CT & PT Sizing Calculation
CT & PT Sizing Calculation
Time: 11:00:45
Ref.No.
Revision 0
CT & PT SIZING CALCULATION
Date 01.02.24
Client
Consultant Senthur Power Services PVT LTD
Project 10 MW POWER PLANT.
SYSTEM DETAILS
Generator Rating 10.5 MW Generator PF 0.8
Generator Voltage : 11 KV Generator FLC : KW 10500 = 10500 688.90405206802
Ö3VCosF (1.732*11*0.8) 15.2416
Generator FLC 688.904052068 Amps
After 25% of Over ucrrent 861.130065085 Amps
References :
1. Secquer Meter Catalogue
2. MICOM Relay manual
2. AVR Panel
Sl. Description CT Circuit (CT 6.1-6.3) Metering Core PT Circuit (PT2: Core-1)
No. Burden in VA Qty Total Burden in VA Burden in VA Qty Total Burden in VA
1 Voltmeter - - - 2 1 2
2 PF Meter 1 1 1 1 1 1
3 AVR Droop Ckt. 5 2 10 - - -
4 AVR Cards - - - 10 2 20
Total Burden 11 23
Ref.No.
Revision 0
CT & PT SIZING CALCULATION
Date 01.02.24
Client
Consultant Senthur Power Services PVT LTD
1 Multifunction relay(G60-2) 0.2 1 0.2
Total Burden 0.2
Sl. Description CT Circuit (CT 9.1-3 ) metering core PT circuit (PT3:core-1 )metering core
No. Burden in VA Qty Total Burden in VA Burden in VA Qty Total Burden in VA
1 Tri Vector Meter 1 1 1 1.5 1 1.5
Total Burden 1 1.5
Ref.No.
Revision 0
CT & PT SIZING CALCULATION
Date 01.02.24
Client
Consultant Senthur Power Services PVT LTD
SYSTEM DETAILS
Generator Rating : 10.5 MW
Generator Voltage : 11 KV
Generator PF : 0.8
Generator FLC : 688.90 Amps
Sub transient reactance Xd" : 19.1 % 0.191 p.u. (Assumed)
CT winding resistance Rct : 4 Ohms
Primary CT current : 1000 Amps
Secondary CT current : 1 Amps
or Cable consider
resistance RL : 0.87 ohms ed 100M 8.7 Ohms/KM
Internal resistance of Relay Rp : 0.2 ohms