Psa Unit 1
Psa Unit 1
INTRODUCTION
Natural Sources
Coal
Water flow
Uranium & Thorium
Fossil Fuel
Wind
Tidal
Solar
Bio-Gas
Page 8 of 122
Analysis for system planning and operational studies
Needs for system analysis in planning and operation of power system
Planning and operation of power system - Operational planning covers the whole
period ranging from the incremental stage of system development
The system operation engineers at various points like area, space, regional & national
load dispatch of power
N
Power balance equation PD = PGi This equation is satisfied it gives good
i1
economy and security
Power system planning and operational analysis covers the maintenance of
generation, transmission and distribution facilities
Implementation of Monitorin
Plannin plans g
Comparing
g plans
with result
Corrective
action
Steps:
Planning of power system
Implementation of the plans
Monitoring system
Compare plans with the results
If no undesirable deviation occurs, then directly go to planning of system
If undesirable deviation occurs then take corrective action and then go to planning ofthe system
Page 9 of 122
Basic calculation required to determine the characteristics of this state is called as
Load flow
Power flow studies - To determine the voltage current active and reactive power
flows in given power system
A number of operating condition can be analyzed including contingencies. That
operating conditions are
(a). Loss of generator
(b).Loss of a transmission
line
(c).Loss of transformer (or) Load
(d). Equipment over load (or) unacceptable voltage levels
The result of the power flow analysis are stating point for the stability analysis and
power factor improvement
Load flow study is done during the planning of a new system or the extension of an
existing one
To determine the magnitude of the current flowing through out the power system at
various time intervals after fault
The objective of short circuit analysis - To determine the current and voltages at
different location of the system corresponding to different types of faults
(a). Three phase to ground
fault (b). Line to ground fault
(c). Line to line fault
(d). Double line to ground
fault (e). Open conductor fault
Page 10 of 122
Basic components of a power system.
Structure of Power system
Page 11 of 122
Vmim
= (cos Φ - cos (2ωt - Φ)
2
RMS value of voltage |V| V max
= 1.414
i max
RMS value of voltage |i| = 1.414
P = |V| |i| [cos Φ - cos (2ωt - Φ)]
=|V| |i| cos Φ - |V| |i| cos (2ωt - Φ)
= |V| |i| cos Φ - |V| |i| (cos 2ωt cos Φ + sin 2ωt sin Φ)
= |V| |i| cos Φ (1 - cos 2ωt) - |V| |i| sin Φ sin 2ωt
P = P (1 -cos 2ωt) - Q sin 2ωt
Where active or useful or real power P=|V| |i| cos Φ
watts Non - active (or) Reactive power Q = |V| |i| sin Φ
VAR
L Load V
Page 12 of 122
RL Load V 0 < Φ < 90 P>0 Q>0
Page 13 of 122
RC Load I -90 < Φ < 0 P>0 Q<0
The Norton form equivalent circuit of the generator i.e. The current source in parallel
with the admittance
Page 14 of 122
Transformer model
Transmission system
model Transmission Line
Transmission line are modelled as (i). Short line model (ii). Medium line model (iii).
Long line model
(i). Short line model : Resistance & inductance are assumed to be lumped
Page 15 of 122
Vs Is A B Vr
C D Ir
Medium line model (lines between 80 to 250km)
Resistance &inductance are assumed to be lumped &the total shunt admittance is
divided in to two equal parts & placed at the receiving and sending ends.
The Π model
Vs Is A B Vr
C D Ir
X=
Lω
Y/2 = Cω/2
A = 1+ZY/2
B=Z
C=Y(1+ZY/4)
D=1+ZY/4
Z’=Z sinhγL / γ L
Y’/2 = 1/Zc tan h (γL/2)
Page 16 of 122
cosh
Vs Is l Zc sinh l Vr
Zc
1/ sinh l cosh l Ir
Shunt Elements:
The shunt capacitor is connected to bus i. If S is MVAR rating of shunt capacitor. So is
base MVA admittance P.u. Y P.u. = 0+jS/S0
Load representation
Load:
Load is represented by a constant power representation. Both MW (P) & MVAR (Q)
- constant
In general electrical power systems are represented by a one line diagram (or) single
Page 17 of 122
line diagram
A single line diagram of a power system shows the main connections & arrangements
of components in a simplified manner
Pictorial representation of the entire power system from generating end to the
consumer premises is known as single line diagram
Standard symbols
2 Bus
Page 18 of 122
6 Wye connection (3Φ,
neutral un grounded)
8 Transmission lines
9 Static load
10 Circuit Breaker
12 Disconnect
13 Fuse
Page 18 of 122
14 Capacitor
15 Current transformer
16 Potential transformer
17 Lighting arrester
(iii). Transformer
Page 20 of 122
(iv). Static load
Impedance diagram:
The impedance diagram on single-phase basis for use under balanced conditions can be
easily drawn from the SLD. The following assumptions are made in obtaining the
impedance diagrams.
Assumptions:
1. The single phase transformer equivalents are shown as ideals with impedance on
appropriate side (LV/HV),
2. The magnetizing reactance of transformers are negligible,
3. The generators are represented as constant voltage sources with series resistance
or reactance,
4. The transmission lines are approximated by their equivalent -Models,
5. The loads are assumed to be passive and are represented by a series branch
of resistance or reactance and
6. Since the balanced conditions are assumed, the neutral grounding impedance do
not appear in the impedance diagram.
Page 21 of 122
Example system
As per the list of assumptions as above and with reference to the system of figure 2, the
impedance diagram can be obtained as shown in figure
Page 22 of 122
Per phase and per unit representation
During the power system analysis, it is a usual practice to represent current, voltage,
impedance, power, etc., of an electric power system in per unit or percentage of the base
or reference value of the respective quantities. The numerical per unit (pu) value of any
quantity is its ratio to a chosen base value of the same dimension. Thus a pu value is a
normalized quantity with respect to the chosen base value.
Definition: Per Unit value of a given quantity is the ratio of the actual value in any given
unit to the base value in the same unit. The percent value is 100 times the pu value. Both
the pu and percentage methods are simpler than the use of actual values. Further, the
main advantage in using the pu system of computations is that the result that comes out of
the sum, product, quotient, etc. of two or more pu values is expressed in per unit itself.
In an electrical power system, the parameters of interest include the current, voltage,
complex power (VA), impedance and the phase angle. Of these, the phase angle is
dimensionless and the other four quantities can be described by knowing any two of
them. Thus clearly, an arbitrary choice of any two base values will evidently fix the other
base values.
Normally the nominal voltage of lines and equipment is known along with the complex
power rating in MVA. Hence, in practice, the base values are chosen for complex power
(MVA) and line voltage (KV). The chosen base MVA is the same for all the parts of the
system. However, the base voltage is chosen with reference to a particular section of the
system and the other base voltages (with reference to the other sections of the systems,
these sections caused by the presence of the transformers) are then related to the chosen
Page 23 of 122
one by the turns-ratio of the connecting transformer.
If Ib is the base current in kilo amperes and Vb, the base voltage in kilo volts, then the
base MVA is,
Sb = (VbIb).
Then the base values of current & impedance are given by
Base current (kA), Ib = MVAb/KVb
= Sb/Vb
Base impedance, Zb = (Vb/Ib)
= (KVb2 / MVAb)
Hence the per unit impedance is given by
Zpu = Zohms/Zb
= Zohms (MVAb/KVb2)
In 3-phase systems, KVb is the line-to-line value & MVAb is the 3-phase MVA. [1-
phase MVA = (1/3) 3-phase MVA].
Change of base.
It is observed from equation (3) that the pu value of impedance is proportional directly to
the base MVA and inversely to the square of the base KV. If Zpunew is the pu impedance
required to be calculated on a new set of base values: MVAbnew & KVbnew from the
already given per unit impedance Zpuold, specified on the old set of base values,
MVAbold & KVbold , then we have
On the other hand, the change of base can also be done by first converting the given pu
impedance to its ohmic value and then calculating its pu value on the new set of base
values.
Merits:
(i). The pu value is the same for both 1-phase and & 3-phase systems
(ii). The pu value once expressed on a proper base, will be the same when refereed
to either side of the transformer. Thus the presence of transformer is totally
eliminated
(iii). The variation of values is in a smaller range 9nearby unity). Hence the
errors involved in pu computations are very less.
(iv). Usually the nameplate ratings will be marked in pu on the base of the name
plate ratings, etc.
Page 24 of 122
Demerits:
If proper bases are not chosen, then the resulting pu values may be highly absurd (such as
5.8 pu, -18.9 pu, etc.). This may cause confusion to the user. However, this problem can
be avoided by selecting the base MVA near the high-rated equipment and a convenient
base KV in any section of the system.
Bus Frame of Reference: There are b independent equations (b = no. of buses) relating
the bus vectors of currents and voltages through the bus impedance matrix and bus
admittance matrix:
EBUS = ZBUS IBUS
IBUS = YBUS EBUS
Branch Frame of Reference: There are b independent equations (b = no. of branches of a
selected Tree sub-graph of the system Graph) relating the branch vectors of currents and
voltages through the branch impedance matrix and branch admittance matrix:
EBR = ZBR IBR
IBR = YBR EBR
Page 25 of 122
Loop Frame of Reference: There are b independent equations (b = no. of branches of a
selected Tree sub-graph of the system Graph) relating the branch vectors of currents and
voltages through the branch impedance matrix and branch admittance matrix:
ELOOP = ZLOOP ILOOP
ILOOP = YLOOP ELOOP
Of the various network matrices refered above, the bus admittance matrix (YBUS) and
the bus impedance matrix (ZBUS) are determined for a given power system by the rule of
inspection as explained next.
Rule of Inspection
Consider the 3-node admittance network as shown in figure5. Using the basic branch
relation: I = (YV), for all the elemental currents and applying Kirchhoff’s Current Law
principle at the nodal points, we get the relations as under:
At node 1: I1 =Y1V1 + Y3 (V1-V3) + Y6 (V1 –
V2) At node 2: I2 =Y2V2 + Y5 (V2-V3) + Y6 (V2
– V1) At node 3: 0 = Y3 (V3-V1) + Y4V3 + Y5
(V3 – V2)
These are the performance equations of the given network in admittance form and they
can be represented in matrix form as:
In other words, the relation of equation (9) can be represented in the form IBUS = YBUS
EBUS
Where, YBUS is the bus admittance matrix, IBUS & EBUS are the bus current and bus
voltage vectors respectively.
By observing the elements of the bus admittance matrix, YBUS of equation (9), it is
observed that the matrix elements can as well be obtained by a simple inspection of the
given system diagram:
Page 26 of 122
Diagonal elements: A diagonal element (Yii) of the bus admittance matrix, YBUS, is
equal to the sum total of the admittance values of all the elements incident at the bus/node
Off Diagonal elements: An off-diagonal element (Yij) of the bus admittance matrix,
YBUS, is equal to the negative of the admittance value of the connecting element present
between the buses I and j, if any.
This is the principle of the rule of inspection. Thus the algorithmic equations for the rule
of inspection are obtained as:
Yii = yij (j = 1,2,…….n)
Yij = - yij (j = 1,2,
…….n)
For i = 1,2,….n, n = no. of buses of the given system, yij is the admittance of element
connected between buses i and j and yii is the admittance of element connected between
bus i and ground (reference bus).
Note: It is to be noted that the rule of inspection can be applied only to those power
systems that do not have any mutually coupled elements.
Page 27 of 122
Problem #2: Obtain YBUS and ZBUS matrices for the impedance network shown aside
by the rule of inspection. Also, determine YBUS for the reduced network after
eliminating the eligible unwanted node. Draw the resulting reduced system diagram.
Page 28 of 122
The operating voltage of motors is 12.5 KV. Assuming the base quantities as 50 MVA,
13.8 KV, draw the per unit reactance diagram. The percentage reactance for generators is
15% and that for motors is 20%.
Solution:
The one line diagram with the data is obtained as shown in figure P1
Solution:
The one line diagram with the data is obtained as shown in figure P1
Page 29 of 122
Selection of base quantities: 50 MVA, 13.8 KV
(Given) Calculation of pu values:
Problem #2:
Draw the per unit reactance diagram for the system shown in figure below. Choose a base
of 11 KV, 100 MVA in the generator circuit.
Solution:
Page 30 of 122
The one line diagram with the data is considered as shown in
figure. Selection of base quantities:
100 MVA, 11 KV in the generator circuit(Given); the voltage bases in other sections are:
11 (115/11.5) = 110 KV in the transmission line circuit and 110 (6.6/11.5) = 6.31 KV in
the motor circuit.
Calculation of pu values:
XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
Xlines = j 20 (100/1102) = j 0.1652 pu.
Problem #3:
A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%. The
generator supplies 2 motors through a step-up transformer - transmission line – step down
transformer arrangement. The motors have rated inputs of 20 MVA and 10 MVA at 12.8
KV with 20% sub transient reactance each. The 3-phase transformers are rated at 35
MVA, 13.2 KV- -Y with 10 % leakage reactance. The line reactance is 80
ohms. Draw the equivalent per unit reactance diagram by selecting the generator ratings
as base values in the generator circuit.
Solution:
The one line diagram with the data is obtained as shown in figure P3
Page 31 of 122
Selection of base quantities:
30 MVA, 13.8 KV in the generator circuit
(Given); The voltage bases in other sections are:
13.8 (115/13.2) = 120.23 KV in the transmission line circuit and
120.23 (13.26/115) = 13.8 KV in the motor circuit.
Calculation of pu values:
XG = j 0.15 pu.
Xm1 = j 0.2 (30/20) (12.8/13.8)2 = j 0.516 pu.
Xm2 = j 0.2 (30/10) (12.8/13.8)2 = j 0.2581
pu.
Xt1 =Xt2 = j 0.1 (30/35) (13.2/13.8)2 = j 0.0784 pu.
Xline = j 80 (30/120.232) = j 0.17 pu.
Problem #4:
A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%. The
generator supplies a motor through a step-up transformer - transmission line – step-down
transformer arrangement. The motor has rated input of 25 MVA at 6.6 KV with 25% sub
transient reactance. Draw the equivalent per unit impedance diagram by selecting 25
Zt1 = 0.005 + j 0.077 (25/30) (13.2/12.09)2 = 0.005 + j 0.0765 pu. (ref. to LV side)
Zt2 = 0.008 + j 0.08 (25/25) (110/105.316)2 = 0.0087 + j 0.0873 pu. (ref. to HV
side) Zline = 75 (0.2+j 0.8) (25/ 105.3162) = 0.0338 + j 0.1351 pu.
Thus the pu reactance diagram can be drawn as shown in figure
Page 33 of 122
1.13. Exercises for Practice
Problems
1. Determine the reactances of the three generators rated as follows on a common base of
200 MVA, 35 KV: Generator 1: 100 MVA, 33 KV, sub transient reactance of 10%;
Generator 2: 150 MVA, 32 KV, sub transient reactance of 8% and Generator 3: 110
MVA, 30 KV, sub transient reactance of 12%.
[Answers: XG1 = j 0.1778, Xg2 = j 0.089, Xg3 = j 0.16 all in per unit]
2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%. The
generator supplies 3 motors through a step-up transformer - transmission line – step down
transformer arrangement. The motors have rated inputs of 30 MVA, 20 MVA and 50
MVA, at 30 KV with 20% sub transient reactance each. The 3-phase transformers are
rated at 100 MVA, 32 KV- -Y with 8 % leakage reactance. The line has a
reactance of 50 ohms. By selecting the generator ratings as base values in the generator
circuit, determine the base values in all the other parts of the system. Hence evaluate
the corresponding pu values and draw the equivalent per unit reactance diagram.
[Answers
Em1 =
Em2
3. A 80 MVA, 10 KV, 3-phase generator has a sub transient reactance of 10%. The
generator supplies a motor through a step-up transformer - transmission line – step-down
transformer arrangement. The motor has rated input of 95 MVA, 6.3 KV with 15% sub
transient reactance. The step-up 3-phase transformer is rated at 90 MVA, 11 KV-Y /110
KV-Y with 10% leakage reactance. The 3-phase step-down transformer consists of three
single phase Y-
leakage reactance. The line has a reactance of 20 ohms. By selecting the 11 KV, 100
MVA as base values in the generator circuit, determine the base values in all the other
parts of the system. Hence evaluate the corresponding pu values and draw the equivalent
per unit reactance diagram.
[Answers
=j
0.114 and Xline = j 0.17 all in per unit]
4. For the three-phase system shown below, draw an impedance diagram expressing all
impedances in per unit on a common base of 20 MVA, 2600 V on the HV side of the
transformer. Using this impedance diagram, find the HV and LV currents.
Page 34 of 122
[Answers
0.107,
Zcable = 0.136 +j 0.204 and Zload = 5.66 + j 2.26, I = 0.158 all in per unit, I
(hv)= 0.7 A and I (lv) = 7.5 A]
Page 35 of 122
2 MARK QUESTIONS WITH ANSWERS
5. Write the equation for converting the p.u. impedance expressed in one base to
another. Zp.u,new = Zp.u,old * (kVb,old / kVb,new) * (MVAb,new / MVAb,old)
1. What is a bus?
The meeting point of various components in a power system is called a bus.
4. Write the equation to find the elements of new bus admittance matrix after eliminating
nth row and column in a n*n matrix.
Yjk = Yjk-(YjnYnk / Ynn)
7. What are the methods available for forming bus impedances matrix?
(1) Form the bus admittances matrix and then take its inverse to get bus impedance
matrix.
Page 37 of 122
(2) Directly form the bus impedance matrix from the reactance
diagram. This method utilizes the techniques of modification of existing
bus impedance matrix due to addition of new bus.
Page 38 of 122