eTRS-IO ENG
eTRS-IO ENG
TRS-IO
Documentation
Date 06/06/2011
Revision 2
Protocol
Typology Documentation
By T.P.A
Group name
Notes
INDEX
CONTENTS............................................................................................................................................... 5
1 DESCRIPTION ................................................................................................................................. 6
4 SPECIFICATIONS......................................................................................................................... 10
6 SELF-TEST..................................................................................................................................... 12
6.1 System errors .......................................................................................................................... 12
9 DIMENSIONS................................................................................................................................. 20
eTRS-IO
Revisions 4
REVISIONS
Revision Date Protocol Changes and/or changed paragraphs
No.
Rev 0 15/07/2010 First release
Rev 1 03/08/2010 General update
Rev 2 06/06/2011 Greenbus cables update
eTRS-IO
Contents 5
CONTENTS
eTRS-IO
Description 6
1 DESCRIPTION
• 16 bidirectional INPUT/OUTPUT lines (PNP logic with High Side Driver) with
yellow led signal status
• 16 OUTPUT group power supply and signal of its presence, software control,
error management of missing power supply
• Anti-rebound digital filter: the input is considered stable, if persists in this state
for almost 2 ms
• Continuous read back of the active outputs, disactivation process of the outputs
in short circuit (after 4 ms approx.), automatic restore of the output in short
circuit (after short circuit removal - within 1 sec.)
• Dimensions: 138x70x23.5 mm
eTRS-IO
Technical specification 7
2 TECNICAL SPECIFICATIONS
o 0 = from 0V to 10V
o short-circuit
o overload
o overvoltage (40V)
• Connections to AWG 24 ÷ 12
• Field power supply galvanically isolated from the power supply of logic circuits
and 4.0 Greenbus interface
• Led signalling the module activity status, the communication and the
input/output status
eTRS-IO
Technical specifications 8
3 ELECTRICAL CHARACTERISTICS
eTRS-IO
Technical specifications 9
eTRS-IO
Specifications 10
4 SPECIFICATIONS
Generally, power supply, temperature and moisture values must not be exceeded
(see chapter 3).
TRS-IO must be interfaced by means of cables/clamps and anything else (see next
chapters).
The terminal blocks must be inserted also when they are not cabled.
TRS-IO must be assembled on a EN50022 or EN50035 DIN rail by means of the rear
spring connection. For coupling and removal, the user should work on the connecting
tongue with a flat-blade screwdriver, in such a way as to move it back and allow the
coupling, or the release from the guide.
Warning! The metal coupling for the DIN rail is electrically connected to the circuit
earth of TRS-IO the connection to earth: MUST be provided through this connection
(that is the DIN rail must be earthed).
Warning! It should be noted that the GreenBus v4.0 works with 4MHz frequency.
Due to the frequency of the data transmission, to prevent from the effect of possible
electromagnetic interferences, we suggest the use of Cat.6 S/STP cables. Globally,
the cabling length must be limited.
TRS-IO is an electronic device for general purposes in the environment of the light
industry.
It is an A - class product, that, if installed in the home environment, can produce
electromagnetic interferences.
Therefore, the final user must take all the necessary precautions.
eTRS-IO
Signal Signal Led 11
5 SIGNAL LED
eTRS-IO
Self-Test 12
6 SELF-TEST
Herewith a further system error is shown, which does not concern the current remote,
but the field bus. The onset or the presence of this error may explain some other
accompanying system errors from the remotes.
eTRS-IO
Self-Test 13
Additional information on the system errors are shown in the Albatros help in the
chapter of the errors related to the remote devices.
eTRS-IO
Cabling Maps 14
7 CABLING MAPS
DIP SWITCH
SW 1 2 3 4 5 SW 1 2 3 4 5
Receiver No. 1 ON ON ON ON ON Receiver No.17 ON ON ON ON OFF
Receiver No. 2 OFF ON ON ON ON Receiver No.18 OFF ON ON ON OFF
Receiver No. 3 ON OFF ON ON ON Receiver No.19 ON OFF ON ON OFF
Receiver No. 4 OFF OFF ON ON ON Receiver No.20 OFF OFF ON ON OFF
Receiver No. 5 ON ON OFF ON ON Receiver No.21 ON ON OFF ON OFF
Receiver No. 6 OFF ON OFF ON ON Receiver No.22 OFF ON OFF ON OFF
Receiver No. 7 ON OFF OFF ON ON Receiver No.23 ON OFF OFF ON OFF
Receiver No. 8 OFF OFF OFF ON ON Receiver No.24 OFF OFF OFF ON OFF
Receiver No. 9 ON ON ON OFF ON Receiver No.25 ON ON ON OFF OFF
Receiver No.10 OFF ON ON OFF ON Receiver No.26 OFF ON ON OFF OFF
Receiver No.11 ON OFF ON OFF ON Receiver No.27 ON OFF ON OFF OFF
Receiver No.12 OFF OFF ON OFF ON Receiver No.28 OFF OFF ON OFF OFF
Receiver No.13 ON ON OFF OFF ON Receiver No.29 ON ON OFF OFF OFF
Receiver No.14 OFF ON OFF OFF ON Receiver No.30 OFF ON OFF OFF OFF
Receiver No.15 ON OFF OFF OFF ON Receiver No.31 ON OFF OFF OFF OFF
Receiver No.16 OFF OFF OFF OFF ON Receiver No.32 OFF OFF OFF OFF OFF
SW 7 ON OFF
SW 8 ON OFF
GBus Termination Last Receiver Last Receiver No
eTRS-IO
Cabling Maps 15
1 +24Vdc
2 GND24
1 I/O 1
2 I/O 2
3 I/O 3
4 I/O 4
5 I/O 5
6 I/O 6
7 I/O 7
8 I/O 8
1 I/O 9
2 I/O 10
3 I/O 11
4 I/O 12
5 I/O 13
6 I/O 14
7 I/O 15
8 I/O 16
eTRS-IO
Cabling Maps 16
This channel, created by TPA. S.p.A. is able to connect remote devices of a field with a
refresh time from 1 to 4 milliseconds. The transmission frequency is 4MHz, the
throughput is 300 Byte/millisecond.
Communication occurs in Full-Duplex-mode.
Within the communication frame max. 8 devices, reacting with a refresh time of 1
millisecond, or up to 16 devices at 2 milliseconds, or 32 devices at 4 milliseconds or a
combination of these values, according to the application requirements, can be
available.
7.2 Cabling
v4.0 GreenBus serial cable requires a cabling from device to device made of Ethernet
cable segments terminated with RJ45 connector. Due to the frequency of the data
transmission, to prevent from the effect of possible electromagnetic interferences, we
suggest the use of Cat.6 S/STP cables. All S/STP cables are equipped with double
twisted, individually shielded wires and a comprehensive shield.
eTRS-IO
Cabling Maps 17
Warning! Without termination the GreenBus v4.0 channel will not work properly and
the Cnc Albatros will return a list of communication errors. In the same manner it will
happen, if the termination is executed also on other remote devices of the same
stretch of line.
eTRS-IO
Cabling Maps 18
It is of note that the maximum current limit available from the +24Vdc power system
along the TRS bus of a remote device (receiver and possible expansions) is equal to
8A. The total loads controlled by a remote, whose +24Vdc power supply is drawn from
the master only, must be dimensioned for a 8A maximum absorption, (for the limits
see chapter 3).
eTRS-IO
Input/Output cabling 19
8 INPUT/OUTPUT CABLING
eTRS-IO
Dimensions 20
9 DIMENSIONS
eTRS-IO
T.P.A. S.p.A. Tecnologie e Prodotti per l’Automazione
Via Carducci, 221 - 20099 Sesto S. Giovanni
Tel. +390236527550 – fax: +39022481008
e-mail: [email protected] - www.tpaspa.it
P.I.: IT02016240968 C.F.: 06658040156