CENTERLINE 1500 Medium Voltage Motor Control Centers: Selection Guide
CENTERLINE 1500 Medium Voltage Motor Control Centers: Selection Guide
CENTERLINE 1500 Medium Voltage Motor Control Centers: Selection Guide
Selection Guide
CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Guide
What’s Inside
Topic Page
Overview 3
Motor Control Center Design 4
IntelliCENTER Technology 5
ArcShield Technology 6
Selection Process 7
Step 1: Technical Specifications 9
Step 2: Network Technology 11
Step 3: Structure Options 15
Step 4: Power Bus Compartment 19
Step 5: Power Cell Compartment 21
Step 6: Low Voltage Compartment 27
Step 7: Medium Voltage Control Types 31
Step 8: Incoming Line Units 53
Step 9: Low Voltage Compartment Door Options 59
CENTERLINE 1500 Medium Voltage Motor Control Centers Selection Checklist 61
What’s New
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect
all changes. Translated versions are not always available for each revision.
Topic Page
Updated Bulletin 1506 power circuit schematic 40
Updated weight and dimension data for Bulletin 1562F starter specifications 44
Replaced Bulletin 1560F and 1562F power circuit schematics 45
Removed Withstand/Fault ratings as these are applicable 62
Corrected the IntelliVAC control module input voltage 63
Overview
Your critical applications rely on medium voltage motors for safe, repeatable operation in harsh industrial environments. To help improve
the protection and performance of your systems, choose Allen-Bradley® CENTERLINE® 1500 medium voltage motor control centers
(MVMCCs)—built tough to meet your application demands.
With one of the broadest suites of motor controls in the marketplace, CENTERLINE 1500 MVMCCs deliver premium quality, tailored solutions
in a centralized package that integrates control and power in one efficient solution.
Matched to your requirements, our UL and NEMA certified medium voltage solutions are designed to mitigate risk and support an extensive
range of control formats and configurations. The result? Smart, cost-effective systems that can deliver power, control, information, and
safety capabilities on a common platform.
To extend system performance further, incorporate additional features—like industry-leading ArcShield™ arc-resistant enclosures and
IntelliCENTER® technology, our built-in network and software package. Our flexible and scalable approach to design means you can choose
the capabilities that you need to enhance safety and maximize productivity.
For nearly 80 years, Rockwell Automation has provided leading medium voltage motor control solutions—solutions like the CENTERLINE 1500
MVMCC.
The low voltage compartment can house various low voltage Intelligent Motor Control (IMC) devices for diverse protection and measurement
capabilities. These IMC devices include:
• Bulletin 193: E300™ Electronic Overload Relay
• Bulletin 1426: PowerMonitor™ 5000
• Bulletin 1503VC: IntelliVAC™ Contactor Control Module(a)
• Bulletin 1794: Flex™ I/O
IntelliCENTER Technology
IntelliCENTER technology enhances the intelligence of the CENTERLINE 1500 MV MCC by using built-in networking to capture information
used for predictive maintenance, process monitoring, and advanced diagnostics. IntelliCENTER technology can save you time because each
MV MCC is pre-wired, and the network is pre-programmed and validated at the factory. Network devices are preconfigured with node
addresses and communication rates, ready to communicate so you can configure device parameters (such as acceleration time and full load
amps) via the network.
IntelliCENTER Software
The addition of IntelliCENTER software provides the ultimate window into your MV MCC. The preconfigured software provides maintenance
personnel with easy access to real-time critical CENTERLINE MV MCC configured information and process data for troubleshooting. The
configurable graphic views provide system status at a glance and help keep facilities running with electronic documentation, remote
diagnostics, and predictive maintenance. IntelliCENTER software significantly reduces HMI programming time and PLC development time
with automatic tag generation and even complete network configuration before the MV MCC is powered up.
Integration Assistant
With IntelliCENTER Integration Assistant, you can seamlessly integrate your IntelliCENTER MV MCCs into Studio 5000® programming software.
This feature helps reduce programming time by automatically adding the CENTERLINE MCC devices to the Studio 5000 I/O tree.
IntelliCENTER Energy
IntelliCENTER Energy offers a preconfigured setup of FactoryTalk® EnergyMetrix™ software for intelligent motor control devices in the MV
MCC, including variable speed drives, overload relays, and SMCs. With IntelliCENTER Energy, you can view energy consumption at the device
level directly from IntelliCENTER software, making it easier to monitor and manage energy usage in the industrial facility.
ArcShield Technology
Allen-Bradley CENTERLINE 1500 MV MCCs with ArcShield arc-resistant enclosures provide rugged process control for applications that
require a higher level of personnel protection. Products with ArcShield enclosures are tested and compliant to the IEEE C37.20.7 standard,
and provide Type 2B protection during a 40 kA or 50 kA arc flash.
The ArcShield controller helps safely redirect the arc flash energy out the top of the unit and away from personnel. This level of protection is
also maintained, even when the low voltage door is open for maintenance purposes.
All ArcShield products have a robust enclosure design, which contains the arc flash energy and exhaust materials until vents on top of the
enclosure open. Once opened, the vents provide a path for materials to exit the enclosure. An overhead plenum is used to direct the
materials to a safe location away from personnel.
An optional chimney design redirects arc flash materials safely into clear space above the enclosure. The low voltage panel is reinforced and
sealed, to help prevent arc flash exhaust materials from entering this compartment.
As standard, a plenum exhaust section is provided with each new ArcShield order. The plenum exhaust section can be mounted on either the
left or right end of the line-up, and it extends past the end of the line-up. Engineered plenum designs are also available.
Features
• Reinforced cabinet and power cell door closure mechanism
• Multi-point latching mechanism, reinforced cross bracing and gasket sealing
• Reinforced back plates–added support plates that are secured with multiple bolts provide increased rigidity and security
• Reinforced low voltage panel to withstand arc flash energy and shield maintenance personnel while working in the isolated low
voltage compartment
• Arc ‘Pressure Relief’ vent to vent arc gases and material safely away from personnel during an arc flash
• Available with removable arc exhaust plenum or exhaust chimneys
Selection Process
Use the following sections in this publication to select a CENTERLINE 1500 Motor Control Center.
Selection Checklist
Complete each corresponding part of the selection checklist as you work through each step. A
completed checklist helps your local sales office better understand your needs. The summary checklist
starts on page 61.
Notes:
The following certifications can be found at the Rockwell Automation Literature Library: https://rok.auto/literature.
Standards • Underwriters Laboratories, Inc. (UL), High Voltage Industrial Control Equipment 347
• Canadian Standards Association (CSA), Industrial Control Equipment C22.2 No. 253 (harmonized with UL 347, fifth edition)
• National Electrical Manufacturers Association (NEMA), Medium Voltage Controllers Rated 1501...7200V AC ICS 3-2 (formerly ICS 2-324)
• American Nation Standards Institute (ANSI), Instrument Transformers C57.13
• Institute of Electrical and Electronic Engineers (IEEE) 519-1992
• IEEE C37.20.7, Type 2B for arc resistance
• National Electrical Code (NEC)
• Canadian Electrical Code (CEC)
• Occupational Safety and Health Act (OSHA)
• European Directives for EMC
EC Directives 2011/65/EU RoHS Directive
2014/30/EU EMC Directive
Certifications and Markings ABS and ABS Shipboard MV-CT008
CE Conformance Marked MV-CT001, MV-CT002, MV-CT003
Registration of Broadcasting and Communication Equipments 1500-CT001
UKCA Declaration of Conformity 1500-CT002, 1560-CT001
UL Certification 1560-CT002
Rated Voltages Maximum Rated Voltage 5000V or 7200V, 3 Phase
Nominal Voltage Ratings 2400V, 3300V, 4160V, 4800V, 6600V, 6900V
Rated Frequency 50…60 Hz
Rated Currents Continuous Current Rating 1200, 2000, 3000 A
(Main Horizontal Power Bus)
Short Circuit Peak Withstand 130 kA Peak
Short Time Withstand Rating 50 kA RMS SYM (80 ka ASYM) for 0.5 second
Creepage Distances and Basic Impulse Level (BIL) 60 kV(1)
Clearances
Minimum Insulation Creepage-to-Ground and Between Phases 89 mm (3.5 in.)
Dielectric Voltage Withstand Rating 2400…5000V 13.25 kV
(Insulation Test) for 60 s
7200V 18.2 kV
Bus Material and Plating Main horizontal power bus Copper, tin plated
Vertical power bus Copper, tin plated
Ground bus Copper, unplated
Enclosure Types NEMA Enclosure/IEC 60529 • Type 1/IP21
• Type 1 with Gasket/IP21
• Type 12/IP52
• Type 3R/IP34
• Arc-resistant Type 2B (Type 12/IP52)
Structural Surface Treatments Interior(2) High gloss white (RAL 9003)
Exterior • ANSI 49 medium light gray
• ANSI 61 light gray
• Additional colors available as custom option
Environment(3) Operating temperature range 0…40°C (32…104°F)
Storage and transportation temperature range -20…+75°C (-4…+149°F)
Altitude(4) 1000 m (3300 ft)
Humidity 5…95% (non condensing)
Pollution degree 2
Seismic (UBC rating)(5) 1, 2, 3, 4
(1) The BIL rating must be derated for altitudes about 1000 m (3300 ft).
(2) All metal back plates in the power cell and low voltage compartment.
(3) UL/CSA/NEMA/IEC.
(4) De-ratings apply for higher altitudes.
(5) Some units may require special bracing. Contact factory for more information.
Notes:
An EtherNet/IP™ network enhances integration, helps reduce your MCC set-up time, and increases the network speed. With EtherNet/IP
technology, you can quickly monitor, troubleshoot, and diagnose your MCC from anywhere. CENTERLINE® MCCs provide robust motor control
capabilities with access to the real-time data you need by using a network that communicates with your entire enterprise. Use of an
EtherNet/IP network enables IntelliCENTER® Integration Assistant that automatically configures and populates your I/O tree and network
configuration.
The cost and performance of a EtherNet/IP network makes them ideal for MCC applications. Open specifications and protocol, managed by
the Open DeviceNet Vendor Association (ODVA), means that vendors are not required to purchase hardware, software, or licensing rights to
connect to a system.
An EtherNet/IP system is qualified to communicate and perform under normal and adverse electrical environments. Its application can be
plant-wide and over multiple disciplines through commercial off-the-shelf (COTS) products like Ethernet switches and devices.
For more information on how to configure MCCs with EtherNet/IP, refer to CENTERLINE 1500 Motor Control Center with IntelliCENTER
Technology Using an EtherNet/IP Network Technical Data, publication 1500-TD001.
753 753
EtherNet/IP Components
Unit Components
Each EtherNet/IP component in an MCC unit is connected to the network through a port in the control and network wireway. Adding or
removing units from the network does not interrupt the other units operating in the system. Network wireways are isolated from the power
wire.
Cabling
Ethernet cables are routed through the low voltage wireway, located on the top of each MV MCC section, to prevent accidental mechanical
damage during MV MCC installation.
Ethernet cables are routed into the low voltage control panel of each MV MCC unit. The EtherNet/IP devices within each low voltage
compartment are factory connected to a managed Ethernet switch in the LV compartment using 600V UL PLTC rated cable.
IntelliCENTER Database
The IntelliCENTER software replicates the MCC lineup on a computer screen, complete with nameplates and indicators on each door to show
status (on, off, warning, fault, communication failure). Graphical views of individual MCC units display device data so you can quickly view
critical amperes, time-to-trip, trip cause, ground fault amperes, and on/off status. Each screen is pre-configured to show the parameters
typically of greatest interest, and you can easily customize parameters. Many screens feature trending graphs and analog dials.
The IntelliCENTER software provides spare parts information, AutoCAD documentation, and event logging. The software also contains ActiveX
controls. These controls provide key views of the software that can be displayed inside Human Machine Interfaces (HMIs) such as RSView®
software.
For EtherNet/IP networks, the configuration file can help in determining the installed firmware revision to properly configure the
Studio 5000 environment Add-on Profile (AOP) that generates all tags for each EtherNet/IP device in the MCC.
Two datasets are available for IntelliCENTER software. Both must be ordered separately from the MCC unit.
Standard Dataset–The standard dataset is the second component of the IntelliCENTER software. The information arrives as a digital
download, and contains data files specific to a particular MCC. This information includes unit nameplates, unit details, wiring diagrams, user
manuals, spare parts, and other details.
Energy Dataset–The energy dataset includes all components of the standard dataset. Additionally, it includes the ability to use the features
of IntelliCENTER Energy (version 4.0 and later) and the additional installation software needed.
Notes:
These controllers can be a single structure or line up of structures with expansion to the left or right.
Low Voltage
Compartment
Power Cell
Compartment
Enclosure Types
• Arc-resistant Type 2B, 40 kA or 50 kA (NEMA Type 12, IP52)
• NEMA Type 1 – General-purpose (IP10)
• NEMA Type 1 w/g – General-purpose with gasket (IP21)
• NEMA Type 12 – Dust-tight and drip proof (IP52)
• NEMA Type 3R – Non walk-in weatherproof (IP34)
The ArcShield controller helps safely redirect the arc flash energy out the top of the unit and away from personnel. This level of protection is
also maintained, even when the low voltage door is open for maintenance purposes.
All ArcShield products have a robust enclosure design, which contains the arc flash energy and exhaust materials until vents on top of the
enclosure open. Once opened, the vents provide a path for materials to exit the enclosure. An overhead plenum is used to direct the
materials to a safe location away from personnel.
An optional chimney design redirects arc flash materials safely into clear space above the enclosure. The low voltage panel is reinforced and
sealed, to help prevent arc flash exhaust materials from entering this compartment.
As standard, a plenum exhaust section is provided with each new ArcShield order. The plenum exhaust section can be mounted on either the
left or right end of the line-up, and it extends past the end of the line-up. Engineered plenum designs are also available.
These medium voltage controller bulletin numbers are available with ArcShield enclosures.
ArcShield Enclosure Specifications
Dimensions, mm (in.) approx. Weight, kg (lb)
Bulletin Number Controller Size Page
Width Depth Height approx.
1506 200/400(1) 915 (36) 1050 (2310) 40
200/400/450(1) 661 (26) 600 (1320)
200/400/450(2) 1118 (44) 1107 (2435)
600(1) 915 (36) 773 (1700)
1512A 31
(2) 1372 (54) 1250 (2750)
600
800(1) 1575 (62) 1400 (3080)
800(2) 2032 (80) 1882 (4135)
3264 (128.5)
(1) 661 (26) 600 (1320)
200/400/450
1512AT 32
600(1) 915 (36) 773 (1700)
915 (36)
200/400(1) 915 (36) 1050 (2310)
1512B 34
200/400(2) 1372 (54) 1530 (3365)
1512BT 200/400(1) 915 (36) 1050 (2310) 35
200/400 915 (36) 886 (1950)
1562F 43
200/400(2) 1372 (54) 1364 (3000)
18(3) 2315 (91)(4) 432 (950)
457 (18)
18(5) 464 (1020)
1591A/B 53
(1)(6) 3264 (128.5)
36
915 (36) 663 (1459)
36(5)
(1) Arc-resistant with plenum.
(2) Arc-resistant with plenum plus PFCC option.
(3) Arc-resistant without plenum.
(4) Added height above standard 91 in. (2315 mm) for the plenum.
(5) Arc-resistant with plenum c/w low voltage panel.
(6) 1591B.
Paint
All metal back plates in the power cell and low voltage compartments are painted high gloss white for high visibility. For all other exterior and
interior metal parts, choose ANSI 49 medium light gray (standard) or ANSI 61 (optional) or specify a custom paint color.
Description Hybrid epoxy powder paint
Standard color ANSI 49 medium light gray (optional ANSI 61 light gray)
Procedure Continuous paint line. All parts are painted before assembly.
Preparation Alkaline wash/rinse/iron phosphate rinse/iron-chrome sealer rinse/recirculated de-ionized water rinse and virgin de-ionized water rinse.
Air-atomized electrostatic spray
Painting Total paint thickness - 0.051 in. (0.002 mm) min
Baking Natural gas oven at 179 °C (355 °F) min
IMPORTANT When optional custom paint colors are specified (including ANSI 61), all external surfaces are painted to the custom
color requirement, except for the external isolating switch handle assembly, lifting angles, and lifting brackets.
All unpainted steel parts are plated for corrosion resistance.
Nameplates
Choose a 3- or 6-line nameplate with black letters on a white background, or white letters on black background.
Notes:
The power bus provides a number of useful functions, such as incoming line cables can be terminated directly to the power bus. Additionally,
the power bus of several cabinets can be joined together to form an electrically continuous lineup. There are bolted 12 gauge back plates
that allow access from the rear. There are removable side plates on each side of the cabinet for side access.
Horizontal Bus
The main horizontal power bus is located at the center rear of the structure to provide optimum heat distribution, ease of maintenance, and
splicing. The power bus is mounted on the edge to a molded bus support insulator in a common vertical plane. This mounting method
provides superior short-circuit withstand capability and protection against the accumulation of dust and tracking between phases. Access
must be provided to the bus compartment from the front or the rear of the structure to allow for installation and regular maintenance of the
power and ground bus splice connections. Choose one of the following continuous current ratings: 1200, 2000, or 3000 amps.
The power bus is tin-plated copper (standard) but silver-plated option is available. In addition, for the main horizontal bus, you choose the
option of an insulated bus.
The material is a sleeve-type, heat shrink insulating material with good flame resistance and self-extinguishing properties. This material has
a minimum wall thickness of 1.4 mm (0.055 in.), and provides a minimum dielectric strength of 49.5 kV (900V/mil).
Vertical Bus
Vertical power bus risers are provided from the main horizontal power bus to the unit isolating switch line terminals. Risers are made of tin-
plated copper and rated according to the unit size.
Ground Bus
The standard ground bus is 9.5 x 51 mm (3/8 x 2 in.) bare copper with an option for tin plating.
A mechanical lug for 8-1/0 AWG or 6-250 MCM cable is supplied at the incoming end of the lineup.
Notes:
The power cell is the heart of the controller. It consists of five basic component groups:
• Non-load break isolation switch
• Current limiting power fuses
• Control power transformer
• Vacuum contactor
• Current transformers
Standard Features
• Three pole, gang operated
• 400, 600, or 800 A full load current
• Auxiliary contacts
- 2 N.O./2 N.C. are standard
- Provisions for 3 N.O. /3 N.C.
• Contact type: Catalog No. 700-CPM
• Contact Rating: NEMA 2 x A600 and 2 x P600
• Clip-on or bolt-on fuses supported
• Line and load fuse clips or bolt-on locations
• Electrically and mechanically interlocked when used with the Allen-Bradley handle module and contactor
• Shutter mechanism fully isolates the power cell from medium voltage power bus
• Switch blades are grounded in the off position
Mechanical Interlocking
• A simple, heavy duty, direct drive mechanism improves reliability and helps provide excellent operator safety
• All mechanical interlock mechanisms remain part of the enclosure to minimize setup adjustment
Catalog Numbers
Non-load-break Isolation Switch Product Selection
Switch Size(1) Non-Load-Break Isolation Switch Options Cat. No.
Clip-on fuse clips 1503S-4C
400 A
Bolt-on fuse clips 1503S-4B
Clip-on fuse clips 1503S-6C
600 A
Bolt-on fuse clips 1503S-6B
800 A Bolt-on fuse clips 1503S-8B
(1) Enclosed rating at 40 °C (104 °F).
Vacuum Contactors
Compact and high-performance vacuum contactors are implemented within the power cell 450 A
compartment of CENTERLINE 1500 MVMCCs. These vacuum contactors are designed to
enable repeatable activation and deactivation of the connected load. Their compact and low
maintenance design also reduces the need to remove the contactor to replace power or
control circuit transformer fuses, or do testing.
These contactors are designed as fixed mounted devices for heavy-duty industrial
performance. This design helps reduce the maintenance and reliability concerns that are
associated with drawout-style contactors. Also, there are no drawout stab and finger
assemblies, which require routine maintenance. The contactors are designed to operate
with Rockwell Automation’s IntelliVAC family of control modules or optional pilot relay-type
control. 800 A
Advantages
• Lightweight, compact design
• Minimal maintenance required
• High interrupting capability
• Low chop current
• Visual contact wear indicator (no measurement tools required) Applications
• Mechanical interlocking to the non-load break isolation switch • Medium voltage (1000…7200V)
• Excellent dielectric recovery for high switching frequency vacuum switching for motor starter
• Single coil/core magnet assembly (800 A only) loads (asynchronous, synchronous)
• Control power transformer primary-fuse holders (400 A only) - Full-voltage
• All major components are easily accessed from the front - Reduced voltage
• Mechanical latch design version (optional) - Variable-frequency drives
• Easily integrated into control circuit with quick connector and wire harness (optional) • Transformer feeder unit loads
• Optimized to complement the advanced features of the IntelliVAC control module • Capacitor loads
Power Fuses
Three R-rated current-limiting power fuses are applied with the vacuum contactors so no
transient overload current reaches the motor.
E-rated power fuses are implemented for some sizes of transformer controllers. Both bolt-
on and clip-on styles are available.
Clip-on Bolt-on
IMPORTANT The control power transformers may be used for metering, but only
if the accuracy of the application does not require conformance to
any potential transformer accuracy ratings.
The maximum quantity/size of the CPT available in a two-high FVNR
controller rated 7200 volts is two 500 VA (with bolt-on power fuses),
or one 1000 VA and one 500 VA (with clip-on power fuses).
Current Transformers
CENTERLINE 1500 MVMCCs use two styles of current transformers; donut type
and bar type. Three of either types are used for overload protection and
metering. Optional ground fault (zero sequence style) current transformers
are also available.
The compact design of the IPMG device does not compromise its rugged
construction and proven performance under industrial operating
conditions. Requiring minimal maintenance, this manually operated
IPMG
device is controlled from the outside of the standard and arc-resistant
(ArcShield™) medium voltage controllers. It is mechanically interlocked to
both the main vacuum contactor and our non-load break isolation switch.
Manual
These features, along with its high electrical and mechanical endurance
Procedure to capabilities, help to provide a long-life and dependable maintenance-free
Close operation.
GFCT (x1)
The IPMG device is mounted on the controller floor plate or on the top of
T1, T2, T3 Motor Terminals
the main medium voltage vacuum contactor (for 600/800 A controllers).
It is connected to the three load phases within the main controller using
copper bus bars. Redundant, flexible grounding conductors ensures the
lowest impedance path to ground is maintained when the IPMG device is
closed. Flexible grounding conductors provide low impedance back to the
main ground bus to complete the grounding (earthing) process.
Notes:
The isolated low voltage compartment allows testing and troubleshooting of the power cell with no exposure to medium voltage. The
standard components housed in the low voltage panel are:
• Normal-Off-Test selector switch
• Male test power receptacle
• Rectifier bridge
• CR1 and CR2 control relays
• Motor protection relay(s)
Modular Design
For exacting application needs
• Wide current range
• Multiple sensing capabilities
• Expansion I/O
• Operator interface
Diagnostic Information
Monitor motor performance, which includes:
• Voltage, current, and energy
• Trip/warning histories
• Percentage of thermal capacity use
• Time to reset
• Operational hours
• Number of starts
FLEX I/O offers all the functions of larger rack-based I/O without the space requirements. Its cost effectiveness, flexibility, modularity, and
reliability have made it one of the most popular distributed I/O platforms.
FLEX I/O helps eliminate multiple long wiring runs, reduces terminations, decreases engineering and installation costs and time, and
substantially reduces down time.
The FLEX I/O system can communicate on EtherNet/IP, ControlNet®, DeviceNet®, and many other open networks including, but not limited to,
Remote I/O, PROFIBUS DP™, and Interbus-S. You can independently select the I/O, termination style, and network to meet your application
needs.
Adapter Terminal base I/O module
Flexbus connectors Keyswitch
Flexbus connectors
2 2
++
Network
Connector 24V DC field power Terminal strips
Notes:
CENTERLINE® 1500 Medium Voltage Motor Control Centers (MCCs) are available in control formats that include arc resistant enclosures.
Controller options include full-voltage, reversing, reduced-voltage, solid-state reduced-voltage, multi-speed, and synchronous control. These
controllers include load break switches that provide integrated intelligence and the lowest-cost solution for starting motor applications.
CT2 T2
F1 M
CT3 T3
F1
M
BLK
F2 F2
CPT1
ISa
CT2
T2
F1 TX
CT3 T3
F1
M
F2 F2
CPT1
ISa
CPT1
ISa
CT2 T2
F1 M
CT3 T3
F1
M
BLK
F2 F2
CPT1
ISa
L1 L2 L3 GND IS Transformer
CT1 H1
F1
CT2
H2
F1 TX
CT3 H3
F1
M
F2 F2
CPT1
ISa
CPT1
ISa
Bulletin 1512DM Variable Frequency Drive Input Contactor with Output Isolator Unit
• Fixed mounted vacuum contactor
• 400A rated unit includes two three-pole, gang-operated, non-load break isolating switches with one
external operating handle. Both switches are mechanically interlocked with each other, the main
contactor and the power cell doors. The 600A and 800A rated units are mechanically interlocked using
key interlocks and a separate external operating handle for each isolating switch
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three current-limiting power fuses
• Three current transformers
• Segregated low voltage panel to house control circuit fusing, “NORMAL-OFF-TEST” circuit, receptacle
for external test power supply, set of control circuit terminal blocks and optional hardware for unit
control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pick-up time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Additional variable frequency output power bus (1200A rating) located in the top of the power bus
compartment
Bulletin 1512DM Starter Specifications
Transformer Size (kVA) Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6900V Width Depth Height
200/400 915 (36) 915 (36) 231 (91) 805 (1770)
Sized based on VFD and continuous
600 1829 (72) 915 (36) 231 (91) 1228 (2700)
current of the motor1250
800 2845 (112) 915 (36) 231 (91) 1591 (3500)
F2 F2
DI
CPT1
DIISa
DOISa
T2
M
T3
DO
Bulletin 1512M Full Voltage Non-Reversing, Output Bypass Starter Unit with Vacuum
Contactors (FVOP)
• Fixed mounted “OUTPUT” and “BYPASS” vacuum contactors
• 400 A rated unit includes two three-pole, gang-operated, non-load break isolating switches with one
external operating handle. Both switches are mechanically interlocked with each other, the contactor
and the power cell doors. The 600 A and 800 A rated units are mechanically interlocked using key
interlocks and a separate external operating handle for each isolating switch.
• A polycarbonate viewing window in the power cell door to view the position of the isolating switch
• Three current-limiting power fuses
• Three current transformers
• Two segregated low voltage panels to house control circuit fusing, “NORMAL-OFF-TEST” circuit,
receptacle for external test power supply, set of control circuit terminal blocks and optional hardware
for unit control and monitoring
• IntelliVAC control module for each vacuum contactor, mounted in low voltage panel, with advanced
features:
- Selectable vacuum contactor drop-out time and consistent pick-up time
- Altitude compensation
- Anti-kiss and anti-plugging protection
• Additional variable frequency output power bus (1200 A rating) located in the top of the power bus
compartment
Bulletin 1512M Starter Specifications
Hp, max Dimensions, mm (in.), approx.
Starter Size (A) Weight, kg (lb), approx.
2400…6600V Width Depth Height
200/400 915 (36) 915 (36) 231 (91) 805 (1770)
Sized based on VFD and continuous
600 1829 (72) 915 (36) 231 (91) 1228 (2700)
current of the motor1
800 2845 (112) 915 (36) 231 (91) 1591 (3500)
L1 L2 L3 GND
BPIS
CT1 T1
F1
CT2 T2
F1 M
CT3 T3
F1
BP
F2 F2
CPT1
BPISa
OPISa
OP
L1 L2 L3 GND
GFCT
IS CT1 (optional)
FWD T1
F1
CT2 T2
FWD
F1 M
CT3 T3
FWD
F1
BLK
REV
W
F2 F2
REV
CPT1
REV
ISa
L1 L2 L3 GND IS
GFCT1
(optional) CT1
T1 T11
F1
S
CT2 T2 T12
F1 M
S
CT3 T3 T13
F1
S
BLK
F2 F2
W
CPT1 GFCT2
(optional) CT4
ISa FC
CT5
FC
CT6
FC
BLK
L1 L2 L3 GND IS
GFCT1
(optional) CT1
T1 T11
F1
S
CT2
T2 T12
F1 M
S
CT3
T3 T13
F1
S
BLK
F2 F2 FC2
FC2
CPT1 GFCT2
(optional) CT4 FC2
ISa FC
CT5
FC
CT6
FC
BLK
Based around the SMC™-50 Smart motor control module, we offer various advanced controlling and electronic
motor-starting styles:
• Soft start with Selectable Kickstart
• Soft stop
• Pump control start/stop
• Torque control
• Current limit start with Selectable Kickstart
• Sensorless linear speed acceleration with Selectable Kickstart
• Sensorless linear speed deceleration
• Dual ramp with Selectable Kickstart
• Emergency run (full-voltage)
The SMC-50 control module offers advanced monitoring/metering functions, and provides motor and controller protection.
The Bulletin 1562F features both isolation and bypass vacuum contactors. The Bulletin 1560F is a retrofit controller that is specifically
designed to integrate smoothly with an existing customer-supplied starter to enable all combination controls listed in this section.
GND
CT1
A IN A OUT
CT2
B IN B OUT
M
CT3
C IN C OUT
L1 L2 L3 GND GFCT1
IS
(optional) CT1
A OUT
F1
CT2
B OUT
F1 M
CT3
C OUT
F1
M
BLK
F2 F2
CPT1
L1 L2 L3 GND IS GFCT
100%
(optional) 1S
80%
50%
65%
CT1
0%
T1
F1 R
100%
1S
80%
50%
65%
CT2
0%
T2
F1 R M
100%
80%
50%
CT3
65%
1S
0%
T3
R
F1
M
BLK
F2 F2
W
CPT1
ISa
L1 L2 L3 GND IS GFCT
CT1 (optional)
100%
1S
80%
50%
65%
0%
FWD T1
F1 R
CT2 FWD
100%
1S
80%
50%
65%
0%
T2
F1 R M
CT3
100%
80%
50%
65%
FWD 1S
0%
T3
R
F1
REV
BLK
W
F2 F2
REV
CPT1
REV
ISa
L1 L2 L3 GND IS GFCT
(optional)
80%
50%
65%
CT1 T1
F1 R
80%
50%
65%
CT2 T2
F1 R M
80%
50%
65%
CT3 T3
F1 R
S
BLK
F2 F2
CPT1
ISa
(a) See the standard features provided with the Bulletin 1506 and 1512 motor controllers.
IS GFCT1
L1 L2 L3 GND
CT1 (optional)
FWD T1 (+)
F1 F1
CT2 R1
FWD T2
F1 M RD
CT3 R2
T3
FWD (-) F2
F1
BLK
W
F2 F2 REV
REV
CPT1
REV
ISa
L1 L2 L3 GND IS GFCT1
(optional) CT1
T1 (+)
F1
F1
CT2 R1
T2
F1 M RD
R2
CT3 T3
F1 (-)
M F2
BLK
CPT1 F2 F2
ISa
(a) See the standard features provided with the Bulletin 1506 and 1512 motor controllers.
L1 L2 L3 GND GFCT1
IS CT1 (optional)
FWD T1
F1 (+)
F1
CT2
FWD T2
F1 M
CT3
FWD T3
F1 (–)
F2
BLK
W
F2 F2 REV
REV
CPT1
REV
ISa
L1 L2 L3 GND GFCT1
(optional) CT1
IS T1
F1 (+)
F1
CT2
T2
F1 M
CT3 T3
F1 (–)
F2
M
BLK
F2 F2
CPT1
ISa
Notes:
1591A 1591B
L1 L2 L3 GND
1L1
Customer’s 1L2
Incoming
Line
1L3
Bulletin 1592BF, 1592F/M, and 1594F/M Fused and Non-fused Load-break Switches
• Main load break switch for switching primary power source
• Feeder load break switch for switching other loads
• Isolation between upper and lower power cells
• The operating handle is fully interlocked with the power cell door
• Provisions on the operating handle for key interlocking
• A polycarbonate viewing window in the power cell door to view the position of the isolation handle
• Protective guard over the line terminals, inside the power cell, to barrier off medium voltage when the
power door is open
• Feeders for two-high structures
• Bulletin 1592BF – fused load break switch, which is designed as a feeder for two-high structures(a)
• Bulletin 1592F/M – fused load break switch, fused feeder, and mains
• Bulletin 1594F/M – non-fused load break switch for feeder and mains
(a) Also available as prepared space (Bulletin 1592BP) and starter kits (Bulletin 1592BS).
L1 L2 L3 GND LBS
H1
F1
H2 Medium
F1 Voltage
Load
H3
F1
LBS L1 L2 L3 GND
1L1
F1
Customer’s 1L2
Incoming F1
Line
1L3
F1
L1 L2 L3 GND LBS
H1
H2 Medium
Voltage
Load
H3
LBS L1 L2 L3 GND
1L1
Customer’s 1L2
Incoming
Line
1L3
Notes:
You can select push buttons, pilot lights, or selector switches for the low voltage compartment door. Options vary based on type of starter
unit that you selected.
Push Buttons
• Green/Red options available for the following functions:
- On
- Off
- Start
- Forward
- Reverse
- Emergency Stop (push/pull)
Selector Switches
• Selector switch on the LV compartment door can be used for the
following functions:
- Hand-Off-Auto
- Normal-Emergency-Bypass
- Forward-Off-Reverse
- Local-Off-Remote
- On-Off
Pilot Lights
• Pilot lights(a) available to indicate:
- On
- Off
- Forward
- Reverse
- Run
- Tripped
- Current Loop Fault
Test Blocks
• 4- or 6-pole GE PK2
Digital Metering
• Allen-Bradley Bulletin 1426-M5E (-DNT, -CNT) PowerMonitor 5000
- ControlNet communication with 1426-DM display module
- DeviceNet communication with 1426-DM display module
- Ethernet communication with 1426-DM display module
Lockout Relays
• Bulletin 700DC-PL lockout relay with a “RESET” pushbutton in the LV door
• Electroswitch Series 24 lockout relay, manual reset
Use this checklist to help you configure your CENTERLINE® 1500 Motor Control Center.
Customer: User:
Office:
Notes:
CENTERLINE 1500 Medium Voltage Motor Control Center Notes
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
General Handling Procedures for Medium Voltage Controllers, Provides information around receiving, storing, and moving medium voltage controllers
publication MV-QS050
CENTERLINE 200/400 A Two-High Cabinet, Standard and Arc-Resistant Provides information on installation (standard and arc-resistant), maintenance, spare parts,
Enclosure, publication 1500-UM055 and ArcShield enclosures for 200/400 A Two-High controllers
CENTERLINE 400 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM100 and ArcShield enclosures for 400 A One-High controllers
CENTERLINE 600 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM101 and ArcShield enclosures for 600 A One-High controllers
CENTERLINE 800 A One-High Cabinet, Standard and Arc-Resistant Enclosure Provides information on installation (standard and arc-resistant), maintenance, spare parts,
User Manual, publication 1512A-UM102 and ArcShield enclosures for 800 A One-High controllers
Provides information on installation, commissioning, programming, metering,
CENTERLINE Medium Voltage SMC-50 Motor Controller User Manual, communications, diagnostics, maintenance, parameters, and ArcShield enclosures for
publication 1560F-UM001 SMC-50 motor controllers
Medium Voltage 450 A Contactor, Series G User Manual, Provides information on handling, installing, maintaining and troubleshooting 450 A medium
publication 1502-UM060 voltage contactors
Medium Voltage Contactor 800 A, 2400…7200V (Series F) User Manual, Provides information on handling, installing, maintaining and troubleshooting 800 A medium
publication 1502-UM054 voltage contactors
IntelliVAC Contactor Control Module, Series F User Manual, Provides information on storing, installing, commissioning, troubleshooting, spare parts,
publication 1503-UM060 and product description for IntelliVAC Series F control module
Provides product overview, specifications, dimensions, catalog number explanation and
E300/E200 Electronic Overload Relay Specifications, publication 193-TD006 features of the E300/E200 relay
Provides information on system configuration, operating modes, trip and warning functions,
E300 Electronic Overload Relay User Manual, publication 193-UM015 metering diagnostics, troubleshooting, and wiring diagrams for the E300 relay
Provides information on installing, metering, monitoring, maintenance, specifications, and
PowerMonitor 5000 Unit User Manual, publication 1426-UM001 product overview for the PowerMonitor 5000 Unit
Provides information on FLEX I/O modules, communication adapters, terminal base units,
FLEX I/O and FLEX I/O-XT Selection Guide, publication 1794-SG002 power supplies, and accessories
Provides technical specifications for push buttons, selector switches, pilot lights, specialty
30 mm Push Button Specifications, publication 800-TD009 devices, and accessories
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, ENET-UM006 network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
UL Standards Listing for Industrial Control Products, Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure
publication CMPNTS-SR002 that they conform to the requirements of Underwriters Laboratories.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
Allen-Bradley, ArcShield, CENTERLINE, E300, EnergyMetrix, expanding human possibility, FactoryTalk, FLEX, IntelliCENTER, IntelliVAC, Logix 5000, POINT I/O, PowerMonitor, Rockwell Automation,
RSView, SMC-50, and Studio 5000 are trademarks of Rockwell Automation, Inc.
ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur