Under Freq
Under Freq
Under Freq
Generator Set
VTA28-G5 Engine with PowerCommand® 1.1 Control
C600 D6
English
Original Instructions 6-2014 A047H770 (Issue 1)
7. Alternator Performance Troubleshooting 6-2014
• Run alternator again and check the excitation voltage across automatic
voltage regulator output. If greater than 70 VDC, the protection circuit is
operating correctly.
6. Main rectifier diodes short circuit
• Check diodes.
• Test diodes on the main rotating rectifier assembly with a multimeter.
7. Open circuit in exciter stator windings
• Remove external leads from generator. Check the resistance value of the exciter
stator across these two leads (approximately 18 to 30 ohms) with a multimeter.
Refer to the procedure(s) in the troubleshooting and repair manual for the specific
alternator for correct values.
8. Faulty automatic voltage regulator
• Replace automatic voltage regulator and re-test.
9. Winding fault, open circuit, or short circuit
• Remove external leads from the alternator.
• Use appropriate metering equipment (Wheatstone bridge or Kelvin bridge).
Measure the low resistance winding of the main rotor and stator.
84 A047H770 (Issue 1)
6-2014 7. Alternator Performance Troubleshooting
3. Non-linear loads causing interaction between dynamic closed loop control systems
• The interaction of the alternator and the engine closed loop systems controls the
load.
• Instability is caused by oversensitive control settings.
• Adjust automatic voltage regulator to high gain (stability) and load drive
system to low gain.
• Increase engine speed droop to stabilize engine.
• Contact factory for further advice regarding non-linear loads.
4. Fluctuations in load current (motor starting or reciprocating loads)
• Check the load current on a stable supply, i.e. mains or separately excite the
machine.
• A variable DC supply is required for on load separate excitation tests.
5. Automatic voltage regulator parameters configured incorrectly
• With the InPower service tool adjust AVR control parameters, until voltage is
stable.
A047H770 (Issue 1) 87
7. Alternator Performance Troubleshooting 6-2014
88 A047H770 (Issue 1)
7. Alternator Performance Troubleshooting 6-2014
90 A047H770 (Issue 1)
6-2014 7. Alternator Performance Troubleshooting
A047H770 (Issue 1) 95
6-2014 13. Troubleshooting_Hydramechanical Fault Codes
4. The diodes on the main rectifier assembly can be checked with a multimeter.
The flexible leads connected to each diode should be disconnected at the terminal
end, and the forward and reverse resistance checked. A healthy diode will indicate
a very high resistance (infinity) in the reverse direction, and a low resistance in the
forward direction. A faulty diode will give a full deflection reading in both directions
with the test meter on the 10,000 Ohms scale, or an infinity reading in both
directions. On an electronic digital meter a healthy diode will give a low reading in
one direction, and a high reading in the other. Replace diode(s) if faulty.
7. The base board is faulty.
a. If the previous steps did not identify a faulty component, replace the control.
Possible Causes:
1. Fault simulation is enabled.
2. Underfrequency threshold is set too high.
3. There are fuel or air delivery problems.
4. Overload.
5. See page 26 Fuel system issue(s).
6. Refer to Generator troubleshooting. Type your text