NGR Sizing and Selection As Per IEEE
NGR Sizing and Selection As Per IEEE
Source 3Ø Load
or Network
AØ BØ
N
CØ
Neutral
Grounding
Resistor
Ir Ic
c
c
Ib Ic
a
➢ Most utilized on Medium Voltage
➢ Some 5kV systems
➢ Mainly 15kV systems
➢ Has been utilized on up to 132kV systems (rare)
➢ Used where system charging current may be
to high for High Resistance Grounding
Source 3Ø Load
or Network
AØ BØ
N
CØ
Neutral
Grounding
Resistor
Ir Ic
c
c
Ib Ic
a
➢ Resistor Amperage (ground fault let through current)
➢ System Capacitance
➢ System Bracing
➢ System Insulation
➢ Relay Trip points (Time current curve)
➢ Selective tripping
➢ Resistance increase with temperature
➢ Resistor time on (how long the fault is on the system)
➢ Single Phase Loads
Every electrical system has some natural capacitance. The capacitive
reactance of the system determines the charging current.
Conductor
Cable
insulation
Cable tray
106
Zero-sequence Capacitance: 𝐶0 = µF/phase
2𝜋𝑓𝑥0
2 3𝜋𝑓𝐶0 𝐸
Charging Current: 3𝐼𝐶0 = A
106
During an arcing or intermittent
fault, a voltage is held on the system
capacitance after the arc is
extinguished. This can lead to a
significant voltage build-up which
can stress system insulation and
lead to further faults.
𝐼𝑓 = 𝐼𝑅2 + 𝐼𝐶0
2
➢ Total fault current must not exceed the value for which the system is
braced.
➢ In many cases, the system is already braced for the three-phase fault
current which is much higher than the single line-ground fault
current of a resistance grounded system.
➢ Resistance grounded systems must be insulated for full line-line
voltage with respect to ground.
➢ Surge Arrestor Selection: NEC 280.4 (2) Impedance or Ungrounded
System. The maximum continuous operating voltage shall be the
phase-to-phase voltage of the system.
➢ Cables: NEC Table 310.13E allows for use of 100% Insulation level,
but 173% is recommended for orderly shutdown.
VAG
VAG
AØ BØ
4160V
N
2400V
CØ
HRG
NGR
4160V
380
7
360
6.5 Current
340
Resistance
6
320
300 5.5
1 2 3 4 5 6 7 8 9 10
IEEE Std 32
➢ Normally, protective relaying will trip
within a few cycles. Time Rating and Permissible
➢ IEEE 32 defines standard resistor on Temperature Rise for Neutral
times. Lowest rate is 10 seconds, but Grounding Resistors
could potentially go less to save
material/space. Time Rating Temp Rise (deg
(On Time) C)
➢ Can go as high as 30 or 60 seconds
as required (rare). Ten Seconds
760oC
(Short Time)
➢ Extended or Continuous ratings are
One Minute
almost never used in this application 760oC
(Short Time)
due to the relatively high fault
currents. Ten Minutes
610oC
(Short Time)
Extended Time 610oC
Continuous 385oC
➢ No line-to-neutral loads allowed, prevents
Hazards. 480V Wye Source
3Ø Load
AØ BØ
N
CØ
NGR
HRG
AØ BØ
N
CØ
Neutral
Grounding
Resistor
Ir Ic
c
c
Ib Ic
a
➢ Most utilized on Low Voltage
➢ Many 600V systems
➢ Some 5kV systems
➢ Has been utilized on up to 15kV systems (rare)
Source 3Ø Load
or Network
AØ BØ
N
CØ
Neutral
Grounding
Resistor
Ir Ic
c
c
Ib Ic
a
➢ Resistor Amperage (ground fault let through current)
➢ System Capacitance
➢ Alarm notification
➢ Fault Location
➢ Pulsing
➢ Data Logging
➢ Relay Coordination (What to do if there is a second fault)
➢ System Insulation
➢ Personnel training
Every electrical system has some natural capacitance. The capacitive
reactance of the system determines the charging current.
Conductor
Cable
insulation
Cable tray
106
Zero-sequence Capacitance: 𝐶0 = µF/phase
2𝜋𝑓𝑥0
2 3𝜋𝑓𝐶0 𝐸
Charging Current: 3𝐼𝐶0 = A
106
During an arcing or intermittent
fault, a voltage is held on the system
capacitance after the arc is
extinguished. This can lead to a
significant voltage build-up which
can stress system insulation and
lead to further faults.
HRG
55.4
ohms
NOTE: Tracking a ground fault can only be done on an
energized system. Due to the inherent risk of
electrocution this should only be performed by trained
and competent personnel.
Alternatives to Manual location:
➢ Add zero sequence CTs & ammeters to each feeder
➢ Use metering inherent to each breaker (newer equipment only)
CØ
HRG
55.4 80A 50A
ohms
30A 30A 30A 55A 50A 50A
0A 5A
ZSCT ZSCT
5A
Meter Meter
5A
0A
ZSCT
Motor Motor
➢ HRG systems with data logging can be used to locate
intermittent ground faults
➢ Example:
➢ Heater with ground fault comes on at 11:00am and then
turns off at 11:01am
➢ Normal Pulsing will not locate since the fault will be “gone”.
➢ HRG Data logging can help locate faulted equipment in
conjunction with DCS/SCADA data records
Fault time
frame
Equipment
On
➢ If there is a second ground
fault on another phase, it
is essentially a phase-
phase fault and at least
one feeder needs to trip
➢ Network protection
scheme should be
designed to trip the lowest
priority feeder first, then
the next, and then move
upstream.
➢ Check MCC GF pickup ratings to be sure the small ground fault current
values do not trip off the motor on the first ground fault.
➢ Also, fusing on small motors can open during a ground fault. Consult
NEC Table 430.52 for Percentage of full load current fuse ratings. Most
are 300% FLC.
➢ Resistance grounded systems must be insulated for full line-line
voltage with respect to ground.
➢ NEC 285.3: An SPD (surge arrestor or TVSS) device shall not be
installed in the following: (2) On ungrounded systems, impedance
grounded systems, or corner grounded systems unless listed
specifically for use on these systems.
VAG
VAG
AØ BØ
480V
N
277V
CØ
HRG
480V