CENTERLINE 1500 Medium Voltage Motor Control Centers: Selection Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

CENTERLINE 1500 Medium

Voltage Motor Control Centers


Bulletin Numbers 1506, 1512A, 1512AD, 1512AT, 1512B, 1512BP, 1512BS,
1512BD, 1512BT, 1512BU, 1512DM, 1512DO, 1512M, 1522E, 1522F/G,
1560F, 1562F, 1572, 1576, 1582, 1591A, 1591B, 1592B, 1592BF, 1592BS,
1592F/M, 1594F/M, 1594T, 1599, 1906B, 1906L, 1912B, 1912L

Selection Guide
CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

What’s Inside
Topic Page
Overview 3
Motor Control Center Design 4
IntelliCENTER Technology 5
ArcShield Technology 6
Selection Process 7
Step 1: Technical Specifications 9
Step 2: Network Technology 11
Step 3: Structure Options 15
Step 4: Power Bus Compartment 19
Step 5: Power Cell Compartment 21
Step 6: Low Voltage Compartment 27
Step 7: Medium Voltage Control Types 31
Step 8: Incoming Line Units 53
Step 9: Low Voltage Compartment Door Options 59
CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist 61

What’s New
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect
all changes. Translated versions are not always available for each revision.
Topic Page
Updated Bulletin 1506 power circuit schematic 40
Updated weight and dimension data for Bulletin 1562F starter specifications 44
Replaced Bulletin 1560F and 1562F power circuit schematics 45
Removed Withstand/Fault ratings as these are applicable 62
Corrected the IntelliVAC control module input voltage 63

2 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

Overview
Your critical applications rely on medium voltage motors for safe, repeatable operation in harsh industrial environments. To help improve
the protection and performance of your systems, choose Allen-Bradley® CENTERLINE® 1500 medium voltage motor control centers
(MVMCCs)—built tough to meet your application demands.

With one of the broadest suites of motor controls in the marketplace, CENTERLINE 1500 MVMCCs deliver premium quality, tailored solutions
in a centralized package that integrates control and power in one efficient solution.

Matched to your requirements, our UL and NEMA certified medium voltage solutions are designed to mitigate risk and support an extensive
range of control formats and configurations. The result? Smart, cost-effective systems that can deliver power, control, information, and
safety capabilities on a common platform.

To extend system performance further, incorporate additional features—like industry-leading ArcShield™ arc-resistant enclosures and
IntelliCENTER® technology, our built-in network and software package. Our flexible and scalable approach to design means you can choose
the capabilities that you need to enhance safety and maximize productivity.

For nearly 80 years, Rockwell Automation has provided leading medium voltage motor control solutions—solutions like the CENTERLINE 1500
MVMCC.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 3


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

Motor Control Center Design


The CENTERLINE 1500 Medium Voltage Motor Control Centers (MVMCCs) robust
structures consist of sections, wireways, doors, and mountable intelligent motor
control (IMC) devices. Power Bus
Compartment
Low Voltage
CENTERLINE 1500 MVMCCs come in an array of enclosure types, in compliance Compartment
with multiple standards.

Each CENTERLINE 1500 MV MCC is assembled with completely isolated, easily


accessible, and modular compartments:
Power Cell
• Centralized power bus compartment Compartment
• One or more medium voltage power cell compartments
• One or more low voltage compartments

Power Bus Compartment


The CENTERLINE 1500 MVMCC features a centralized horizontal power bus compartment with removable cover plates for premium
accessibility and power distribution throughout the entire lineup.
• Controllers are expandable from the left-to-right or right-to-left
• Designed for direct connection of incoming line cables, from top or bottom
• Horizontal edge-to-edge bus bar configuration opposes magnetic forces, moisture, and dust collection
• One-piece 3-phase bus brace helps reduce maintenance and provides excellent distribution of forces during faults
• Side and rear access, which is protected by removable, bolted grounded plates; power bus accessible from the front for all motor
controllers

Power Cell Compartment


The MVMCC power cell compartment is the heart of the controller. It contains all power circuitry, including proprietary non-load break
isolation switches, integrated power fuses, contactors, and current and control power transformers. The MVMCC power cell compartment is
fully interlocked (electrically and mechanically) to provide an enhanced safety level.

Low Voltage Compartment


The unique swing-out, low voltage compartment provides a separate and fully isolated area. All CENTERLINE 1500 low voltage compartments
include these features.
• Enables controller testing and troubleshooting without exposing personnel to medium voltage for maximum safety
• By using the unique Test Selector Switch and external test power supply receptacle, all low voltage components can be configured
and tested safely without medium voltage applied
• The Test Selector Switch additionally helps help prevent backfeeding through the control transformer
• All low voltage panels are painted white, providing increased visibility, better component identification, simple access, easy product
integration, and higher maintainability

The low voltage compartment can house various low voltage Intelligent Motor Control (IMC) devices for diverse protection and measurement
capabilities. These IMC devices include:
• Bulletin 193: E300™ Electronic Overload Relay
• Bulletin 1426: PowerMonitor™ 5000
• Bulletin 1503VC: IntelliVAC™ Contactor Control Module(a)
• Bulletin 1794: Flex™ I/O

(a) A Flex I/O module or E300 relay is needed.

4 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

IntelliCENTER Technology
IntelliCENTER technology enhances the intelligence of the CENTERLINE 1500 MV MCC by using built-in networking to capture information
used for predictive maintenance, process monitoring, and advanced diagnostics. IntelliCENTER technology can save you time because each
MV MCC is pre-wired, and the network is pre-programmed and validated at the factory. Network devices are preconfigured with node
addresses and communication rates, ready to communicate so you can configure device parameters (such as acceleration time and full load
amps) via the network.

IntelliCENTER Software
The addition of IntelliCENTER software provides the ultimate window into your MV MCC. The preconfigured software provides maintenance
personnel with easy access to real-time critical CENTERLINE MV MCC configured information and process data for troubleshooting. The
configurable graphic views provide system status at a glance and help keep facilities running with electronic documentation, remote
diagnostics, and predictive maintenance. IntelliCENTER software significantly reduces HMI programming time and PLC development time
with automatic tag generation and even complete network configuration before the MV MCC is powered up.

Integration Assistant
With IntelliCENTER Integration Assistant, you can seamlessly integrate your IntelliCENTER MV MCCs into Studio 5000® programming software.
This feature helps reduce programming time by automatically adding the CENTERLINE MCC devices to the Studio 5000 I/O tree.

IntelliCENTER Energy
IntelliCENTER Energy offers a preconfigured setup of FactoryTalk® EnergyMetrix™ software for intelligent motor control devices in the MV
MCC, including variable speed drives, overload relays, and SMCs. With IntelliCENTER Energy, you can view energy consumption at the device
level directly from IntelliCENTER software, making it easier to monitor and manage energy usage in the industrial facility.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 5


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

ArcShield Technology
Allen-Bradley CENTERLINE 1500 MV MCCs with ArcShield arc-resistant enclosures provide rugged process control for applications that
require a higher level of personnel protection. Products with ArcShield enclosures are tested and compliant to the IEEE C37.20.7 standard,
and provide Type 2B protection during a 40 kA or 50 kA arc flash.

The ArcShield controller helps safely redirect the arc flash energy out the top of the unit and away from personnel. This level of protection is
also maintained, even when the low voltage door is open for maintenance purposes.

All ArcShield products have a robust enclosure design, which contains the arc flash energy and exhaust materials until vents on top of the
enclosure open. Once opened, the vents provide a path for materials to exit the enclosure. An overhead plenum is used to direct the
materials to a safe location away from personnel.

An optional chimney design redirects arc flash materials safely into clear space above the enclosure. The low voltage panel is reinforced and
sealed, to help prevent arc flash exhaust materials from entering this compartment.
As standard, a plenum exhaust section is provided with each new ArcShield order. The plenum exhaust section can be mounted on either the
left or right end of the line-up, and it extends past the end of the line-up. Engineered plenum designs are also available.

Features
• Reinforced cabinet and power cell door closure mechanism
• Multi-point latching mechanism, reinforced cross bracing and gasket sealing
• Reinforced back plates–added support plates that are secured with multiple bolts provide increased rigidity and security
• Reinforced low voltage panel to withstand arc flash energy and shield maintenance personnel while working in the isolated low
voltage compartment
• Arc ‘Pressure Relief’ vent to vent arc gases and material safely away from personnel during an arc flash
• Available with removable arc exhaust plenum or exhaust chimneys

6 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

Selection Process
Use the following sections in this publication to select a CENTERLINE 1500 Motor Control Center.

Step 1: Technical Specifications


Determine what certifications, ratings, and other technical specifications are needed for your
application. Step 1 starts on page 9.

Step 2: Network Technology


Choose the level and type of networking technology, diagnostic, and HMI software tools. Step 2 starts on
page 11.

Step 3: Structure Options


Choose enclosure type, optional ArcShield protection, and paint. Step 3 starts on page 15.

Step 4: Power Bus Compartment


Understand the design of the Power Bus Compartment. Step 4 starts on page 19.

Step 5: Power Cell Compartment


Review standard power components offered. Step 5 starts on page 21.

Step 6: Low Voltage Compartment


Choose from a variety of Intelligent Motor Control Devices to populate the LV compartment. Step 6 starts
on page 27.

Step 7: Medium Voltage Control Types


Choose your MV control type. Step 7 starts on page 31.

Step 8: Incoming Line Units


Choose your incoming line unit type. Step 8 starts on page 53.

Step 9: Low Voltage Compartment Door Options


Choose interface options. Step 9 starts on page 59.

Selection Checklist
Complete each corresponding part of the selection checklist as you work through each step. A
completed checklist helps your local sales office better understand your needs. The summary checklist
starts on page 61.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 7


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

Notes:

8 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 1: Technical Specifications

The following certifications can be found at the Rockwell Automation Literature Library: https://rok.auto/literature.

Standards • Underwriters Laboratories, Inc. (UL), High Voltage Industrial Control Equipment 347
• Canadian Standards Association (CSA), Industrial Control Equipment C22.2 No. 253 (harmonized with UL 347, fifth edition)
• National Electrical Manufacturers Association (NEMA), Medium Voltage Controllers Rated 1501...7200V AC ICS 3-2 (formerly ICS 2-324)
• American Nation Standards Institute (ANSI), Instrument Transformers C57.13
• Institute of Electrical and Electronic Engineers (IEEE) 519-1992
• IEEE C37.20.7, Type 2B for arc resistance
• National Electrical Code (NEC)
• Canadian Electrical Code (CEC)
• Occupational Safety and Health Act (OSHA)
• European Directives for EMC
EC Directives 2011/65/EU RoHS Directive
2014/30/EU EMC Directive
Certifications and Markings ABS and ABS Shipboard MV-CT008
CE Conformance Marked MV-CT001, MV-CT002, MV-CT003
Registration of Broadcasting and Communication Equipments 1500-CT001
UKCA Declaration of Conformity 1500-CT002, 1560-CT001
UL Certification 1560-CT002
Rated Voltages Maximum Rated Voltage 5000V or 7200V, 3 Phase
Nominal Voltage Ratings 2400V, 3300V, 4160V, 4800V, 6600V, 6900V
Rated Frequency 50…60 Hz
Rated Currents Continuous Current Rating 1200, 2000, 3000 A
(Main Horizontal Power Bus)
Short Circuit Peak Withstand 130 kA Peak
Short Time Withstand Rating 50 kA RMS SYM (80 ka ASYM) for 0.5 second
Creepage Distances and Basic Impulse Level (BIL) 60 kV(1)
Clearances
Minimum Insulation Creepage-to-Ground and Between Phases 89 mm (3.5 in.)
Dielectric Voltage Withstand Rating 2400…5000V 13.25 kV
(Insulation Test) for 60 s
7200V 18.2 kV
Bus Material and Plating Main horizontal power bus Copper, tin plated
Vertical power bus Copper, tin plated
Ground bus Copper, unplated
Enclosure Types NEMA Enclosure/IEC 60529 • Type 1/IP21
• Type 1 with Gasket/IP21
• Type 12/IP52
• Type 3R/IP34
• Arc-resistant Type 2B (Type 12/IP52)
Structural Surface Treatments Interior(2) High gloss white (RAL 9003)
Exterior • ANSI 49 medium light gray
• ANSI 61 light gray
• Additional colors available as custom option
Environment(3) Operating temperature range 0…40°C (32…104°F)
Storage and transportation temperature range -20…+75°C (-4…+149°F)
Altitude(4) 1000 m (3300 ft)
Humidity 5…95% (non condensing)
Pollution degree 2
Seismic (UBC rating)(5) 1, 2, 3, 4
(1) The BIL rating must be derated for altitudes about 1000 m (3300 ft).
(2) All metal back plates in the power cell and low voltage compartment.
(3) UL/CSA/NEMA/IEC.
(4) De-ratings apply for higher altitudes.
(5) Some units may require special bracing. Contact factory for more information.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 9


Step 1: Technical Specifications

Notes:

10 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 2: Network Technology

An EtherNet/IP™ network enhances integration, helps reduce your MCC set-up time, and increases the network speed. With EtherNet/IP
technology, you can quickly monitor, troubleshoot, and diagnose your MCC from anywhere. CENTERLINE® MCCs provide robust motor control
capabilities with access to the real-time data you need by using a network that communicates with your entire enterprise. Use of an
EtherNet/IP network enables IntelliCENTER® Integration Assistant that automatically configures and populates your I/O tree and network
configuration.

The cost and performance of a EtherNet/IP network makes them ideal for MCC applications. Open specifications and protocol, managed by
the Open DeviceNet Vendor Association (ODVA), means that vendors are not required to purchase hardware, software, or licensing rights to
connect to a system.

An EtherNet/IP system is qualified to communicate and perform under normal and adverse electrical environments. Its application can be
plant-wide and over multiple disciplines through commercial off-the-shelf (COTS) products like Ethernet switches and devices.

An EtherNet/IP system has the following capabilities:


• Automatic Device Configuration (ADC) automatically downloads the IP address, firmware, and device parameter settings to a newly
replaced device without user interaction.
• Switch-level linear or switch-level ring topologies provide network flexibility for any sized operation.
• Heavy traffic performance.
• Add or subtract nodes on-the-fly.
• Advanced network configuration, security, and diagnostics are provided by layer-2 managed Ethernet switches.
• The EtherNet/IP system in the MCC is designed to operate at 100 Mbaud.

For more information on how to configure MCCs with EtherNet/IP, refer to CENTERLINE 1500 Motor Control Center with IntelliCENTER
Technology Using an EtherNet/IP Network Technical Data, publication 1500-TD001.

Example of an EtherNet/IP Network

753 753

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 11


Step 2: Network Technology

EtherNet/IP Components

Unit Components

Each unit can be provided with an EtherNet/IP component.


• Starter units can be provided with a solid-state overload relay, like the E300™ Electronic Overload Relay.
• AC drives can be provided with an EtherNet/IP communication module and/or an embedded option.
• Solid-state controllers can be provided with EtherNet/IP communication modules and, in some instances, an EtherNet/IP
POINT I/O™ system.
• Feeder circuits can be provided with an EtherNet/IP POINT I/O system.

Each EtherNet/IP component in an MCC unit is connected to the network through a port in the control and network wireway. Adding or
removing units from the network does not interrupt the other units operating in the system. Network wireways are isolated from the power
wire.

Cabling

Ethernet cables are routed through the low voltage wireway, located on the top of each MV MCC section, to prevent accidental mechanical
damage during MV MCC installation.

Ethernet cables are routed into the low voltage control panel of each MV MCC unit. The EtherNet/IP devices within each low voltage
compartment are factory connected to a managed Ethernet switch in the LV compartment using 600V UL PLTC rated cable.

IntelliCENTER Software Features


The CENTERLINE 1500 MCC is available with preconfigured IntelliCENTER software. IntelliCENTER software is an intuitive software package
that is customized to your MCC. The software is a monitoring and diagnostics tool capable of viewing, managing, and configuring multiple
MCC line-ups. The IntelliCENTER software communication driver lets the software be installed and operated on an EtherNet/IP network. The
IntelliCENTER software can function as a standalone software package or as an ActiveX control in an HMI.

The IntelliCENTER software features:


• Integration Assistant - takes customized MCC information within the IntelliCENTER software and exports it to Studio 5000®
programming software, providing quick device integration and reducing programming time.
• IntelliCENTER Energy - energy monitoring and management with integration to FactoryTalk® EnergyMetrix™ software.
• Elevation View - an easy-to-identify, graphical representation of your entire MCC lineup.
• Monitor View - an overview of the intelligent motor control device being monitored, with configurable gauges, trend graphs, I/O
status on the device and configurable data fields.
• Spreadsheet View - for sorting and editing data that seldom changes, including network address, device type and description, and
nameplate data.
• Event Log View - a history of changes to equipment parameters, like trip settings, warnings, and faults.
• Documentation Management - access to the complete documentation for your MCC, including wiring diagrams, device manuals, and
spare parts list.

12 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 2: Network Technology

IntelliCENTER Database
The IntelliCENTER software replicates the MCC lineup on a computer screen, complete with nameplates and indicators on each door to show
status (on, off, warning, fault, communication failure). Graphical views of individual MCC units display device data so you can quickly view
critical amperes, time-to-trip, trip cause, ground fault amperes, and on/off status. Each screen is pre-configured to show the parameters
typically of greatest interest, and you can easily customize parameters. Many screens feature trending graphs and analog dials.

The IntelliCENTER software provides spare parts information, AutoCAD documentation, and event logging. The software also contains ActiveX
controls. These controls provide key views of the software that can be displayed inside Human Machine Interfaces (HMIs) such as RSView®
software.

For EtherNet/IP networks, the configuration file can help in determining the installed firmware revision to properly configure the
Studio 5000 environment Add-on Profile (AOP) that generates all tags for each EtherNet/IP device in the MCC.

Two datasets are available for IntelliCENTER software. Both must be ordered separately from the MCC unit.

Standard Dataset–The standard dataset is the second component of the IntelliCENTER software. The information arrives as a digital
download, and contains data files specific to a particular MCC. This information includes unit nameplates, unit details, wiring diagrams, user
manuals, spare parts, and other details.

Energy Dataset–The energy dataset includes all components of the standard dataset. Additionally, it includes the ability to use the features
of IntelliCENTER Energy (version 4.0 and later) and the additional installation software needed.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 13


Step 2: Network Technology

Notes:

14 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 3: Structure Options

The medium voltage controllers feature two basic styles:


• 1-High: One medium voltage controller in one vertical section
• 2-High: Two medium voltage controllers in one vertical section

These controllers can be a single structure or line up of structures with expansion to the left or right.

Medium Voltage Controller Configurations

Low Voltage
Compartment

Low Voltage Power Cell


Compartment Compartment

Power Cell
Compartment

Enclosure Types
• Arc-resistant Type 2B, 40 kA or 50 kA (NEMA Type 12, IP52)
• NEMA Type 1 – General-purpose (IP10)
• NEMA Type 1 w/g – General-purpose with gasket (IP21)
• NEMA Type 12 – Dust-tight and drip proof (IP52)
• NEMA Type 3R – Non walk-in weatherproof (IP34)

Motor Control Centers with ArcShield Enclosure Options


Allen-Bradley CENTERLINE 1500 MVMCCs with ArcShield arc-resistant enclosures provide rugged process control for applications that require
a higher level of personnel protection. Products with ArcShield enclosures are tested and compliant to the IEEE C37.20.7 standard, and
provide Type 2B protection during a 40 kA or 50 kA arc flash.

The ArcShield controller helps safely redirect the arc flash energy out the top of the unit and away from personnel. This level of protection is
also maintained, even when the low voltage door is open for maintenance purposes.

All ArcShield products have a robust enclosure design, which contains the arc flash energy and exhaust materials until vents on top of the
enclosure open. Once opened, the vents provide a path for materials to exit the enclosure. An overhead plenum is used to direct the
materials to a safe location away from personnel.

An optional chimney design redirects arc flash materials safely into clear space above the enclosure. The low voltage panel is reinforced and
sealed, to help prevent arc flash exhaust materials from entering this compartment.

As standard, a plenum exhaust section is provided with each new ArcShield order. The plenum exhaust section can be mounted on either the
left or right end of the line-up, and it extends past the end of the line-up. Engineered plenum designs are also available.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 15


Step 3: Structure Options

ArcShield enclosures provide these engineered safety features:


• Reinforced cabinet and power cell door closure mechanism
• Multi-point latching mechanism, reinforced cross bracing and gasket sealing
• Reinforced back plates–added support plates that are secured with multiple bolts provide increased rigidity and security
• Reinforced low voltage panel to withstand arc flash energy and shield maintenance personnel while working in the isolated low
voltage compartment
• Arc ‘Pressure Relief’ vent to vent arc gases and material safely away from personnel during an arc flash
• Available with removable arc exhaust plenum or exhaust chimneys

These medium voltage controller bulletin numbers are available with ArcShield enclosures.
ArcShield Enclosure Specifications
Dimensions, mm (in.) approx. Weight, kg (lb)
Bulletin Number Controller Size Page
Width Depth Height approx.
1506 200/400(1) 915 (36) 1050 (2310) 40
200/400/450(1) 661 (26) 600 (1320)
200/400/450(2) 1118 (44) 1107 (2435)
600(1) 915 (36) 773 (1700)
1512A 31
(2) 1372 (54) 1250 (2750)
600
800(1) 1575 (62) 1400 (3080)
800(2) 2032 (80) 1882 (4135)
3264 (128.5)
(1) 661 (26) 600 (1320)
200/400/450
1512AT 32
600(1) 915 (36) 773 (1700)
915 (36)
200/400(1) 915 (36) 1050 (2310)
1512B 34
200/400(2) 1372 (54) 1530 (3365)
1512BT 200/400(1) 915 (36) 1050 (2310) 35
200/400 915 (36) 886 (1950)
1562F 43
200/400(2) 1372 (54) 1364 (3000)
18(3) 2315 (91)(4) 432 (950)
457 (18)
18(5) 464 (1020)
1591A/B 53
(1)(6) 3264 (128.5)
36
915 (36) 663 (1459)
36(5)
(1) Arc-resistant with plenum.
(2) Arc-resistant with plenum plus PFCC option.
(3) Arc-resistant without plenum.
(4) Added height above standard 91 in. (2315 mm) for the plenum.
(5) Arc-resistant with plenum c/w low voltage panel.
(6) 1591B.

16 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 3: Structure Options

Paint
All metal back plates in the power cell and low voltage compartments are painted high gloss white for high visibility. For all other exterior and
interior metal parts, choose ANSI 49 medium light gray (standard) or ANSI 61 (optional) or specify a custom paint color.
Description Hybrid epoxy powder paint
Standard color ANSI 49 medium light gray (optional ANSI 61 light gray)
Procedure Continuous paint line. All parts are painted before assembly.
Preparation Alkaline wash/rinse/iron phosphate rinse/iron-chrome sealer rinse/recirculated de-ionized water rinse and virgin de-ionized water rinse.
Air-atomized electrostatic spray
Painting Total paint thickness - 0.051 in. (0.002 mm) min
Baking Natural gas oven at 179 °C (355 °F) min

IMPORTANT When optional custom paint colors are specified (including ANSI 61), all external surfaces are painted to the custom
color requirement, except for the external isolating switch handle assembly, lifting angles, and lifting brackets.
All unpainted steel parts are plated for corrosion resistance.

Nameplates
Choose a 3- or 6-line nameplate with black letters on a white background, or white letters on black background.

Low Voltage Wireway


An optional low voltage wireway is located across the roof of the structure.

There are two sizes of low voltage wireway available:


• 51 x 102 mm (2 x 4 in.)
• 152 x 152 mm (6 x 6 in.)
The low voltage wireway provides a convenient method of interconnecting control wire from one controller to another when interfacing with
a master panel or with programmable controller circuits.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 17


Step 3: Structure Options

Notes:

18 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 4: Power Bus Compartment

The power bus provides a number of useful functions, such as incoming line cables can be terminated directly to the power bus. Additionally,
the power bus of several cabinets can be joined together to form an electrically continuous lineup. There are bolted 12 gauge back plates
that allow access from the rear. There are removable side plates on each side of the cabinet for side access.

Horizontal Bus
The main horizontal power bus is located at the center rear of the structure to provide optimum heat distribution, ease of maintenance, and
splicing. The power bus is mounted on the edge to a molded bus support insulator in a common vertical plane. This mounting method
provides superior short-circuit withstand capability and protection against the accumulation of dust and tracking between phases. Access
must be provided to the bus compartment from the front or the rear of the structure to allow for installation and regular maintenance of the
power and ground bus splice connections. Choose one of the following continuous current ratings: 1200, 2000, or 3000 amps.

The power bus is tin-plated copper (standard) but silver-plated option is available. In addition, for the main horizontal bus, you choose the
option of an insulated bus.

The material is a sleeve-type, heat shrink insulating material with good flame resistance and self-extinguishing properties. This material has
a minimum wall thickness of 1.4 mm (0.055 in.), and provides a minimum dielectric strength of 49.5 kV (900V/mil).

Vertical Bus
Vertical power bus risers are provided from the main horizontal power bus to the unit isolating switch line terminals. Risers are made of tin-
plated copper and rated according to the unit size.

Bus and Cable Bracing


The horizontal/vertical bus work and the cabling/bus in the main power cell are braced and tested in accordance with NEMA ICS 3-2 and
UL 347 to withstand the let-through energy allowed by the largest fuse during a short-circuit fault.

Ground Bus
The standard ground bus is 9.5 x 51 mm (3/8 x 2 in.) bare copper with an option for tin plating.

A mechanical lug for 8-1/0 AWG or 6-250 MCM cable is supplied at the incoming end of the lineup.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 19


Step 4: Power Bus Compartment

Notes:

20 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 5: Power Cell Compartment

The power cell is the heart of the controller. It consists of five basic component groups:
• Non-load break isolation switch
• Current limiting power fuses
• Control power transformer
• Vacuum contactor
• Current transformers

Non-load Break Isolation Switch


The isolation switch is a non-load break type switch, and is available in clip-on
or bolt-on fuse versions. The isolation switch works in conjunction with the
contactor and the isolation switch handle to isolate the power cell when the
isolation switch handle is moved to the OFF position.
The power cell door is interlocked with the handle mechanism to help prevent
the door from being opened when the cell is energized. The state of the isolation
switch can be quickly determined through a polycarbonate viewing window.

Standard Features
• Three pole, gang operated
• 400, 600, or 800 A full load current
• Auxiliary contacts
- 2 N.O./2 N.C. are standard
- Provisions for 3 N.O. /3 N.C.
• Contact type: Catalog No. 700-CPM
• Contact Rating: NEMA 2 x A600 and 2 x P600
• Clip-on or bolt-on fuses supported
• Line and load fuse clips or bolt-on locations
• Electrically and mechanically interlocked when used with the Allen-Bradley handle module and contactor
• Shutter mechanism fully isolates the power cell from medium voltage power bus
• Switch blades are grounded in the off position

Mechanical Interlocking
• A simple, heavy duty, direct drive mechanism improves reliability and helps provide excellent operator safety
• All mechanical interlock mechanisms remain part of the enclosure to minimize setup adjustment

Catalog Numbers
Non-load-break Isolation Switch Product Selection
Switch Size(1) Non-Load-Break Isolation Switch Options Cat. No.
Clip-on fuse clips 1503S-4C
400 A
Bolt-on fuse clips 1503S-4B
Clip-on fuse clips 1503S-6C
600 A
Bolt-on fuse clips 1503S-6B
800 A Bolt-on fuse clips 1503S-8B
(1) Enclosed rating at 40 °C (104 °F).

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 21


Step 5: Power Cell Compartment

Vacuum Contactors
Compact and high-performance vacuum contactors are implemented within the power cell 450 A
compartment of CENTERLINE 1500 MVMCCs. These vacuum contactors are designed to
enable repeatable activation and deactivation of the connected load. Their compact and low
maintenance design also reduces the need to remove the contactor to replace power or
control circuit transformer fuses, or do testing.

These contactors are designed as fixed mounted devices for heavy-duty industrial
performance. This design helps reduce the maintenance and reliability concerns that are
associated with drawout-style contactors. Also, there are no drawout stab and finger
assemblies, which require routine maintenance. The contactors are designed to operate
with Rockwell Automation’s IntelliVAC family of control modules or optional pilot relay-type
control. 800 A

Advantages
• Lightweight, compact design
• Minimal maintenance required
• High interrupting capability
• Low chop current
• Visual contact wear indicator (no measurement tools required) Applications
• Mechanical interlocking to the non-load break isolation switch • Medium voltage (1000…7200V)
• Excellent dielectric recovery for high switching frequency vacuum switching for motor starter
• Single coil/core magnet assembly (800 A only) loads (asynchronous, synchronous)
• Control power transformer primary-fuse holders (400 A only) - Full-voltage
• All major components are easily accessed from the front - Reduced voltage
• Mechanical latch design version (optional) - Variable-frequency drives
• Easily integrated into control circuit with quick connector and wire harness (optional) • Transformer feeder unit loads
• Optimized to complement the advanced features of the IntelliVAC control module • Capacitor loads

Bulletin 1502 Vacuum Contactors


Contactor Current Control Circuit
Rating Vacuum Contactor Type Cat. No. Wire Harness Cat.No. (1)

Fixed-mounted, Electrically-held(4)(5) 1502-V4DBDA-__


1503-WHE4D
Electromechanical (4)(5)(6) 1502-V4DBDD-__
Fixed-mounted, Electrically-held (fast drop-out)
450 A(2)(3) Fixed-mounted, Mechanical Latch(4) 1502-VC4DBDB-__ 1503-WHM4D
Fixed-mounted, Electrically-held(6)(7)(8) 1502-VC4DBDA-0 1503-WHE4V
IntelliVAC module
Fixed-mounted, Mechanical Latch 1502-VC4DBDB-0 1503-WHM4V
(4)(5)(6) 1502-V8DXDA-__
Fixed-mounted, Electrically-held
1503-WHE8D
Electromechanical Fixed-mounted, Electrically-held (fast drop-out)(4)(5)(6) 1502-V8DXDD-__
800 A Fixed-mounted, Mechanical Latch(4) 1502-V8DXDB-__ 1503-WHM8D
Fixed-mounted, Electrically-held(8) 1502-VC8DXDA-__ 1503-WHE8V
IntelliVAC module
Fixed-mounted, Mechanical Latch 1502-VC8DXDB-__ 1503-WHM8V
(1) If a 1503F OEM power cell and frame, a 1503C, or 1503E control panel are ordered, a wire harness is provided.
(2) The contactors listed include integrated fuse clips for 5.0 kV max. control power transformer primary fuses. Change the fifth position of the catalog number from ‘B’ to ‘C’ for contactors with
7.2 kV max. fuse clips, e.g. 1502-V4DCDA-1. No extra charge applies.
(3) 450A rating is applicable for class E1 controllers only. For class E2 controllers, 400A rating should be considered for the maximum rating based on power fuse coordination.
(4) Complete the contactor catalog numbers by selecting the altitude rating from Appendix B, e.g. 1502-V4DBDA-2. This altitude code is valid for electrically held and mechanical latch
contactors. If a mechanical latch contactor is used with electromechanical control, select altitude code 1…5. These contactors must only be used with electromechanical (relay) control.
(5) The electrically held contactors are also available with 210V DC coils (210V DC coils are not available for mechanical latch contactors and they are not required when using IntelliVAC control).
Change the sixth position of the contactor catalog number from ‘D’ to E’ (e.g. 1502-V4DCEA-1). Change the last position of the wire harness catalog number from ‘D’ to ‘E’. No extra charge.
(6) For use as bypass contactors with Bulletin 1503E MV SMC™-50 controllers.
(7) When IntelliVAC control is used, select altitude code zero (0) which allows the same contactor to be used from -1000…5000 m.
(8) 1502-VC electrically-held contactors are provided as fast drop out type, and drop out delays are controlled by the IntelliVAC control module.

22 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 5: Power Cell Compartment

Power Fuses
Three R-rated current-limiting power fuses are applied with the vacuum contactors so no
transient overload current reaches the motor.

E-rated power fuses are implemented for some sizes of transformer controllers. Both bolt-
on and clip-on styles are available.

Clip-on Bolt-on

Recommended Clip-on Power Fuses


Clip-on Fuses
(1) Maximum Full Maximum Locked 5 kV 5 kV 7.2 kV 7.2 kV
Fuse Rating Load Current (A) Rotor Current (A) Allen-Bradley Mersen Allen-Bradley Mersen
Part Number Part Number Part Number Part Number
2R, 70 A 32 160 25173-555-01(2) A480R-2R(2) 80025-650-01(2) A072F1DORO-2R(2)
3R, 100 A 45 235 25173-555-02(2) A480R-3R(2) 80025-650-02(2) A072F1DORO-3R(2)
4R, 130 A 65 325 25173-555-03(2) A480R-4R(2) 80025-650-03(2) A072F1DORO-4R(2)
5R, 150 A 80 405 25173-555-09(2) A480R-5R(2) 80025-650-04(2) A072F1DORO-5R(2)
6R, 170 A 95 490 25173-555-04(2) A480R-6R(2) 80025-650-05(2) A072F1DORO-6R(2)
9R, 200 A 140 725 25173-555-05(2) A480R-9R(2) 80025-650-06(2) A072F1DORO-9R(2)
12R, 230 A 190 950 25173-555-06(2) A480R-12R(2) 80025-650-07(2) A072F1DORO-12R(2)
(1) Continuous ampere rating at 40 °C (104 °F) as recommended by fuse manufacturer. The fuse rating must be derated if the internal temperature exceeds 40 °C (104 °F). Rockwell Automation
recommends that the continuous load current does not exceed 80% of the fuse rating.
(2) Single-barrel fuse.

Recommended Bolt-on Power Fuses


Bolt-on Fuses
Maximum Full Maximum Locked 5 kV 5 kV 7.2 kV 7.2 kV
Fuse Rating(1) Load Current (A) Rotor Current (A) Allen-Bradley Mersen Allen-Bradley Mersen
Part Number Part Number Part Number Part Number
18R, 390 A 280 1450 80025-296-07(4) A051B1DARO-18R(4) 80025-651-01(4) A072B2DARO-18R(4)

19R, 315 A(2) 275 1470(3) 80025-296-10(5) A051B1DARO-19R(5) 80026-437-01(5) A072B1DORO-19R(5)


24R, 450 A 360 1980 80025-296-08(4) A051B1DARO-24R(4) 80025-651-02(4) A072B2DARO-24R(4)
32R, 600 A 440 2450 80025-296-13(4) A051B2DARO-32R(4) 80026-437-02(4) A072B2DORO-32R(4)
38R, 700 A 525 2820 80025-296-09(4) A051B2DARO-38R(4) 80026-437-03(4) A072B2DORO-38R(4)
48X, 750 A 600 3545 80025-296-12(4) A051B3DARO-48X(4) 80026-437-04(4) A072B3DBRO-48X(4)
57X, 900 A 745 4230 80025-296-11(6) A051B3DARO-57X(6) 80026-437-05(6) A072B3DBRO-57X(6)
(1) Continuous ampere inch rating at an internal temperature of 40 °C (104 °F) as recommended by fuse manufacturer. The fuse rating must be derated if the internal temperature exceeds an
internal temperature of 40 °C (104 °F). Rockwell Automation recommends that the continuous load current does not exceed 80% of the fuse rating.
(2) 7.2 kV: 300 A.
(3) 7.2 kV: 1455 A
(4) Double-barrel fuse.
(5) Single-barrel fuse.
(6) Triple-barrel fuse.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 23


Step 5: Power Cell Compartment

Control Power Transformers


The standard CPT transforms the primary side medium voltage to a single-phase 120V or
240 V secondary side voltage to run the control circuitry efficiently in the isolated low
voltage compartment. The CPT features a standard accuracy of ±4%, with the option of
±1% accuracy per customer request.
As standard, the dry-type CPT must be 500 VA in size, with approximately 350 VA extra
capacity. Appropriately sized primary and secondary fuses are supplied. Optional sizes of
1000 VA, 2000 VA and 3000 VA control power transformers must also be available. The
secondary circuit of the transformer is disconnected from the control circuit by means of
the isolating switch auxiliary contacts to prevent backfeeding through the transformer
and to isolate the power cell when the control circuit is in the test mode.

IMPORTANT The control power transformers may be used for metering, but only
if the accuracy of the application does not require conformance to
any potential transformer accuracy ratings.
The maximum quantity/size of the CPT available in a two-high FVNR
controller rated 7200 volts is two 500 VA (with bolt-on power fuses),
or one 1000 VA and one 500 VA (with clip-on power fuses).

Current Transformers
CENTERLINE 1500 MVMCCs use two styles of current transformers; donut type
and bar type. Three of either types are used for overload protection and
metering. Optional ground fault (zero sequence style) current transformers
are also available.

The medium voltage power cell includes three current transformers of


sufficient VA capacity to meet the requirements of all the devices connected
to them.

Each current transformer has the primary rating sized appropriately in


relation to the full-load current rating of the load. The secondary of the
current transformers has a 5 A output and an accuracy suitable for the type
and quantity of protection or metering devices connected to it. All current
transformer control wiring are terminated on the current transformer with
locking-type, fork tongue lugs.

Ground Fault Current Transformer


The power cell has provisions to locate a toroid (donut) style, ground fault
sensing current transformer, when the optional zero sequence ground fault
protection feature is required.

Load Cable Terminations


When either bar- or donut-type current transformers are supplied,
appropriate load termination points is provided to accommodate lugs with
single or two-hole mounting to connect the load cables.

24 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 5: Power Cell Compartment

Integrated Protective Maintenance Grounding Device


The Integrated Protective Maintenance Grounding device (IPMG) is an
optional feature that provides an over-center, spring loaded, snap action
device that provides a low impedance grounding path for all load
connections on CENTERLINE™ Bulletin 1500/1900 medium voltage motor
Main Power and Ground Bus controllers. The IPMG device can make and withstand short-circuit
currents within its capabilities, from both feeding directions within the
IS motor controller, without any latching mechanism. It is applied to safely
ground/earth the load connections to three-phase motors, power
transformers, and power capacitors ensuring that no harmful voltages
R/E Type are left or become present on the load connections before maintenance
personnel enter the motor controller or service the equipment at the end
Mechanical Interlock

of the load cable connections.

The compact design of the IPMG device does not compromise its rugged
construction and proven performance under industrial operating
conditions. Requiring minimal maintenance, this manually operated
IPMG
device is controlled from the outside of the standard and arc-resistant
(ArcShield™) medium voltage controllers. It is mechanically interlocked to
both the main vacuum contactor and our non-load break isolation switch.
Manual
These features, along with its high electrical and mechanical endurance
Procedure to capabilities, help to provide a long-life and dependable maintenance-free
Close operation.
GFCT (x1)

To help fulfill your safety program requirements, a visual indication of the


blade positions of the IPMG device (OPEN or CLOSED) is available through
90 the standard viewing window on the medium voltage compartment door.
CT (x3)

The IPMG device is mounted on the controller floor plate or on the top of
T1, T2, T3 Motor Terminals
the main medium voltage vacuum contactor (for 600/800 A controllers).
It is connected to the three load phases within the main controller using
copper bus bars. Redundant, flexible grounding conductors ensures the
lowest impedance path to ground is maintained when the IPMG device is
closed. Flexible grounding conductors provide low impedance back to the
main ground bus to complete the grounding (earthing) process.

Integrated Protective Mounting Grounding Device

400 A IPMG 800 A IPMG

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 25


Step 5: Power Cell Compartment

Notes:

26 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 6: Low Voltage Compartment

The isolated low voltage compartment allows testing and troubleshooting of the power cell with no exposure to medium voltage. The
standard components housed in the low voltage panel are:
• Normal-Off-Test selector switch
• Male test power receptacle
• Rectifier bridge
• CR1 and CR2 control relays
• Motor protection relay(s)

Bulletin 193/592 E300 Electronic Overload Relay


The Allen-Bradley E300 Electronic Overload Relay is the next generation electronic overload relay. Its modular design, communication
options, diagnostic information, simplified wiring, and integration into Logix 5000® controllers make it the ideal overload for motor control
applications in an automation system.
The E300 Overload Relay provides flexibility, helps reduce engineering time, and maximizes
uptime for important motor starter applications.

Modular Design
For exacting application needs
• Wide current range
• Multiple sensing capabilities
• Expansion I/O
• Operator interface

Intelligent Motor Control


Easy automation system integration
• Network connectivity
• Native I/O
• DeviceLogix technology enabled
• Integrated into Logix
• Preprogrammed operating modes

Diagnostic Information
Monitor motor performance, which includes:
• Voltage, current, and energy
• Trip/warning histories
• Percentage of thermal capacity use
• Time to reset
• Operational hours
• Number of starts

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 27


Step 6: Low Voltage Compartment

Bulletin 1503VC IntelliVAC Contactor Control Modules


The Bulletin 1503VC IntelliVAC controllers offer an excellent, efficient, and flexible
means to control Bulletin 1502 vacuum contactors. The IntelliVAC control module
family offers a scalable solution for multiple medium voltage control applications. A
wire harness for 1502 vacuum contactors is generally required.

IntelliVAC Control Module


The IntelliVAC module provides basic control capabilities for 400 A, 450 A, and 800 A
contactors (electrically held and mechanical latch) using a single device. It offers
enhanced reliability through better diagnostics and coordination between the
power fuses and the vacuum contactor drop-out time. Productivity is improved
using the power loss ride through (TDUV) and contactor re-closing control features.
• Universal input voltage (110…240V AC, 50/60 Hz or 110…250V DC)
• Consistent vacuum contactor pick-up time
• Selectable and repeatable vacuum contactor drop-out times
(50, 75, 100, 130, 150, 175, 200, or 240 ms)
• Altitude compensation (-1000…+5000 m) eliminates mechanical hardware
changes at high altitude (450 A vacuum contactors)
• Power loss ride-through logic (TDUV) with selectable drop out time
(0.2, 0.5, 1.0, or 2.0 s) requires only an external capacitor
• Re-closing control features (anti-kiss and anti-pumping protection)
• Status indication (LEDs and relay outputs) allows integration in control
system and aids troubleshooting
• Temporary motor jog function (separate input) to allow process set-up
• Delayed motor re-start prevents rapid cycling of vacuum contactor,
protecting the connector motor
IntelliVAC Control Module Specifications
IntelliVAC Catalog Numbers(1) Vacuum Contactor Type
1503VC-BMC5 IntelliVAC Module Electrically Held or Mechanical Latch
Ratings and Approvals
AC 110…240V, 47…63 Hz(2)
Input Voltage
DC 110…250V
Inrush (max.) 25 A (1/2 cycle)
Idle (max.) 125 mA
AC(2) Close (max.) 11.3 A
Hold (max.) 300 mA
Latch Trip (max.) 7.0 A
Input Current(3)
Inrush (max.) 25 A
Idle (max.) 35 mA
DC Close (max.) 4.8 A
Hold (max.) 100 mA
Latch Trip (max.) 3.7 A
AC 70…240V rms
Command Inputs
DC 70…250V
AC 250V rms, 5 A, R load; 2 A (reactive), PF = 0.4
Status Output Contacts
DC 30V, 5 A, R load; 2 A (reactive), L/R = 7 ms
Standards and Approval cULus, CE
(1) A wire harness is required for Bulletin 1502 vacuum contactors when an IntelliVAC control module is used.
(2) All AC values are rms, except where noted.
(3) The maximum currents shown are for either the 450A or 800A Bulletin 1502 vacuum contactors. Close current duration is 200 milliseconds.

28 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 6: Low Voltage Compartment

Bulletin 1794 FLEX I/O


Bulletin 1794 FLEX™ I/O modules offer flexibility for your application with digital, analog, HART analog, and specialty I/O, with 4…32 points per
module. It complements all Rockwell Automation controller platforms and can communicate on EtherNet/IP for a distributed I/O solution.

FLEX I/O offers all the functions of larger rack-based I/O without the space requirements. Its cost effectiveness, flexibility, modularity, and
reliability have made it one of the most popular distributed I/O platforms.

FLEX I/O helps eliminate multiple long wiring runs, reduces terminations, decreases engineering and installation costs and time, and
substantially reduces down time.

The FLEX I/O system can communicate on EtherNet/IP, ControlNet®, DeviceNet®, and many other open networks including, but not limited to,
Remote I/O, PROFIBUS DP™, and Interbus-S. You can independently select the I/O, termination style, and network to meet your application
needs.
Adapter Terminal base I/O module
Flexbus connectors Keyswitch

Flexbus connectors

2 2
++

Network
Connector 24V DC field power Terminal strips

Bulletin 1426 PowerMonitor 5000


The PowerMonitor family of meters provides advanced
technology, fast response, and excellent accuracy.

The M5 model is the base version and provides an


extensive range of metering functionality.

The M6 model expands the metering capabilities of the M5


with basic power quality monitoring functionality,
including harmonics up to the 63rd, waveforms and
logging, and classification of power quality events.

The M8 model adds advanced power quality monitoring


functions, including flicker that is caused by voltage
fluctuations, sub-cycle transient capture, harmonics up to
the 127th order, and inter-harmonic groups up to the 50th
order.
The PowerMonitor 5000 unit communicates power and
energy parameters to controllers, HMI software, and other
applications over the EtherNet/IP network.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 29


Step 6: Low Voltage Compartment

Notes:

30 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

CENTERLINE® 1500 Medium Voltage Motor Control Centers (MCCs) are available in control formats that include arc resistant enclosures.
Controller options include full-voltage, reversing, reduced-voltage, solid-state reduced-voltage, multi-speed, and synchronous control. These
controllers include load break switches that provide integrated intelligence and the lowest-cost solution for starting motor applications.

Bulletin 1512A One-high Full-voltage Non-reversing Motor Starter


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features
• Additional low voltage control panel accessories which include:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Two-high structure design for two complete motor controllers
• Available in optional ArcShield enclosure
• Also available as ‘Prepared Space’ (Bulletin 1512BP) and Starter Kits (Bulletin 1512BS)
Bulletin 1512A Starter Specifications
Hp, max Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 800 1000 1250 1500 2250 2500
661 (26) 490 (1075)(2)
400 1500 2250 2750 3000 4500 5000
915 (36) (1)
2311 (91)
600 2750 3500 4500 5500 8000 915 (36) 611 (1350)(2)
800 3000 5000 6000 7000 9000 1422 (56)(3) 816 (1800)
(1) Height is 3264 mm (128.5 in.) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.
(3) Width is 1576 mm (62 in.) with ArcShield enclosure.

Bulletin 1512A Power Circuit Schematic


L1 L2 L3 GND
IS GFCT
(optional) CT1
T1
F1

CT2 T2
F1 M
CT3 T3
F1
M
BLK

F2 F2

CPT1

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 31


Step 7: Medium Voltage Control Types

Bulletin 1512AT Full-voltage Transformer Feeder Unit Starter


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three E-rated current-limiting power fuses (R-rated power fuses that are used for controller sizes and
voltages)
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features
• Additional low voltage control panel accessories which include:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• One-high structure design for one complete motor controller
• Available in optional ArcShield enclosure
• Also available as ‘Prepared Space’ (Bulletin 1512AP, only in 200 A and 400 A) or Feeder Kits (Bulletin 1512AU)
Bulletin 1512AT Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 700 1000 1250 2000
660 (26) 490 (1075)(2)
400 1250 2000 2500 2750 4500 2311 (91)(1)
914 (36)
600 2250 3000 4000 4500 6500 914 (36) 611 (1350)(2)
800 3000 4000 5500 6000 8000 1422 (56)(3) 2311 (91) 816 (1800)
(1) Height is 3264 mm (128.5 in.) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.
(3) Width is 1576 mm (62 in.) with ArcShield enclosure.

Bulletin 1512AT Power Circuit Schematic


L1 L2 L3 GND IS Transformer
CT1 T1
F1

CT2
T2
F1 TX

CT3 T3
F1
M
F2 F2

CPT1

ISa

32 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1512AD One-high Full-voltage Non-reversing Drive Input Starter Controller


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three current-limiting power fuses
• Three current transformers
- Segregated low voltage panel to house circuit control fusing that includes:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Optional hardware for unit control and monitoring
- IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pickup time
- Altitude compensation
- Anti-kiss and anti-plugging protection
- Set of control circuit terminal blocks
• Unit output must be cabled to VFD input. Customer is responsible for inter-wiring between input contactor unit and variable-
frequency drive (VFD)
Bulletin 1512AD Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.(1)
2400…6900 V Width Depth Height
200
Sized based on variable- 660 (26) 488 (1075)
400 frequency drive and
continuous current of the 914 (36) 2311 (91)(2)
600 914 (36) 611 (1350)
motor
800 1423 (56)(3) 816 (1800)
(1) Weight is different with ArcShield enclosure.
(2) Height is 3264 mm (128.5 in.) with ArcShield enclosure with plenum.
(3) Width is 1576 mm (62 in.) with ArcShield enclosure.

Bulletin 1512AD Power Circuit Schematic


L1 L2 L3 GND IS
CT1 H1
F1
Medium
CT2 Voltage
H2
F1 Variable
Frequency
CT3 H3 Drive
F1
M
F2 F2

CPT1

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 33


Step 7: Medium Voltage Control Types

Bulletin 1512B Two-high Full-voltage Non-reversing Motor Starter


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features
• Additional low voltage control panel accessories that include:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Two-high structure design for two complete motor controllers
• Available in optional ArcShield enclosure
• Also available as ‘Prepared Space’ (Bulletin 1512BP) and Starter Kits (Bulletin 1512BS)
Bulletin 1512B Starter Specifications
Hp, max Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 800 1000 1250 1500 2250 2500
915 (36) 915 (36) 2311 (91)(1) 802 (1770)(2)
400 1500 2250 2750 3000 4000 4000
(1) Height is 3264 mm (128.5 in) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.

Bulletin 1512B Power Circuit Schematic


L1 L2 L3 GND IS GFCT
(optional) CT1 T1
F1

CT2 T2
F1 M
CT3 T3
F1
M
BLK

F2 F2

CPT1

ISa

34 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1512BT Two-high Full-voltage Transformer Feeder Unit Starter


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three E-rated or R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features
• Additional low voltage control panel accessories that include:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Two-high structure design for one complete motor controller
• Available in optional ArcShield enclosure
• Also available as ‘Prepared Space’ (Bulletin 1512BP) or Starter Kit (Bulletin 1512BU)
Bulletin 1512BT Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 700 1000 1250 2000
915 (36) 915 (36) 2311 (91)(1) 802 (1770)(2)
400 1500 2000 2500 2750 4000
(1) Height is 3264 mm (128.5 in.) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.

Bulletin 1512BT Power Circuit Schematic

L1 L2 L3 GND IS Transformer
CT1 H1
F1

CT2
H2
F1 TX

CT3 H3
F1
M
F2 F2

CPT1

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 35


Step 7: Medium Voltage Control Types

Bulletin 1512BD Two-high Full-voltage Non-reversing Drive Input Starter Controller


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pickup time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Unit output must be cabled to VFD input. Customer is responsible for inter-wiring between input
contactor unit and VFD.
Bulletin 1512BD Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6900V Width Depth Height
200 Sized based on VFD and continuous
current of the motor1250 915 (36) 915 (36) 2311 (91)(1) 802 (1770)(2)
400
(1) Height is 3264 mm (128.5 in) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.

Bulletin 1512BD Power Circuit Schematic


L1 L2 L3 GND IS
CT1
H1
F1
Medium
CT2 Voltage
H2
F1 Variable
Frequency
CT3 Drive
H3
F1
M
F2 F2

CPT1

ISa

36 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1512DM Variable Frequency Drive Input Contactor with Output Isolator Unit
• Fixed mounted vacuum contactor
• 400A rated unit includes two three-pole, gang-operated, non-load break isolating switches with one
external operating handle. Both switches are mechanically interlocked with each other, the main
contactor and the power cell doors. The 600A and 800A rated units are mechanically interlocked using
key interlocks and a separate external operating handle for each isolating switch
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three current-limiting power fuses
• Three current transformers
• Segregated low voltage panel to house control circuit fusing, “NORMAL-OFF-TEST” circuit, receptacle
for external test power supply, set of control circuit terminal blocks and optional hardware for unit
control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pick-up time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Additional variable frequency output power bus (1200A rating) located in the top of the power bus
compartment
Bulletin 1512DM Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6900V Width Depth Height
200/400 915 (36) 915 (36) 231 (91) 805 (1770)
Sized based on VFD and continuous
600 1829 (72) 915 (36) 231 (91) 1228 (2700)
current of the motor1250
800 2845 (112) 915 (36) 231 (91) 1591 (3500)

Bulletin 1512DM Power Circuit Schematic


L1 L2 L3 GND
DIIS
CT1 H1
F1 To
Medium
CT2 H2 Voltage
F1 Variable
CT3 Frequency
H3 Drive
F1

F2 F2
DI

CPT1
DIISa

DOISa

VF1 VF2 VF3


DOIS
U
From
Medium
V Voltage
Variable
Frequency
W Drive

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 37


Step 7: Medium Voltage Control Types

Bulletin 1512DO Variable Frequency Drive Output Contactor Unit


• Fixed mounted vacuum contactor
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Segregated low voltage panel to house control circuit fusing, “NORMAL-OFF-TEST” circuit, receptacle
for external test power supply, set of control circuit terminal blocks and optional hardware for unit
control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pick-up time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Additional variable frequency output power bus (1200 A rating) located in the top of the power bus
compartment

Bulletin 1512DO Starter Specifications


Hp, max Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6900V Width Depth Height
200
Sized based on VFD and continuous 660 (26) 488 (1075)
400 914 (36) 2311 (91)
current of the motor12
600 914 (36) 611 (1350)

Bulletin 1512DO Power Circuit Schematic

VF1 VF2 VF3 GRD DO


T1

T2
M
T3
DO

38 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1512M Full Voltage Non-Reversing, Output Bypass Starter Unit with Vacuum
Contactors (FVOP)
• Fixed mounted “OUTPUT” and “BYPASS” vacuum contactors
• 400 A rated unit includes two three-pole, gang-operated, non-load break isolating switches with one
external operating handle. Both switches are mechanically interlocked with each other, the contactor
and the power cell doors. The 600 A and 800 A rated units are mechanically interlocked using key
interlocks and a separate external operating handle for each isolating switch.
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three current-limiting power fuses
• Three current transformers
• Two segregated low voltage panels to house control circuit fusing, “NORMAL-OFF-TEST” circuit,
receptacle for external test power supply, set of control circuit terminal blocks and optional hardware
for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pick-up time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Additional variable frequency output power bus (1200 A rating) located in the top of the power bus
compartment
Bulletin 1512M Starter Specifications
Hp, max Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6600V Width Depth Height
200/400 915 (36) 915 (36) 231 (91) 805 (1770)
Sized based on VFD and continuous
600 1829 (72) 915 (36) 231 (91) 1228 (2700)
current of the motor1
800 2845 (112) 915 (36) 231 (91) 1591 (3500)

Bulletin 1512M Power Circuit Schematic

L1 L2 L3 GND
BPIS
CT1 T1
F1

CT2 T2
F1 M
CT3 T3
F1
BP
F2 F2

CPT1

BPISa
OPISa

VF1 VF2 VF3 OPIS

OP

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 39


Step 7: Medium Voltage Control Types

Bulletin 1506 Full-voltage Reversing Motor Starter


• Fixed mounted vacuum contactors (forward and reverse)
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
• Additional low voltage control panel accessories that include:
- “NORMAL-OFF-TEST” circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Available for motor loads
• Plugging or anti-plugging duty
• Mechanically and electrically interlocked contactors
Bulletin 1506 Starter Specifications
Hp, max Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V Width Depth Height approx.
200 800 1000 1250 1500
914 (36) 2311 (91)(1) 1770 (802)(2)
400 1500 2250 2750 3000 914 (36)
800 3500 5000 6000 7000 1422 (56) 2311 (91) 1950 (885)
(1) Height is 3264 mm (128.5 in) with ArcShield enclosure with plenum.
(2) Weight is different with ArcShield enclosure.

Bulletin 1506 Power Circuit Schematic

L1 L2 L3 GND
GFCT
IS CT1 (optional)
FWD T1
F1

CT2 T2
FWD
F1 M
CT3 T3
FWD
F1
BLK

REV
W

F2 F2

REV
CPT1
REV

ISa

40 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1522E/F/G Two-speed Non-reversing Motor Starter


• Fixed mounted vacuum contactor
• HIGH and LOW speed settings for two-speed separate winding, Bulletin 1522E starter
• HIGH/LOW speeds and HIGH SPEED SHORTING settings for two-speed consequent pole, Bulletin 1522F/G
starter
• Three-pole, gang-operated, non-load break isolating switch with an external operating handle, fully
interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three R-rated current-limiting power fuses
• Six current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features
• Additional low voltage control panel accessories that include:
- ‘NORMAL-OFF-TEST’ circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• Constant or variable torque, and constant horsepower applications
Bulletin 1522E/F/G Starter Specifications
Hp, max Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V Width Depth Height approx.
200 800 1000 1250 1500
915 (36) 915 (36) 2311 (91) 802 (1770)
400 1500 2250 2750 3000

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 41


Step 7: Medium Voltage Control Types

Bulletin 1522E Power Circuit Schematic

L1 L2 L3 GND IS
GFCT1
(optional) CT1
T1 T11
F1
S
CT2 T2 T12
F1 M
S
CT3 T3 T13
F1
S

BLK
F2 F2

W
CPT1 GFCT2
(optional) CT4

ISa FC
CT5

FC
CT6

FC

BLK

Bulletin 1522E Power Circuit Schematic

L1 L2 L3 GND IS
GFCT1
(optional) CT1
T1 T11
F1
S
CT2
T2 T12
F1 M
S
CT3
T3 T13
F1
S
BLK

F2 F2 FC2

FC2
CPT1 GFCT2
(optional) CT4 FC2

ISa FC
CT5

FC
CT6

FC
BLK

42 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1560F/1562F SMC-50 Smart Electronic Soft Start Motor Controller


The Bulletin 1562F is a flexible combination motor controller available in two main configurations:
• A modified two-high cabinet (two complete controllers)
• A combination of a one-high full-voltage non-reversing (FVNR) cabinet and a 1560F unit (one complete
controller)

Based around the SMC™-50 Smart motor control module, we offer various advanced controlling and electronic
motor-starting styles:
• Soft start with Selectable Kickstart
• Soft stop
• Pump control start/stop
• Torque control
• Current limit start with Selectable Kickstart
• Sensorless linear speed acceleration with Selectable Kickstart
• Sensorless linear speed deceleration
• Dual ramp with Selectable Kickstart
• Emergency run (full-voltage)

The SMC-50 control module offers advanced monitoring/metering functions, and provides motor and controller protection.

The Bulletin 1562F features both isolation and bypass vacuum contactors. The Bulletin 1560F is a retrofit controller that is specifically
designed to integrate smoothly with an existing customer-supplied starter to enable all combination controls listed in this section.

Bulletin 1560F and Bulletin 1562F Controllers

Retrofit Controller Combination Controller

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 43


Step 7: Medium Voltage Control Types

Bulletin 1560F/1562F Starter Specifications


Dimensions, mm (in.), approx.
Bulletin Voltage Starter Size (A) Hp, max Weight, kg (lb), approx.
Width Depth Height
200 800
660 (26) 363 (800)
2400 400 1500
600 2750 1118 (44) 590 (1300)
200 1000
660 (26) 363 (800)
3300 400 2250
600 4000 1118 (44) 590 (1300)
200 1250
660 (26) 363 (800)
1560F 4160 400 2750 914 (36) 2311 (91)
600 4500 1118 (44) 590 (1300)
200 2250
914 (36) 636 (1400)
6600 400 4500
600 7500 1118 (44) 590 (1300)
200 2500
914 (36) 554 (1220)
6900 400 5000
600 7500 1118 (44) 590 (1300)
200 800
914 (36) 914 (36)(1) 2311 (91)(2) 636 (1400)(3)
2400 400 1500
600 2750 2032 (80) 914 (36) 2311 (91) 1227 (2700)
200 1000
914 (36) 914 (36)(1) 2311 (91)(2) 636 (1400)(3)
3300 400 2250
600 4000 2032 (80) 914 (36) 2311 (91) 1227 (2700)
200 1250
914 (36) 914 (36)(1) 2311 (91) 636 (1400)(3)
1562F 4160 400 2750
600 4500 2032 (80) 914 (36) 1227 (2700)
200 2250
1575 (62) 2311 (91) 1056 (2325)
6600 400 4500 914 (36)
600 7500 2032 (80) 1227 (2700)
200 2500
1575 (62) 914 (36) 2311 (91) 1056 (2325)
6900 400 5000
600 7500 2032 (80) 914 (36) 2311 (91) 1227 (2700)
(1) Depth is 1168 mm (46 in.) with ArcShield enclosure with plenum.
(2) Height is 3264 mm (128.5 in.) with ArcShield enclosure with plenum.
(3) Weight is different with ArcShield enclosure.

44 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1560F Power Circuit Schematic

GND
CT1
A IN A OUT

CT2
B IN B OUT
M
CT3
C IN C OUT

Bulletin 1562F Power Circuit Schematic

L1 L2 L3 GND GFCT1
IS
(optional) CT1
A OUT
F1

CT2
B OUT
F1 M
CT3
C OUT
F1
M
BLK

F2 F2

CPT1

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 45


Step 7: Medium Voltage Control Types

Bulletin 1572/1576/1582 Reduced Voltage Reversing and Non-reversing Autotransformer


and Reactor Motor Starter
• Fixed mounted vacuum contactors
• (1S, 2S, and RUN) contactors, with closed transition operation, Bulletin 1572 non-reversing
starter
• (1S, FORWARD, REVERSE, and RUN) contactors, with closed transition operation, Bulletin 1576
reversing starter
• A three-pole, gang-operated, non-load break isolating switch with an external operating
handle, fully interlocked with main contactor and power cell doors
• A polycarbonate viewing window in the power cell door to view the position of the
isolating switch
• Three R-rated current-limiting power fuses
• Three current transformers
• Control power transformer with primary and secondary fuses
• Segregated low voltage panel to house standard and optional hardware for unit control and
monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with
advanced features
• Additional low voltage control panel accessories that include:
- “NORMAL-OFF-TEST” circuit
- Receptacle for external test power supply
- Set of control circuit terminal blocks
• NEMA medium duty, dry type, three-winding autotransformer with 50%, 65% and 80% taps. The 65% tap is used unless otherwise
specified.
Bulletin 1572/1576/1582 Starter Specifications
Hp, max Dimensions, mm (in.), approx. Weight, kg (lb),
Controller Type Starter Size (A)
2400V 3300V 4160V 4800V Width Depth Height approx.
200 800 1000 1250 1500
1422 (56) 1703 (3750)
400 1500 2250 2750 3000
1572
600 2250 4000 4500 5500 2032 (80)
2270 (5000)
800 3500 5000 6000 7000
200 800 1000 1250 1500
2032 (80) 1703 (3750)
1576 400 1500 2250 2750 3000 914 (36) 2311 (91)
800 3500 5000 6000 7000 2540 (100) 2270 (5000)
200 800 1000 1250 1500
1422 (56) 1703 (3750)
400 1500 2250 2750 3000
1582
600(1) 2250 4000 4500 5500 2032 (80)
2270 (5000)
(1) 3500 5000 6000 7000 2540 (100)
800
(1) 600 A and 800 A controllers require a separately quoted autotransformer with minimum dimensions of 1321 x 1168 x 1676 mm (52 x 46 x 66 in.).

46 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1572 Power Circuit Schematic

L1 L2 L3 GND IS GFCT

100%
(optional) 1S

80%

50%
65%
CT1

0%
T1
F1 R

100%
1S

80%

50%
65%
CT2

0%
T2
F1 R M

100%
80%

50%
CT3

65%
1S

0%
T3
R
F1
M

BLK
F2 F2

W
CPT1

ISa

Bulletin 1576 Power Circuit Schematic

L1 L2 L3 GND IS GFCT
CT1 (optional)

100%
1S

80%

50%
65%

0%
FWD T1
F1 R

CT2 FWD

100%
1S

80%

50%
65%

0%
T2
F1 R M
CT3

100%
80%

50%
65%
FWD 1S

0%
T3
R
F1

REV
BLK

W
F2 F2
REV

CPT1
REV

ISa

Bulletin 1582 Power Circuit Schematic

L1 L2 L3 GND IS GFCT
(optional)
80%

50%
65%

CT1 T1
F1 R
80%

50%
65%

CT2 T2
F1 R M
80%

50%
65%

CT3 T3
F1 R
S
BLK

F2 F2

CPT1

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 47


Step 7: Medium Voltage Control Types

Bulletin 1906B/1912B Full-voltage Reversing and Non-reversing Brush-type Synchronous


Motor Starter
• Bulletins 1906B and 1912B are designed as a complete reversing and non-reversing synchronous
starter, respectively(a)
• Available with or without static exciter
• Features a control power transformer (CPT) with primary and secondary fuses for converting line
voltage to single-phase 120V for low voltage devices
• Forward-mounted vacuum contactors are implemented within the Bulletin 1906B starter
• The Bulletin 1912B starter showcases both forward and reverse vacuum contactors
• Standard SyncProIIB field application and protection system

Bulletin 1906B Starter Specifications


Hp, max Dimensions, mm (in.), approx.(1) Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V Width Depth Height approx.
200 800 1000 1250 1500
660 (26) 490 (1075)
400 1500 2250 2750 3000 914 (36) 2311 (91)
800 3500 5000 6000 7000 2337 (92) 1619 (3570)
(1) These dimensions exclude static exciter.

Bulletin 1912B Starter Specifications


Hp, max Dimensions, mm (in.), approx.(1) Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 800 1000 1250 1500 2000 2250
660 (26) 490 (1075)
400 1500 2250 2750 3000 4500
914 (36) 2311 (91)
600 2750 3500 4500 5500 914 (36) 773 (1700)
Contact factory
800 3500 5000 6000 7000 1422 (56) 885 (1950)
(1) These dimensions exclude static exciter.

(a) See the standard features provided with the Bulletin 1506 and 1512 motor controllers.

48 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1906B Power Circuit Schematic

IS GFCT1
L1 L2 L3 GND
CT1 (optional)
FWD T1 (+)
F1 F1
CT2 R1
FWD T2
F1 M RD

CT3 R2
T3
FWD (-) F2
F1

BLK

W
F2 F2 REV

REV
CPT1
REV
ISa

Bulletin 1912B Power Circuit Schematic

L1 L2 L3 GND IS GFCT1
(optional) CT1
T1 (+)
F1
F1
CT2 R1
T2
F1 M RD
R2
CT3 T3
F1 (-)
M F2
BLK

CPT1 F2 F2

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 49


Step 7: Medium Voltage Control Types

Bulletin 1906L/1912LFull-voltage Reversing and Non-reversing Brushless Synchronous


Motor Starter
• Bulletins 1906L and 1912L are designed as complete reversing and non-reversing synchronous starters,
respectively(a)
• Available with or without static exciter
• Features a control power transformer (CPT) with primary and secondary fuses for converting line
voltage to single phase 120V for low voltage devices
• Forward-mounted vacuum contactors are implemented within the Bulletin 1906B starter
• The Bulletin 1912L starter showcases both forward and reverse vacuum contactors

Bulletin 1906L Starter Specifications


Hp, max Dimensions, mm (in.), approx.(1) Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V Width Depth Height approx.
200 800 1000 1250 1500
1372 (54) 1076 (2370)
400 1500 2250 2750 3000 914 (36) 2311 (91)
800 3500 5000 6000 7000 1880 (74) 1090 (2400)
(1) These dimensions exclude static exciter.

Bulletin 1912L Starter Specifications


Hp, max Dimensions, mm (in.), approx.(1) Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
200 800 1000 1250 1500
660 (26) 490 (1075)
400 1500 2250 2750 3000
Contact factory 914 (36) 2311 (91)
600 2750 3500 4500 5500 1372 (54) 885 (1950)
800 3500 5000 6000 7000 1880 (74) 1090 (2400)
(1) These dimensions exclude static exciter.

(a) See the standard features provided with the Bulletin 1506 and 1512 motor controllers.

50 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 7: Medium Voltage Control Types

Bulletin 1906L Power Circuit Schematic

L1 L2 L3 GND GFCT1
IS CT1 (optional)
FWD T1
F1 (+)
F1
CT2
FWD T2
F1 M
CT3
FWD T3
F1 (–)
F2

BLK

W
F2 F2 REV

REV
CPT1
REV

ISa

Bulletin 1912L Power Circuit Schematic

L1 L2 L3 GND GFCT1
(optional) CT1
IS T1
F1 (+)
F1
CT2
T2
F1 M
CT3 T3
F1 (–)
F2
M
BLK

F2 F2

CPT1

ISa

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 51


Step 7: Medium Voltage Control Types

Notes:

52 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 8: Incoming Line Units

Bulletin 1591A/B Incoming Line Units


• Incoming bus arrangement for top or bottom cables
• Provision for the low voltage panel and door
• Metering CTs and PTs available
• Lug pad with provision for multiple incoming cable lug terminations
• Only Bulletin 1591B comes as a two-high structure; also available in
ArcShield designs

1591A 1591B

Bulletin 1591A/B Incoming Line Units Specifications

Incomer Size, Dimensions, mm (in.), approx.


Voltage Rating (V) Weight, kg (lb), approx.
mm (in.) Width Depth Height
457 (18) 457 (18) 2311 (91)(1)(2) 272 (600)(3)
2400…6900 914 (36) 914 (36) 914 (36) 2311 (91)(1) 363 (800)(3)
1118 (44)(4) 1118 (44) 2311 (91) 545 (1200)
(1) Height is 128. in. (3264 mm) with ArcShield enclosure with plenum.
(2) Only available size for 1591B.
(3) Weight is different with ArcShield enclosure.
(4) A 44-in. (1118-mm) incomer is only available when a 3000 A power bus is used.

Bulletin 1591A/B Power Circuit Schematic

L1 L2 L3 GND

1L1

Customer’s 1L2
Incoming
Line
1L3

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 53


Step 8: Incoming Line Units

Bulletin 1592BF, 1592F/M, and 1594F/M Fused and Non-fused Load-break Switches
• Main load break switch for switching primary power source
• Feeder load break switch for switching other loads
• Isolation between upper and lower power cells
• The operating handle is fully interlocked with the power cell door
• Provisions on the operating handle for key interlocking
• A polycarbonate viewing window in the power cell door to view the position of the isolation handle
• Protective guard over the line terminals, inside the power cell, to barrier off medium voltage when the
power door is open
• Feeders for two-high structures
• Bulletin 1592BF – fused load break switch, which is designed as a feeder for two-high structures(a)
• Bulletin 1592F/M – fused load break switch, fused feeder, and mains
• Bulletin 1594F/M – non-fused load break switch for feeder and mains

Bulletin 1592BF Switch Specifications(1)


Transformer Size (kVA) Dimensions, mm (in.), approx. Weight, kg (lb),
Starter Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.(2)
200 700 1000 1250 2000 804 (1770)(3)
914 (36) 2311 (91)
400 1500 2000 2500 2750 — 804 (1770)
(1) One 1592BF occupies half of a two-high structure.
(2) Weight is different with ArcShield enclosure.
(3) Includes complete two-high structure weight with two 1592BF units.

Bulletins 1592F/M and 1594F/M Switch Specifications


Switch Size, max Dimensions, mm (in.), approx. Weight, kg (lb),
Switch Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
600 (1) 914 (36)(2) 914 (36) 804 (1770)
91 (2311)
1200 — 1372 (54)(3) 1067 (42) 1135 (2500)
(1) Available in all sizes except 1200 A at 6600V and 6900V.
(2) If an isolated, low-voltage panel is required, the width increases by 457 mm (18 in.) and weight increases accordingly.
(3) If an isolated, low-voltage panel is required or incoming cables are fed from the bottom, the width increases by 457 mm (18 in.) and the weight increases accordingly. If the 1067 mm (42 in.)
deep unit is positioned on either end of 36 in. (914 mm) deep structures, the width increases by an additional 4 in. (102 mm).

(a) Also available as prepared space (Bulletin 1592BP) and starter kits (Bulletin 1592BS).

54 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 8: Incoming Line Units

Bulletin 1592BF/1592F Power Circuit Schematic

L1 L2 L3 GND LBS

H1
F1

H2 Medium
F1 Voltage
Load
H3
F1

Bulletin 1592M Power Circuit Schematic

LBS L1 L2 L3 GND

1L1
F1

Customer’s 1L2
Incoming F1
Line
1L3
F1

Bulletins 1592F and 1594F Power Circuit Schematics

L1 L2 L3 GND LBS

H1

H2 Medium
Voltage
Load
H3

Bulletins 1592M and 1594M Power Circuit Schematics

LBS L1 L2 L3 GND

1L1

Customer’s 1L2
Incoming
Line
1L3

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 55


Step 8: Incoming Line Units

Bulletin 1594T Non-Fused Load Break Switch Tie Switch Arrangements


• Three-pole, gang-operated load break switch with an external operating handle
• The operating handle is fully interlocked with the power cell door
• Provisions on the operating handle for key interlocking
• Power cell door with a viewing window to examine the position of the switch
• Protective guard over the line terminals, inside the power cell, to barrier off medium voltage when the
power door is open

Bulletin 1594T Switch Specifications


Switch Size, max Dimensions, mm (in.), approx. Weight, kg (lb),
Switch Size (A)
2400V 3300V 4160V 4800V 6600V 6900V Width Depth Height approx.
600 (1) 914 (36) 914 (36) 804 (1770)
91 (2311)
1200 — 1372 (54) 1067 (42) 1135 (2500)
(1) Available in all sizes except 1200 A at 6600V and 6900V.

Bulletin 1594T Power Circuit Schematic

1L1 1L2 1L3 GND


2L1 2L2 2L3 GND
LBS

56 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 8: Incoming Line Units

Bulletin 1599 Auxiliary Unit/Structure


• Completely customizable interior (typically used to hold metering equipment and/or low voltage
control devices.
• Dimensions equivalent to other Bulletin 1500/1900 units D x H (914 x 2311 mm [36 x 91 in.])
• Large full-height door is available
• For arc-resistant enclosures, contact your local Rockwell Automation sales office or Allen-Bradley
distributor

Bulletin 1599 Starter Specifications


Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
Width Depth Height
N/A 458 (18) 915 (36) 2312 (91) 273 (600)
N/A 915 (36) 915 (36) 2312 (91) 614 (1350)

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 57


Step 8: Incoming Line Units

Notes:

58 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


Step 9: Low Voltage Compartment Door Options

You can select push buttons, pilot lights, or selector switches for the low voltage compartment door. Options vary based on type of starter
unit that you selected.

Push Buttons
• Green/Red options available for the following functions:
- On
- Off
- Start
- Forward
- Reverse
- Emergency Stop (push/pull)

Selector Switches
• Selector switch on the LV compartment door can be used for the
following functions:
- Hand-Off-Auto
- Normal-Emergency-Bypass
- Forward-Off-Reverse
- Local-Off-Remote
- On-Off

Pilot Lights
• Pilot lights(a) available to indicate:
- On
- Off
- Forward
- Reverse
- Run
- Tripped
- Current Loop Fault

E300 Overload Relay


• E300 Basic Overload Relay with Voltage Sensing (if PTs specified)
- Ground fault sensing
- Six 120V AC inputs
- Four 120V AC relay outputs
- Twelve RTD inputs(b)
- Four universal analog outputs(b)
- EtherNet/IP communication
- Door mounted diagnostic station

Test Blocks
• 4- or 6-pole GE PK2

(a) Push-to-test options available


(b) Option 7FE3B only.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 59


Step 9: Low Voltage Compartment Door Options

GE Multilin 369/869 Motor Protection Relay(a)


• RTD inputs and metering package, enhanced diagnostics
• Voltage/power monitoring
• Differential protection
• 120V AC Inputs
• 120V AC Form C Relay Outputs
• Modbus TCP/Modbus RTU communications

Images courtesy of General Electric. Multilin and the monogram


are copyright of the General Electric Company © 2021.

SEL 710(-5) Motor Protection Relay(a)


• Voltage/power monitoring
• 120V AC/DC inputs
• 120V AC/DC relay outputs
• RTD inputs
• 4…20 mA output and Modbus TCP/IEC 61850 communications
• 20 mA/10V inputs
• 20 mA/10V outputs and Modbus TCP communications

Images courtesy of Schweitzer Engineering Laboratories, Inc. © 2021.

Digital Metering
• Allen-Bradley Bulletin 1426-M5E (-DNT, -CNT) PowerMonitor 5000
- ControlNet communication with 1426-DM display module
- DeviceNet communication with 1426-DM display module
- Ethernet communication with 1426-DM display module

Panel Type or Switchboard Type Metering


• AC ammeter and ammeter switch
• Voltmeter switch
• Operations counter
• Elapsed time meter

Lockout Relays
• Bulletin 700DC-PL lockout relay with a “RESET” pushbutton in the LV door
• Electroswitch Series 24 lockout relay, manual reset

(a) Options vary based on option number.

60 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

Use this checklist to help you configure your CENTERLINE® 1500 Motor Control Center.
Customer: User:
Office:

Step 1: Review MCC Technical Specifications


Certifications and Markings
 UL Labeled  NEMA  ICS Specification No.______  CSA Certified  Service Entrance  ABS and ABS Shipboard
 Other (specify):

Step 2: Select Network and IntelliCENTER® Options


Embedded Network
EtherNet/IP™  No  Yes
IntelliCENTER Options
Compact disc (CD)  None  Standard data  IntelliCENTER software and data

Step 3: Select Structure Options


Structure
Configuration  One-High  Two-High
Enclosure rating  IP52  IP10  IP21  IP34
ArcShield™ enclosure (Type 2B)  No (standard)  Yes
Low voltage wireway  51 x 102 mm  152 x 152 mm  Export crating  Arc resistant
Ambient temperature, max _________ °C
Altitude __________________ meters
External paint  ANSI 49 medium light gray  ANSI 61 light gray  Other (specify):
Internal paint  High visibility gloss white  Other (specify):
Master nameplate  No
 Yes (3 line; 40 characters maximum per line)
Line 1:
Line 2:
Line 3:
 Yes (6 line; 40 characters maximum per line)
Line 1:
Line 2:
Line 3:
Line 4:
Line 5:
Line 6:
Master nameplate lettering  White letters on black background  Black letters on white background
Options  Space heater with thermostat  Cable supports for vertical wireways
 Other (specify):

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 61


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

Step 4: Power Bus Compartment


Incoming Power
Line voltage  2400V  3300V  4160V  4800V
 6000V  6600V  7200V  Other:
Frequency  50 Hz  60 Hz
Available fault current _________ kA
Bus
Horizontal power bus rating  1200 A  2000 A  3000 A
Horizontal power bus material  Copper, tin plated  Copper, unplated
(standard)
Horizontal ground bus material  Copper, tin plated (standard)  Copper, unplated

Step 5: Select Power Cell Compartments


Load Termination
Outgoing load cable connection  Top  Bottom
Load cable per phase  1  2
Cable size: __________________
Non-load Break Isolation Switch
Switch size  400 A  600 A  800 A
Fuse clips  Clip-on  Bolt-on
Isolation switch handle module  400 A  600/800 A
Vacuum Contactors
Current rating  450 A  800 A
Control circuit  Electromechanical  IntelliVAC module
Vacuum contactor type  Fixed-mounted,  Fixed-mounted,  Fixed-mounted, electrically held
electrically held mechanical latch (fast dropout)
Power Fuses
Clip-on fuse  2R, 70 A  3R, 100 A  4R, 130 A  5R, 150 A
 6R, 170 A  9R, 200 A  12R, 230 A
Bolt-on fuses  19R, 315 A(1)  18 R, 390 A  24R, 450 A  48X, 750 A
 32R, 600 A  38R, 700 A  57X, 900 A
Control Power
Separate control  120V  Other:
Control power transformer  120V/s  120/240V/s  500VA (standard)
 1000VA  2000VA  3000VA
Ground Fault Current Transformer
Style  Bar  Donut
Integrated Protective Maintenance Grounding Device
Rating  450 A  600/800 A
(1) 300 A, 7.2 kV.

62 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

Step 6: Select Low Voltage Components


Relay Control Panel
Voltage  110/120V AC, 50/60 Hz  220/230V AC, 50/60 Hz
Contactor type  Electrically held, 450 A  Mechanical latch, 450 A
 Electrically held, 800 A  Mechanical latch, 800 A
Control Module
IntelliVAC module Input voltage:
 110…240V AC (47…63 Hz)  100…250V DC
High altitude application:
 1001…2000 m  2001…3000 m
 3001…4000 m  4001…5000 m
Other Components
Motor protection relay  E300 electronic overload relay  SEL 710(-5) motor protection relay  GE Multilin 369/869 motor protection relay
 GE Multilin 869 or SEL 710-5 with  SyncPro IIB field application and protection system
Synchronous motor protection
Metering  Bulletin 1426 PowerMonitor 5000  Panel type (3.5 in.)  Switchboard type (4.5 in.)
Control network interface  POINT I/O module  FLEX I/O  Other:

Step 7: Select Medium Voltage Control Type


Combination Starter Unit
Starter type  Full voltage, non-reversing (One-high)  Full voltage, non-reversing (Two-high)  Full voltage, reversing
 Reduced voltage, autotransformer  Reduced voltage, reactor  Prepared space(1)
 Brush-type, sychronous  Brushless, synchronous  Other:
(1) Full voltage, non-reversing only.

Step 8: Select Incoming Line Unit Options


To Main Power Bus
Cable location Section number: ________  Top  Bottom Number per phase: __________ Cable size: ______________
Lugs  By others  Crimp compression
Incoming Line Unit
Cable location Section number: ________  Top  Bottom Number per phase: __________ Cable size: ______________
Lugs  By others  Crimp compression
Main Load Break
Switch
Ampere Size: ________  Fused  Non-fused
Cable location Section number: ________  Top  Bottom Number per phase: __________ Cable size: ______________
Lugs  By others  Crimp compression
Incoming Metering
Ampere Size: ________  Fused  Non-fused
Cable location Section number: ________  Top  Bottom Number per phase: __________ Cable size: ______________
Transition
Existing structure  Series number:
 Other - describe:
Outgoing Load Termination
Load cable connection  Top  Bottom
Load cables per phase  1  2
Load cable size Specify:

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 63


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

Step 9: Select Low Voltage Door Options


Options and Accessories
Pilot lights (light-  Standard light
emitting diode [LED])
 Push-to-test light
 ON  OFF  FORWARD
 REVERSE  RUN  TRIPPED
 CURRENT LOOP FAULT  No pilot light
Push buttons  Green On  Red Off  Green Start
 Green Forward  Green Reverse  Red Stop
(1)
 Red Emergency Stop  Red Emergency Stop  No push button
Selector switch  HAND-OFF-AUTO  NORMAL-EMERGENCY-BYPASS  FORWARD-OFF-REVERSE
 LOCAL-OFF-REMOTE  ON-OFF  No selector switch
(1) Illuminated when control power is present.

64 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

Notes:
CENTERLINE 1500 Medium Voltage Motor Control Center Notes

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 65


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

CENTERLINE 1500 Medium Voltage Motor Control Center Notes

66 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

CENTERLINE 1500 Medium Voltage Motor Control Center Notes

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 67


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist

CENTERLINE 1500 Medium Voltage Motor Control Center Notes

68 Rockwell Automation Publication 1500-SG001F-EN-P - May 2022


CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide

Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
General Handling Procedures for Medium Voltage Controllers, Provides information around receiving, storing, and moving medium voltage controllers
publication MV-QS050
CENTERLINE 200/400 A Two-High Cabinet, Standard and Arc-Resistant Provides information on installation (standard and arc-resistant), maintenance, spare parts,
Enclosure, publication 1500-UM055 and ArcShield enclosures for 200/400 A Two-High controllers
CENTERLINE 400 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM100 and ArcShield enclosures for 400 A One-High controllers
CENTERLINE 600 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM101 and ArcShield enclosures for 600 A One-High controllers
CENTERLINE 800 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM102 and ArcShield enclosures for 800 A One-High controllers
Provides information on installation, commissioning, programming, metering,
CENTERLINE Medium Voltage SMC-50 Motor Controller User Manual, communications, diagnostics, maintenance, parameters, and ArcShield enclosures for
publication 1560F-UM001 SMC-50 motor controllers
Medium Voltage 450 A Contactor, Series G User Manual, Provides information on handling, installing, maintaining and troubleshooting 450 A medium
publication 1502-UM060 voltage contactors
Medium Voltage Contactor 800 A, 2400…7200V (Series F) User Manual, Provides information on handling, installing, maintaining and troubleshooting 800 A medium
publication 1502-UM054 voltage contactors
IntelliVAC Contactor Control Module, Series F User Manual, Provides information on storing, installing, commissioning, troubleshooting, spare parts,
publication 1503-UM060 and product description for IntelliVAC Series F control module
Provides product overview, specifications, dimensions, catalog number explanation and
E300/E200 Electronic Overload Relay Specifications, publication 193-TD006 features of the E300/E200 relay
Provides information on system configuration, operating modes, trip and warning functions,
E300 Electronic Overload Relay User Manual, publication 193-UM015 metering diagnostics, troubleshooting, and wiring diagrams for the E300 relay
Provides information on installing, metering, monitoring, maintenance, specifications, and
PowerMonitor 5000 Unit User Manual, publication 1426-UM001 product overview for the PowerMonitor 5000 Unit
Provides information on FLEX I/O modules, communication adapters, terminal base units,
FLEX I/O and FLEX I/O-XT Selection Guide, publication 1794-SG002 power supplies, and accessories
Provides technical specifications for push buttons, selector switches, pilot lights, specialty
30 mm Push Button Specifications, publication 800-TD009 devices, and accessories
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, ENET-UM006 network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
UL Standards Listing for Industrial Control Products, Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure
publication CMPNTS-SR002 that they conform to the requirements of Underwriters Laboratories.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 1500-SG001F-EN-P - May 2022 69


Rockwell Automation Support
Use these resources to access support information.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.

Allen-Bradley, ArcShield, CENTERLINE, E300, EnergyMetrix, expanding human possibility, FactoryTalk, FLEX, IntelliCENTER, IntelliVAC, Logix 5000, POINT I/O, PowerMonitor, Rockwell Automation,
RSView, SMC-50, and Studio 5000 are trademarks of Rockwell Automation, Inc.
ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 1500-SG001F-EN-P - May 2022