Fluid Kinetic Energy As A Selection Criteria For Control Valves
Fluid Kinetic Energy As A Selection Criteria For Control Valves
Fluid Kinetic Energy As A Selection Criteria For Control Valves
Nomentclature
Ao Valve Throttling Area, in2 or m2
c Fluid Sonic Velocity, ft/s or m/s
KE Fluid Kinetic Energy, psi or Kpa
M1 Units Conversion Factor, Table 1
M2 Units Conversion Factor, Table 1
Vo Fluid Velocity at Trim Throttling Area, ft/s or m/s
w Mass Flow Rate, lb/h or kg/s
ro Fluid Density at Trim Exit, lb/ft3 or kg/m3
Introduction
For many years the traditional method of sizing and selecting control valves has been to
select a valve that contains the design pressure and temperature and meets the maximum
capacity requirements. In addition to meeting capacity requirements and serving as a pressure
boundary vessel, the valve should perform its intended control function, have long internals
(trim) life, provide good shut-off and be relatively maintenance free. There is a need for
guidelines to evaluate if a valve and its trim will provide this type of service.
This paper presents a criteria for selecting a valve design capable of eliminating problems.
The guideline imposes limits on the kinetic energy of the fluid exiting from the valve trim.
The criteria applies to all linear motion valve types. Each type of valve is capable of meeting
the kinetic energy criteria for many of the flow conditions that have been dictated by tradition
and experience.
Butterfly and Ball valves usually meet the proposed criteria for kinetic energy. The pressure
drop across these valves is not large enough to accelerate the flow to a high velocity level.
Thus, a much lower value of energy is realized.
Examples are given in which measurements have been made on problem valves and the same
measurements made after the valve has been retrofitted with a different trim that limits the
kinetic energy exiting from the valve trim. The measurements that are reported are vibration
measurements that quantify the effect of the change in the valve trim. The vibration of the
valve and the piping system is a strong indicator of valve integrity. It is a direct result of the
energy levels in the fluid passing through the valve. As such, it is an indicator of the ability of
the valve to provide good control with long life and low maintenance costs.
Valve designs have ranges for the amount of pressure drop (energy) that they can effectively
absorb. For example, low pressure drops are handled by butterfly valves. As the pressure
drop level increases, a ball valve would be needed. Still larger pressure drops would require
the linear motion globe/angle type valves. The globe/angle designs incorporate many
different valve trims depending upon the level of pressure drop starting with a simple plug
that opens an orifice. The next range of pressure drops would require a ported cage to help
guide the plug and contain the energy dissipation. For the largest pressure drops, a tortuous
path trim design is needed. For different valve and trim selections, the acceptable pressure
drop ranges overlap. In general, the cost of the selected valve increases with the valve's
ability to handle higher pressure drops. Manufacturers have developed designs to extend the
pressure drop ranges in order to serve the market with the lowest first cost equipment. This
extension of ranges usually is achieved by harder materials that may tolerate the resulting
cavitation, erosion, vibration and noise levels.
Driskell (1983) in his chapter titled “Velocity, Vibration, and Noise” discusses the reasons
why velocity should be controlled. Excessive velocity causes all of the destructive effects that
result in a poor valve application. He notes that velocity induced vibration and noise are “...a
blessing in disguise in that they are a warning of impending failure.” Driskell does not
discuss where in the valve the velocity needs to be controlled. Unfortunately, when velocity
guidelines have been translated to control valve selection they have been interpreted as the
velocity exiting the valve body. By the time the fluid is ready to exit the valve body, the
influence of “high energy” has already been imprinted into the fluid stream. For example, the
fluid velocity exiting the trim may have created high velocity, erosive jets, areas of low
pressure with resulting flashing and cavitation damage and noisy shock waves. Velocities
should be controlled at the trim outlet, not the valve outlet.
The valve industry has in some cases defined velocity through the trim as a design guideline.
These are presented in Ho (1995), Kowalski, et al. (1996), Laing, et al. (1995), Miller (1993,
1996), Stratton and Minoofar (1995) and are used as a basis for the presentation of the criteria
discussed in this paper. Schafbush (1993) argues for emphasis on the driving force, pressure
drop, instead of the results of the driving force (velocity and kinetic energy) as the selection
criteria. Just looking at the pressure drop or fluid velocity at the trim exit ignores the density
of the fluid, which is an important parameter in accessing potential problems. A guideline
based on the kinetic energy exiting the valve trim involves the driving force, pressure drop,
the resultant velocity and the fluid density. Many years of experience in applying this criteria
have indicated it is a reliable indicator that is not overly conservative and is applicable to all
valve designs.
Figure 1 shows the throttle area for various kinds of valve trim. For a top guided globe valve,
the trim outlet flow area is the annulus area between the plug and seat. In a cage guided
valve, the trim outlet flow area is the exposed area of the windows in the cage. For a multi-
path cage, the trim outlet flow area is the total area of all the exposed flow paths. For multi-
stage trims, the flow area from stage to stage must not increase too rapidly or else the
throttling will take place across the first stages and the later stages will be ineffective, see
Figure 1(e).
In a valve, the disk or plug moves to increase or decrease the area through which flow can
pass. For a given set of conditions, a fixed area of the trim is open to flow. Under any
significant pressure drop conditions, this area will be considerably less than the inlet or outlet
area of the valve. As a result, the fluid passing this point will have much higher velocities and
kinetic energy levels than in other valve locations. The only way to increase this flow area
without increasing the flow rate, is to increase the resistance of the throttling flow path. The
flow conditions define how far the valve is open and the valve’s trim design (flow path
resistance) defines how much flow area exists at the trim outlet. Once this area is defined, the
continuity equation can be used to calculate the velocity of the fluid at the outlet of the trim.
(1)
Figure 1. Throttling exit area (Ao ) examples for typical valve trim designs
The fluid density and velocity are used to establish the fluid’s kinetic energy.
(2)
For gas or steam, the fluid velocity at the trim outlet may be sonic. If it is, the density of the
fluid at the trim outlet must be higher than the outlet density, ro, in order to pass the given
mass flow rate, w. This higher density can be estimated using Equation 1 by substituting the
fluid’s sonic velocity, c, for the outlet velocity, Vo, and solving for density. Then, this density
and sonic velocity are used in Equation 2 to find the kinetic energy.
M w ro Ao Vo KE
M 2
4636.8 - lb/ft3 - ft/s psi
Velocity criteria for liquids are much lower than for gases because liquid densities are much
higher, resulting in higher energy levels. While the velocity limits are quite different, the
kinetic energy limits are very close to the same.
Table 2 shows criteria for a valve trim’s outlet kinetic energy. The valve trim should be
selected to keep the kinetic energy below these levels. The examples that follow support the
values shown in the table.
ft/
psi KPa m/s
sec
Continuous
Service, Single 70 480 100 30
Phase Fluids
Cavitating and
Multi-phase 40 275 75 23
Fluid Outlet
Vibration
Sensitive 11 75 40 12
System
For most conditions, an acceptance criteria of 70 psi (480 KPa) for the trim outlet kinetic
energy will lead to a trouble free valve. In some applications, where the service is intermittent
(the valve is closed more than 95% of the time) and the fluid is clean (no cavitation, flashing
or entrained solids), the acceptance criteria can be increased, but should never be higher than
150 psi (1030 KPa).
In flashing service, liquid droplets are carried by their vapor at much higher velocities. To
eliminate the risk of erosion, the acceptance criteria for flashing or potentially cavitating
service should be lowered to 40 psi (275 KPa). The same criteria exists for liquids carrying
entrained solids.
Special applications may require even more stringent kinetic energy criteria. For example,
pressure letdown valves used in pump test loops must be vibration free so that proper
evaluation of the pump can be made. These valves are designed with trims that reduce the
kinetic energy to less than 11 psi (75 KPa). Gas or steam valves with very low noise
requirements may also result in extra low trim outlet kinetic energy requirements.
Retrofit Examples
Table 3 shows a summary of the service conditions, before and after trim style, and the
corresponding kinetic energy levels for four valve designs retrofitted with multi-stage trim.
Each of these valves was retrofitted because the original valve trim was not allowing good
control or there were limitations in the valve’s use due to excessive vibration. In some cases,
the valves would cause the system to trip. After repeated attempts to fix the problems and the
plant’s need for working valves, the valves were retrofitted with trim designed to reduce the
kinetic energy at the trim outlet. The only change made to the valves was to change the
internal valve trim and hence, the trim outlet kinetic energy. No changes were made to the
valve bodies. Since the bodies were not changed, the fluid velocities exiting the valve bodies
were the same before and after the retrofit. In all cases, significant improvements in valve
performance were achieved by retrofitting the trim to meet the suggested kinetic energy
design criteria.
Example Number
Units 1 2 3 4
Application Residual Feedwater Core Spray Steam Dump
Heat Regulator
Removal
Quantity 4 2 4 1
Fluid Water Water Water Steam
MM
Flow Rate lb/hr 4.5 560 4.4 550 2.2 280 1.8 230
kg/s
psia
Inlet Pressure 155 1070 1546 10660 295 2030 740 5100
KPaa
Inlet Temperature F C 100 38 440 227 110 43 511 266
psia
Outlet Pressure 35 240 972 6700 15 100 334 2300
KPaa
Capacity, Cvreq’d/Cvtotal 820 / 830 400 / 780 290 / 300 1400 / 1432
Valve Size 14” x 14” 12” x 12” 8” x 8” 18” x 18”
Valve Inlet/Outlet psi 5.5 / 5.5 38 /
3 / 3 20 / 20 5 / 5 34 / 34 6.4 / 14 44 / 97
Kinetic Energy KPa 38
Plug Size 12” 9.5” 5.5” 14”
3 Concentric
Original Trim Top Guided Drilled Hole Top Guided
Drilled Hole
Type Plug Cage Plug
Cages
Original Trim
psi
Outlet Kinetic 148 1020 380 2630 290 2020 83 570
KPa
Energy
4 and 2 10, 6 and 4 4 and 2
New Trim/Cage 8 Stages
Stages Stgs Stages
New Trim Outlet psi 13 - 24 88 - 17 - 61 118 - 30 - 57 204 -
25 172
Kinetic Energy KPa 168 420 390
For examples 1 and 3, the water outlet pressures were close enough to the water’s vapor
pressure to suggest cavitation and two phase flow conditions may exist. Therefore, the
acceptance criteria for the trim outlet kinetic energy was the more stringent 40 psi (275 KPa)
value for the pressure conditions that could result in vaporization.
The valves were originally top guided, Figure 1(a) control valves without a cage. The valves
were retrofit with a tortuous path trim such as shown in Figure 1(g). The kinetic energy on
the top guided version is calculated in the annulus area created between the plug and the seat
ring. The kinetic energy for the retrofitted trim is at the outlets of each of the disks forming
the cage.
A typical reduction of the vibration velocity is shown on Figure 2. The accelerometer that
resulted in this maximum output was located on the actuator and measured a direction that
was rotational around the centerline of the pipeline. Vibration velocity for the five
accelerometers located on each of four valves showed reductions in value that ranged from 49
to 91 percent with even larger reductions occurring on piping components in the system.
The retrofitted valves were able to pass full design flow rates without the accompanying
cavitation. All concerns regarding the potential of piping fatigue as a result of the vibration
were eliminated.
The original trim started out as a cage guided trim and was later changed to a drilled hole
cage in one of many attempts to salvage the valve design. The retrofit used a tortuous path
trim, Figure 1(g), that absorbs the fluid energy inside the trim and has an acceptable exit
kinetic energy. The throttling points in the original trim are the cage orifices, Figure 1(b), and
the small holes in the drilled hole cage, Figure 1(c), tried later.
The vibration velocity results are shown in Figure 3. The reductions in the vibration are quite
dramatic because the vibration levels are not very high to begin with. The comparison of
results is made with the drilled hole cage trim as results did not exist with the original cage
trim. The reductions resulted in at least a 40 percent reduction in the velocity at the piping
frequency of 10 Hertz and essentially an elimination of the vibration at the higher
frequencies. Displacement measurements showed reductions of 53 percent and acceleration
measurements showed an 86 percent reduction.
All of the problems of vibration, plant trips, and broken stems were resolved by the lower
kinetic energy levels at the trim exit. The plant was started up and power escalated to full
load for the first time on automatic control as was intended from the inception of the plant
design.
Another change in the system was made in this application. When the retrofitted trim was
installed, downstream restricting orifices were removed. Thus, the valve pressure drop was
increased to a value equivalent to the original trim and the orifice. This represents a more
severe set of conditions for the retrofit trim in controlling any destructive affects due to the
higher potential energy that would be converted to kinetic energy across the trim.
The downstream piping system vibration measurements were the most significant changes
recorded between the pre and post retrofitted valves. These measurements showed that the
pipe displacement dropped from 64 to 92 percent. Pre-retrofit values of displacement were
0.090 inches (2.3 mm) or greater and the largest displacement after the retrofit was 0.020
inches (0.51 mm).
The root cause of the system vibration was cavitation. The post retrofit vibration levels were
minor and eliminated any concern regarding the piping system stresses and potential for
damage due to fatigue.
The valve instrumented was a steam valve with a flow to open trim consisting of three
concentric cages with drilled holes in each cage. The cages were tightly touching so that there
was no axial flow between the cages. Each cage was
slightly offset to create a tortuous path for the pressure letdown. This type of trim is shown in
Figure 1(f). The throttling area is the flow area caused by the restriction of the last two cages.
The outlet area of the last cage is not the throttling area because there is little pressure
letdown associated with the expansion from the overlap orifice. The expansion is too large to
have much influence and the jet from the overlap area is the dominate kinetic energy source
exiting the trim.
The values reported in this case were a sum of the vibration velocity peaks in the 0 to 500
Hertz range. The results are shown in Figure 4 where the vibration velocity magnitude is
plotted as a function of the valve stroke. Values are not available beyond 65 percent of stroke
for the original trim as the valve was not operated in this region because of the severity of the
vibration.
The reduced trim exit kinetic energy solved the severe vibration problems associated with
this steam system.
Other Examples
All of the examples presented above happen to be installed in nuclear plants. However, these
are typical control valve applications and are representative of the many applications in
different industries that have been experienced. In the past 20 years, over 150 valves ranging
in size from 2" to 24" x 36" have been retrofitted to achieve the kinetic energy criteria
identified above.
Applications
Table 4 is a partial list of applications involved. All of these retrofits arose as a result of a
problem with the original installation. In all of the cases, the retrofits were successful in
resolving the root cause of the valve problem and the only significant change was the limiting
of the fluid kinetic energy exiting the valve trim.
Conclusions
A criteria for the selection of a control valve has been provided which goes beyond the many
rules and exceptions being used in the industry. The criteria is a limit on the kinetic energy
exiting from the valve trim, defined as the throttling point of the trim. It addresses the energy
that contributes to the problems associated with valves. The combination of fluid velocity and
density cause:
Using the kinetic energy criteria, which has many years of application experience, will
eliminate valve problems. It will provide the user with a means to evaluate the different types
of valve designs that look as though they will meet the system needs.
The first step is to select the valves that can meet the capacity requirements. Then the valve
types are sorted to select the correct valve by using the kinetic energy levels. This will assure
the engineer that the lowest cost system is installed.
Acknowledgements
We wish to thank the utilities that shared their vibration measurements so that the retrofitted
valve benefits could be quantified. Dr. S. V. Sherikar is also acknowledged for his arranging,
collection and analyzing the Example 2 data.
References
ANSI/ISA S75.01-1985, Flow Equations for Sizing Control Valves, Instrument Society of
America, Research Triangle Park, NC.
Arnold, J. R., Miller, H. L., Katz, R. E. , 1996, “Multi-stage Valve Trim Retrofits Eliminate
Damaging Vibration,” Power - Gen 96 International, Orlando, Dec. 4 - 6, Penn Well
Conferences and Exhibitions, Houston, Book IV pp. 102 - 119.
Driskell, L. R. , 1983, Control Valve Selection and Sizing, Instrument Society of America,
Research Triangle Park, NC.
Kowalski, R. A., Mueller, T. J., Ng, K. C., Miller, H. L., 1996, “Black Point Gas Pipeline
Storage Pressure Letdown Control Valves,” ASME International Pipeline Conference, June 9
- 14, Calgary, Alberta Canada.
Ho, T. R., 1995, “DragÔ Valves give Kuosheng a 24 MW Boost,” Nuclear Engineering
International, January.
ISA Handbook of Control Valves, 1976, 2d ed., Hutchinson, J. W., Editor, Instrument
Society of America, Research Triangle Park, NC, pp 180-220.
Laing, D. E., Miller, H. L., McCaskill, J. W., 1995, “Redesigned Recycle Valves Abate
Compressor Vibration,” Oil and Gas Journal, June 5.
Miller, H. L. , 1993, “Controlling Valve Fluid Velocity,” Intech, Volume 40, Number 5, pp
32-34, Instrument Society of America, Research Triangle Park, NC.
Miller, H. L. , 1996, “Tortuous Path Control Valves for Vibration and Noise Control,” ASME
- API Energy Week Conference and Exhibition, Jan 29 - Feb. 2, Houston.
Parker, Q., Avery, K. J., Miller, H. L., Sterud, C. G., 1994, “Retrofitting Feedwater Valves at
North Anna Reduces Vibration and Improves Control,” Power Engineering, November, pp.
69 - 71.
Schafbush, P., 1993, “Take Account of Pressure Control to Avoid Control Valve Cavitation,”
Power, August, pp. 55-57.
Stratton, L. R. and Minoofar, D., 1995, “Specifying Control Valves for Severe Service
Applications,” Instrumentation & Control Systems (I&CS), October.