Report On Lab Tests
Report On Lab Tests
Student Name:
Student Number:
Introduction
This report presents experimental procedure, results and discussion of three experiments. The
three experiments were on Fuel, Nozzle and Heat Exchanger. The report is divided into three
Heat of combustion of fuels is an important parameter in the selection and utilization of fuels. Its
1.1. Objectives
To determine the heat of combustion of solid and liquid fuels using a semi-automated Parr 6100
Bomb Calorimeter.
ii. To determine the Energy Equivalent in calories and Joules per kelvin
iv. To determine the higher and lower heat values in calories and Joules per kg
Results in Appendix B1 illustrates sample temperature and octane numbers. The value of
research octane number (RON) was found as 102.9 and mean octane number (MON) was 92.5.
The average value was found to be 97.7. The standard grade of petrol in literature is E10, which
has a Research Octane Number (RON) of 97 to 98 (Jargon Burster, 2023). The average value
found in this experiment fell within the range in the standard E10 for super unleaded petrol.
Appendix B1 further illustrates results of determination of cetane number. The cetane number
obtained was 47.9 for sample and freezing point temperatures of 22.2 oC and -37oC, respectively.
Generally, diesel engines operate well with a cetane number between 48 and 51 (Hidayat et al.,
2023). The cetane number of 47.9 obtained in the experiment was slightly below the optimal
range in literature but still within a reasonable range for many diesel engines. The temperatures
of 22.2°C and -37°C obtained in the experiment were relevant depending on the specific
Appendix B3 illustrates results of burning diesel and biomass. Results for burning biomass show
that temperature change was 1.2319oC and the value of EE was 2391 Cal/ oC and 0.85478MJ/oC.
The observed higher heating value for biomass was 18.537MJ/kg and the calculated value was
18.524MJ/kg. The values are close to that of polysaccharides whose HHV is 18.60MJ/kg and
falls within that of wood ranging from 15.6 to 28.5MJ/kg (Esteves et al., 2023).
1.3. Discussion
Observed higher heating value for diesel was slightly lower than the calculated value. The
observed higher heating value for biomass was slightly higher than that of the calculated value.
The differences were very small meaning that the results of the experiment agree with the
calculations. This indicates that the experiment was conducted accurately and reliably, and that
the fuels have consistent and predictable heating values. The sources of errors that could have
caused the differences were possibly related to the accuracy of the apparatus and measuring
instruments used in the experiment, such as the bomb calorimeter, the thermometer, and the
balance (Oyebanji et al., 2023). Additionally, errors could have arisen from factors such as
incomplete combustion, heat loss, moisture content, and ash content of the biomass fuel (Gani et
al., 2023).
Higher heating value is the amount of heat produced by the complete combustion of a unit
quantity of fuel when all the products of combustion are cooled down to the initial temperature
and the water vapor formed during combustion is condensed (Favrat and Kane, 2023). Lower
heating value is the amount of heat produced by the same process when the water vapor remains
as vapor and is not condensed (Favrat and Kane, 2023; Yang et al., 2023). Therefore, higher
heating value is always higher than lower heating value because it includes the latent heat of
vaporization of water. To convert LHV to HHV, there is need to add the heat of vaporization of
water multiplied by the mass of water produced per unit mass of fuel. To convert HHV to LHV,
same quantity of heat of vaporization is subtracted. The difference between HHV and LHV is
applications such as gas turbines, LHV is used to calculate the efficiency, while in boilers HHV
Diesel was found to have a higher HHV than biomass because it contains more hydrogen and
less oxygen per unit mass than biomass (Douvartzides et al., 2019). Hydrogen has a higher heat
of combustion compared to carbon and oxygen, and water vapor has a higher heat capacity than
carbon dioxide or nitrogen (Alaedini et al., 2023). Therefore, diesel released more heat per unit
The observed higher heat value for biomass was found as 18.537MJ/kg and that of diesel was
45MJ/kg. Energy equivalent for the two fuels were 2391 and 2410 Cal/ oC, respectively.
Calculated higher heat values for biomass and diesel were 18.532MJ/kg and 45.1MJ/kg,
respectively. There were very small differences between calculated and observed higher heat
values. The results indicate that the experiment was conducted accurately and reliably since the
Sources of errors were possibly related to the accuracy of the apparatus and measuring
instruments used in the experiment and factors such as incomplete combustion, heat loss,
moisture content, and ash content of the biomass fuel. Future research can focus on ways of
i. Checking of the accuracy of the apparatus and measuring instruments used in the
ii. The combustion of the biomass fuel should be complete and uniform, which can be
achieved by using a sufficient amount of oxygen and ensuring a good mixing of the fuel
and oxygen.
iii. Heat loss from the bomb calorimeter to the surroundings should be minimized by using
proper insulation and avoiding opening the lid during the measurement.
iv. Moisture content and ash content of the biomass fuel should be measured and accounted
for in the calculation of the heat value, as they affect the mass and energy balance of the
system.
1.5. References
Alaedini, A.H., Tourani, H.K., Saidi, M., 2023. A review of waste-to-hydrogen conversion
technologies for solid oxide fuel cell (SOFC) applications: Aspect of gasification process
Douvartzides, S.L., Charisiou, N.D., Papageridis, K.N., Goula, M.A., 2019. Green diesel:
Esteves, B., Sen, U., Pereira, H., 2023. Influence of Chemical Composition on Heating Value of
https://doi.org/10.3390/en16104226
Favrat, D., Kane, M., 2023. From the fuel heating values to the fuel exergy value in advanced
Gani, A., Zaki, M., Mamat, R., Nizar, M., Rosdi, S., Yana, S., Sarjono, R., 2023. Analysis of
Hidayat, J., Sugiarto, B., Anggarani, R., Aisyah, L., Fathurrahman, N.A., Yogi, P., Riza, F.M.,
Hasfi, N.M., 2023. Evaluation of Quality of Biodiesel and Diesel Fuel with High Ratio
Blends. Presented at the IOP Conference Series: Earth and Environmental Science, IOP
Publishing, p. 012018.
Jargon Burster, 2023. Petrol Grades Explained [WWW Document]. UKCO. URL
selected fuel woods as bio-fuel sources in developing countries. Fuel 340, 127600.
World Nuclear Association, 2019. Heat values of various fuels - World Nuclear Association
Yang, H., Lin, X., Pan, H., Geng, S., Chen, Z., Liu, Y., 2023. Energy saving analysis and thermal
The lab report presents results of an experiment, analysis and discussions of pressure
2.1. Objectives
To measure the actual performance of a convergent-divergent nozzle and to compare the results
with theory.
i. To measure and plot pressure distributions along the length of the nozzle;
ii. To determine the ideal and actual mass flow parameter against actual pressure ratio;
Appendix A1 illustrates data obtained from the test for all the 30 positions of the nozzle.
Regulator was set at 400kN/m2 and inlet air temperature ranged between 18.8 and 19.7 oC. Total
inlet reservoir pressure (P01) was determined. Inclined manometer factor was 0.2. pressures P2.
Appendix A1 further illustrates nozzle data that was used in the calculations. The coefficient of
discharge of the orifice of the convergent -divergent nozzle, CD, was 0.52.
Figure 2.1 is the graph showing pressures at points along the Nozzle. Pressures at Points 1-5
remained at 400kN/m2. The pressures decreased gradually from the entrance of the nozzle to
orifice. Sharp reduction of pressures occurred between Points 7 and 10 (at the orifice). Between
Points 21 and 26 (exit), there was general increase of pressures. The pressure at the exit of the
nozzle was the back pressure. The pressures generally stabilized after Point 27.
Pressure at Points along the Nozzle
450
400
Pressure (kPa)
350
300
250
200
150
100
50
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
The mass flow rate was found as 0.03443kg/s and the actual mass flow parameter was 0.1333.
Ideal mass flow parameter for test run 1 was 0.6363, which was higher than the actual mass flow
parameter. Values for test run 1 and other test runs are presented in Table 2.3.
Figure 2.2. illustrates the variations of actual and ideal mass flow parameters with pressure ratio.
As pressure ratio increased from 0.475 to 0.925, there was general reduction of both ideal and
actual mass flow parameters. However, the ideal mass flow parameter values were higher than
factual fideal
Figure 2. 2: Variation of actual and ideal mass flow parameters with pressure ratios
Both ideal and actual mass flow parameters reduced as a result of friction, heat transfer, and
shock waves in the nozzle that lower the efficiency and performance nozzles and cause deviation
of actual values from those of ideal isentropic flow (Karabeyoglu, 2019). The ideal mass flow
parameter was calculated based on assumption that isentropic flow through the nozzle is an
idealized scenario that does not account for the effects of friction, heat transfer, and shock waves
2.3. Discussion
The pressures decreased gradually from the entrance of the nozzle to orifice. Sharp reduction of
pressures occurred between Points 7 and 10 (at the orifice). Between Points 21 and 26 (exit),
there was general increase of pressures. The pressures generally stabilized after Point 27.
Pressure variations obtained in test runs 6, 7 and 8 were for sub-sonic flows while test runs 1, 2,3
and 4 represented supersonic flows. Shock inside the nozzle was experienced in test runs 2,3, 4
and 5. Shock outside was experienced in test run 1. Maximum thrust can be achieved with the
nozzle when there is high exit pressure and velocity which calls for optimal nozzle to achieve
The experiment can be improved using various measures that optimize nozzle performance. The
measures include reducing direct effects of friction and prevention of shock induced boundary
layer separation (Karabeyoglu, 2019). The use of better optimal bell-shaped nozzles can balance
2.4. Conclusion
Pressure distributions along the length of the nozzle were measured and plotted. The plots
showed that pressure generally reduced between the entrance and nozzle orifice. Shock inside the
nozzle was experienced in test runs 2,3, 4 and 5. Shock outside was experienced in test run 1.
Both ideal and actual mass flow parameters reduced with increase in pressure ratios.
In the current experiment, the flow was not chocked at the throat. Future experiment can adjust
the inlet pressure and throat area ratio to achieve Mach number of 1 for critical flow at the throat
(NASA, 2021). Also, there were shock waves and flow separation in the nozzle. In future, the
exit pressure should be equal to the ambient pressure to avoid shock waves. Friction and heat
2.5. References
interaction on condensation flow and energy recovery in supersonic nozzle. Energy 263,
125662.
NASA, 2021. Nozzle Design - Converging/Diverging (CD) Nozzle [WWW Document]. URL
This part presents results, analysis and discussions on heat exchanger lab experiment. Thes
experiment sought to study practical applications of heat transfer principles and differences in
3.1. Objectives
Counter-current flow heat exchanger was associated with higher rates of heat transfer than co-
current heat flow. Generally, increase in flow rate of cold water was associated with increase in
heat transfer in both types of heat exchangers. However, increase in flow rate of cold water was
associated with reduction of temperature differences at inlet and outlet of cold water in both
types of heat exchangers. The reduction in temperature differences was from 11.9 oC to 4.5oC
with counter-current flow heat exchanger and from 12 oC to 4.5 with co-current flow heat
exchanger. Effectiveness of the heat exchangers increased with increase in flow rates of the cold
water in both types. The increase in heat exchanger effectiveness was from 0.957 at flow rate of
0.5 l/min to 0.9595 at flow rate of 1 l/min with counter-current flow heat exchanger and from
0.965 to 0.986 with co-current flow heat exchanger. The logarithmic mean temperature
difference was generally lower with counter-flow heat exchanger compared with co-current heat
exchanger. It decreased with increase in flow rate of cold water in both types of heat exchangers.
Flow rate of cold water of 0.5 l/min was associated with higher heat gain of 18.449W with
counter-flow heat exchanger and 14.919W with co-current flow heat exchanger. Counter-flow
heat exchanger was associated with higher heat losses from cold water than co-current heat
exchanger.
Figure 3.1 illustrates that higher heat transfer rates are possible with counter-current heat
exchangers compared with co-current ones. The graph shows a steady increase in heat transfer
rates from 18.45W to 28.82W as flow rates of cold water increased from 0.5l/min to 1.9l/min for
counter-current heat exchanger. For co-current flow heat exchanger, the heat transfer rate first
decreased from 14.92W at 0.5l/min to 7.07 at 1l/min and then increased thereafter to 15W at
2l/min.
30
25
20
15
10
5
0
0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1
counter-current co-current
Figure 3. 1: Variation of heat transfer for co-current and counter-current heat exchangers
Figure 3.2 illustrates the relationship between heat exchanger effectiveness and cold water flow
rate. co-current flow heat exchanger was more effective than counter-current flow heat
exchanger where hot water flow rate was kept constant at 1.0 l/min. As flow rate of cold water
rose from 0.5 l/min to 1.0 l/min, the effectiveness of both heat exchangers also increased.
Beyond flow rate of 1.0 l/min of cold water, the effectiveness of counter-current and co-current
0.98
0.97
0.96
0.95
0.94
0.93
0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1
counter-current co-current
Figure 3. 2: Variation of heat exchanger effectiveness with cold water flow rate
Results in Figure 3.3 illustrates variation of universal heat transfer coefficient (U) with cold
water flow rate. There is general reduction of universal heat transfer coefficient with increase in
flow rate of cold water. Surprisingly, co-current flow heat exchanger had higher universal heat
transfer coefficient than counter-current flow heat exchanger. The rate of reduction of universal
heat transfer coefficient was higher for both types of heat exchangers when cold water flow rate
was increased from 0.5 l/min to 1 l/min, thereafter the rate was constant. It implies that high rates
of heat transfer are possible with low cold water flow rates.
Variation of Universal Heat Transfer Coefficient with
Cold Water Flow Rate
counter-current co-current
Figure 3. 3: Variation of universal heat transfer coefficient with cold water flow rate
Figure 3.4 illustrates variation of changes in hot water temperatures with increase on cold water
flow rate when the flow was changed from counter-current to co-current. There was slight
Change in dH (oC)
9.5
9
8.5
8
7.5
7
6.5
6
0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1
counter-current co-current
Figure 3. 4: Variation of temperature differences in hot water with cold water flow rate
Figure 3.5 illustrates variation of temperature differences in cold water with cold water flow rate.
There was no remarkable difference in variation of temperature of cold water with the change
13
Temperature (oC)
12
11
10
9
8
7
6
5
4
0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1
counter-current co-current
Figure 3. 5: Variation of temperature differences in cold water with cold water flow rate
Figure 3.6 illustrates variation of LMTD with flow rate of cold water. It was found that LMTD in
co-current flow heat exchanger dropped at a higher rate with increase of cold water flow rate
from 0.5 to 1.0 l/min than in counter-current flow heat exchanger. The rate of drop of LMTD
with increase in flow rate of cold water was generally linear above cold water flow rate of 1.2
l/min and was higher in counter-current flow than in co-current flow heat exchanger. At flow rate
of 1.8 l/min, the LMTD for the two types of heat exchanger were generally equal. This was also
true for cold water flow rates between 0.5 and 0.6 l/min.
7.5
7
6.5
6
0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1
counter-current co-current
3.3. Discussion
The energy balance for a heat exchanger represents the difference between the heat transfer rates
of the hot and cold streams. The results of the experiment show that the counter-current heat
exchanger has a higher heat transfer rate than the co-current heat exchanger for all flow rates of
cold water. This is consistent with the theoretical prediction that counter-current heat exchangers
have a higher heat transfer than co-current heat exchangers, since they can achieve a greater
temperature difference between the two streams. The co-current heat exchanger exhibits a non-
monotonic behavior, with a minimum heat transfer rate at 1 l/min of flow rate of cold water. This
may be due to the thermal resistance of the heat exchanger wall, which reduces the heat transfer
For cold water flow rates that were higher than hot water flow rate, the effectiveness of both
types of heat exchangers reduced. It was realized that as effectiveness of both types of heat
exchangers increased with increase of flow rates of cold water from 0.5 l/min to peak at 1 l/min,
universal heat transfer coefficient reduced. It means that optimal universal heat transfer
coefficient and effectiveness is possible with cold water flow rates that are lower than hot water
flow rates.
A possible way to improve the performance of the co-current heat exchanger is to increase the
surface area or reduce the thickness of the wall (Xu et al., 2022). The results of this experiment
corroborate findings in literature on the effects of flow rates on heat transfer rates for different
The results show a general reduction of overall heat transfer coefficient with increase in flow rate
of cold water. It could be due to the decrease in temperature difference between the hot and cold
fluids, which reduces the driving force for heat transfer. This could also be due to the increase in
fouling factor of the cold water side, which reduces the individual heat transfer coefficient and
The rate of reduction of overall heat transfer coefficient was higher for both types of heat
exchangers when cold water flow rate was increased from 0.5 l/min to 1 l/min, thereafter the rate
was constant. This implies that high rates of heat transfer are possible with low cold water flow
rates. This behavior could be because at low cold water flow rates, the cold water has a longer
residence time in the heat exchanger, which allows more heat transfer to occur. However, at high
cold water flow rates, the residence time is shorter and the temperature difference is smaller,
There was slight increase in difference of hot water temperature (∆TH) when the flow was
changed from counter-current to co-current heat exchanger. However, there was no remarkable
variation in difference of temperature of cold water (∆TC) with the change from counter-current
to co-current flows. This can be explained by the fact that in a counter-current heat exchanger,
the hot and cold fluids enter at opposite ends and have a larger temperature difference along the
length of the heat exchanger, resulting in a higher heat transfer rate and a lower ∆TH
(Alrwashdeh et al., 2022). In contrast, in a co-current heat exchanger, the hot and cold fluids
enter at the same end and have a smaller temperature difference along the length of the heat
exchanger, resulting in a lower heat transfer rate and a higher ∆TH. However, the ∆TC is not
affected by the flow direction because it depends only on the inlet and outlet temperatures of the
cold fluid, which are fixed by the experimental conditions (Kraus et al., 2001). The small and
LMTD in co-current flow heat exchanger dropped at a higher rate with increase of cold water
flow rate from 0.5 to 1.0 l/min than in counter-current flow heat exchanger. This was possibly
because in co-current flow, the temperature difference between the hot and cold fluids decreases
along the length of the heat exchanger, resulting in a lower driving force for heat transfer
(Mohanty et al., 2019). In contrast, in counter-current flow, the temperature difference remains
relatively constant along the length of the heat exchanger, maintaining a higher driving force for
heat transfer (Guo et al., 2015). The rate of drop of LMTD with increase in flow rate of cold
water was generally linear above cold water flow rate of 1.2 l/min and was higher in counter-
current flow than in co-current flow heat exchanger. This can be attributed to the fact that as the
cold water flow rate increases, the cold water outlet temperature approaches the hot water inlet
temperature, reducing the LMTD. However, this effect is more pronounced in counter-current
flow than in co-current flow, because in counter-current flow, the cold water outlet temperature
can exceed the hot water inlet temperature, leading to a negative LMTD. At flow rate of 1.8
l/min, the LMTD for the two types of heat exchanger were generally equal. This was also true for
cold water flow rates between 0.5 and 0.6 l/min. At these flow rates of cold water, the
temperature profiles of the two types of heat exchangers were similar, and thus the LMTD values
were comparable.
Effectiveness of both co-current and counter-current flow heat exchanger was found to be above
0.95, indicating a high degree of thermal contact and efficient heat exchange between the hot and
cold water. Effectiveness of both types of heat exchangers was highest at cold water flow rate of
1 l/min. This corresponds to the lowest Reynolds number and the highest heat transfer coefficient
(Moya-Rico et al., 2020). Counter-current flow had highest effectiveness of 0.9595 and co-
current flow heat exchanger had 0.986. Co-current flow heat exchanger performed better than
counter-current one which can be attributed to the lower temperature difference between the inlet
and outlet streams in the co-current configuration. As flow rate of cold water rose from 0.5 l/min
to 1.0 l/min, the effectiveness of both heat exchangers also increased. This can be linked to
increased Reynolds number and the decrease in heat transfer coefficient. Beyond flow rate of 1.0
l/min of cold water, the effectiveness of counter-current and co-current heat exchangers reduced.
3.4. Conclusion
Heat transfer principles of temperature difference, hot and flow rates of cold water, counter-
current flow and co-current flow tube-in-tube heat exchanger were studied. Counter-current flow
heat exchanger was found to have higher heat transfer rates than co-current one. There was
increase of effectiveness of both types of heat exchangers as flow rates of cold water increased
from 0.5 l/min until it was the same as that of hot water. Effectiveness of heat exchangers
reduced with increase in cold water flow rate beyond the flow rate of hot water. LMTD dropped
with increase in flow rate of cold water in both types of heat exchangers. Variation of
temperature differences in hot water increased with increase of flow rate of cold water. The
3.5. References
Alrwashdeh, S., Ammari, H., Madanat, M., Al-Falahat, A., 2022. The Effect of Heat Exchanger
Design on Heat Transfer Rate and Temperature Distribution. Emerg. Sci. J. 6, 128–137.
https://doi.org/10.28991/ESJ-2022-06-01-010
Guo, K., Zhang, N., Smith, R., 2015. Optimisation of fin selection and thermal design of
https://doi.org/10.1016/j.applthermaleng.2014.11.071
Kraus, A.D., Aziz, A., Welty, J., 2001. Extended Surface Heat Transfer. John Wley & Sos. Inc.,
New York.
Mohanty, S., Arora, R., Parkash, O., 2019. Performance prediction and comparative analysis for
https://doi.org/10.1615/ComputThermalScien.2019028520
Moya-Rico, J.D., Molina, A.E., Belmonte, J.F., Córcoles Tendero, J.I., Almendros-Ibáñez, J.A.,
https://doi.org/10.1016/j.applthermaleng.2020.115234
Shah, R.K., Sekulib, D., 1998. Heat exchangers, in: Handbook of Heat Transfer. University of
Kentucky.
Xu, K., Qin, K., Wu, H., Smith, R., 2022. A New Computer-Aided Optimization-Based Method
for the Design of Single Multi-Pass Plate Heat Exchangers. Processes 10, 767.
https://doi.org/10.3390/pr10040767
Appendix A (Nozzle Lab)
Test Run 1 2 3 4 5 6 7 8
P01 (kN/m^2) 400 400 400 400 400 400 400 400
T01 (oC) 19.7 19.3 19.2 19.1 18.9 18.9 18.8 18.9
T3 (oC) 19.6 19.1 19 18.9 18.7 18.7 18.6 18.7
Orifice Plate ∆P3 (cm
H2O) 22 21.5 21.2 21 21 21 16.1 6.9
Inclined manometer
factor 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
P2 (kN/m2) 1 2 3 4 5 6 7 8
1 400 400 400 400 400 400 400 400
2 400 400 400 400 400 400 400 400
3 400 400 400 400 400 400 400 400
4 400 400 400 400 400 400 400 400
5 400 400 400 400 400 400 400 400
6 400 400 390 390 390 400 400 400
7 400 390 390 390 390 390 400 400
8 380 370 370 370 370 370 390 400
9 310 310 310 310 300 310 360 380
10 (throat) 190 190 190 190 190 200 290 370
11 150 150 150 150 150 200 290 370
12 130 130 130 130 130 210 290 370
13 120 120 120 120 120 220 290 370
14 110 110 110 110 110 220 300 370
15 100 100 100 100 100 220 300 370
16 90 90 90 90 90 230 300 370
17 90 90 90 90 120 240 300 370
18 80 80 80 80 180 240 300 370
19 70 70 70 70 180 230 310 370
20 70 70 70 70 180 230 310 370
21 60 60 60 60 190 260 310 370
22 50 60 60 130 200 260 320 380
23 50 50 50 150 210 270 320 380
24 50 50 50 150 220 270 320 380
25 40 40 110 170 220 270 320 380
26 (exit) 30 80 130 180 230 280 320 380
27 0 100 140 190 240 280 330 380
28 0 100 140 190 240 280 330 380
29 20 100 140 190 240 280 330 380
30 20 100 140 190 240 280 330 380
Nozzle data
ṁ √ R T 01
f= (1.1)
A t P01
Where,
R= Gas constant;
2
πd
At = (1.2)
4
−3 2
π ( 6.37 × 10 )
¿
4
−5 2
¿ 3.1869 ×10 m
Mass flow rate, ṁ , can be calculated using orifice plate theory as shown in Equation 1.3.
ṁ=C D A t ρ
√ 2 ∆ P3
4
ρ(1−d )
(1.3)
Where,
6.37
d = Ratio of orifice diameter to pipe diameter, d= =0.083595801
76.2
∆ P3 =ρgh(1.4)
Where,
h= Head of water, m;
∆ P3 =1000∗9.81∗0.22
¿ 2158.2 Pa
For test run 1, we have mass flow rate given as follows:
ṁ=0.52∗3.1869 ×10−5∗1000
√ 2∗2158.2
1000(1−0.0835958014 )
¿ 0.03443 0516 kg /s
For test run 1 we have actual mass flow parameter given as shown below:
0.034430516∗√ 8.314∗(273.15+19.7)
f actual=
( 3.1869 ×10−5 )∗( 400 ×103 )
¿ 0.13327317
Pt
PR= (1.5)
P01
Where,
190
¿
400
¿ 0.475
Where,
γ = 1.2;
For test run 1, ideal mass flow parameter is calculated as shown below:
√ ( )
2 1.2−1
2∗1.2
f ideal= ( 0.475 ) 1.2 1−( 0.475 ) 1.2
1.2−1
¿ 0.680475834
Test Run 1 2 3 4 5 6 7 8
∆P3 (Pa) 2158.2 2109.15 2079.72 2060.1 2060.1 2060.1 1579.41 676.89
ṁ (kg/s) 0.0344 0.0340 0.0338 0.0336 0.0336 0.0336 0.0295 0.0193
f actual 0.1333 0.1317 0.1307 0.1301 0.1300 0.1300 0.1138 0.0745
f ideal 0.6363 0.6363 0.6363 0.6363 0.6363 0.6422 0.6053 0.3688
Calculated higher heat value for biomass (HHV) is given in Equation 1.7
∆ T b∗EEb
HHV cb = (1.7)
mb
Where,
1.2319∗2391
HHV cb =
0.665
¿ 4429.28 Cal / g
¿ 18.53210752 MJ /kg
Calculated higher heat value for diesel (HHV) is given in Equation 1.2.
∆ T d∗EEd
HHV cd = (1.8)
md
Where,
md = Mass of diesel, g;
3.6945∗2410
¿
0.826
¿ 10779.35 Cal /g
¿ 45.1008004 MJ /kg
The results show that burning 0.826g of diesel gave EE value of 2410 calories per oC with
temperature increase of 3.6945oC resulting into higher heating value of 45MJ/kg. The results
confirm literature that the values range between 44 and 48MJ/kg (World Nuclear Association,
2019).
Percentage difference (ε b) between observed and calculated HHV for biomass was found as
HHV ob−HHV cb
ε b= ×100 % (1.9)
HHV ob
Where,
18.537−18.53210752
ε b= × 100 %
18.537
¿ 0.000264 %
Percentage difference (ε d) between observed and calculated HHV for diesel was found as shown
in Equation 1.4.
HHV od −HHV cd
ε d= ×100 % (1.10)
HHV od
Where,
45.0038−45.1008004
ε d= × 100 %
45.0038
¿−0.002155 %
No. Flow type T set Hot Cold Tin Tout Tmid Tin Tout Tmid
point flow flow hot hot hot cold cold cold
rate rate water water water water water water
Fhot Fcold H1 H2 H3 C1 C2 C3
o o o o o o o
C L/min L/min C C C C C C
Specific heat capacity (kJ/kgK) and density (kg/m3) of each water at 60 oC and at 19.8oC from
∆ T hot =H 2−H 1
¿ 59.1−52.8
¿ 6.3 K
b. Increase in cold fluid temperature
∆ T cold=C 2−C 1
¿ 31.7−19.8
¿ 11.9 K
Where,
ρ hot v̇ 983.2∗1.0
ṁhot = Mass flow rate of water, kg/s; ṁ= = =0.016387 kg/ s
1000∗60 1000∗60
h=ṁ c ∆ T hot
¿ 0.016387∗4181∗6.3
¿ 431.64 W
Where,
ρcold v̇ 996.3∗0.5
ṁcold = Mass flow rate of water, kg/s; ṁcold= = =0.0083025 kg /s
1000∗60 1000∗60
¿ 0.0083025∗4182∗11.9
¿ 413.18 W
¿ 431.64−413.18 W
¿ 18.46 W
413.18
¿
431.64
¿ 0.9572
∆T cold −∆ T hot
LMTD=
ln
( ∆ T cold
∆ T hot )
11.9−6.3
¿
ln ( )
11.9
6.3
¿ 8.805187
1
U=
1 tw 1
+ +
hi k h 0
Where,
D 0−Di 12−10
t w= Wall thickness, = =1 mm
2 2
Heat transfer coefficient of water at H3 (56.4oC) and at C3 (26oC) are given by hi =9.97W/m2K
15.2+ 16.6
and h 0= 25.3W/m2K, respectively. Average k is given by =15.9 W /mK .
2
1
U= −3
1 1× 10 1
+ +
9.97 15.9 25.3
2
¿ 7.14849999 W /m K
Heat Heat
∆Thot ∆Tcold ∆Hhot ∆Hcold
Loss/gain exchanger LMTD U
(oC) (oC) (W) (W)
rate (W) Effectiveness
6.3 11.9 431.630 413.181 18.449 0.957 8.805 7.148
7.2 7.4 493.710 514.510 -20.800 0.960 7.300 6.764
8.7 4.5 597.316 626.132 -28.817 0.954 6.371 6.406
6.3 12 431.865 416.945 14.919 0.965 8.846 7.440
7.3 7.3 500.618 507.691 -7.072 0.986 7.111 6.876
8.9 4.5 611.109 626.108 -14.999 0.976 6.452 6.492