TechRef StationController
TechRef StationController
Station Controller
StaCtrl
DIgSILENT GmbH
Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany
http://www.digsilent.de
[email protected]
r1029
Copyright ©2011, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH.
No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.
Contents
1 General Description 3
1.1 Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures 13
List of Tables 14
1 General Description
The Station Control object (or station controller) is used in load flow calculations to simulate the
behaviour of automatic control devices and/ or operator action. It acts on sources of reactive
power and, optionally, on transformers with tap changers, to achieve a target voltage at a certain
bus or a target reactive power flow through a cubicle/ boundary, or a target power factor at a
cubicle/ boundary.
The Station Control object has numerous options. For example, the user may select whether
voltage control should include reactive power droop, whether the target voltage should be de-
rived from the busbar properties by considering the switching arrangement, whether the con-
troller may act on the tap changers of step-up transformers, and what the relative contribution
of reactive power of the individual sources should be.
1.1 Definition
In order to define a station controller, multi-select the reactive power sources and the bus whose
voltage is to be controlled. Valid reactive power sources include synchronous and asynchronous
machines, static generators and static var systems (SVS). Then enter the desired name in the
Basic Data tab of the dialog.
• Left-clicking the first element (e.g. the bus) and, while keeping the Control key pressed,
left-click the remaining elements (e.g. the reactive power sources).
• right-click on any of the selected elements, and select Define → Station Control from
the pop-up menu.
The station controller acts on the selected machines (or static generators or SVSs). It
does not act on elements that are in a separated area, or that are out of service.
1.2 Options
The calculation options under Load Flow tab are shown in Figure 1.1, and explained further
below.
Control Mode
Three different control modes are available: Voltage control, reactive power control and power
factor control. Voltage control is done at a certain busbar/ terminal, whereas reactive power and
power factor control is done at a cubicle or boundary.
Controlled Phases
The voltage value to be controlled can be the positive sequence voltage value, the average of
the three phases voltage, or a specific phase voltage value. This option has relevance only in
the unbalanced load flow.
Controlled Busbar
This is the busbar or the terminal where the voltage will be controlled by adapting the reactive
power. The busbar can either be user or automatically selected.
within the station controller or within the controlled terminal according the option Station Con-
troller/ Bus target voltage.
For example, the upstream busbar may be a single busbar system with a section breaker having
a group of generators connected to each of the terminals. With the option Automatic Selection
enabled, the controller defines either one controlling group or two controlling groups, depending
on whether the section breaker is closed or open. If the breaker is closed, the busbar section
with the lowest priority determines the target voltage. If the breaker is open, each busbar section
determines a target voltage.
Enable Droop
This option is only available if the controller mode is set to Voltage Control and the controlled
busbar is user selected. A cubicle or a boundary can be selected as Q-measurement point
(pQmeas). The voltage set point is modified depending on the reactive power flow at the Q-
measurement point as follows:
where:
The droop can be inserted alternatively as percent value of the rated reactive power:
where:
If no Q-Measurement Point is selected the measured reactive power is set to zero. The Q-flow
direction of the Q-Measurement Point should be equal to the Q-flow direction of the SVS.
Control Q at
A cubicle or a boundary can be selected, at which the reactive power flow is controlled by the
station controller. The value entered at Q Setpoint is used as the target reactive power value.
Example:
The Option: Orientation defines the orientation of the controlled cubicle or boundary interchange
related to the generator in-feed. The parameter must be set to “+Q” if the “Q” flow of the
controlled point is in the same direction as the Q flow of the generators (see red example). If
the “Q” flow is in opposite direction the “Orientation” must be set to “-Q” (see blue example).
Control Q at
A cubicle or a boundary can be selected at which the power factor is controlled by the station
controller. The value entered for Power Factor and the option cap./ind. determine the target
power factor.
Contribution of the different reactive power sources to the control of the voltage is specified
in this part of the dialog. Every source is assigned a contribution factor (Kp ) that indicates the
percentage to feed an actual value, in addition to its set point. This factor is calculated according
to four different options:
• Nominal Power
The contribution Kp factor is proportional to the nominal apparent power (MVA) of the
device.
• Individual Reactive Power
The percentage of each contribution can be set individually. The Kp factors for each
source will be normalized, so that their sum always will be 100%.
• Maximise Reactive Reserve
The contribution Kp factor is calculated to optimize the reactive power reserve of the
sources.
1.3.1 Calculation of Contributions (Dispatched Active Power, Nominal Power and Indi-
vidual Reactive Power)
The relationships between the station controller and the belonging sources are as follows:
Qi = Qdispacht i + dQi
where:
where:
The relationships between the station controller and the belonging sources are as follows:
Qi = Qstati
where:
If the load flow option Consider Reactive Power Limits is enabled and a machine runs in his
limits (Qmin,Qmax), the machine is ignored for the reactive power participation calculation.
The station control object is not displayed graphically. However it is a specific calculation ele-
ment that is also listed when selecting the icon Objects relevant for the calculation . It’s icon
is shown as . If you experience problems with the station control, please check that you did
not define multiple station controls for the same bus, as these may result in conflicts during the
calculation.
List of Figures
List of Tables