HF-3 Instruction Manual
HF-3 Instruction Manual
�
1. Component Arrangement and Function
1) Product Front
* RUN - Run start button (Display of manual stop via lamp flashing)
2) Internal Terminal
�
2. Parameters
1) PARA Setting Table
Setting
Parameter Default Description
Range
Control Reverse Sets the polarity reversal of S1 control signal.
S1 no / nC nC
S1 POLE Control signal is On ☞ select operation or stop
Off Delay OFF DELAY oF 0.1~9.9 2.0 Off delay after Off condition
Accelerating Time ACCEL AC 0.1~9.9 1.0 Accelrating time of set voltage after On time
Decelerating Time DESEL dE 0.1~9.9 0.5 Stop and deceleration time after Off time
External Volume EXT VR Rd oF / on oF Selects to set and use the external voltage
Vibration Sensor F/B Fd on / oF on Selects and use the compensation function of vibrating sensor
Vibration Sensor F/B TIME Fb 01~99 10 Sets the compensation cycle of vibration sensor (10=0.1sec)
� � � � �
Open PARA window (PARA screen) Turn Volume to find PARA item Select the item to set
� � � �
Change the set value with Encoder Volume Screen after ENT has been changed Close PARA window
�
3. Button Function
1) RUN : Run start button (Power outage maintained)
2) STOP : Stops the operation compulsively, flashes the run display lamp, and becomes
an output stop condition.
3) PARA : Sets a time and operation method necessary for operation. (See the parameter item)
4) V/F ENT : Used as a voltage/frequency selection button on the V/F screen and as an ENT button
on the PARA screen.
5) Encoder Volume : An item selection and value setting volume.
1) Saving : Pushing the RUN button on the V/F display screen for 3 seconds flashes the 3 lamps
marked with M. Pushing the ENT button when M flashes saves it.
2) Importing : Pushing the STOP button on the V/F screen for 3 seconds flashes the 3 lamps
marked with R. Pushing the ENT button when R flashes imports the saved value.
�
2) RELAY
: A relay contact terminal installed for external signal and control that works according to the PARA setting.
a) PARA Setting Content : rU RUN, Er ERR, S1 Control signal
- RUN : The relay works during feeder operation.(The OUT display lamp ON)
- ERR : The relay works in case of an abnormality. (Used as signals to check abnormalities in the controller)
- S1 : S1 control signal ON Relay ON (Used to detect defects during bowl feeder operation)
b) Wiring Method
A) Sol Valve and Lamp B) Use of Contacts
10KΩ
�
6. Voltage/Frequency
1) Voltage/Frequency Description
V : Set the strength of vibrations, i.e. a force that the feeder coil pulls the upper plate of the feeder via.
F : Set the resonant frequency of the feeder, i.e. the frequency per second that the feeder coil pulls
the upper plate. The frequency with the highest strength of vibration is a resonant frequency.
2) Voltage Setting
: Turning the encoder volume with the VOLT-marked lamp ON changes the set voltage.
* Pushing the ENT button for 3 seconds turns ON the 3 lamps to start automatic conversion of
frequency. (Repeats 40Hz~400Hz)
Check the resonant frequency band and push the STOP button manually to stop it.
Turn the encoder volume to General(varying in a 0.1 unit) in a resonant frequency band to
check the starting point and final point of the resonant frequency band.
Set the frequency to the middle point of the resonant frequency band.
(Frequency setting completed)
Set the voltage to a strength of vibration necessary for voltage setting. (Voltage setting completed)
* If the voltage control range is large, then the frequency resonance band may differ.
Control the frequency finely through frequency setting to check whether it is at the middle point
of the resonance band.
�
4) Automatic Setting of Frequency(Auto Tuning)
: Install a vibration sensor VS50 to find the resonant frequency automatically and to use it
for the purpose of automatically compensating the vibration variation.
VS50 Specification
* Working power voltage : DC5V
* Working voltage range : DC3.5~6V
* Working temperature : -30℃~+85℃
* Cable length : 2M(basic), 3M, 5M
* Sensor operation outline : This works in a principle of measuring
the change in the condenser capacity
of a sensing cell that changes depending on motion.
* If the voltage control range is large, then the frequency resonance band may differ.
Control the frequency finely through frequency setting to check whether it is at the middle point
of the resonance band.
�
7. External Dimension
�
8. Fabrication Specification
Maximum Auto
3A 5A
Current Interception
Control
FET FET
Element
Output Output
0.0V ~ 200.0V
specification Voltage
Variable
40Hz ~ 400Hz
Frequency