CT Screw Touching With The Busbar of The Transformer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

6/21/23, 2:04 PM Mail - mtalha.

sticco - Outlook

Fwd: STC PSS


musheer Khan <[email protected]>
Tue 9/1/2020 11:31 AM
To:mtalha. sticco <[email protected]>;Shahid Hussain <[email protected]>

3 attachments (6 MB)
image6d8e14.PNG; 20200831_155658.jpg; 20200831_155005.jpg;

---------- Forwarded message ---------


From: Antonino A. Loste <[email protected]>
Date: Tue, 1 Sep 2020, 8:32 am
Subject: RE: STC PSS
To: musheer Khan <[email protected]>
Cc: najmul qamar <[email protected]>, [email protected]
<[email protected]>, Jerry A. Consorte <[email protected]>, Usman
Gauhar <[email protected]>, Mohammed Ebrahim Khan <[email protected]>

Classified as MARAFIQ Internal Use

Dear Qamar / Musheer,

This methodology (mounting the CT’s via screws and penetrating/damaging the bus bars insolation’s)
is not a good workmanship & practice. Kindly rectify this PSS (STC Tower area) immediately to avoid
any such electrical hazard in future. Once done, invite concerned PJ & T&D personnel for inspection.

Furthermore, apply the same rectifications to other PSS’s (on-going Constructions) in Saudi Aramco
Bachelor Housing, RC Health Services, Ansari Hospital, and Golden Kindergarten, etc. Thanks.

Regards,

From: musheer Khan <[email protected]>


Sent: Monday, August 31, 2020 4:35 PM
To: Antonino A. Loste <[email protected]>
Cc: najmul qamar <[email protected]>; [email protected]; Jerry A. Consorte
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 1/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

<[email protected]>; Usman Gauhar <[email protected]>


Subject: Re: STC PSS

EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to [email protected].

Hope everything is fine at your end.

I would like to inform that this the normal & general configuration from Al-Fanar side.

I have check today few Al-Fanar PSS and I found the same configuration in all.

Moreover the Insulation value from secondary to gorund found satisfactory.

Tomorrow Engr'Talha will take the PTWC for STC transformer and check again the insulation value from secondary
(Low voltage)to ground on 1KV for confirm the value again.

I had also shared the video also on your watsapps for your reference.

Regards

Musheer

On Mon, 31 Aug 2020, 3:15 pm Antonino A. Loste <[email protected] wrote:

Classified as MARAFIQ Internal Use

Dear Qamar,

Please find the attached pictures showing the LV CT’s mounted inside the PSS. Methodology
mounting it is not correct. Kindly rectify immediately.

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 2/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 31/08/2020
2:11 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y Department

+966 14 396 6295 | [email protected]

cid:[email protected] www.marafiq.com.sa
bcd

Power and Water Utility Company for Jubail and Yanbu

cid:[email protected]
a8

cid:[email protected]
2a3

cid:[email protected]
c3

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 3/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 01/09/2020
8:31 AM.

Antonino A. Loste
Project Engineer Electrical
Projects Implementation-Y Department

+966 14 396 6295 | [email protected]


www.marafiq.com.sa
Power and Water Utility Company for Jubail and Yanbu

From: Mohammed Ebrahim Khan


Sent: Monday, August 31, 2020 10:49 AM
To: Antonino A. Loste <[email protected]>; Hussain Abdullah Abdulrahman Qashqari
<[email protected]>
Cc: Najmul Qamar <[email protected]>; musheer Khan <[email protected]>;
[email protected]; Zulfiqar Ahmad ([email protected])
<[email protected]>; mtalha. sticco <[email protected]>; Yasser Mohammed Al-
Harbi <[email protected]>; Jerry A. Consorte <[email protected]>; Abdullah
Moayedh Hasan Al-Muhaya <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>; Usman Gauhar <[email protected]>; Mohammed Abdullah
Mohammed Al-Najdi <[email protected]>; Abdullah Moayedh Hasan Al-Muhaya
<[email protected]>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

With reference to the attached , Please instruct the contractor to carry out the rectification work in a
Professional manner , in order to avoid any safety Related Incidents. Please arrange to expedite the
rectification work at the earliest.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 4/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 31/08/2020 10:48
AM.

Mohammed Ebrahim Khan

Supervisor, Distribution Operation

Power Distribution

Tel 6636

From: Mohammed Ebrahim Khan


Sent: Sunday, August 30, 2020 7:00 AM
To: Antonino A. Loste <[email protected]>; Mohammed Abdullah Mohammed Al-Najdi
<[email protected]>; Hussain Abdullah Abdulrahman Qashqari
<[email protected]>
Cc: Najmul Qamar <[email protected]>; musheer Khan <[email protected]>;
[email protected]; Zulfiqar Ahmad ([email protected])
<[email protected]>; mtalha. sticco <[email protected]>; Yasser Mohammed Al-
Harbi <[email protected]>; Jerry A. Consorte <[email protected]>; Abdullah
Moayedh Hasan Al-Muhaya <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear,

Please advise the APR to Co Ordinate with our API ( Najdi) & Project Team ( Huassain Qasqari) for
Permit and access. We r ready to issue the requested Permit.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 5/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 30/08/2020 6:59
AM.

From: Antonino A. Loste <[email protected]>


Sent: Thursday, August 27, 2020 2:20 PM
To: Saad Nuwayfi Al-Sulami <[email protected]>; Mohammed Ebrahim Khan
<[email protected]>
Cc: Najmul Qamar <[email protected]>; musheer Khan <[email protected]>;
[email protected]; Zulfiqar Ahmad ([email protected])
<[email protected]>; mtalha. sticco <[email protected]>; Yasser Mohammed Al-
Harbi <[email protected]>; Jerry A. Consorte <[email protected]>; Abdullah
Moayedh Hasan Al-Muhaya <[email protected]>
Subject: RE: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Gentlemen,

Please find attached PTW for your Signature & approval. We & our Contractor are ready to repair
the Misaligned MV Switches of the PSS of STC Tower project. Appreciate for your support. Thank
you very much.

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 27/08/2020
2:19 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y

Tel 6295
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 6/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

From: mtalha. sticco <[email protected]>


Sent: Thursday, August 27, 2020 2:08 PM
To: Jerry A. Consorte <[email protected]>; Antonino A. Loste <[email protected]>;
Yasser Mohammed Al-Harbi <[email protected]>
Cc: Najmul Qamar <[email protected]>; musheer Khan <[email protected]>;
[email protected]; Zulfiqar Ahmad ([email protected])
<[email protected]>
Subject: Re: STC Tower Energization Clearance

EXTERNAL: This is an external email received from outside MARAFIQ. If the email contains any suspicious
content, please report it immediately using phishing reporter or email it to [email protected].

Dear Sir,

Greeting's

You are requested to arrange PTWC, to get access in 18TXF-015A Medium Voltage Door to
check and rectify the operating Switch comment.

Thanks & Regards

M.Talha Burny
Electrical Engineer
Saudi Al-Terais Trading Industrial Contracting Co. Ltd. (STICCO)
( : + 966500545640

: E Mail : [email protected]
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 7/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

City: Yanbu (KSA)

From: najmul qamar <[email protected]>


Sent: Thursday, August 27, 2020 1:55 PM
To: mtalha. sticco <[email protected]>
Subject: Fwd: FW: Re: STC Tower Energization Clearance

FYA

Najmul Qamar
Project Manager, SAMA / STICCO Construction Limited

+966 143 213268, Ext.: 118 | +966 556698345 |


[mailto:[email protected]+&+najmul@samaa-
group.com][email protected] & [email protected]

---------- Forwarded message ---------


From: Jerry A. Consorte <[email protected]>
Date: Thu, Aug 27, 2020 at 1:54 PM
Subject: FW: Re: STC Tower Energization Clearance
To: najmul qamar <[email protected]>
Cc: Antonino A. Loste <[email protected]>, musheer Khan <[email protected]>,
Kashif Khan <[email protected]>, Zulfiqar Ahmad ([email protected])
<[email protected]>

Classified as MARAFIQ Internal Use

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 8/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

TOP URGENT!

Dear Qamar,

Feeder 2KA07 / 2KB07 is in radial mode. Please expedite to rectify IAI #1 for misaligned switch.

Plan to energize the cable in loop thru mode today.

Regards,

This email has been classified as MARAFIQ Internal Use by Jerry Consorte on 27/08/2020 1:53 PM.

cid:[email protected] Jerry A. Consorte


30

Engineer, Electrical

Projects Implementation - Yanbu Department

+966 14 324 6562 | [email protected]

www.marafiq.com.sa

Power and Water Utility Company for Jubail and Yanbu

cid:[email protected]
30

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 9/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

cid:[email protected]
30

cid:[email protected]
30

From: Abdullah Moayedh Hasan Al-Muhaya


Sent: Thursday, August 27, 2020 1:41 PM
To: Antonino A. Loste <[email protected]>
Cc: Yasser Mohammed Al-Harbi <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>; Fahad Saleem Saadi <[email protected]>; Hani Abdullah
Baabdullah <[email protected]>; Antonino A. Loste <[email protected]>; Jerry A.
Consorte <[email protected]>; Mohammed Ebrahim Khan <[email protected]>
Subject: RE: Re: STC Tower Energization Clearance

Dear Antonino,

Contractor spoke with me and he confirm that he need 10 minutes to raise the shutter up. However,
please coordinate with the concerned to complete this task today ASAP.

Abdullah Moayedh Hasan Al-Muhaya

Supervisor, Power Connection

Power Distribution

Tel 6602

From: Abdullah Moayedh Hasan Al-Muhaya


Sent: Thursday, August 27, 2020 1:31 PM
To: Mohammed Ebrahim Khan <[email protected]>; Antonino A. Loste
<[email protected]>
Cc: Yasser Mohammed Al-Harbi <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>; Fahad Saleem Saadi <[email protected]>; Hani Abdullah
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 10/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Baabdullah <[email protected]>; Antonino A. Loste <[email protected]>; Jerry A.


Consorte <[email protected]>
Subject: RE: Re: STC Tower Energization Clearance

Dear Antonino,

Please prepare the energization clearance for cable only as per operation request.

From: Mohammed Ebrahim Khan


Sent: Thursday, August 27, 2020 1:22 PM
To: Antonino A. Loste <[email protected]>; Abdullah Moayedh Hasan Al-Muhaya
<[email protected]>; Jerry A. Consorte <[email protected]>; Hussain
Abdullah Abdulrahman Qashqari <[email protected]>; Turki Abdulhafiz Al-Marwani
<[email protected]>
Cc: Yasser Mohammed Al-Harbi <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>; Fahad Saleem Saadi <[email protected]>; Bandar Lafi Al-Harbi
<[email protected]>; Faisal Mokhaydheer Bakheet Hojaily <[email protected]>;
Hani Abdullah Baabdullah <[email protected]>
Subject: RE: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

Please be informed that Distribution Feeder 2KA07 / 2KB07 is a Single Loop Distribution Feeder
and is currently on radial Mode, Due to Cut over work. If any Power interruption occurs in the
Subject Feeder, Power to Majority of the connected customers will be lost due to radial mode.

Please arrange to expedite to energization clearance of the newly Installed Package Substation
with Comments in Loop Thru Mode , in order for us to Operate in Loop Mode during Emergencies.

Note : No Deficiency was signed by all involved parties prior to the Spiking of the Loop Feeder.

Regards,

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 11/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 1:21
PM.

Mohammed Ebrahim Khan

Supervisor, Distribution Operation

Power Distribution

Tel 6636

From: Mohammed Ebrahim Khan


Sent: Thursday, August 27, 2020 10:05 AM
To: Antonino A. Loste <[email protected]>; Abdullah Moayedh Hasan Al-Muhaya
<[email protected]>; Jerry A. Consorte <[email protected]>; Hussain
Abdullah Abdulrahman Qashqari <[email protected]>; Turki Abdulhafiz Al-Marwani
<[email protected]>
Cc: Yasser Mohammed Al-Harbi <[email protected]>; Saad Nuwayfi Al-Sulami
<[email protected]>; Fahad Saleem Saadi <[email protected]>; Bandar Lafi Al-Harbi
<[email protected]>; Faisal Mokhaydheer Bakheet Hojaily <[email protected]>;
Hani Abdullah Baabdullah <[email protected]>
Subject: RE: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Dear all,

Please find attached the Pictures taken site , showing the Misalignment of the Medium Voltage
Switches in the Newly Installed Package Substation. Please arrange to expedite the rectification
works at the earliest , in order for us to Energize the New Transformer safely.

https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 12/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook

Regards,

This email has been classified as MARAFIQ Internal Use by Mohammed Khan on 27/08/2020 10:04
AM.

From: Antonino A. Loste <[email protected]>


Sent: Wednesday, August 26, 2020 2:29 PM
To: Abdullah Moayedh Hasan Al-Muhaya <[email protected]>; Bandar Lafi Al-Harbi
<[email protected]>; Mohammed Ebrahim Khan <[email protected]>
Cc: Jerry A. Consorte <[email protected]>; Yasser Mohammed Al-Harbi
<[email protected]>
Subject: Re: STC Tower Energization Clearance

Classified as MARAFIQ Internal Use

Gentlemen,

Please find attached Cables & Equipment Testing and Energization Clearance for STC Tower for your
approval. Thank you very much.

Regards,

This email has been classified as MARAFIQ Internal Use by Antonino Loste on 26/08/2020 2:28 PM.

Antonino A. Loste

Project Engineer Electrical

Projects Implementation-Y
https://outlook.live.com/mail/0/id/AQQkADAwATYwMAItZWUAN2EtOGM5Ny0wMAItMDAKABAACGbWKOmg%2F02yrqNGV6%2F56Q%3D%3D 13/14
6/21/23, 2:04 PM Mail - mtalha. sticco - Outlook
j p

Tel 6295

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or
opinions presented in this email are solely those of the author and do not necessarily
represent Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally,
the recipient should check this email and any attachments for the presence of viruses.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability
for any damage caused by any virus transmitted by this email.

DISCLAIMER: This email and any files transmitted with it are confidential and intended
solely for the use of the individual or entity to whom they are addressed. If you have
received this email in error, please notify the sender. Please note that any views or opinions
presented in this email are solely those of the author and do not necessarily represent
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ). Finally, the recipient
should check this email and any attachments for the presence of viruses. Power and Water
Utility Company for Jubail and Yanbu (MARAFIQ) accepts no liability for any damage caused
by any virus transmitted by this email.