TechRef 3-W-Transformer 3phase
TechRef 3-W-Transformer 3phase
Technical Reference
Three-Winding Transformer
ElmTr3,TypTr3
F2021
Contents
1 General Description 1
2.2.1 Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.2 Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.3.1 Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.3.2 Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3 Harmonics/Power Quality 29
List of Figures 35
List of Tables 36
1 General Description
The 3-winding transformer is a 3-port element connecting 3 cubicles in the network. PowerFac-
tory comes with a built-in model for three-winding transformers explained in this document.
Section 1.1 presents the sequence equivalent models of the three-winding transformer including
generalized tap-changers (for phase and magnitude). Section 4 discusses typical applications
of three-winding transformers in power systems.
Saturation of the magnetizing reactance is represented in the same way as for the three-phase
2-winding transformer model. Please refer to the three-phase 2-winding transformer technical
reference for further details.
The detailed positive-sequence models with impedances in per unit are shown in Figure 1.1
and Figure 1.2. The negative-sequence models are identical to the positive-sequence models.
Each of the HV, MV, and LV windings has a resistance and a leakage reactance designated
by rCu and Xσ together with the corresponding winding initials. An ideal transformer with a
1:1 turns ratio links the three windings at the magnetic star point. The models also include a
magnetisation reactance and an iron loss resistance designated respectively by xM and rF e .
The magnetisation reactance and the iron loss resistance can be modelled at different positions
(default: star point, HV-Side, MV-Side or LV-Side). Also the position of the taps can be changed
from the star point (Figure 1.1) to the terminal sides (Figure 1.2) with the default position being
the star point.
Figure 1.1: PowerFactory positive-sequence model of the 3-winding transformer, taps modelled
at star point
Figure 1.2: PowerFactory positive-sequence model of the 3-winding transformer, taps modelled
at terminals
Rated currents
The following sections briefly describe the measurements performed in order to determine the
parameters of a three-winding transformer.
The short-circuited winding (MV-side) should carry the current according to:
M in(Sr,HV ,Sr,M V )
Im,M V = √ (kA)
3 · Ur,M V
The positive-sequence short-circuit voltage HV-MV can be calculated from the measured volt-
age on the HV-side:
Usc,HV
usc,HV −M V = · 100%
Ur,HV
The real part of the short-circuit voltage can be specified in different ways:
The short-circuit voltage and impedance are referred to the minimum of the HV-side and MV-
side rated powers.
ur,sc,HV −M V
rCu,HV −M V = = rCu,HV + rCu,M V
100%
ui,sc,HV −M V
xσ,HV −M V = = xσ,HV + xσ,LV
100%
The short-circuited winding (LV-side) should carry the current calculated as:
M in(Sr,M V ,Sr,LV )
Im,LV = √ (kA)
3 · Ur,LV
The positive-sequence short-circuit voltage MV-LV can be calculated from the measured voltage
on the MV-side as:
Usc,M V
usc,M V −LV = · 100%
Ur,M V
The real part of the short-circuit voltage can be specified in different ways:
PCu,M V −LV
ur,sc,M V −LV = · 100%
M in(Sr,M V ,Sr,LV ) · 1000
• X/R ratio:
Imaginary part of the short-circuit voltage HV-MV:
q
2 2
ui,M V −LV = Usc,M V −LV − Ur,sc,M V −LV
The short-circuit voltage and impedance are referred to the minimum of the MV-side and LV-side
rated powers.
ur,sc,M V −LV
rCu,M V −LV = = rCu,M V + rCu,LV
100%
ui,sc,M V −LV
xσ,M V −LV = = xσ,M V + xσ,LV
100%
The short-circuited winding (LV-side) should carry the current calculated as:
M in(Sr,HV ,Sr,LV )
Im,LV = √ (kA)
3 · Ur,LV
The positive-sequence short-circuit voltage LV-HV can be calculated from the measured voltage
on the HV-side as:
Usc,HV
usc,LV −HV = · 100%
Ur,HV
The real part of the short-circuit voltage can be specified in different ways:
The short-circuit voltage and impedance are referred to the minimum of the LV-side and HV-side
rated powers.
ur,sc,LV −HV
rCu,LV −HV = = rCu,LV + rCu,HV
100%
ui,sc,LV −HV
xσ,LV −HV = = xσ,LV + xσ,HV
100%
The no-load current in % referred to the HV-side rated power is calculated according to the
following equation:
I0 Sr,LV Sr,LV
i0 = Ir,LV · Sref × 100% with Ir,LV = √
3·Ur,LV
in kA
Sref = Sr,HV in MVA → reference power in PowerFactoryis equal to HV-side rated power
The measured active power PF e in kW is entered directly into the corresponding PowerFactory
input field.
i0
yM =
100%
Sref
rF e = PF e in kW and Sref in M V A
PF e · 1000
1
xM = p 2
yM − (1/rF e )2
The relation between the input parameters in the type and element dialogues and the absolute
impedances are described in the following:
M in(Sr,HV ,Sr,M V )
usc,HV −M V = ZHV,M V · 2
Ur,HV
× 100% with ZHV −M V in Ohm referred to Ur,HV
M in(Sr,M V ,Sr,LV )
usc,M V −LV = ZM V,LV · 2
Ur,M
× 100% with ZM V −LV in Ohm referred to Ur,M V
V
M in(Sr,LV ,Sr,HV )
usc,LV −HV = ZLV,HV · 2
Ur,LV
× 100% with ZLV −HV in Ohm referred to Ur,LV
The zero-sequence model of a three-winding transformer depends on the vector group of each
winding. The following sections describe the different vector groups, the measurement of the
zero-sequence data and the input parameters. Please note that the dashed connections to the
neutral terminals exist only if the option External Star Point is enabled (see transformer dialog).
The option is only possible if one side (HV, MV or LV) is on grounded star (grounded wye) or
grounded Z connection.
Note: If the transformer has a delta winding, the magnetising impedance is neglected since in
reality it is effectively short circuited by the delta winding impedance (this impedance is much
lower than the magnetising impedance).
The zero sequence admittance y M 0 is calculated using the zero sequence resistance and reac-
tance as:
100% 1
xM 0 = ·p
i0M 1 + (R0M /X0M )2
rM 0 = xM 0 · R0M /X0M
1
yM 0 =
rM 0 + xM 0
The zero sequence magnetisation reactance and iron loss resistance can be modelled at differ-
ent positions (default: star point, HV-Side, MV-Side or LV-Side). For simplicity, in the following
figures it is always shown at the star point.
xσ0,LV rCu0,LV
u0,LV
rCu0,HV xσ0,HV
1:1
rCu0,HV
According to Figure 1.7 the zero-sequence
xσ0,HV r impedances xσ0,MVhave
rCu0,MV
no influence on the zero-sequence
voltage. It is recommended for a D-d-dM0transformer to set the zero-sequence short-circuit volt- u0,MV
age equal to the positive sequence short-circuit voltage.
xM0
DIgSILENT PowerFactory 2021, Technical Reference 8
Three-Winding Transformer (ElmTr3,TypTr3)
xσ0,LV rCu0,LV
u0,LV uN,MV
u0,HV 3xE,HV
rCu0,HV xσ0,HV
xσ0,LV rCu0,LV
u0,LV uN,MV
u0,HV 3xE,HV
uN,HV
3rE,HV
1:1 uN,LV
Figure 1.8 shows that the LV-side and the MV-side have no zero-sequence connection to the
terminals. Both delta windings are short-circuited in the zero-sequence system.
xσ0,LV rCu0,LV
u0,LV uN,MV
u0,HV 3xE,HV 3xE,MV
uN,HV
3rE,HV 3rE,MV
1:1 uN,LV
xσ0,LV rCu0,LV
u0,LV uN,MV
u0,HV
uN,HV
1:1
uN,LV
3xE,HV 3xE,LV 3xE,MV
xσ0,LV rCu0,LV
u0,LV
xM0
u0,MV
1:1
uN,MV
u0,HV 3xE,HV
uN,HV
3rE,HV
xσ0,LV rCu0,LV
u0,LV
xM0
1:1 uN,MV
u0,HV 3xE,HV 3xE,LV
uN,HV
3rE,HV 3rE,LV
xM0
1:1 uN,MV
u0,HV 3xE,HV
uN,HV
3rE,HV
The pocket calculator is a tool, which transforms measured zero sequence impedance values
(from test certificates with three measurements) into equivalent zero sequence impedances
used by the TypTr3 type of the three-winding transformer element. It can be used only for
transformers having YN-yn-d, YN-d-yn or D-yn-yn connections.
For a YN-yn-d transformer, three impedance measurements are performed (Figure 1.14):
1. Zero sequence current is injected at the HV side with MV terminal kept open. The
impedance Z 0HV −LV is measured.
2. Zero sequence current is injected at the MV side with HV terminal kept open. The
impedance Z 0M V −LV is measured.
3. Zero sequence current is injected at the HV side with MV terminal short-circuited. The
impedance Z 0HV −M V ||LV is measured.
The measured data is entered in the pocket calculator in form of impedances (magnitude) and
resistances. The measured complex impedance values are calculated using the entered data
and are then referred to the rated power of the HV winding:
SHV
q
2
Z a0 = Ra0 + Za0 − Ra0 ·2
Smeas. side
SHV
q
Z b0 = (Rb0 + Zb02 − R2 ) ·
b0
Smeas. side
SHV
q
Z c0 = (Rc0 + Zc02 − R2 ) ·
c0
Smeas. side
where Smeas. side is the apparent power of the measured side (for YN-yn-d transformer, Smeas. side =
SHV when calculating Z a0 and Z c0 , and Smeas. side = SM V when calculating Z b0 ).
Note that for a YN-yn-d transformer, the entered data corresponds to the measured impedances
as follows: Z a0 ≡ Z 0HV −LV , Z b0 ≡ Z 0M V −LV and Z c0 ≡ Z 0HV −M V ||LV . Similar is valid for the
YN-d-yn and D-yn-yn transformers.
The zero sequence impedances for the HV, MV and LV side are calculated depending on the
vector group of the transformer:
• YN-yn-d
p
Z 0LV1,2 = ± Z b0 · (Z a0 − Z c0 )
Z 0M V1,2 = Z b0 − Z 0LV1,2
Z 0HV1,2 = Z a0 − Z 0LV1,2
• YN-d-yn
p
Z 0M V1,2 = ± Z b0 · (Z a0 − Z c0 )
Z 0LV1,2 = Z b0 − Z 0M V1,2
Z 0HV1,2 = Z a0 − Z 0M V1,2
• D-yn-yn
p
Z 0HV1,2 = ± Z b0 · (Z a0 − Z c0 )
Z 0LV1,2 = Z b0 − Z 0HV1,2
Z 0M V1,2 = Z a0 − Z 0HV1,2
where there are two solutions for the impedances (subindex “1 ” is used for the positive and
subindex “2 ” is used for the negative solution). Which solution is used depends on the sum
of HV-MV, MV-LV and LV-HV reactances for both solutions (X 0HV −M V1 = =(Z 0HV1 + Z 0M V1 ),
X 0HV −M V2 = =(Z 0HV2 + Z 0M V2 ), etc . . . ). Usually the first solution is used. The second
solution is used when not all reactances of the first solution are positive and all reactances of
the second solution are positive, and in some other specific cases.
The zero sequence impedances (magnitude) and resistances as result of the pocket calculator,
used by the TypTr3 type of the three-winding transformer element, are obtained as:
min(SHV , SM V )
uk0hm = |Z 0HV + Z 0M V | ·
SHV
min(SHV , SM V )
ur0hm = <(Z 0HV + Z 0M V ) ·
SHV
min(SM V , SLV )
uk0ml = |Z 0M V + Z 0LV | ·
SHV
min(SM V , SLV )
ur0ml = <(Z 0M V + Z 0LV ) ·
SHV
min(SLV , SHV )
uk0hl = |Z 0LV + Z 0HV | ·
SHV
min(SLV , SHV )
ur0hl = <(Z 0LV + Z 0HV ) ·
SHV
The stray capacitances of a transformer do not only depend on the physical characteristics of
the transformer (i.e. the length of the windings, insulating material, core dimensions, etc) but
also on the installation environment as well (indoor or outdoor transformer, proximity to other
grounded components, walls, etc.).
The following capacitances can be defined after enabling the field Consider Capacitances option
of the transformer element:
The model is valid only for transformers not having neutral connection (if Consider Capacitances
is enabled the neutral wire connection of the element is disabled).
The positive sequence model of a three winding transformer with stray capacitances is shown
in Figure 1.15.
The nominal powers and currents for the corresponding windings are used e.g. to calculate the
loading of the transformer. They are also displayed in the transformer dialogue and can also be
used in scripts or on the flexible data page.
When e.g. a characteristic is defined for the rating factor, the actual values (considers charac-
teristics) can be accessed as follow:
The calculation of the nominal currents depends whether a thermal rating object for the corre-
sponding side is selected or not. If it is not selected, the nominal currents (in kA) are calculated
as:
where the rated currents Ir,HV , Ir,M V and Ir,LV are defined in equation (1) at section 1.1.2
and
• ratf ac h, ratf ac m and ratf ac l are the rating factors for the transformer HV-, MV- and
LV-side, defined on the element Basic Data page
• nt3nm is the number of parallel transformers, defined on the element Basic Data page
• Sr,HV , Sr,M V , Sr,LV , Ur,HV , Ur,M V , Ur,LV are defined in section 1.1.2
If a thermal rating object is selected for the corresponding side, the nominal currents are deter-
mined as follows:
ContRating · nt3num
Inomhv = √
3 · Un(bushv)
ContRating · nt3num
Inommv = √
3 · Un(busmv)
ContRating · nt3num
Inomlv = √
3 · Un(buslv)
where Un(bushv) , Un(busmv) and Un(buslv) are the busbar line-line nominal voltages in kV at the
high, medium and low-voltage side.
The nominal powers (Snom h, Snom m, Snom l) and also the corresponding actual value
(Snom h a, Snom m a, Snom l a) are defined as follow:
where:
• Sr,HV , Sr,M V , and Sr,LV , are the rated apparent powers, see also in section 1.1.2
• nt3nm is the number of parallel transformers, defined on the element Basic Data page
• ratf ac h, ratf ac m and ratf ac l are the rating factors for the transformer HV-, MV- and
LV-side, defined on the element Basic Data page
• ratf ac h a, ratf ac m a and ratf ac l a are the actual rating factors incl. defined charac-
teristics.
√
Snom h = 3 · Un(bushv) · Inomhv
√
Snom m = 3 · Un(busmv) · Inommv
√
Snom l = 3 · Un(buslv) · Inomlv
Snom h a = Snom h
Snom m a = Snom m
Snom l a = Snom l
where:
• Inomhv , Inommv , and Inomlv are the nominal currents at high, medium and low- voltage
side, see section 1.2.1.
• Un(bushv) , Un(busmv) , and Un(buslv) are the busbar line-line nominal voltages in kV at the
high, medium and low-voltage side.
As the tap changer is of particular interest in load flow calculations, data relating to the tap
changer is entered as follows:
• On the Load Flow page of the transformer element: control data and measurement re-
port);
• On the Load Flow page of the transformer type: tap changer positions and tap-dependent
impedance).
Tap Position For each tap controller, the actual tap position used during the load flow calcula-
tion. If Automatic Tap Changing is ticked, this value corresponds to the initial tap position.
According to Measurement Report If this option is enabled, then instead of using the type
data for the tap-dependent transformer values, the Measurement Report defined in the
element is used.
In addition, there are two tap changer controllers available, which can be set to control either
the HV, the MV or the LV side. When both are active, they can be set to simultaneously control
active power and voltage, or active power and reactive power (other combinations are not pos-
sible). Each controller has the option Automatic Tap Changing, which activates automatic tap
adjustment (see Section 2.1).
This is activated by setting the corresponding option for Controller 1 or Controller 2 on the Load
Flow page of the transformer element. Additionally, automatic tap adjustment can be globally
enabled or disabled via the Load Flow Calculation command (ComLdf ).
Control Mode The type of control for the tap. It has the following options, whose description
can be seen in the Two-Winding Transformer Technical Reference.
• V : Voltage control. For unbalanced load flow analysis, the controlled phase needs to
be additionally defined. The internal (LDC) line drop compensation is not supported.
• Q: Reactive power control.
• P: Active power control (only applicable to phase-shifters).
Phase For unbalanced load flow analysis, the controlled phase needs to be additionally de-
fined.
Setpoint Specifies how to enter the voltage setpoint and its range.
• local: The Voltage Setpoint and voltage range settings (Lower Bound and Upper
Bound) must be entered in the transformer dialogue.
• bus target voltage: The voltage setpoint and voltage range settings (max./min. volt-
age) are taken from the controlled busbar (topological search).
Remote Control Allows for the selection of a busbar different to that at the transformer termi-
nals.
Voltage Setpoint Voltage reference.
Lower/Upper Bound Lower and upper bound of the voltage. In the case of discrete tap chang-
ers, the tap control can drive the voltage into a permitted band. In the case of continuous
tap changers, the tap controller ideally regulates to the reference point.
Compensation Different types of compensation are supported:
• none
• external (LDC) line drop compensation: Via a Line Drop Compensation (StaLdc)
object.
• current compounding: See Section 2.1.1.1).
Voltage control also includes an optional current compounding method, which controls the trans-
former voltage within acceptable limits, by increasing the voltage setpoint as the load current
increases.
Note The control curve is the same whether the control node is at the HV side or at the LV side.
However, the active and reactive power and current flows measured in PowerFactory depend on
the measurement side, as it can be seen in Figure 2.3.
Therefore, the measured power flows and currents are always considered as the flows from HV
to LV side (or HV to MV side in the case of three-winding transformers), as follows:
P :bushv if Controlled Node at HV side
P meas = −P :busmv if Controlled Node at MV side for 3-winding transformers (3)
−P :buslv if Controlled Node at LV side
The same equation 3 applies for reactive power, and for active and reactive currents. For un-
balanced load flow and RMS simulation the active and reactive power is always the total power
of all phases (neutral wire is ignored).
nphase
X
Psum = Pi
i=1
nphase
X
Qsum = Qi
i=1
For current compounding based on currents is dependent on the controlled note at phase set-
ting:
• Pos.Seq (positive sequence), only possible for 3-phase transformers: the positive se-
quence current/voltage is used e.g. Iactive = |I 1 | · cos(φU1 ,I1 )
The following inputs are valid for the reactive power control:
Remote Control The flow through any selected cubicle can be controlled.
Reactive Power Setpoint Reactive power reference.
Lower/Upper Bound Lower and upper bound of the reactive power. In the case of discrete tap
changers, the tap control can drive the reactive power into a permitted band. In the case
of continuous tap changers, the tap controller ideally regulates to the reference point.
The following inputs are valid for the active power control:
Remote Control The flow through any selected cubicle can be controlled.
Active Power Setpoint Active power reference.
Lower/Upper Bound Lower and upper bound of the active power. In the case of discrete tap
changers, the tap control can drive the active power into a permitted band. In the case of
continuous tap changers, the tap controller ideally regulates to the reference point.
Active Power Participation Allows the control of active power flow as a percentage of the
power flow through a (parallel) user-defined boundary. See Section 2.1.3.1.
Participation factor The participation factor of the measured power flow of the selected
boundary.
Tolerance In the case of discrete tap changers, the tap control can drive the active power
into a permitted band. In the case of continuous tap changers, the tap controller
ideally regulates to the reference point.
P measured at The user-defined boundary.
Below there is an example of the use of active power participation control. The first figure 2.4
shows the load flow solution without any control, and the set tap position at zero. In the second
figure, 2.5, the transformer tap is set to carry 100% of the power measured at the Line on bus
T0. The solution brings the tap position of the transformer to 0.49.
There is usually more than one possible solution to a load flow problem considering automatic
tap changer control. In meshed networks in particular, several transformers can control the
voltage in certain areas. In the case of parallel transformers, the problem can usually be solved
by operating the two parallel transformers in master-slave mode.
In a general configuration however, especially when parallel transformers have different short-
circuit impedances or different tap steps, the steady-state network solution cannot be easily
obtained. PowerFactory addresses this problem by allowing the user to enter a controller time
constant, specifying the speed of control actions and hence the participation of several trans-
formers regulating the voltage at the same busbar.
The approach is based on controller block diagrams according to Figure 2.6. In the case of
flow controllers (P-/Q-control), the controller sensitivity translating a power mismatch into an
equivalent turns-ratio percentage can be entered additionally.
In the load flow algorithm, which only considers steady-state conditions, controller time con-
stants and sensitivities are translated into equivalent participation factors.
(a) (b)
The controller input parameters for the transformer element are described in Table 2.2.
Hint: The controller sensitivities can be calculated directly from the Load Flow Sensitivities com-
mand (ComVstab). However, it must be noted, that the quantities calculated by this command
are the inverse of the controller sensitivities. Thus,
1
Kpctrl = (4)
dP dtap
1
Kqctrl =
dQdtap
Where
• dQdtap is the Branch Sensitivity dQbranch/dtap in Mvar/tap calculated by the Load Flow
Sensitivities command.
To improve the outer loop convergence, automatic tap hunting detection is available in the trans-
former models. For a discrete transformer tap, PowerFactory checks whether the control con-
dition can be fulfilled according to the setpoint (bounds). If for example, the upper and lower
bounds are too close, the transformer will not be able to maintain the control condition within
the bounds.
In the Load Flow Calculation command, Advanced Options page, the number of max. transitions
can be entered (default = 3).
• the voltage is above the upper bound of the setpoint and in the next iteration the voltage
is below the lower bound (or vice versa)
• the delta tap change is one
In addition the delta tap per load flow outer loop will be limited (if the load flow tap adjustment
method is set to stepped) e.g. in the case of large relaxation factors.
The delta tap per outer loop will be limited after the first transition.
2.2.1 Loading
Ibushv
loading h = · 100 (%)
Inomhv
Ibusmv
loading m = · 100 (%)
Inommv
Ibuslv
loading l = · 100 (%)
Inomlv
loading = max(loading h, loading m, loading l) (%)
• Inomhv : Nominal current at the high voltage side in kA, see section 1.2.1.
• Inommv : Nominal current at the medium voltage side in kA, see section 1.2.1.
• Inomlv : Nominal current at the low voltage side in kA, see section 1.2.1.
• Ibushv : Magnitude of the current at high voltage terminal
For an unbalanced load flow calculation the highest current of all phases/neutral is used.
2.2.2 Losses
and
• umag is the actual phasor voltage over the transformer magnetising branch in p.u.
• imag is the actual phasor current over the transformer magnetising branch in p.u.
2.3.1 Loading
|Pbushv |
loading h = · 100 (%)
Pnomhv
|Pbusmv |
loading m = · 100 (%)
Pnommv
|Pbuslv |
loading l = · 100 (%)
Pnomlv
loading = max(loading h, loading m, loading l) (%)
where:
The calculation of the nominal powers depends whether a thermal rating object for the corre-
sponding side is selected or not. If it is not selected, the nominal currents are calculated as:
√
• Pnomhv = 3 · Un(bushv) · Inomhv
√
• Pnommv = 3 · Un(busmv) · Inommv
√
• Pnomlv = 3 · Un(buslv) · Inomlv
with the nominal currents of the transformer Inomhv , Inommv and Inomlv (see equation (2)).
Un(bushv) , Un(busmv) and Un(buslv) are the busbar line-line nominal voltages in kV at the high,
medium and low voltage side.
If a thermal rating object is selected for the corresponding side, the nominal powers are deter-
mined as follows:
where the rated currents Ir,HV , Ir,M V and Ir,LV are defined in equation (1) at section 1.1.2.
2.3.2 Losses
3 Harmonics/Power Quality
In order to accurately model the high frequency effects of transformers, additional capacitances
need to be considered, as explained in Section 1.1.5.
On the Harmonics page of the transformer type, frequency-dependent positive and zero se-
quence (short-circuit) impedances can be defined. If the characteristic is defined through a
Frequency Polynomial Characteristic (ChaPol) element, then it is automatically defined as rela-
tive to rated values. If the characteristic is defined through a Parameter Characteristic - Vector
(ChaVec) element, then it can be defined as relative (in p.u. or %) or in absolute p.u. values.
If the positive and zero sequence (short-circuit) impedances are defined in the Measurement
Report, the characteristic should be defined as relative otherwise the value in the Measurement
Report will be overwritten. A frequency-dependent positive sequence magnetizing admittance
can also be defined, by defining a characteristic for the imaginary and real part of the admit-
tance.
In PowerFactory each winding of a transformer can have taps, however only one of the tap
changers can be controlled in the Load Flow calculation. The specification of the tap changers
for each winding is done in the load flow page of the transformer type. Then, in the load flow
page of the element a tap changer is specified for automatic control. Note that in order to have
the load flow algorithm adjust the taps while trying to find a solution, in the Load Flow command
Basic Options page, the option Automatic Tap Adjust of Transformers must be enabled.
In entering positive and zero sequence voltages for a three-winding transformer, one must note
that they are referred to the minimum rated power of the two windings. For example, for a
60/60/10 MVA, 132/22/11 kV transformer, a value of 10% is specified both for the HV-MV and
LV-HV positive-sequence short-circuit voltages. The impedance value (referred to HV-side) of
the impedance between the HV and MV terminals is
(132kV )2
0.1 × = 29.04 primary Ω
60M V A
while the impedance value (referred to HV-side) of the impedance between HV and LV terminals
is
(132kV )2
0.1 × = 174.24 primary Ω
10M V A
It is possible to use manufacturers or any other available measurement data for load flow cal-
culation. By clicking on the right-arrow in the load flow specification page of a transformer
element, the user goes to a new window where the option According to Measurement Report is
displayed. Checking this option shows a table where data from measurements can be directly
entered.
The impact of third-harmonic currents from one star-connected side to the other star-connected
side is reduced because these currents see the delta-connected side as a short-circuited wind-
ing. The effect can be explained using the zero-sequence diagrams in Figure 1.9 and Fig-
ure 1.11.
Let us assume a third-harmonic source at the HV side and a load at the MV side. For simplicity,
the magnetizing and grounding impedances are ignored. If the MV and LV winding resistances
and leakage reactances are referred to the HV side, the circuit in Figure 4.1 is obtained. The
impedance of the middle leg is normally much less than that of the right leg which is why the
third-harmonic current content of the load is reduced.
In this application the tertiary winding can be internal with no terminals provided for connection.
However, if the terminals are brought out of the transformer tank, then the tertiary winding can
also be used to connect shunt reactors, capacitors, or SVCs (Figure 4.2). In Figure 4.2, the
star-connected windings are shown as separate windings; however, this application is common
also in case of autotransformer.
Figure 4.2: Small tertiary winding for zero-sequence and reactive compensation
Step-up transformers especially for hydro power plants can be three-winding transformers where
there is one high-voltage side, and two low-voltage sides with the same voltage rating. This is
cost-effective because then only one switchgear is needed for the high-voltage side (Figure 4.3).
The same argument goes for network transformers for example in distribution networks.
Another application of three-winding transformers is when at some location in the network three
different voltage levels for example 132kV, 22kV, and 11kV are to be connected together.
In HVDC systems, three winding transformers are used to combine two 6-pulse rectifiers into a
12-pulse one to give a smoother dc voltage. In this application, the 30◦ phase shift between a
star-connected winding and a delta-connected winding is employed (Figure 4.4).
Figure 5.1: Input/Output Definition of 3-winding transformer model for RMS and EMT simulation
List of Figures
5.1 Input/Output Definition of 3-winding transformer model for RMS and EMT simulation 33
List of Tables