximum capacity of history memory is
• 5" LCD Display - 320x240dpi resolution approximated at 999 events.
• 21 key user-friendly control switches
• 15 LED status indicators The controller can accommodate which is adequate enough for
• Menu driven functions small to medium sized life safety applications. Each device has a
• RS485 communication for fire repeater display panel code that is to be set using the LF-DP-6190 device programmer.
• Laptop programming
• 3 Level system password protection An auto-learn feature for devices is also present in the system.
• Logic controlled output functions The controller analyzes the environment on which the detection
• Circular history event flash memory storage devices are installed and adjust the detector's actuation level
• Data transfer speed and reliability accordingly.
• High performance at low cost
• Well mount enclosures It also utlizes a specialized loop circuit design, in which the
• Monitoring and reporting of fire events in up to 254 zones device's transmitted data is sorted out based on its priority. The
• Duplicate Address detection information with the highest priority would transfer first. Other
information from the field devices up to the controller shall be
processed accordingly which ensured a rapid and efficient
response of the system. Fire alarm from a field device is trans-
Dimension Details mitted in less than 1 second.

24V KA2 Fire Voltage-Free Output Contact T+


LOOP3 OUT

24V DC Output (0.5A) Loop Alarm Bus 3 Out


GND KA1 (30V DC, 5A)
T-
LOOP1 OUT

T+ YA2 Fire Voltage-Free Output Contact T+


Loop Alarm Bus 1 Out
LOOP3 IN

T- YA1 (30V DC, 5A) Loop Alarm Bus 3 In


T-
T+ FB
LOOP1 IN

Loop Alarm Bus 1 In Repeater Panel RS485 Communication Line


T- FA T+
LOOP4 OUT

Loop Alarm Bus 4 Out


T+ MB T-
LOOP2 OUT

Loop Alarm Bus 2 Out COMM Port


T- MA T+
LOOP4 IN

Loop Alarm Bus 4 In


T+ CL T-
LOOP2 IN

Loop Alarm Bus 2 In CAN Bus


T- CH
NAC+
Notification Alarm Current
NAC-

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.
Unit 8, Calibre Industrial Park, Laches Close, Four Ashes, Wolverhampton, WV10 7DZ, United Kingdom T +44 1902 798 706 F +44 1902 798 679 E [email protected] www.lifeco-uk.com 1
Addressable Fire Alarm Control Panel
Model No: LF-6100A/4

Technical Specifications

220V AC 50Hz/60Hz +10%-15%


Main Power Supply
(≤10WattConsumption)
Back-up Power Supply DC 24V,12AH(built-in)
Battery Charge Voltage 27.3v DC ±0.3V
Operating Voltage (DC) 19v -26v DC (-2%)
Maximum Ripple Current (Peak-Peak) 400mV
Output Current Load (1 min) 10mA
Output Current Load (1 max a) 388mA
Output Current Load (1 max b) 904mA
Fuse Size, Rating and Locations See Annex C Fuse Replacement in user manual
Basic supervise capacity 4 loops, 127 addressable points per loop
≤10 seconds (single point continuous searching in
Polling cycle
abnormal situation)
Transmission distance ≤1000m (RVS-2×1.5mm2); ≤1500m (RVS-2×2.0mm2);
Line wiring method 2-wire bus
Alarm Bus Loop
Output Voltage 18V~26V
Max Current 87.5mA (Per Loop)
Transmission distance ≤1000m (RVS-2×1.5mm2);
Repeat panel
communication loop Output Signal RS485
(FA,FB)
Maximum Quantity ≤2 Repeater Panels
Transmission distance ≤2000m (RVS-2×1.5mm2);
FACPs communication
Output Signal CAN bus
loop (CH/CL)
Maximum Quantity ≤16 FACPs
Fire Alarm Output Output Voltage 19V~27V
(NAC+, NAC-) Max Current 50mA
Fire alarm output Contact Capacity 30VDC/5.0A, Voltage Free Contact
(KA1,KA2) In fire alarm state Contacts Closed in Fire Alarm Condition
Contact Capacity 30VDC/5.0A, Voltage Free Contact
Fault output (YA1,YA2)
In fault state Contacts Open in Fault Condition
Operation temperature 0℃~55℃
Working environment indoor use
Relative humidity ≤95%
Is able to store 999 records, including opening machine,
Memory Capacity close machine, reset, fire alarm, supervising, associated
operation and fault alarm).
Associated operation programmable number 100 pieces, including OR1, OR2 & AND logic.
4×127 addressable device positions each can have 20
Location conversion capacity English characters. A maximum of 254 zone positions can
be used each can have up to 20 English characters.

In line with our policy of continuous product improvement LIFECO reserves the right to modify specifications without prior notice.