JSV-FF200 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Cat No.

FF200 Vol.1

Think Safety!

Total Safety Solution Provider!


JOKWANG
Pressure Relief Valves
for V & UV Stamp

JOKWANG
JSV-FF200
Total Safety Solution Provider!

Cat No. FF200


JOKWANG

Vol.1

JOKWANG I.L.I. CO.,LTD.


HEAD OFFICE & FACTORY
No.37, Sanmakgongdan buk10-gil, Yangsan-si, Gyeongsangnam-do(Zip Code : 50567)
Tel : +82-55-360-0200 Fax : +82-55-360-0260 E-mail : [email protected]
Copyright ⓒ 2016 by JOKWANG I.L.I. CO., LTD. All rights reserved@1209 www.jokwang.co.kr
INTRODUCTION OF COMPANY COMPANY HISTORY
Nov. 1968 Founded JOKWANG Industries Company in Busan, Korea
May. 1987 Acquired K.S(Korean Industrial Standard) Mark
Apr. 1989 Acquired Type approval from KR(Korea)
Since its establishment in 1968, JOKWANG I.L.I CO., LTD. with its JK trademark has put every Dec. 1992 Technical Collaboration with VENN in Japan
Dec. 1998 Acquired ISO 9001 Certificate
Dec. 1999 Changed Company name to JOKWANG I.L.I Co., Ltd.
Its devotion has concentrated especially in the area of safety & relief valve, pressure reducing Oct. 2000 Moved to Noksan Industrial Complex in Busan, Korea
valve, stop valve and steam trap. Nov. 2003 Acquired Type approval from DNV(Norway)
Mar. 2004 Acquired Type approval from BV(France)
With almost half a century of experience, we have earned over a good reputation for quality, Apr. 2004 Acquired KEPIC Certificate
reliability, reasonable price and excellent performance. Jun. 2004 Acquired Type approval from LR(UK)
May. 2006 Acquired Safety Relief Valve ASME "UV" Stamp
We determined to contribute to serve your need for your heat control and energy saving Nov. 2006 Patent registered for Pilot-Operated Safety Valve
May. 2010 Acquired Type approval from GL(Germany)
Apr. 2011 Acquired Safety Relief Valve ASME "UV" Stamp(Up to 6,000psig)
would be much appreciated, and we will do our best to give you our business suggestions Dec. 2011 Awarded Export Tower of 3 Mil. U.S Dollar
Dec. 2011 Acquired Type approval from CCS(China)
on them, which can be competitive in your market. In closing, we promise for our continuous Dec. 2011 Acquired ISO14001 Certificate
endeavor, for more research, and for development work to pay back your positive supports Mar. 2012 Acquired OHSAS18001 Certificate
Mar. 2013 Acquired Pilot type Safety Relief Valve ASME "UV"Stamp
and encouragement. Jun. 2014 Acquired Safety Relief Valve ASME "V"Stamp
Jun. 2015 Acquired Safety Relief Valve C-Sel(China)
May. 2016 Renewed ASME "UV"Stamp
Jan. 2016 Moved to Sanmak Complex in Yangsan, Korea
Sep. 2016 Renewed ASME "V"Stamp
Certificate
General
information

01 About SRV(Safety Relief Valve) 06

02 Sizing Program Basis 09

03 Numbering System 10

Quality System Certificate Type Apprival


‘ V ’ Stamp of ASME Sec.I
LR - Lloyd's Register
‘ UV ’ Stamp of ASME Sec.VIII
BV - Bureau Veritas
Certificate of NBBI Safety Valve Capacity
KR - Korean Register
ISO 9001 Certificate
CCS - China Classification Society
ISO 14001 Certificate
DNV ∙ GL - Det norske Veritas
OHSAS 18001 Certificate
∙ Germanischer Veritas
C-SEL China Special Equipment License
General information

01
01 General Definition of Safety Relief Valve(SRV) 03 Pressure Relief Devices

A pressure relief device is any device that can when the system pressure has returned to a safe Pressure relief device may be used as either a safety or reliefvalve
purge a system from an overpressure condition. lever at values determined by the codes. depending on the application.
Actuated by inlet static pressure and designed to
More particularly, an SRV is a pressure relief device
SRVs must be designed with materials compatible open during emergency or abnormal conditions
that is self-actuated, and whose primary purpose d A conventional pressure relief valve
with many process fluids, from simple air and to prevent a rise of internal fluid pressure in
is the protection of life and equipment. Through a It is a spring loaded pressure relief valve whose
water to the most corrosive and toxic media. excess of a specified design value. The device
controlled discharge of a required(rated) amount operational characteristics are directly affected
They must also be designed to operate in a also may be designed to prevent excessive
of fluid at a predetermined pressure, an SRV must by changes in the back pressure.
consistently smooth manner on a variety of fluids internal vacuum. The device may be designed to
prevent overpressure in pressurized vessels and
and fluid phases. These design parameters lead prevent excessive internal vacuum. The device
systems, and it operates within limits which are
to a wide array of SRV products available in the may be a pressure relief valve, a non-reclosing e A balanced pressure relief valve
determined by international codes. An SRV is
market today, with the on constant being that pressure relief device, or a vacuum relief valve. A It is spring loaded pressure relief valve that
often the final control device in the prevention of
they all must comply with the internationally incorporates a bellows or other means for
accidents or explosions caused by overpressure.
recognized codes. minimizing the effect of back pressure on the
The SRV must close at a predetermined pressure operational characteristics of the valve.
Pressure relief valve
A pressure relief device designed to open and f A pilot operated pressure relief valve
relieve excess pressure and to reclose and
It is a pressure relief valve in which the major
02 Where do SRVs fit in the process? prevent the further flow of fluid after normal
conditions have been restored.
relieving device or main valve is combined
with and controlled by a self actuated auxiliary
Every industrial process system is designed to works correctly in the system, should never have pressure relief valve(pilot).
a A relief valve
work against a certain maximum pressure and to work. However, practice proves the contrary,
temperature called its rating or design pressure. and there are a variety of incidents which will It is a spring loaded pressure relief valve actuated
It is in the economic interest of the users to work allow the system pressure to exceed the design by the static pressure upstream of the valve.
The valve opens normally in proportion to the Non-reclosing pressure relief device
as close as possible towards the maximum limits pressure.
of this design pressure in order to optimize the pressure increase over the opening pressure. A A pressure relief device which remains open
Although many pressure relief devices are called

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


process output, hence increase the profitability of relief valve is used primarily with incompressible after operation. A manual resetting means may
SRVs, not every SRV has the same characteristics fluids.
the system. be provided.
of or operational precision. Only the choice of
Nowadays, pressures and flow in the process the correct pressure safety device for the right
b A safety valve
industry are controlled by electronic process application will assure the safety of the system
It is a spring loaded pressure relief valve actuated
systems and highly sophisticated instrumentation and allow the user to maximize process output Rupture disk device
devices. Almost all control systems are powered and minimize down-time for maintenance by the static pressure upstream of the valve and
characterized by rapid opening or pop action. A A non-reclosing pressure relief device actuated
by an outside power source(electric, pneumatic, purposes. Making the correct choice also means
safety valve is normally used with compressible by static differential pressure between the
hydraulic). The law requires that when everything avoiding interference between the process
fluids. inlet and outlet of the device and designed to
fails regardless of the built-in redundancies, there instrumentation set points in the control loop
function by the bursting of a rupture disk. A
is still an independent working device powered and the pressure relief device limits selected.
c A safety relief valve rupture disk device includes a rupture disk and a
only by the medium it protects. This is the There SRV operation al limits can vary greatly
rupture disk holder.
function of the SRV, which, when everything else even when all are complying with the codes. It is a spring loaded pressure relief valve that

6 7
General information

02
a A rupture disk
It is a pressure containing, pressure and
In truction of Sizing Program
temperature sensitive element of a rupture disk After receiving the inquiry or P/O(purchase order) API STD 520 and so on.
device. from our precious customers, we input the data
Also the variety of pressure unit including Kg/
for specification of PSV in the COMPUTER SIZING
cm2g, Barg, MPag, kPag, pisg and so on could be
b A rupture disk holder PROGRAM(see fig. 1).
used in the system.
It is the structure which encloses and clamps This helps calculate the valve capacity and select
the rupture disk in position.(Some disks are The whole information for the each PSV is saved
the exact size compared than required capacity.
designed to be installed between standard in our system and the data sheet with calculation
flanges without holders.) When we calculate the capacity, must-have sheet(see fig. 2) based on it could be printed out
information such as fluid name & states, automatically.
c A non fragmenting rupture disk temperature, pressure, required capacity and
It is possible to trace the saved information
allowable overpressure condition(3%) are consi-
It is a rupture disk designed and manufactured of each PSV with customer’s name and serial
dered and reflected in the system according to
to be installed upstream of other piping number on the customer’s request.
the calculation standard as ASME Sec.l and
components, such as pressure relief valves, and
will not impair the function of those components
when the disk ruptures.

Pressure Safety & Relief Valve Specification and Calculation Sheet


Sheet No. 65 of 114 Rev. No. 0

JOKWANG I.L.I Project Name


Project No.
RAPID and Petrochemicals Intergrated Development in Malaysia

Date 2016. 04. 29 By M. J LEE


Checked M. S KIM Approved S. C KIM

Pin-actuated device
P&ID No. 1 3200-0701-1
Tag No. 2 PSV-7116

GENERAL
Service Line 3 PSV return to HHD Storage Drum (3200-V-711)
Model No. 4 JSV-FF100 / FF200 / FT100
Calculation
Quantity 5 1
Nozzle Type 6 Full Calculation of Area

A non-reclosing pressure relief device actuated Design Type 7 Bellows (Balanced Piston)

TYPE
Bonnet Type 8 Closed
Lever Type 9 No A1 = W1/(159.44*Kd*√((P*1.10-Pb)*G))
Cap Type 10 Screwed

by static pressure and designed to function by Size. Inlet / Outlet 11 1" X 2"

CONN.
Inlet. Rating / Facing 12 ASME CL. 300 / RF = 21400/(159.44*0.615*√((10.2*1.10-0)*1000))
Outlet. Rating / Facing 13 ASME CL. 150 / RF
Body (Base) 14 SA216 WCB

buckling or breaking a pin which holds a piston Bonnet


Seat
15
16
SA216 WCB
SA276 316-st.
= 2.06 ㎠

MATERIALS
Disc 17 SA276 316-st.
A351 CF8M

or a plug in place. Upon buckling or breaking of


Guide 18
Gasket (Bonnet) 19 PTFE Calculation of Capacity
Spring 20 SWOSC
Bellows 21 INCONEL 625-LCF

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


the pin, the piston or plug instantly moves to the
Approved by 22 UV W= 159.44*A*Kd*√((P*1.10-Pb)*G)
Comply with NACE 23 No
EN 10204 24 Type 3.1

BASIS
Code 25 ASME Section VIII = 159.44*3.265*0.615*1*√((10.2*1.10-0)*1000)

full open position.


Fire 26 No
Sizing Basis 27 Closed Outlet
Rupture Disk 28 No = 33,912 kg/h
Fluid / State 29 PENTANE / Liquid
Mol. Weight / Specific Gravity 30 0.56
Compressibility Factor 31 -
Ratio of Specific Heat 32 - W1 (Required Capacity) 1,008 kg/h
Viscosity 33 0.25 cp W (Valve Actual Capacity) 2,702 kg/h
Operating / Relieving Temp. 34 40 / 40 ℃ A1 (Calculated Orifice Area) 0.26 ㎠

SERVICE CONDITION
Design Min. / Design Max. Temp. 35 - / 80 ℃ A (Selected Orifice Area) 0.71 ㎠
Operating / Set Pressure 36 0.5 / 4.4 barg P (Set Pressure) 4.49 kgf/㎠g
Design Pressure / C.D.T.P 37 4.4 / 4.4 barg G (Specific Weight) 560 kg/㎥
Superimposed - Constant 38 2.2 barg Pb (Back Pressure) 2.25 kgf/㎠g
Back Superimposed - Variable 39 - Kd (Coefficient of Discharge) 0.615
Pressure Built-up 40 0.003 barg Kc (Rupture disc for factor) 1
Total 41 2.2003 barg
Remarks
Allowable Overpressure 42 10%
Closing Pressure / Blowdown(%) 43 Min. 4.092 barg / 7%
Hydrostatic Test Pressure (Body) 44 6.6 barg * Inlet Stud Bolt & Nuts
Required Capacity 45 1,008 kg/h : A193 Gr.B7 & A194 Gr.2H

SIZING & SELECTION


Valve Actual Capacity 46 2,702 kg/h
Calculated Orifice Area 47 0.26 ㎠
Selected Orifice Area 48 0.710 ㎠
Orifice Dia.(mm) 49 D (9.5)
Reaction Force 50
Noise Level 51
Paint System & Color 52

ETC
Test Gag 53 No
Bug screen 54 Yes

Ref. No : 160425-060-650-399769-0 JOKWANG I.L.I CO.,LTD. No.TTIPCF500-2

Fig. 1 - Sizing Program – ERP System Fig. 2 - Data & Calculation Sheet
* Reference
- The Safety Relief Valve Handbook - API STD 520 Part 2.

8 9
General information

03 JSV-FF200
F2 C - 1 F 2 A 2 1 - 2 1 1 - O L I

Model Body Material


F2 : JSV-FF200 1 : Carbon Steel
2 : Stainless Steel
3 : etc.
Pilot Part
C : Conventional
E : etc.

Trim Material
Inlet Size
1 : 316 SS
1” ~ 14”
2 : etc.

Orifice
F ~Y

Spring Material
Outlet Size 1 : Carbon Steel
2” ~ 18” 2 : Stainless Steel 01 Product Information 12
3 : Inconel X-750
02 Specification 13
Connection Code 03 Orifice Designation 14
A : ASME 04 Part Name & Material 15
05 Valve Selection 16
Bonnet & Lever Type 06 Dimension 26
Inlet Flange Rating
CN : Close Non Lever
1 : 150 lb PL : Close Packed Lever
07 Steam Capacities (USC Units) 28
2 : 300 lb
08 Steam Capacities (Metric Units) 30
3 : 600 lb
4 : 900 lb 09 Super Heat Correction Factor,KSH (USC Units) 32
5 : 1500 lb 10 Super Heat Correction Factor,KSH (Metric Units) 34
6 : 2500 lb
11 Super Critical Correction Factor,Ksc (USC Units) 36
Test Gag 12 Super Critical Correction Factor,Ksc (Metric Units) 38
Outlet Flange Rating 1 : Yes
2 : No 13 Technical Data 40
1 : 150 lb
2 : 300 lb

10
JSV-FF200

01 02 Specification
Type Conventional & Bellows
INTRODUCTION Applicable Code ASME Sec. I
Over almost half a century, we have been supplying a variety of safety relief valves to satisfy the highly Size 1" × 2" ~ 8" × 12"
variable requirements of customers. Orifice F(0.438in2) ~ Y(76.078 in2)
Set Pressure Range 15 ~ 5020 psig(1.03 ~ 346.2 bar)
JSV-FF200 as representative POSRV of Jokwang is designed and produced based on the accumulated
Allowable Leakage API STD 527
technology of long experience.

We strongly recommend JSV-FF200 to protect overpressure of the Power Boiler and process line using
Inlet Outlet
in the various industries. Flange Flange
Orifice F G H J L N P Rating Rating
ASME ASME
B 16.34 B 16.34

APPLICABLE CODES, STANDARD and AUTHORIZATIONS 1"×2"


1 1/2"×2
1/2"
1 1/2"×2
1/2"
2"×3" 2 1/2"×4" 3"×6" 4"×6" 300

The JSV-FF200 series is compliant with the following codes and standards.
1"×2" 1 1/2"×3" 1 1/2"×3" 2"×4" 2 1/2"×6" 3"×6" 4"×8" 600
• ASME SEC. I Inlet
150
• RELIEVING CAPACITY tested & certifi ed by NBBI ×
Outlet 1"×2" 1 1/2"×3" 1 1/2"×3" 2"×4" 2 1/2"×6" 3"×6" 4"×8" 900
• API STD 527 / SEAT TIGHTNESS OF PRESSURE RELIEF VALVES Size
(inch)
• ASME B16.34 / VALVES – FLANGED, THREADED, AND WELDING END 1 1/2×3 1 1/2"×3" 2"×3" 3"×6" 3"×6" 4"×6" 4"×8" 1500

1 1/2×3 1 1/2"×3" 2"×3" 3"×6" 3"×6" 4"×6" 4"×8" 2500 300


DESIGN FEATURE
• Certified Discharge Capacity
Inlet Outlet
JSV-FF200 is designed and manufactured in accordance with ASME Sec. I.
Flange Flange
Orifice Q R T Rating Rating

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


Also the discharge capacity is certied by NBBI(National Board OF Boiler and Pressure Vessel
ASME ASME
Inspections) as well. B 16.34 B 16.34
Total Safety Solution Provider!

• Excellent Seat Tightness 6"×8" 6"×8" 8"×10" 300

Disc construction of JSV-FF200 is composed of a disc and disc holder.


Inlet
6"×8" 6"×10" 8"×12" 600
This kind of simple shaped disc permits a uniform pressure distribution not to make any distortion of ×
Outlet 150
seat, thus maintaining excellent seat tightness. Size
6"×8" 6"×10" 8"×12" 900
(inch)
In addition, the seat is machined and lapped with a high precision to enhance the seat tightness.

6"×8" 6"×10" 1500

12 13
JSV-FF200

02
03 Specification
Orifice Designation 04 Part Name & Material
3
Area Diameter
Orifice
Sq. in Sq. mm In mm 15
13
12
F 0.439 283.23 0.748 19.0 14
10
17 11
G 0.701 452.26 0.945 24.0 18

2
5 1
H 1.095 706.45 1.181 30.0
6 8
7 9
J 1.758 1134.19 1.496 38.0
16

4
L 2.922 1885.16 1.929 49.0
Material
No Part Name
N 4.531 2923.22 2.402 61.0 400˚C (752˚F) 500˚C (932˚F) 538˚C (1,000 ˚F) 604˚C (1,120 ˚F)
1 Body A216 WCB A217 WC6 A217 WC9 A217 C12A
2 Bonnet A216 WCB A217 WC6
P 7.031 4,536.12 2.992 76.0
3 Cap A216 WCB
4 Seat A351 CF8M A182 F22 A182 F91
Q 10.986 7,087.73 3.74 95.0 5 Guide 316 Stainless Steel
6 Holder 316 Stainless Steel
7 Disc A564 630 / Inconel
R 16.103 10,389.01 4.528 116.4

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


8 Upper Adjust Ring 316 Stainless Steel
9 Lower Adjust Ring 316 Stainless Steel
Total Safety Solution Provider!
T 27.395 17,674.16 5.906 150.0 10 Stem Stainless Steel
11 Lower Spring Seat Stainless Steel
12 Upper Spring Seat Stainless Steel
V 39.447 25,449.63 7.087 180.0
13 Adjust Screw Stainless Steel
14 Spring Carbon Steel Alloy Steel
W 55.748 35,966.38 8.425 214.0 15 Lock Nut Stainless Steel
16 Set Screw 316 Stainless Steel
Y 76.078 49,082.48 9.842 250.0 17 Stud Bolt A193 B7
18 Nut A194 2H

14 15
JSV-FF200

05 Valve Selection
F orifice
USC Units
Area = 0.439 sq. in.
Diameter : 0.748 in. G orifice
USC Units
Area = 0.701 sq. in.
Diameter : 0.945 in.

Connections Connections
Maximum Set Pressure. (Psig) Standard Materials Maximum Set Pressure. (Psig) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring
Bonnet Bonnet
1× 2 300 150 435 11/2 × 2 1/2 300 150 435

1× 2 600 150 870 11/2 × 3 600 150 870

1×2 900 150 1450 Carbon Steel Carbon Steel 11/2 × 3 900 150 1450 Carbon Steel Carbon Steel

11/2 × 2 1500 150 2320 11/2 × 3 1500 150 2320

11/2 × 2 2500 300 4061 11/2 × 3 2500 300 4061

1×2 300 150 362 261 203 11/2 × 2 1/2 150 150 362 261 203

1×2 600 150 725 522 420 11/2 × 3 600 150 725 522 420
Stainless Stainless
Chrome Steel Chrome Steel
1×2 900 150 1087 797 623 Moly Steel or 11/2 × 3 900 300 1087 797 623 Moly Steel or
Alloy Steel Alloy Steel
11/2 × 2 1500 150 1812 1334 1058 11/2 × 3 1500 300 1812 1334 1058

11/2 × 2 2500 300 2900 2219 1754 11/2 × 3 2500 300 2900 2219 1754

Metric Units Metric Units


Connections Connections
Maximum Set Pressure. (Bar) Standard Materials Maximum Set Pressure. (Bar) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring
Bonnet Bonnet
1× 2 300 150 30 11/2 × 2 1/2 300 150 30

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


1× 2 600 150 60 11/2 × 3 600 150 60

1×2 900 150 100 Carbon Steel Carbon Steel 11/2 × 3 900 150 100 Carbon Steel
Total Safety Carbon
Solution Steel
Provider!

11/2 × 2 1500 150 160 11/2 × 3 1500 150 160

11/2 × 2 2500 300 280 11/2 × 3 2500 300 280

1×2 300 150 25 18 14 11/2 × 2 1/2 150 150 25 18 14

1×2 600 150 50 36 29 11/2 × 3 600 150 50 36 29


Stainless Stainless
Chrome Steel Chrome Steel
1×2 900 150 75 55 43 Moly Steel or 11/2 × 3 900 300 75 55 43 Moly Steel or
Alloy Steel Alloy Steel
11/2 × 2 1500 150 125 92 73 11/2 × 3 1500 300 125 92 73

11/2 × 2 2500 300 200 153 121 11/2 × 3 2500 300 200 153 121

16
14 17
JSV-FF200

Valve Selection

H orifice
USC Units
Area = 1.095 sq. in.
Diameter : 1.181 in. J orifice
USC Units
Area = 1.758 sq. in.
Diameter : 1.496 in.

Connections Connections
Maximum Set Pressure. (Psig) Standard Materials Maximum Set Pressure. (Psig) Standard Materials
ASME Flanges Size ASME Flanges
Size
Body / Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Body / Bon- Spring
Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring
Bonnet
2×3 300 150 435
11/2 × 2 1/2 300 150 435
2×4 600 150 870
11/2 × 3 600 150 870
2×4 900 150 1450 Carbon Steel Carbon Steel
11/2 × 3 900 150 1450 Carbon Steel Carbon Steel
3×6 1500 150 2320
2×3 1500 150 2320
3×6 2500 300 4061
2×3 2500 300 4061
2×3 150 150 362 261 203
11/2 × 2 1/2 150 150 362 261 203
2×4 600 150 725 522 420
11/2 × 3 600 150 725 522 420 Stainless
Stainless Chrome Steel
Chrome Steel 2×4 900 300 1087 797 623 Moly Steel or
11/2 × 3 900 300 1087 797 623 Moly Steel or Alloy Steel
Alloy Steel 3×6 1500 300 1812 1334 1058
2×3 1500 300 1812 1334 1058
3×6 2500 300 2900 2219 1754
2×3 2500 300 2900 2219 1754

Metric Units Metric Units


Connections Connections
Maximum Set Pressure. (Bar) Standard Materials Maximum Set Pressure. (Bar) Standard Materials
ASME Flanges Size ASME Flanges
Size
Body / Inlet Outlet 400℃ 500℃ 538℃ 604℃ Body / Bon- Spring
Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring
Bonnet
2×3 300 150 30
11/2 × 2 1/2 300 150 30

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


2×4 600 150 60
11/2 × 3 600 150 60
2×4 900 150 100 Carbon Steel Carbon Steel
11/2 × 3 900 150 100 Carbon Steel Carbon Steel Total Safety Solution Provider!

3×6 1500 150 160


2×3 1500 150 160
3×6 2500 300 280
2×3 2500 300 280
2×3 150 150 25 18 14
11/2 × 2 1/2 150 150 25 18 14
2×4 600 150 50 36 29
11/2 × 3 600 150 50 36 29 Stainless
Stainless Chrome Steel
Austenitic 2×4 900 300 75 55 43
Steel Moly Steel or
11/2 × 3 900 300 75 55 43 Stainless or Alloy Steel
Steel Alloy Steel 3×6 1500 300 125 92 73
2×3 1500 300 125 92 73
3×6 2500 300 200 153 121
2×3 2500 300 200 153 121

18
14 19
JSV-FF200

Valve Selection

L orifice
USC Units
Area = 2.922 sq. in.
Diameter : 1.929 in. N orifice
USC Units
Area = 4.531 sq. in.
Diameter : 2.402 in.

Connections Connections
Maximum Set Pressure. (Psig) Standard Materials Maximum Set Pressure. (Psig) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring
Bonnet Bonnet
21/2 × 4 300 150 435 3×6 300 150 435

21/2 × 6 600 150 870 3×6 600 150 870

21/2 × 6 900 150 1450 Carbon Steel Carbon Steel 3×6 900 150 1450 Carbon Steel Carbon Steel

3×6 1500 150 2320 4×6 1500 150 2320

3×6 2500 300 4061 4×6 2500 300 2987

21/2 × 4 150 150 362 261 203 3×6 150 150 362 261 203

21/2 × 6 600 150 725 522 420 3×6 600 150 725 522 420
Stainless Stainless
Chrome Steel Chrome Steel
21/2 × 6 900 300 1087 797 623 Moly Steel or 3×6 900 300 1087 797 623 Moly Steel or
Alloy Steel Alloy Steel
3×6 1500 300 1812 1334 1058 4×6 1500 300 1812 1334 1058

3×6 2500 300 2900 2219 1754 4×6 2500 300 2900 2219 1754

Metric Units Metric Units


Connections Connections
Maximum Set Pressure. (Bar) Standard Materials Maximum Set Pressure. (Bar) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring
Bonnet Bonnet
21/2 × 4 300 150 30 3×6 300 150 30

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


21/2 × 6 600 150 60 3×6 600 150 60

21/2 × 6 900 150 100 Carbon Steel Carbon Steel 3×6 900 150 100 Carbon Steel
Total Safety Carbon
Solution Steel
Provider!

3×6 1500 150 160 4×6 1500 150 160

3×6 2500 300 280 4×6 2500 300 206

21/2 × 4 150 150 25 18 14 3×6 150 150 25 18 14

21/2 × 6 600 150 50 36 29 3×6 600 150 50 36 29


Stainless Stainless
Chrome Steel Chrome Steel
21/2 × 6 900 300 75 55 43 Moly Steel or 3×6 900 300 75 55 43 Moly Steel or
Alloy Steel Alloy Steel
3×6 1500 300 125 92 73 4×6 1500 300 125 92 73

3×6 2500 300 200 153 121 4×6 2500 300 200 153 121

20
14 21
JSV-FF200

Valve Selection

P orifice
USC Units
Area = 7.031 sq. in.
Diameter : 2.992 in. Q orifice
USC Units
Area = 10.986 sq. in.
Diameter : 3.74 in.

Connections Connections
Maximum Set Pressure. (Psig) Standard Materials Maximum Set Pressure. (Psig) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring
Bonnet Bonnet
4×6 300 150 435 6×8 300 150 435
4×8 600 150 870
6×8 600 150 870
4×8 900 150 1450 Carbon Steel Carbon Steel Carbon Steel Carbon Steel
6×8 900 150 1450
4×8 1500 150 2320

4×8 2500 300 2987 6×8 1500 150 1987

4×6 150 150 362 261 203 6×8 300 150 362 261 203

4×8 600 150 725 522 420


Stainless 6×8 600 150 725 522 420 Stainless
Chrome Steel Chrome Steel
4×8 900 300 1087 797 623 Moly Steel or Moly Steel or
Alloy Steel 6×8 900 150 1087 797 623 Alloy Steel
4×8 1500 300 1812 1334 1058

4×8 2500 300 2900 2219 1754 6×8 1500 150 1812 1334 1058

Metric Units Metric Units


Connections Maximum Set Pressure. (Bar) Standard Materials Connections Maximum Set Pressure. (Bar) Standard Materials
Size ASME Flanges
Body / Size
Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring Body /
Bonnet Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring
Bonnet
4×6 300 150 30
6×8 300 150 30

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


4×8 600 150 60
6×8 600 150 60
4×8 900 150 100 Carbon Steel Carbon Steel Carbon Steel Carbon Steel
Total Safety Solution Provider!

4×8 1500 150 160 6×8 900 150 100

4×8 2500 300 206 6×8 1500 150 137

4×6 150 150 25 18 14 6×8 300 150 25 18 14


4×8 600 150 50 36 29
Stainless 6×8 600 150 50 36 29 Stainless
Chrome Steel Chrome Steel
4×8 900 300 75 55 43 Moly Steel or Moly Steel or
Alloy Steel 6×8 900 150 75 55 43 Alloy Steel
4×8 1500 300 125 92 73

4×8 2500 300 200 153 121 6×8 1500 150 125 92 73

22
14 23
JSV-FF200

Valve Selection

R orifice
USC Units
Area = 16.103 sq. in.
Diameter : 4.528 in. T orifice
USC Units
Area = 27.395 sq. in.
Diameter : 5.906 in.

Connections Connections
Maximum Set Pressure. (Psig) Standard Materials Maximum Set Pressure. (Psig) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring Inlet Outlet 752 ℉ 932 ℉ 1000 ℉ 1120 ℉ Spring
Bonnet Bonnet
6×8 300 150 435 8 × 10 300 150 435
6 × 10 600 150 870
Carbon Steel Carbon Steel 8 × 12 600 150 870 Carbon Steel Carbon Steel
6 × 10 900 150 1450

6 × 10 1500 150 1987 8 × 12 900 150 1450

6×8 300 150 362 261 203 8 × 10 300 150 362 261 203
Stainless Stainless
6 × 10 600 150 725 522 420 Chrome Steel
Chrome Steel 8 × 12 600 150 725 522 420
Moly Steel or Moly Steel or
6 × 10 900 150 1087 797 623 Alloy Steel Alloy Steel
8 × 12 900 150 1087 797 623
6 × 10 1500 150 1812 1334 1058

Metric Units Metric Units


Connections Connections
Maximum Set Pressure. (Bar) Standard Materials Maximum Set Pressure. (Bar) Standard Materials
ASME Flanges ASME Flanges
Size Size
Body / Body /
Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring Inlet Outlet 400℃ 500℃ 538℃ 604℃ Spring
Bonnet Bonnet
6×8 300 150 30 8 × 10 300 150 30

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


6 × 10 600 150 60
Carbon Steel Carbon Steel 8 × 12 600 150 60 Carbon Steel Carbon Steel
6 × 10 900 150 100 Total Safety Solution Provider!

6 × 10 1500 150 137 8 × 12 900 150 100

6×8 300 150 25 18 14 8 × 10 300 150 25 18 14


Stainless Stainless
6 × 10 600 150 50 36 29 Chrome Steel
Chrome Steel 8 × 12 600 150 50 36 29
Moly Steel or Moly Steel or
6 × 10 900 150 75 55 43 Alloy Steel Alloy Steel
8 × 12 900 150 75 55 43
6 × 10 1500 150 125 92 73

24
14 25
JSV-FF200

06 Dimension
Safety Relief Vlave L H1 H T L H1 H T L H1 H T L H1 H T L H1 H T
Dimension [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in]

Flange Rating Class 300 × 150 600 × 150 900 × 300 1500 × 300 2500 × 300

Valve Size 1F2 1F2 1F2 1 1/2 F 3 1 1/2 F 3

F 4 4 14 2/3 6/7 7 5/7 4 16 2/3 1 4 5/7 4 1/4 16 7/8 1 1/8 6 2/3 6 1/4 24 1 1/3 6 2/3 6 1/4 24 1 4/5

Valve Size 1 1/2 G 1 1/2 1 1/2 G 3 1 1/2 G 3 1 1/2 G 3 1 1/2 G 3

G 4 5/7 4 2/3 17 5/9 9 4/9 6 1/7 5 1/2 25 5/6 1 1/9 6 1/7 5 2/3 29 1 1/4 6 7/8 4 1/2 26 4/5 1 1/3 6 7/8 4 1/2 26 4/5 1 4/5

Valve Size 1 1/2 H 1 1/2 1 1/2 H 3 1 1/2 H 3 2H3 2H3

H 4 5/7 4 2/3 17 5/9 1 6 1/7 5 1/2 25 5/6 1 1/9 6 1/7 5 2/3 26 1 1/4 7 2/3 6 2/3 28 1/7 1 5/9 7 2/3 6 2/3 28 1/7 2

Valve Size 2J3 2J4 2J4 3J6 3J6

J 5 1/4 5 1/9 21 3/8 1 7 1/8 6 27 7/8 1 1/6 7 1/8 6 2/5 28 1/6 1 1/2 9 4/9 9 36 1/2 2 9 4/9 9 36 1/2 2 2/3

Valve Size 2 1/2 L 4 2 1/2 L 6 2 1/2 L 6 3L6 3L6

L 6 6 24 1 1/6 8 5/8 7 7/8 32 1/4 1 1/3 8 5/8 8 1/7 32 1/2 1 3/5 10 5/8 9 42 1/5 2 10 5/8 9 42 1/5 2 2/3

Valve Size 3N6 3N6 3N6 4N6 4N6

N 6 7/8 6 4/9 27 1 1/8 8 1/4 7 1/3 35 5/8 1 2/5 8 1/4 7 4/9 35 5/7 1 1/2 12 1/3 9 5/6 46 2/9 2 1/6 12 1/3 9 5/6 46 2/9 3

Valve Size 4P6 4P8 4P8 4P8 4P8

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


P 7 5/8 8 31 1 2/5 10 1/3 9 40 2/3 1 4/7 10 1/3 9 1/7 40 5/6 1 3/4 14 3/8 11 53 1/6 2 1/6 14 3/8 11 53 1/6 3

Valve Size 6Q8 6Q8 6Q8 6Q8 Total Safety Solution Provider!

Q 9 1/8 9 40 3/7 1 2/3 12 10 49 5/9 2 12 10 51 2 1/4 13 11 2/5 55 8/9 3 1/3

Valve Size 6R8 6 R 10 6 R 10 6 R 10

H
R 10 5/8 8 4/7 46 1/2 1 3/7 14 11 56 2/3 2 14 11 63 8/9 2 1/4 14 12 1/2 65 3/7 3 1/3

Valve Size 8 T 10 8 T 12 8 T 12

H1
T 13 3/8 10 5/9 57 1 5/8 15 5/9 13 72 1/4 2 1/4 15 5/9 13 72 1/4 2 5/9

T
L

26
14 27
JSV-FF200

07 Set Pressure
Steam Capacity (USC Units)
Orifice
Capacity for air (lb/h at Letter and 10% Overpressure) =
60℉ with
CKdAP MKc Effective Area (in2) Set Pressure
psig F G H J L N P ZT Q R T V W Y psig
API 0.75 0.95 1.18 1.5 1.93 2.4 2.99 3.74 4.53 5.91 7.09 8.43 9.84 API
Actual 0.44 0.70 1.10 1.76 2.92 4.53 7.03 10.99 16.10 27.40 39.45 55.75 76.10 Actual
15 624 993 1,561 2,497 4,143 6,427 9,973 15,591 22,841 38,872 55,967 79,092 107,962 15
28 880 1,400 2,201 3,521 5,841 9,062 14,063 21,985 32,208 54,813 78,919 111,527 152,237 28
43 1,176 1,870 2,939 4,702 7,802 12,103 18,783 29,363 43,016 73,207 105,402 148,952 203,323 43
57 1,451 2,309 3,628 5,805 9,631 14,941 23,187 36,249 53,103 90,374 130,119 183,882 251,003 57
71 1,730 2,751 4,324 6,918 11,478 17,806 27,633 43,198 63,284 107,701 155,066 219,137 299,126 71
85 2,013 3,203 5,034 8,054 13,362 20,729 32,170 50,291 73,674 125,384 180,525 255,115 348,237 85
100 2,318 3,687 5,794 9,271 15,381 23,862 37,030 57,890 84,807 144,329 207,802 293,662 400,856 100
114 2,602 4,139 6,504 10,407 17,265 26,785 41,567 64,982 95,197 162,012 233,261 329,640 449,967 114
128 2,886 4,591 7,214 11,542 19,150 29,709 46,104 72,074 105,587 179,694 258,720 365,618 499,077 128
142 3,170 5,042 7,924 12,678 21,034 32,632 50,641 79,167 115,977 197,377 284,179 401,596 548,188 142
156 3,454 5,494 8,634 13,814 22,919 35,555 55,178 86,259 126,367 215,059 309,638 437,574 597,299 156
171 3,758 5,978 9,394 15,031 24,938 38,688 60,038 93,858 137,499 234,005 336,915 476,122 649,918 171
185 4,042 6,430 10,104 16,167 26,822 41,611 64,575 100,950 147,889 251,687 362,374 512,100 699,028 185
199 4,326 6,882 10,814 17,303 28,707 44,534 69,112 108,043 158,279 269,369 387,833 548,078 748,139 199
213 4,610 7,333 11,524 18,438 30,591 47,458 73,649 115,135 168,669 287,052 413,292 584,056 797,250 213
228 4,914 7,817 12,285 19,655 32,610 50,590 78,510 122,734 179,801 305,997 440,569 622,604 849,869 228
242 5,198 8,269 12,994 20,791 34,494 53,513 83,046 129,826 190,191 323,680 466,028 658,582 898,979 242
256 5,482 8,721 13,704 21,927 36,379 56,437 87,583 136,919 200,582 341,362 491,487 694,560 948,090 256
270 5,766 9,173 14,414 23,063 38,263 59,360 92,120 144,011 210,972 359,045 516,946 730,538 997,201 270
284 6,050 9,624 15,124 24,199 40,148 62,284 96,657 151,103 221,362 376,727 542,405 766,516 1,046,312 284
299 6,354 10,108 15,885 25,415 42,167 65,416 101,518 158,702 232,494 395,673 569,682 805,064 1,098,931 299
313 6,638 10,560 16,595 26,551 44,051 68,339 106,054 165,795 242,884 413,355 595,141 841,042 1,148,041 313
327 6,922 11,012 17,304 27,687 45,935 71,263 110,591 172,887 253,274 431,038 620,600 877,020 1,197,152 327
341 7,206 11,464 18,014 28,823 47,820 74,186 115,128 179,979 263,664 448,720 646,059 912,998 1,246,263 341
356 7,510 11,948 18,775 30,040 49,839 77,318 119,989 187,578 274,796 467,666 673,336 951,546 1,298,882 356
370 7,794 12,399 19,485 31,176 51,723 80,242 124,525 194,671 285,186 485,348 698,795 987,524 1,347,992 370
384 8,078 12,851 20,195 32,311 53,608 83,165 129,062 201,763 295,576 503,031 724,254 1,023,502 1,397,103 384
398 8,362 13,303 20,905 33,447 55,492 86,089 133,599 208,855 305,966 520,713 749,713 1,059,480 1,446,214 398
412 8,646 13,755 21,614 34,583 57,376 89,012 138,136 215,948 316,356 538,396 775,172 1,095,458 1,495,325 412
427 8,950 14,239 22,375 35,800 59,395 92,144 142,997 223,547 327,489 557,341 802,449 1,134,006 1,547,944 427
569 11,830 18,821 29,575 47,320 78,509 121,796 189,013 295,483 432,874 736,692 569
711 14,710 23,403 36,775 58,841 97,622 151,448 235,028 367,420 538,259 916,042 711

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


853 17,590 27,984 43,976 70,361 116,735 181,100 281,044 439,357 643,643 1,095,393 853
996 20,491 32,599 51,227 81,962 135,983 210,960 327,384 511,800 749,771 1,276,007 996
1138 23,371 37,181 58,427 93,483 155,097 240,612 373,400 583,737 855,155 1,455,358 1138
1280 26,251 41,763 65,627 105,003 174,210 270,264 419,416 655,673 960,540 1,634,708 Total Safety Solution
1280Provider!
1422 29,131 46,345 72,827 116,524 193,323 299,916 465,432 727,610 1,065,925 1,814,059 1422
1565 32,004 50,916 80,011 128,017 212,392 329,499 511,341 799,380 1,171,066 1565
1707 35,166 55,946 87,916 140,665 233,376 362,052 561,860 878,357 1,286,764 1707
1849 38,407 61,101 96,016 153,626 254,880 395,413 613,631 959,290 1,405,329 1849
1991 41,738 66,401 104,344 166,951 276,987 429,710 666,856 1,042,496 1,527,224 1991
2134 45,200 71,909 113,001 180,801 299,965 465,357 722,176 2134
2276 48,765 77,580 121,912 195,059 323,621 502,056 779,128 2276
2418 52,480 83,490 131,199 209,918 348,273 540,301 838,480 2418
2560 56,375 89,688 140,939 225,502 374,128 580,411 900,726 2560
2702 60,493 96,238 151,231 241,970 401,451 622,798 966,506 2702
2845 64,916 103,275 162,289 259,663 430,804 668,336 1,037,175 2845
2987 69,654 110,814 174,136 278,618 462,252 717,124 1,112,888 2987
3200 77,636 123,512 194,090 310,543 515,220 3200

28
14 29
JSV-FF200

08 Set Pressure
Steam Capacities (Metric Units)
Orifice Letter and Effective Area (mm2) Set Pressure
Bar F G H J L N P Q R T V W Y Bar
API 19 24 30 38 49 61 76 95 115 150 180 214 250 API
Actual 283.2 452.3 706.5 1134.2 1885.2 2923.2 4536.1 7087.7 10389.0 17674.2 25449.6 35966.4 49082.5 Actual
1.055 282 450 704 1,129 1,877 2,911 4,517 7,058 10,345 17,599 25,342 35,814 48,874 1.055
2 402 642 1,002 1,609 2,674 4,147 6,435 10,054 14,737 25,072 36,102 51,020 69,626 2
3 528 844 1,318 2,116 3,518 5,455 8,464 13,225 19,385 32,979 47,488 67,112 91,586 3
4 655 1,046 1,634 2,624 4,361 6,762 10,494 16,396 24,034 40,887 58,874 83,203 113,546 4
5 783 1,251 1,953 3,136 5,212 8,082 12,542 19,597 28,725 48,868 70,366 99,444 135,709 5
6 914 1,459 2,279 3,659 6,081 9,429 14,632 22,863 33,512 57,012 82,094 116,018 158,328 6
7 1,044 1,667 2,605 4,181 6,950 10,777 16,723 26,129 38,300 65,157 93,822 132,593 180,946 7
8 1,175 1,876 2,930 4,704 7,819 12,124 18,813 29,395 43,087 73,302 105,550 149,167 203,565 8
9 1,305 2,084 3,256 5,227 8,687 13,471 20,903 32,662 47,875 81,447 117,277 165,741 226,183 9
10 1,436 2,293 3,581 5,749 9,556 14,818 22,994 35,928 52,662 89,591 129,005 182,315 248,802 10
11 1,566 2,501 3,907 6,272 10,425 16,165 25,084 39,194 57,450 97,736 140,733 198,890 271,420 11
12 1,697 2,710 4,232 6,795 11,294 17,512 27,174 42,460 62,237 105,881 152,461 215,464 294,038 12
13 1,827 2,918 4,558 7,317 12,162 18,859 29,265 45,726 67,025 114,026 164,189 232,038 316,657 13
14 1,958 3,126 4,884 7,840 13,031 20,206 31,355 48,993 71,812 122,170 175,917 248,612 339,275 14
15 2,088 3,335 5,209 8,363 13,900 21,553 33,445 52,259 76,600 130,315 187,644 265,187 361,894 15
16 2,219 3,543 5,535 8,885 14,769 22,900 35,536 55,525 81,387 138,460 199,372 281,761 384,512 16
17 2,349 3,752 5,860 9,408 15,637 24,247 37,626 58,791 86,175 146,604 211,100 298,335 407,131 17
18 2,480 3,960 6,186 9,931 16,506 25,595 39,717 62,057 90,963 154,749 222,828 314,909 429,749 18
19 2,610 4,169 6,511 10,453 17,375 26,942 41,807 65,324 95,750 162,894 234,556 331,484 452,368 19
20 2,741 4,377 6,837 10,976 18,244 28,289 43,897 68,590 100,538 171,039 246,284 348,058 474,986 20
21 2,871 4,585 7,163 11,499 19,112 29,636 45,988 71,856 105,325 179,183 258,011 364,632 497,605 21
22 3,002 4,794 7,488 12,021 19,981 30,983 48,078 75,122 110,113 187,328 269,739 381,206 520,223 22
23 3,132 5,002 7,814 12,544 20,850 32,330 50,168 78,388 114,900 195,473 281,467 397,781 542,842 23
24 3,263 5,211 8,139 13,067 21,719 33,677 52,259 81,655 119,688 203,618 293,195 414,355 565,460 24
25 3,393 5,419 8,465 13,589 22,587 35,024 54,349 84,921 124,475 211,762 304,923 430,929 588,079 25
26 3,524 5,628 8,790 14,112 23,456 36,371 56,439 88,187 129,263 219,907 316,651 447,503 610,697 26
27 3,654 5,836 9,116 14,635 24,325 37,718 58,530 91,453 134,050 228,052 328,378 464,078 633,316 27
28 3,785 6,044 9,442 15,157 25,194 39,065 60,620 94,719 138,838 236,197 340,106 480,652 655,934 28
29 3,915 6,253 9,767 15,680 26,062 40,412 62,710 97,986 143,625 244,341 351,834 497,226 678,553 29
30 4,046 6,461 10,093 16,203 26,931 41,760 64,801 101,252 148,413 252,486 363,562 513,800 701,171 30
40 5,351 8,546 13,348 21,429 35,619 55,230 85,704 133,914 196,288 333,933 40
50 6,656 10,630 16,604 26,656 44,306 68,701 106,608 166,576 244,163 415,381 50

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


60 7,961 12,714 19,860 31,883 52,994 82,172 127,511 199,238 292,038 496,828 60
70 9,266 14,799 23,116 37,109 61,681 95,643 148,415 231,900 339,914 578,275 70
80 10,571 16,883 26,371 42,336 70,369 109,114 169,318 264,562 387,789 659,723 80
90 11,876 18,967 29,627 47,563 79,056 122,585 190,222 297,224 435,664 741,170 Total Safety Solution
90Provider!
100 13,181 21,052 32,883 52,790 87,744 136,056 211,125 329,886 483,539 822,617 100
110 14,512 23,177 36,202 58,119 96,601 149,790 232,438 363,187 532,352 110
120 15,956 25,484 39,806 63,903 106,216 164,700 255,574 399,337 585,339 120
130 17,439 27,852 43,505 69,843 116,088 180,007 279,327 436,452 639,742 130
140 18,967 30,293 47,318 75,963 126,261 195,780 303,804 474,696 695,799 140
150 20,549 32,818 51,263 82,296 136,788 212,103 329,133 150
160 22,193 35,445 55,366 88,884 147,737 229,082 355,480 160
170 23,915 38,195 59,660 95,778 159,196 246,850 383,052 170
180 25,730 41,093 64,188 103,046 171,276 265,582 412,118 180
190 27,660 44,176 69,003 110,776 184,125 285,505 443,035 190
200 29,735 47,490 74,181 119,088 197,941 306,928 476,278 200
210 31,997 51,102 79,823 128,146 212,996 330,273 512,504 210
220 34,503 55,104 86,074 138,181 229,677 220

30
14 31
JSV-FF200

09 Flowing
Super Heat Correction Factor, KSH (USC Units)
SUPERHEAT CORRECTION FACTOR,KSH
Total Temperature ,˚F,of Superheated Steam
SUPERHEAT CORRECTION FACTOR,KSH
Total Temperature ,˚F,of Superheated Steam
Flowing Pressure
Pressure (psia) (psia)
400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
50 0.987 0.957 0.930 0.905 0.882 0.861 0.841 0.823 0.805 0.789 0.774 0.759 0.745 0.732 0.719 0.708 0.696 50
100 0.998 0.963 0.935 0.909 0.885 0.864 0.843 0.825 0.807 0.790 0.775 0.760 0.746 0.733 0.720 0.708 0.697 100
150 0.984 0.970 0.940 0.913 0.888 0.866 0.846 0.826 0.808 0.792 0.776 0.761 0.747 0.733 0.721 0.709 0.697 150
200 0.979 0.977 0.945 0.917 0.892 0.869 0.848 0.828 0.810 0.793 0.777 0.762 0.748 0.734 0.721 0.709 0.698 200
250 ... 0.972 0.951 0.921 0.895 0.871 0.850 0.830 0.812 0.794 0.778 0.763 0.749 0.735 0.722 0.710 0.698 250
300 ... 0.968 0.957 0.926 0.898 0.874 0.852 0.832 0.813 0.796 0.780 0.764 0.750 0.736 0.723 0.710 0.699 300
350 ... 0.968 0.963 0.930 0.902 0.877 0.854 0.834 0.815 0.797 0.781 0.765 0.750 0.736 0.723 0.711 0.699 350
400 ... ... 0.963 0.935 0.906 0.880 0.857 0.836 0.816 0.798 0.782 0.766 0.751 0.737 0.724 0.712 0.700 400
450 ... ... 0.961 0.940 0.909 0.883 0.859 0.838 0.818 0.800 0.783 0.767 0.752 0.738 0.725 0.712 0.700 450
500 ... ... 0.961 0.946 0.914 0.886 0.862 0.840 0.820 0.801 0.784 0.768 0.753 0.739 0.725 0.713 0.701 500
550 ... ... 0.962 0.952 0.918 0.889 0.864 0.842 0.822 0.803 0.785 0.769 0.754 0.740 0.726 0.713 0.701 550
600 ... ... 0.964 0.958 0.922 0.892 0.867 0.844 0.823 0.804 0.787 0.770 0.755 0.740 0.727 0.714 0.702 600
650 ... ... 0.968 0.958 0.927 0.896 0.869 0.846 0.825 0.806 0.788 0.771 0.756 0.741 0.728 0.715 0.702 650
700 ... ... ... 0.958 0.931 0.899 0.872 0.848 0.827 0.807 0.789 0.772 0.757 0.742 0.728 0.715 0.703 700
750 ... ... ... 0.958 0.936 0.903 0.875 0.850 0.828 0.809 0.790 0.774 0.758 0.743 0.729 0.716 0.703 750
800 ... ... ... 0.960 0.942 0.906 0.878 0.852 0.830 0.810 0.792 0.774 0.759 0.744 0.730 0.716 0.704 800
850 ... ... ... 0.962 0.947 0.910 0.880 0.855 0.832 0.812 0.793 0.776 0.760 0.744 0.730 0.717 0.704 850
900 ... ... ... 0.965 0.953 0.914 0.883 0.857 0.834 0.813 0.794 0.777 0.760 0.745 0.731 0.718 0.705 900
950 ... ... ... 0.969 0.958 0.918 0.886 0.860 0.836 0.815 0.796 0.778 0.761 0.746 0.732 0.718 0.705 950
1000 ... ... ... 0.974 0.959 0.923 0.890 0.862 0.838 0.816 0.797 0.779 0.762 0.747 0.732 0.719 0.706 1000
1050 ... ... ... ... 0.960 0.927 0.893 0.864 0.840 0.818 0.798 0.780 0.763 0.748 0.733 0.719 0.707 1050
1100 ... ... ... ... 0.962 0.931 0.896 0.867 0.842 0.820 0.800 0.781 0.764 0.749 0.734 0.720 0.707 1100
1150 ... ... ... ... 0.964 0.936 0.899 0.870 0.844 0.821 0.801 0.782 0.765 0.749 0.735 0.721 0.708 1150
1200 ... ... ... ... 0.966 0.941 0.903 0.872 0.846 0.823 0.802 0.784 0.766 0.750 0.735 0.721 0.708 1200
1250 ... ... ... ... 0.969 0.946 0.906 0.875 0.848 0.825 0.804 0.785 0.767 0.751 0.736 0.722 0.709 1250
1300 ... ... ... ... 0.973 0.952 0.910 0.878 0.850 0.826 0.805 0.786 0.768 0.752 0.737 0.723 0.709 1300
1350 ... ... ... ... 0.977 0.958 0.914 0.880 0.852 0.828 0.807 0.787 0.769 0.753 0.737 0.723 0.710 1350
1400 ... ... ... ... 0.982 0.963 0.918 0.883 0.854 0.830 0.808 0.788 0.770 0.754 0.738 0.724 0.710 1400
1450 ... ... ... ... 0.987 0.968 0.922 0.886 0.857 0.832 0.809 0.790 0.771 0.754 0.739 0.724 0.711 1450
1500 ... ... ... ... 0.993 0.970 0.926 0.889 0.859 0.833 0.811 0.791 0.772 0.755 0.740 0.725 0.711 1500
1550 ... ... ... ... ... 0.972 0.930 0.892 0.861 0.835 0.812 0.792 0.773 0.756 0.740 0.726 0.712 1550
1600 ... ... ... ... ... 0.973 0.934 0.894 0.863 0.836 0.813 0.792 0.774 0.756 0.740 0.726 0.712 1600
1650 ... ... ... ... ... 0.973 0.936 0.895 0.863 0.836 0.812 0.791 0.772 0.755 0.739 0.724 0.710 1650
1700 ... ... ... ... ... 0.973 0.938 0.895 0.863 0.835 0.811 0.790 0.771 0.754 0.738 0.723 0.709 1700
1750 ... ... ... ... ... 0.974 0.940 0.896 0.862 0.835 0.810 0.789 0.770 0.752 0.736 0.721 0.707 1750
1800 ... ... ... ... ... 0.975 0.942 0.897 0.862 0.834 0.810 0.788 0.768 0.751 0.735 0.720 0.705 1800
1850 ... ... ... ... ... 0.976 0.944 0.897 0.862 0.833 0.809 0.787 0.767 0.749 0.733 0.718 0.704 1850
1900 ... ... ... ... ... 0.977 0.946 0.898 0.862 0.832 0.807 0.785 0.766 0.748 0.731 0.716 0.702 1900
1950 ... ... ... ... ... 0.979 0.949 0.898 0.861 0.832 0.806 0.784 0.764 0.746 0.729 0.714 0.700 1950
2000 ... ... ... ... ... 0.982 0.952 0.899 0.861 0.831 0.805 0.782 0.762 0.744 0.728 0.712 0.698 2000
2050 ... ... ... ... ... 0.985 0.954 0.899 0.860 0.830 0.804 0.781 0.761 0.742 0.726 0.710 0.696 2050
2100 ... ... ... ... ... 0.988 0.956 0.900 0.860 0.828 0.802 0.779 0.759 0.740 0.724 0.708 0.694 2100
2150 ... ... ... ... ... ... 0.956 0.900 0.859 0.827 0.801 0.778 0.757 0.738 0.722 0.706 0.692 2150

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


2200 ... ... ... ... ... ... 0.955 0.901 0.859 0.826 0.799 0.776 0.755 0.736 0.720 0.704 0.690 2200
2250 ... ... ... ... ... ... 0.954 0.901 0.858 0.825 0.797 0.774 0.753 0.734 0.717 0.702 0.687 2250
2300 ... ... ... ... ... ... 0.953 0.901 0.857 0.823 0.795 0.772 0.751 0.732 0.715 0.699 0.685 2300
2350 ... ... ... ... ... ... 0.952 0.902 0.856 0.822 0.794 0.769 0.748 0.729 0.712 0.697 0.682 2350
Total Safety Solution Provider!
2400 ... ... ... ... ... ... 0.952 0.902 0.855 0.820 0.791 0.767 0.746 0.727 0.710 0.694 0.679 2400
2450 ... ... ... ... ... ... 0.951 0.902 0.854 0.818 0.789 0.765 0.743 0.724 0.707 0.691 0.677 2450
2500 ... ... ... ... ... ... 0.951 0.902 0.852 0.816 0.787 0.762 0.740 0.721 0.704 0.688 0.674 2500
2550 ... ... ... ... ... ... 0.951 0.902 0.851 0.814 0.784 0.759 0.738 0.718 0.701 0.685 0.671 2550
2600 ... ... ... ... ... ... 0.951 0.903 0.849 0.812 0.782 0.756 0.735 0.715 0.698 0.682 0.664 2600
2650 ... ... ... ... ... ... 0.952 0.903 0.848 0.809 0.779 0.754 0.731 0.712 0.695 0.679 0.664 2650
2700 ... ... ... ... ... ... 0.952 0.903 0.846 0.807 0.776 0.750 0.728 0.708 0.691 0.675 0.661 2700
2750 ... ... ... ... ... ... 0.953 0.903 0.844 0.804 0.773 0.747 0.724 0.705 0.687 0.671 0.657 2750
2800 ... ... ... ... ... ... 0.956 0.903 0.842 0.801 0.769 0.743 0.721 0.701 0.684 0.668 0.653 2800
2850 ... ... ... ... ... ... 0.959 0.902 0.839 0.798 0.766 0.739 0.717 0.697 0.679 0.663 0.649 2850
2900 ... ... ... ... ... ... 0.963 0.902 0.836 0.794 0.762 0.735 0.713 0.693 0.675 0.659 0.645 2900
2950 ... ... ... ... ... ... ... 0.902 0.834 0.790 0.758 0.731 0.708 0.688 0.671 0.655 0.640 2950
3000 ... ... ... ... ... ... ... 0.901 0.831 0.786 0.753 0.726 0.704 0.684 0.666 0.650 0.635 3000
3050 ... ... ... ... ... ... ... 0.899 0.827 0.782 0.749 0.722 0.699 0.679 0.661 0.645 0.630 3050
3100 ... ... ... ... ... ... ... 0.896 0.823 0.777 0.744 0.716 0.693 0.673 0.656 0.640 0.625 3100
3150 ... ... ... ... ... ... ... 0.894 0.819 0.772 0.738 0.711 0.688 0.668 0.650 0.634 0.620 3150
3200 ... ... ... ... ... ... ... 0.889 0.815 0.767 0.733 0.705 0.682 0.662 0.644 0.628 0.614 3200

32
14 33
JSV-FF200

10 Flowing
Pressure
Super Heat Correction Factor, KSH (Metric Units)
SUPERHEAT CORRECTION FACTOR,KSH
Total Temperature ,˚C,of Superheated Steam
SUPERHEAT CORRECTION FACTOR,KSH
Total Temperature ,˚C,of Superheated Steam
Flowing
Pressure
(Mpa) 205 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 (Mpa)
0.50 0.991 0.968 0.942 0.919 0.896 0.876 0.857 0.839 0.823 0.807 0.792 0.778 0.765 0.752 0.740 0.728 0.717 0.706 0.50
0.75 0.995 0.972 0.946 0.922 0.899 0.878 0.859 0.841 0.824 0.808 0.793 0.779 0.766 0.753 0.740 0.729 0.717 0.707 0.75
1.00 0.985 0.973 0.950 0.925 0.902 0.880 0.861 0.843 0.825 0.809 0.794 0.780 0.766 0.753 0.741 0.729 0.718 0.707 1.00
1.25 0.981 0.976 0.954 0.928 0.905 0.883 0.863 0.844 0.827 0.810 0.795 0.781 0.767 0.754 0.741 0.729 0.718 0.707 1.25
1.50 ... ... 0.957 0.932 0.907 0.885 0.865 0.846 0.828 0.812 0.796 0.782 0.768 0.755 0.742 0.730 0.718 0.708 1.50
1.75 ... ... 0.959 0.935 0.910 0.887 0.866 0.847 0.829 0.813 0.797 0.782 0.769 0.756 0.743 0.731 0.719 0.708 1.75
2.00 ... ... 0.960 0.939 0.913 0.889 0.868 0.849 0.831 0.814 0.798 0.784 0.769 0.756 0.744 0.731 0.720 0.708 2.00
2.25 ... ... 0.963 0.943 0.916 0.892 0.870 0.850 0.832 0.815 0.799 0.785 0.770 0.757 0.744 0.732 0.720 0.709 2.25
2.50 ... ... ... 0.946 0.919 0.894 0.872 0.852 0.834 0.816 0.800 0.785 0.771 0.757 0.744 0.732 0.720 0.710 2.50
2.75 ... ... ... 0.948 0.922 0.897 0.874 0.854 0.835 0.817 0.801 0.786 0.772 0.758 0.745 0.733 0.721 0.710 2.75
3.00 ... ... ... 0.949 0.925 0.899 0.876 0.855 0.837 0.819 0.802 0.787 0.772 0.759 0.746 0.733 0.722 0.710 3.00
3.25 ... ... ... 0.951 0.929 0.902 0.879 0.857 0.838 0.820 0.803 0.788 0.773 0.759 0.746 0.734 0.722 0.711 3.25
3.50 ... ... ... 0.953 0.933 0.905 0.881 0.859 0.840 0.822 0.804 0.789 0.774 0.760 0.747 0.734 0.722 0.711 3.50
3.75 ... ... ... 0.956 0.936 0.908 0.883 0.861 0.841 0.823 0.806 0.790 0.775 0.761 0.748 0.735 0.723 0.711 3.75
4.00 ... ... ... 0.959 0.940 0.910 0.885 0.863 0.842 0.824 0.807 0.791 0.776 0.762 0.748 0.735 0.723 0.712 4.00
4.25 ... ... ... 0.961 0.943 0.913 0.887 0.864 0.844 0.825 0.808 0.792 0.776 0.762 0.749 0.736 0.724 0.713 4.25
4.50 ... ... ... ... 0.944 0.917 0.890 0.866 0.845 0.826 0.809 0.793 0.777 0.763 0.749 0.737 0.725 0.713 4.50
4.75 ... ... ... ... 0.946 0.919 0.892 0.868 0.847 0.828 0.810 0.793 0.778 0.764 0.750 0.737 0.725 0.713 4.75
5.00 ... ... ... ... 0.947 0.922 0.894 0.870 0.848 0.829 0.811 0.794 0.779 0.765 0.751 0.738 0.725 0.714 5.00
5.25 ... ... ... ... 0.949 0.926 0.897 0.872 0.850 0.830 0.812 0.795 0.780 0.765 0.752 0.738 0.726 0.714 5.25
5.50 ... ... ... ... 0.952 0.930 0.899 0.874 0.851 0.831 0.813 0.797 0.780 0.766 0.752 0.739 0.727 0.714 5.50
5.75 ... ... ... ... 0.954 0.933 0.902 0.876 0.853 0.833 0.815 0.798 0.782 0.767 0.753 0.739 0.727 0.715 5.75
6.00 ... ... ... ... 0.957 0.937 0.904 0.878 0.855 0.834 0.816 0.798 0.783 0.768 0.753 0.740 0.727 0.716 6.00
6.25 ... ... ... ... 0.960 0.940 0.907 0.880 0.856 0.836 0.817 0.799 0.783 0.768 0.754 0.740 0.728 0.716 6.25
6.50 ... ... ... ... 0.964 0.944 0.910 0.882 0.859 0.837 0.818 0.801 0.784 0.769 0.754 0.741 0.729 0.716 6.50
6.75 ... ... ... ... 0.966 0.946 0.913 0.885 0.860 0.839 0.819 0.802 0.785 0.769 0.755 0.742 0.729 0.717 6.75
7.00 ... ... ... ... ... 0.947 0.916 0.887 0.862 0.840 0.820 0.802 0.786 0.770 0.756 0.742 0.729 0.717 7.00
7.25 ... ... ... ... ... 0.949 0.919 0.889 0.863 0.842 0.822 0.803 0.787 0.771 0.756 0.743 0.730 0.717 7.25
7.50 ... ... ... ... ... 0.951 0.922 0.891 0.865 0.843 0.823 0.805 0.788 0.772 0.757 0.744 0.730 0.718 7.50
7.75 ... ... ... ... ... 0.953 0.925 0.893 0.867 0.844 0.824 0.806 0.788 0.772 0.758 0.744 0.731 0.719 7.75
8.00 ... ... ... ... ... 0.955 0.928 0.896 0.869 0.846 0.825 0.806 0.789 0.773 0.758 0.744 0.732 0.719 8.00
8.25 ... ... ... ... ... 0.957 0.932 0.898 0.871 0.847 0.827 0.807 0.790 0.774 0.759 0.745 0.732 0.719 8.25
8.50 ... ... ... ... ... 0.960 0.935 0.901 0.873 0.849 0.828 0.809 0.791 0.775 0.760 0.746 0.732 0.720 8.50
8.75 ... ... ... ... ... 0.963 0.939 0.903 0.875 0.850 0.829 0.810 0.792 0.776 0.760 0.746 0.733 0.721 8.75
9.00 ... ... ... ... ... 0.966 0.943 0.906 0.877 0.852 0.830 0.811 0.793 0.776 0.761 0.747 0.734 0.721 9.00
9.25 ... ... ... ... ... 0.970 0.947 0.909 0.879 0.853 0.832 0.812 0.794 0.777 0.762 0.747 0.734 0.721 9.25
9.50 ... ... ... ... ... 0.973 0.950 0.911 0.881 0.855 0.833 0.813 0.795 0.778 0.763 0.748 0.734 0.722 9.50
9.75 ... ... ... ... ... 0.977 0.954 0.914 0.883 0.857 0.834 0.814 0.796 0.779 0.763 0.749 0.735 0.722 9.75
10.00 ... ... ... ... ... 0.981 0.957 0.917 0.885 0.859 0.836 0.815 0.797 0.780 0.764 0.749 0.735 0.722 10.00
10.25 ... ... ... ... ... 0.984 0.959 0.920 0.887 0.860 0.837 0.816 0.798 0.780 0.764 0.750 0.736 0.723 10.25
10.50 ... ... ... ... ... ... 0.961 0.923 0.889 0.862 0.838 0.817 0.799 0.781 0.765 0.750 0.737 0.723 10.50
10.75 ... ... ... ... ... ... 0.962 0.925 0.891 0.863 0.839 0.818 0.799 0.782 0.766 0.751 0.737 0.724 10.75
11.00 ... ... ... ... ... ... 0.963 0.928 0.893 0.865 0.840 0.819 0.780 0.782 0.766 0.751 0.737 0.724 11.00
11.25 ... ... ... ... ... ... 0.964 0.930 0.893 0.865 0.840 0.819 0.799 0.781 0.765 0.750 0.736 0.723 11.25
11.50 ... ... ... ... ... ... 0.964 0.931 0.894 0.865 0.840 0.818 0.798 0.780 0.764 0.749 0.735 0.722 11.50
11.75 ... ... ... ... ... ... 0.965 0.932 0.894 0.865 0.839 0.817 0.797 0.780 0.763 0.748 0.734 0.721 11.75
12.00 ... ... ... ... ... ... 0.966 0.933 0.894 0.864 0.839 0.817 0.797 0.779 0.762 0.747 0.733 0.719 12.00
12.25 ... ... ... ... ... ... 0.967 0.935 0.895 0.864 0.839 0.816 0.796 0.778 0.761 0.746 0.732 0.718 12.25
12.50 ... ... ... ... ... ... 0.967 0.936 0.896 0.864 0.838 0.816 0.796 0.777 0.760 0.745 0.731 0.717 12.50
12.75 ... ... ... ... ... ... 0.968 0.937 0.896 0.864 0.838 0.815 0.795 0.776 0.759 0.744 0.729 0.716 12.75
13.00 ... ... ... ... ... ... 0.969 0.939 0.896 0.864 0.837 0.814 0.794 0.775 0.758 0.743 0.728 0.715 13.00
13.25 ... ... ... ... ... ... 0.971 0.940 0.897 0.864 0.837 0.813 0.792 0.774 0.757 0.741 0.727 0.713 13.25
13.50 ... ... ... ... ... ... 0.972 0.942 0.897 0.863 0.837 0.813 0.792 0.773 0.756 0.740 0.725 0.712 13.50
14.00 ... ... ... ... ... ... 0.976 0.946 0.897 0.863 0.835 0.811 0.790 0.771 0.753 0.737 0.723 0.709 14.00
14.25 ... ... ... ... ... ... 0.978 0.947 0.898 0.862 0.834 0.810 0.789 0.770 0.752 0.736 0.721 0.707 14.25
14.50 ... ... ... ... ... ... 0.000 0.948 0.898 0.862 0.833 0.809 0.787 0.768 0.751 0.734 0.720 0.706 14.50
14.75 ... ... ... ... ... ... ... 0.948 0.898 0.862 0.832 0.808 0.786 0.767 0.749 0.733 0.719 0.704 14.75
15.00 ... ... ... ... ... ... ... 0.948 0.899 0.861 0.832 0.807 0.785 0.766 0.748 0.732 0.717 0.703 15.00

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


15.25 ... ... ... ... ... ... ... 0.947 0.899 0.861 0.831 0.806 0.784 0.764 0.746 0.730 0.716 0.702 15.25
15.50 ... ... ... ... ... ... ... 0.947 0.899 0.861 0.830 0.804 0.782 0.763 0.745 0.728 0.714 0.700 15.50
15.75 ... ... ... ... ... ... ... 0.946 0.899 0.860 0.829 0.803 0.781 0.761 0.743 0.727 0.712 0.698 15.75
16.00 ... ... ... ... ... ... ... 0.945 0.900 0.859 0.828 0.802 0.779 0.759 0.741 0.725 0.710 0.696 16.00
16.25 ... ... ... ... ... ... ... 0.945 0.900 0.859 0.827 0.801 0.778 0.757 0.739 0.723 0.708 0.694
Total Safety Solution16.25
Provider!
16.50 ... ... ... ... ... ... ... 0.945 0.900 0.858 0.826 0.799 0.776 0.756 0.738 0.721 0.706 0.692 16.50
16.75 ... ... ... ... ... ... ... 0.944 0.900 0.857 0.825 0.797 0.774 0.754 0.736 0.719 0.704 0.690 16.75
17.00 ... ... ... ... ... ... ... 0.944 0.900 0.856 0.823 0.796 0.773 0.752 0.734 0.717 0.702 0.688 17.00
17.25 ... ... ... ... ... ... ... 0.944 0.900 0.855 0.822 0.794 0.771 0.750 0.732 0.715 0.700 0.686 17.25
17.50 ... ... ... ... ... ... ... 0.944 0.900 0.854 0.820 0.792 0.769 0.748 0.730 0.713 0.698 0.684 17.50
17.75 ... ... ... ... ... ... ... 0.944 0.900 0.853 0.819 0.791 0.767 0.746 0.728 0.711 0.696 0.681 17.75
18.00 ... ... ... ... ... ... ... 0.944 0.901 0.852 0.817 0.789 0.765 0.744 0.725 0.709 0.694 0.679 18.00
18.25 ... ... ... ... ... ... ... 0.945 0.901 0.851 0.815 0.787 0.763 0.742 0.723 0.706 0.691 0.677 18.25
18.50 ... ... ... ... ... ... ... 0.945 0.901 0.850 0.814 0.785 0.761 0.739 0.720 0.704 0.689 0.674 18.50
18.75 ... ... ... ... ... ... ... 0.945 0.901 0.849 0.812 0.783 0.758 0.737 0.718 0.701 0.686 0.671 18.75
19.00 ... ... ... ... ... ... ... 0.946 0.901 0.847 0.810 0.781 0.756 0.734 0.715 0.698 0.683 0.669 19.00
19.25 ... ... ... ... ... ... ... 0.948 0.901 0.846 0.808 0.778 0.753 0.732 0.713 0.696 0.681 0.666 19.25
19.50 ... ... ... ... ... ... ... 0.950 0.900 0.844 0.806 0.776 0.750 0.729 0.710 0.693 0.677 0.663 19.50
19.75 ... ... ... ... ... ... ... 0.952 0.899 0.842 0.803 0.773 0.748 0.726 0.707 0.690 0.674 0.660 19.75
20.00 ... ... ... ... ... ... ... ... 0.899 0.840 0.801 0.770 0.745 0.723 0.704 0.687 0.671 0.657 20.00
20.25 ... ... ... ... ... ... ... ... 0.899 0.839 0.798 0.767 0.742 0.720 0.701 0.683 0.668 0.654 20.25
20.50 ... ... ... ... ... ... ... ... 0.899 0.837 0.795 0.764 0.738 0.717 0.697 0.680 0.665 0.651 20.50
20.75 ... ... ... ... ... ... ... ... 0.898 0.834 0.792 0.761 0.735 0.713 0.694 0.677 0.661 0.647 20.75
21.00 ... ... ... ... ... ... ... ... 0.896 0.832 0.790 0.758 0.732 0.710 0.691 0.673 0.658 0.643 21.00
21.25 ... ... ... ... ... ... ... ... 0.894 0.829 0.786 0.754 0.728 0.706 0.686 0.669 0.654 0.640 21.25
21.50 ... ... ... ... ... ... ... ... 0.892 0.826 0.783 0.750 0.724 0.702 0.682 0.665 0.650 0.636 21.50
21.75 ... ... ... ... ... ... ... ... 0.891 0.823 0.779 0.746 0.720 0.698 0.679 0.661 0.646 0.631 21.75
22.00 ... ... ... ... ... ... ... ... 0.887 0.820 0.776 0.730 0.716 0.694 0.674 0.657 0.641 0.627 22.00

34
14 35
JSV-FF200

11 Super Critical Correction Factor, Ksc (USC Units)


Flowing Pressure (psia)
SUPERCRITICAL CORRECTION FACTOR,Ksc
Total Temperature ,˚F,of Supercritical Steam
SUPERCRITICAL CORRECTION FACTOR,Ksc
Total Temperature ,˚F,of Supercritical Steam Flowing Pressure (psia)
750 800 850 900 950 1,000 1,050 1,100 1,150 1,200
3,208.2 1.059 0.971 0.913 0.872 0.839 0.811 0.788 0.767 0.748 0.731 3,208.2
3,250 1.064 0.975 0.916 0.874 0.841 0.813 0.788 0.767 0.748 0.731 3,250
3,300 1.070 0.980 0.919 0.876 0.842 0.814 0.790 0.768 0.749 0.732 3,300
3,350 1.077 0.985 0.922 0.878 0.844 0.815 0.791 0.769 0.750 0.732 3,350
3,400 1.084 0.990 0.925 0.881 0.846 0.817 0.792 0.770 0.750 0.733 3,400
3,450 1.091 0.996 0.929 0.883 0.848 0.818 0.793 0.771 0.751 0.734 3,450
3,500 1.100 1.002 0.932 0.885 0.849 0.819 0.794 0.772 0.752 0.734 3,500
3,550 1.109 1.008 0.935 0.888 0.851 0.821 0.795 0.773 0.753 0.735 3,550
3,600 1.118 1.014 0.939 0.890 0.853 0.822 0.796 0.774 0.754 0.735 3,600
3,650 1.129 1.020 0.943 0.893 0.855 0.824 0.797 0.775 0.754 0.736 3,650
3,700 1.141 1.027 0.946 0.895 0.857 0.825 0.799 0.775 0.755 0.737 3,700
3,750 1.153 1.034 0.950 0.898 0.859 0.827 0.800 0.776 0.756 0.737 3,750
3,800 1.168 1.041 0.954 0.900 0.861 0.828 0.801 0.777 0.757 0.738 3,800
3,850 1.186 1.048 0.958 0.903 0.862 0.830 0.802 0.778 0.757 0.739 3,850
3,900 1.205 1.056 0.962 0.906 0.864 0.831 0.803 0.779 0.758 0.739 3,900
3,950 1.227 1.064 0.966 0.908 0.866 0.833 0.804 0.780 0.759 0.740 3,950
4,000 1.251 1.072 0.970 0.911 0.868 0.834 0.806 0.781 0.760 0.741 4,000
4,050 1.279 1.080 0.974 0.914 0.870 0.836 0.807 0.782 0.760 0.741 4,050
4,100 1.310 1.089 0.978 0.916 0.872 0.837 0.808 0.783 0.761 0.742 4,100
4,150 1.343 1.098 0.983 0.919 0.874 0.839 0.809 0.784 0.762 0.743 4,150
4,200 1.395 1.107 0.987 0.922 0.876 0.840 0.810 0.785 0.763 0.743 4,200
4,250 1.444 1.116 0.992 0.925 0.878 0.842 0.812 0.786 0.764 0.744 4,250
4,300 1.491 1.125 0.997 0.928 0.881 0.844 0.813 0.787 0.765 0.745 4,300
4,350 1.538 1.135 1.002 0.931 0.883 0.845 0.814 0.788 0.765 0.745 4,350
4,400 ... 1.146 1.007 0.934 0.885 0.847 0.815 0.789 0.766 0.746 4,400
4,450 ... 1.157 1.012 0.937 0.887 0.848 0.817 0.790 0.767 0.746 4,450
4,500 ... 1.169 1.017 0.940 0.889 0.850 0.818 0.791 0.768 0.747 4,500
4,550 ... 1.181 1.022 0.943 0.892 0.852 0.819 0.792 0.768 0.748 4,550
4,600 ... 1.194 1.027 0.947 0.894 0.853 0.820 0.793 0.769 0.749 4,600
4,650 ... 1.207 1.033 0.950 0.896 0.855 0.822 0.794 0.770 0.749 4,650
4,070 ... 1.220 1.038 0.953 0.898 0.857 0.823 0.795 0.771 0.750 4,070
4,570 ... 1.234 1.044 0.957 0.900 0.858 0.824 0.796 0.772 0.751 4,570
4,800 ... 1.248 1.050 0.960 0.903 0.860 0.826 0.797 0.773 0.751 4,800
4,850 ... 1.263 1.056 0.963 0.905 0.862 0.827 0.798 0.774 0.752 4,850
4,900 ... 1.278 1.062 0.967 0.908 0.863 0.828 0.799 0.774 0.753 4,900
4,950 ... 1.294 1.069 0.970 0.910 0.865 0.830 0.800 0.775 0.753 4,950
5,000 ... 1.310 1.075 0.974 0.912 0.867 0.831 0.801 0.776 0.754 5,000
5,050 ... 1.326 1.082 0.978 0.915 0.869 0.832 0.803 0.777 0.755 5,050

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


5,100 ... 1.343 1.088 0.981 0.917 0.871 0.834 0.804 0.778 0.755 5,100
5,150 ... 1.360 1.095 0.985 0.920 0.872 0.835 0.805 0.779 0.756 5,150
5,200 ... 1.377 1.102 0.989 0.922 0.874 0.837 0.806 0.780 0.757 5,200
5,250 ... 1.393 1.109 0.993 0.925 0.876 0.838 0.807 0.780 0.758 Total Safety Solution
5,250 Provider!
5,300 ... 1.411 1.116 0.997 0.927 0.878 0.839 0.808 0.781 0.758 5,300
5,350 ... 1.427 1.123 1.001 0.930 0.880 0.841 0.809 0.782 0.759 5,350
5,400 ... 1.443 1.131 1.004 0.933 0.882 0.842 0.810 0.783 0.760 5,400
5,450 ... 1.460 1.139 1.009 0.935 0.884 0.844 0.811 0.784 0.760 5,450
5,500 ... 1.476 1.146 1.013 0.938 0.886 0.845 0.812 0.785 0.761 5,500
5,550 ... 1.491 1.154 1.017 0.941 0.887 0.846 0.813 0.786 0.762 5,550
5,600 ... 1.507 1.162 1.021 0.943 0.889 0.848 0.815 0.787 0.763 5,600
5,650 ... 1.522 1.171 1.025 0.946 0.891 0.849 0.816 0.788 0.763 5,650
5,700 ... 1.536 1.179 1.030 0.949 0.893 0.851 0.817 0.788 0.764 5,700
5,750 ... 1.551 1.187 1.034 0.952 0.895 0.852 0.818 0.789 0.765 5,750
5,800 ... 1.565 1.195 1.038 0.955 0.897 0.854 0.819 0.790 0.765 5,800
5,850 ... 1.578 1.204 1.043 0.957 0.899 0.855 0.820 0.791 0.766 5,850
5,900 ... 1.591 1.212 1.047 0.960 0.901 0.857 0.821 0.792 0.767 5,900
5,950 ... 1.603 1.221 1.052 0.963 0.903 0.858 0.823 0.793 0.768 5,950
6,000 ... 1.615 1.229 1.057 0.966 0.906 0.860 0.824 0.794 0.768 6,000

36
14 37
JSV-FF200

12 MPa
Super Critical Correction Factor, Ksc (Metric Units)
Flowing Pressure
400 425
SupercriticaL Correction Factor,Ksc
Total Temperature,˚C,of Supercritical Steam
450 475 500 525 550 575
SupercriticaL Correction Factor,Ksc
Total Temperature,˚C,of Supercritical Steam
600 625 650
Flowing Pressure
MPa
22.12 1.056 0.976 0.922 0.883 0.851 0.824 0.801 0.781 0.762 0.745 0.730 22.12
22.25 1.058 0.978 0.924 0.884 0.852 0.825 0.802 0.781 0.763 0.746 0.730 22.25
22.50 1.063 0.982 0.926 0.886 0.853 0.826 0.803 0.782 0.763 0.746 0.731 22.50
22.75 1.067 0.985 0.929 0.887 0.855 0.827 0.803 0.783 0.764 0.747 0.731 22.75
23.00 1.072 0.989 0.931 0.889 0.856 0.828 0.804 0.783 0.764 0.747 0.732 23.00
23.25 1.077 0.993 0.934 0.891 0.858 0.830 0.805 0.784 0.765 0.748 0.732 23.25
23.50 1.082 0.997 0.937 0.893 0.859 0.831 0.806 0.785 0.766 0.748 0.732 23.50
23.75 1.087 1.001 0.939 0.895 0.860 0.832 0.807 0.785 0.766 0.749 0.733 23.75
24.00 1.093 1.006 0.942 0.897 0.862 0.833 0.808 0.786 0.767 0.749 0.733 24.00
24.25 1.099 1.010 0.945 0.899 0.863 0.834 0.809 0.787 0.768 0.750 0.734 24.25
24.50 1.106 1.014 0.948 0.901 0.865 0.835 0.810 0.788 0.768 0.751 0.734 24.50
24.75 1.112 1.019 0.950 0.903 0.866 0.836 0.811 0.789 0.769 0.751 0.735 24.75
25.00 1.120 1.024 0.953 0.905 0.868 0.837 0.812 0.789 0.769 0.752 0.735 25.00
25.25 1.128 1.029 0.956 0.907 0.869 0.839 0.813 0.790 0.770 0.752 0.736 25.25
25.50 1.136 1.034 0.959 0.909 0.871 0.840 0.814 0.791 0.771 0.753 0.736 25.50
25.75 1.145 1.039 0.962 0.911 0.872 0.841 0.815 0.792 0.771 0.753 0.737 25.75
26.00 1.155 1.045 0.966 0.913 0.874 0.842 0.816 0.792 0.772 0.754 0.737 26.00
26.25 1.166 1.050 0.969 0.915 0.875 0.843 0.817 0.793 0.773 0.754 0.737 26.25
26.50 1.178 1.056 0.972 0.917 0.877 0.845 0.818 0.794 0.773 0.755 0.738 26.50
26.75 1.192 1.062 0.975 0.919 0.879 0.846 0.819 0.795 0.774 0.755 0.738 26.75
27.00 1.206 1.068 0.979 0.921 0.880 0.847 0.820 0.796 0.775 0.756 0.739 27.00
27.25 1.222 1.074 0.982 0.924 0.882 0.848 0.820 0.796 0.775 0.756 0.739 27.25
27.50 1.239 1.081 0.985 0.926 0.883 0.850 0.821 0.797 0.776 0.757 0.740 27.50
27.75 1.258 1.088 0.989 0.928 0.885 0.851 0.822 0.798 0.777 0.758 0.740 27.75
28.00 1.278 1.095 0.992 0.930 0.887 0.852 0.824 0.799 0.777 0.758 0.741 28.00
28.25 1.300 1.102 0.996 0.933 0.888 0.854 0.825 0.800 0.778 0.759 0.741 28.25
28.50 1.323 1.109 1.000 0.935 0.890 0.855 0.826 0.801 0.779 0.759 0.742 28.50
28.75 1.354 1.117 1.004 0.937 0.892 0.856 0.827 0.801 0.779 0.760 0.742 28.75
29.00 1.390 1.126 1.007 0.940 0.893 0.857 0.828 0.802 0.780 0.760 0.743 29.00
29.25 1.424 1.134 1.011 0.942 0.895 0.859 0.829 0.803 0.781 0.761 0.743 29.25
29.50 1.457 1.143 1.015 0.945 0.897 0.860 0.830 0.804 0.781 0.762 0.744 29.50
29.75 1.490 1.151 1.019 0.947 0.899 0.861 0.831 0.805 0.782 0.762 0.744 29.75
30.00 ... 1.158 1.023 0.950 0.900 0.863 0.832 0.806 0.783 0.763 0.745 30.00
30.25 ... 1.098 1.028 0.952 0.902 0.864 0.833 0.806 0.784 0.763 0.745 30.25
30.50 ... 1.083 1.032 0.955 0.904 0.865 0.834 0.807 0.784 0.764 0.746 30.50
30.75 ... 1.090 1.036 0.957 0.906 0.867 0.835 0.808 0.785 0.764 0.746 30.75
31.00 ... 1.099 1.041 0.960 0.908 0.868 0.836 0.809 0.786 0.765 0.746 31.00
31.25 ... 1.107 1.046 0.963 0.910 0.870 0.837 0.810 0.786 0.766 0.747 31.25
31.50 ... 1.115 1.050 0.966 0.911 0.871 0.838 0.811 0.787 0.766 0.748 31.50
31.75 ... 1.124 1.055 0.968 0.913 0.872 0.839 0.812 0.788 0.767 0.748 31.75
32.00 ... 1.133 1.060 0.971 0.915 0.874 0.840 0.812 0.788 0.767 0.748 32.00
32.25 ... 1.142 1.065 0.974 0.917 0.875 0.841 0.813 0.789 0.768 0.749 32.25
32.50 ... 1.151 1.070 0.977 0.919 0.877 0.843 0.814 0.790 0.769 0.750 32.50
32.75 ... 1.160 1.075 0.980 0.921 0.878 0.844 0.815 0.791 0.769 0.750 32.75
33.00 ... 1.170 1.080 0.983 0.923 0.879 0.845 0.816 0.791 0.770 0.750 33.00
33.25 ... 1.180 1.085 0.986 0.925 0.881 0.846 0.817 0.792 0.770 0.751 33.25
33.50 ... 1.190 1.091 0.988 0.927 0.882 0.847 0.818 0.793 0.771 0.751 33.50
33.75 ... 1.201 1.096 0.992 0.929 0.884 0.848 0.819 0.793 0.772 0.752 33.75
34.00 ... 1.211 1.102 0.995 0.931 0.885 0.849 0.820 0.794 0.772 0.752 34.00
34.25 ... 1.222 1.108 0.998 0.933 0.887 0.850 0.820 0.795 0.773 0.753 34.25
34.50 ... 1.233 1.114 1.001 0.935 0.888 0.852 0.821 0.796 0.773 0.753 34.50
34.75 ... 1.244 1.119 1.004 0.937 0.890 0.853 0.822 0.796 0.774 0.754 34.75
35.00 ... 1.255 1.125 1.007 0.939 0.891 0.854 0.823 0.797 0.775 0.754 35.00

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


35.25 ... 1.267 1.131 1.011 0.941 0.893 0.855 0.824 0.798 0.775 0.755 35.25
35.50 ... 1.278 1.137 1.014 0.944 0.894 0.856 0.825 0.799 0.776 0.755 35.50
35.75 ... 1.290 1.144 1.017 0.946 0.896 0.858 0.826 0.799 0.776 0.756 35.75
36.00 ... 1.301 1.150 1.021 0.948 0.898 0.859 0.827 0.800 0.777 0.757 36.00
36.25 ... 1.313 1.156 1.024 0.950 0.899 0.860 0.828 0.801 0.778 0.757 Total Safety Solution
36.25 Provider!
36.50 ... 1.324 1.162 1.027 0.952 0.901 0.861 0.829 0.802 0.778 0.758 36.50
36.75 ... 1.336 1.169 1.031 0.955 0.902 0.862 0.830 0.802 0.779 0.758 36.75
37.00 ... 1.347 1.175 1.034 0.957 0.904 0.864 0.831 0.803 0.779 0.759 37.00
37.25 ... 1.358 1.182 1.038 0.959 0.906 0.865 0.832 0.804 0.780 0.759 37.25
37.50 ... 1.369 1.188 1.042 0.961 0.907 0.866 0.833 0.805 0.781 0.760 37.50
37.75 ... 1.380 1.195 1.045 0.964 0.909 0.867 0.834 0.805 0.781 0.760 37.75
38.00 ... 1.391 1.201 1.049 0.966 0.910 0.868 0.834 0.806 0.782 0.761 38.00
38.25 ... 1.402 1.208 1.053 0.968 0.912 0.870 0.835 0.807 0.783 0.761 38.25
38.50 ... 1.412 1.215 1.056 0.971 0.914 0.871 0.836 0.808 0.783 0.762 38.50
38.75 ... 1.422 1.222 1.060 0.973 0.915 0.872 0.837 0.809 0.784 0.762 38.75
39.00 ... 1.433 1.228 1.064 0.975 0.917 0.873 0.838 0.809 0.784 0.763 39.00
39.25 ... 1.443 1.235 1.068 0.978 0.919 0.875 0.839 0.810 0.785 0.763 39.25
39.50 ... 1.453 1.242 1.072 0.980 0.921 0.876 0.840 0.811 0.786 0.764 39.50
39.75 ... 1.463 1.248 1.076 0.983 0.922 0.877 0.841 0.812 0.786 0.764 39.75
40.00 ... 1.472 1.255 1.080 0.985 0.924 0.879 0.842 0.812 0.787 0.765 40.00
40.25 ... 1.481 1.262 1.084 0.988 0.926 0.880 0.843 0.813 0.788 0.765 40.25
40.50 ... 1.490 1.268 1.088 0.990 0.928 0.881 0.844 0.814 0.788 0.766 40.50
40.75 ... 1.499 1.275 1.092 0.993 0.929 0.882 0.845 0.815 0.789 0.766 40.75
41.00 ... 1.507 1.282 1.096 0.995 0.931 0.884 0.846 0.816 0.790 0.767 41.00
41.25 ... 1.515 1.288 1.100 0.998 0.933 0.885 0.847 0.816 0.790 0.767 41.25

38
14 39
JSV-FF200

13 Technical Data

A Regulation Code, or Standard & Example B Testing System of JOKWANG I.L.I


ASME Sec. I (POWER BOILER) Our company carry out test according to ASME code by using equipment below.
PG ≤ 10.3 MPag W = 5.25 A · P1 · Kd · Ksh
10.3 < PG ≤ 22.1 MPag W = 5.25 A · P1 · Kd · Ksh · (27.6P-1,000/33.2P-1,061) Steam Test System
22.1 MPag < PG W = 5.25 A · P1 · Kd · KSC
• Max. operating pressure : 225kgf/cm2
• Max. operating temperature : 600℃
Nomenclature
W = Steam discharge capacity (kg/hr)
A = Nozzle throat area (mm2)
P = Set pressure*1.03 (MPa)
P1 = Set pressure+0.014+0.101 or 1.03xset pressure+0.101 whichever is Larger (MPa) CONTROL ROOM

Kd = Coefficient of discharge 0.869 BOILER

Ksh = Superheated steam correction facotr


SUPER
HEATER
WATER

Ksc = Supercritical Correction Factor


TANK

PRESSURE
VESSEL

Example #1
Testing With Auxiliary Lift-Assist Devices
Set Pressure 3 MPa 3 MPa P1 = 3+0.014+0.101=3.115
Over Pressure 3% P1 = 3×1.03+0.101=3.191 This test system has the ability to test relief valves and Force exerted against
Orifice H identify those in need of adjustment or full service Valve Spring
Nozzle throat area 706.5 mm2 with no operational interruptions.

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


Ksh 1 W = 5.25×706.5×(3×1.03+0.101)×0.869×1
Kd 0.869 = 10,285.33 (kg/hr) • Totally automated operation produces accurate,
consistent, reproducible results within all ASME
Total Safety Solution Provider!
codes.
• Temperature compensated load and pressure sensors Essential Parameters:
Example #2
provide wide range of valve sizes and line pressures. 1- Seat Area
Set Pressure 11 MPa P1 = 11+0.014+0.101=11.115 2- Line Pressure
• Standard load rig allows for lift forces up to 4,500 3- Set Pressure
Over Pressure 3% P1 = 11×1.03+0.101=11.431
Orifice H P = 11×1.03=11.33
kgf(10,000 lbf).
Nozzle throat area 706.5 mm2
Ksh 1 W = 5.25×706.5×(11×1.03+0.101)×0.869×1
Kd 0.869 ×{(27.6P−1,000)/(33.2P−1,061)}
=36,976.44 (kg/hr)

40
14 41
JSV-FF200

Technical Data

C Single & Multiple Installation (by_ASME Sec.I) D Noise (by_API STD 521 7.3.4.3.1-2007)

7.3.4.3.1 The noise level at 30m (100ft) from the point of discharge to the atmosphere can be
approximated by Equation :

L 30(100) = L +10Log (0.5qm ∙ c 2 )


Primary PRV Supplemental PRV Vessel
Specifications Specifications Pressure (%) c = 223{(k·T )/M} 0.5 [US Unit]
(single) (Multiple) c = 91.2(k·T )/M} 0.5 [Metric Unit]

106
Supplemental PRV
Overpressure L30(100) = the noise level at 30m(100ft) from the point of discharge, expressed in decibels;
(3%)
L = the noise level from Figure, expressed in decibels;
Supplemental PRV 103 qm = the mass flow through the valve, expressed in kilograms persecond (pound per second)
Set Pressure
c = the speed of sound in the gas at the valve, expressed in meters per second (feet per second)
Primary PRV
Overpressure k = the ratio of the specific heats in the gas
(3%) Supplemental PRV
Blowdown M = the relative molecular mass of the gas
(4%)
Primary PRV 100 T = the gas tamperature, expressed in kelvin (degrees rankin)
Set Pressure

Reseat Pressure 99
Primary PRV Y
Blowdown
70

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


(4%)

60
Reseat Pressure 96 Absolute Relieving Pressure
Total Safety Solution Provider!
RP =
Absolute Back Pressure
50

X = pressure ratio, PR
40
Y = sound pressure level = L

30

20
1.5 2 3 4 5 6 7 8 9 10 X

42
14 43
JSV-FF200

Technical Data

E Reaction Force (by_API STD 520 5.8.2_6 edition) F Safety Valve Installation (by_ASME B31.1-2012)
The following formula is based on a condition of critical steady-state flow of a compressible fluid that An installation where the fluid is discharged directly to the atmosphere or to a vent pipe that is uncoupled
discharges to the atmosphere through an elbow and a vertical discharge pipe.
from the safety valve. Figure 1 shows a typical open discharge installation with an elbow installed at the
The reaction force (F) includes the effects of both momentum and static pressure; thus, for any gas,
vapor, or steam. valve discharge to direct the flow into a vent pipe.
The values for ' l ' and 'm' on Figure 1 are upper limits for which the rules for open discharge systems may
be used. ' l ' shall be limited to a value less than or equal to 4Do ; 'm' shall be limited to a value less than
or equal 6Do.
W kT
F= + AP [USC Units]
366 (k+1)M

kT
F = 129W + 0.1 (AP) [Metric Units]
(k+1)M

Outlet
Safety valve flanges

F = reaction force at the point of discharge to the atmosphere, lbs [N]

k = flow of any gas or vapor, lbs [kg/s]

C p = specific heat at constant pressure

C v = specific heat at constant volume

Total Safety Solution Provider! l JOKWANG CAT.NO. FF 200


Discharge
o o pipe
T = temperature at the outlet, R [ K]
Inlet flanges
Total Safety Solution Provider!
M = molecular weight of the process fluid
Inlet pipe
2
A = area of the outlet at the point of discharge, in [mm ] 2 Branch connection

P = static pressure within the outlet at the point of discharge, psig [barg] Run pipe

Figure 1

l ≤ 4Do, m ≤ 6Do

≤ ≤

44
14 45
Memo