CT Screw Touching With The Busbar of The Transformer
CT Screw Touching With The Busbar of The Transformer
CT Screw Touching With The Busbar of The Transformer
sticco - Outlook
3 attachments (6 MB)
image6d8e14.PNG; 20200831_155658.jpg; 20200831_155005.jpg;
This methodology (mounting the CT’s via screws and penetrating/damaging the bus bars insolation’s)
is not a good workmanship & practice. Kindly rectify this PSS (STC Tower area) immediately to avoid
any such electrical hazard in future. Once done, invite concerned PJ & T&D personnel for inspection.
Furthermore, apply the same rectifications to other PSS’s (on-going Constructions) in Saudi Aramco
Bachelor Housing, RC Health Services, Ansari Hospital, and Golden Kindergarten, etc. Thanks.
Regards,
EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to [email protected].
I would like to inform that this the normal & general configuration from Al-Fanar side.
I have check today few Al-Fanar PSS and I found the same configuration in all.
Tomorrow Engr'Talha will take the PTWC for STC transformer and check again the insulation value from secondary
(Low voltage)to ground on 1KV for confirm the value again.
I had also shared the video also on your watsapps for your reference.
Regards
Musheer
Dear Qamar,
Please find the attached pictures showing the LV CT’s mounted inside the PSS. Methodology
mounting it is not correct. Kindly rectify immediately.
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 2/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
Regards,
This email has been classified as MARAFIQ Internal Use by Antonino Loste on 31/08/2020
2:11 PM.
Antonino A. Loste
cid:[email protected] www.marafiq.com.sa
bcd
cid:[email protected]
a8
cid:[email protected]
2a3
cid:[email protected]
c3
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 3/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
This email has been classified as MARAFIQ Internal Use by Antonino Loste on 01/09/2020
8:31 AM.
Antonino A. Loste
Project Engineer Electrical
Projects Implementation-Y Department
Dear all,
With reference to the attached , Please instruct the contractor to carry out the rectification work in a
Professional manner , in order to avoid any safety Related Incidents. Please arrange to expedite the
rectification work at the earliest.
Regards,
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 4/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 31/08/2020 10:48
AM.
Power Distribution
Tel 6636
Dear,
Please advise the APR to Co Ordinate with our API ( Najdi) & Project Team ( Huassain Qasqari) for
Permit and access. We r ready to issue the requested Permit.
Regards,
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 5/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 30/08/2020 6:59
AM.
Gentlemen,
Please find attached PTW for your Signature & approval. We & our Contractor are ready to repair
the Misaligned MV Switches of the PSS of STC Tower project. Appreciate for your support. Thank
you very much.
Regards,
This email has been classified as MARAFIQ Internal Use by Antonino Loste on 27/08/2020
2:19 PM.
Antonino A. Loste
Projects Implementation-Y
Tel 6295
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 6/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to [email protected].
Dear Sir,
Greeting's
You are requested to arrange PTWC, to get access in 18TXF-015A Medium Voltage Door to
check and rectify the operating Switch comment.
M.Talha Burny
Electrical Engineer
Saudi Al-Terais Trading Industrial Contracting Co. Ltd. (STICCO)
( : + 966500545640
: E Mail : [email protected]
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 7/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
FYA
Najmul Qamar
Project Manager, SAMA / STICCO Construction Limited
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 8/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
TOP URGENT!
Dear Qamar,
Feeder 2KA07 / 2KB07 is in radial mode. Please expedite to rectify IAI #1 for misaligned switch.
Regards,
This email has been classified as MARAFIQ Internal Use by Jerry Consorte on 27/08/2020 1:53 PM.
Engineer, Electrical
www.marafiq.com.sa
cid:[email protected]
30
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 9/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
cid:[email protected]
30
cid:[email protected]
30
Dear Antonino,
Contractor spoke with me and he confirm that he need 10 minutes to raise the shutter up. However,
please coordinate with the concerned to complete this task today ASAP.
Power Distribution
Tel 6602
Dear Antonino,
Please prepare the energization clearance for cable only as per operation request.
Dear all,
Please be informed that Distribution Feeder 2KA07 / 2KB07 is a Single Loop Distribution Feeder
and is currently on radial Mode, Due to Cut over work. If any Power interruption occurs in the
Subject Feeder, Power to Majority of the connected customers will be lost due to radial mode.
Please arrange to expedite to energization clearance of the newly Installed Package Substation
with Comments in Loop Thru Mode , in order for us to Operate in Loop Mode during Emergencies.
Note : No Deficiency was signed by all involved parties prior to the Spiking of the Loop Feeder.
Regards,
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 11/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 1:21
PM.
Power Distribution
Tel 6636
Dear all,
Please find attached the Pictures taken site , showing the Misalignment of the Medium Voltage
Switches in the Newly Installed Package Substation. Please arrange to expedite the rectification
works at the earliest , in order for us to Energize the New Transformer safely.
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 12/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
Regards,
This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 10:04
AM.
Gentlemen,
Please find attached Cables & Equipment Testing and Energization Clearance for STC Tower for your
approval. Thank you very much.
Regards,
This email has been classified as MARAFIQ Internal Use by Antonino Loste on 26/08/2020 2:28 PM.
Antonino A. Loste
Projects Implementation-Y
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 13/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
j p
Tel 6295
DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.
DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.
DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or opinions
presented in this email are solely those of the author and do not necessarily represent
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally, the recipient
should check this email and any attachments for the presence of viruses. Power and Water
Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability for any damage caused
by any virus transmitted by this email.
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 14/14