System - Load - Summary Im...

The document summarizes system load data for two air handling units (AHUs) on a given date. AHU 01 had a peak time of 4/21 15:00:00 with outside temperatures of 0.5°C dry bulb and 35.1°C wet bulb. The largest loads were from internal gains like people and infiltration. AHU 00 also peaked at the same time and had the largest loads from the building envelope like the ceiling and from internal gains.

Uploaded by

SADDAM HOSSAIN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views10 pages

System - Load - Summary Im...

The document summarizes system load data for two air handling units (AHUs) on a given date. AHU 01 had a peak time of 4/21 15:00:00 with outside temperatures of 0.5°C dry bulb and 35.1°C wet bulb. The largest loads were from internal gains like people and infiltration. AHU 00 also peaked at the same time and had the largest loads from the building envelope like the ceiling and from internal gains.

Uploaded by

SADDAM HOSSAIN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

System Load Summary AHU 01 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 4682.725 ft3/min
Time at Peak: 4/21 15:00:00
Ventilation: 43.988 ft3/min
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 23.43 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 288.436695
Return: 23.9 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 10,866 - - 10,866 5.6
Glass - Solar - 15,623 - 15,623 8.0
Door - 66 - 66 0.0
Wall - 7,110 - 7,110 3.6
Below-grade Wall - 0 - 0 0.0
Partition - -978 - -978 -0.5
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 4,794 - 604 5,399 2.8
Subtotal 15,660 21,821 604 38,085 19.5

Internal Gains
People 32,020 6,239 42,866 81,124 41.6
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 32,020 6,239 42,866 81,124 41.6

Systems
Zone Ventilation 32,773 - 3,185 35,958 18.5
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 12,531 - - 12,531 6.4
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 45,304 0 3,185 48,489 24.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 27,119 - 27,119 13.9
Grand Total 92,984 55,179 46,655 194,818 100.0
System Load Summary AHU 00 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 6165.941 ft3/min
Time at Peak: 4/21 15:00:00
Ventilation: 43.988 ft3/min
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 17.82 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 316.926341
Return: 23.9 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 31,346 - 31,346 13.4
Glass - Conduction 10,511 - - 10,511 4.5
Glass - Solar - 3,522 - 3,522 1.5
Door - 3,195 - 3,195 1.4
Wall - 13,391 - 13,391 5.7
Below-grade Wall - 0 - 0 0.0
Partition - 7,434 - 7,434 3.2
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 4,710 - 833 5,543 2.4
Subtotal 15,222 58,888 833 74,943 32.1

Internal Gains
People 32,020 1,721 42,866 76,607 32.8
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 32,020 1,721 42,866 76,607 32.8

Systems
Zone Ventilation 32,757 - 5,253 38,010 16.3
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 16,480 - - 16,480 7.1
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 49,237 0 5,253 54,490 23.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 27,426 - 27,426 11.7
Grand Total 96,479 88,035 48,952 233,466 100.0
System Load Summary AHU 02 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 6780.416 ft3/min
Time at Peak: 4/21 10:00:00
Ventilation: 43.988 ft3/min
Outside
DB: 0.5 C
HR: 27.4100 kg/kg
ENGINEERING CHECKS
WB: 33.3 C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 16.22 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 337.146155
Return: 23.9 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 12,131 - - 12,131 5.0
Glass - Solar - 0 - 0 0.0
Door - 2,296 - 2,296 1.0
Wall - 37,822 - 37,822 15.7
Below-grade Wall - 0 - 0 0.0
Partition - 32,000 - 32,000 13.3
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 3,417 - 761 4,178 1.7
Subtotal 15,548 72,119 761 88,429 36.6

Internal Gains
People 32,020 0 42,866 74,886 31.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 32,020 0 42,866 74,886 31.0

Systems
Zone Ventilation 25,187 - 5,773 30,960 12.8
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 18,104 - - 18,104 7.5
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 43,291 0 5,773 49,065 20.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 28,956 - 28,956 12.0
Grand Total 90,860 101,075 49,400 241,335 100.0
System Load Summary AHU 03 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 5954.053 ft3/min
Time at Peak: 4/21 15:00:00
Ventilation: 43.988 ft3/min
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 18.47 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 314.047636
Return: 23.9 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 25,937 - 25,937 11.4
Glass - Conduction 11,571 - - 11,571 5.1
Glass - Solar - 4,651 - 4,651 2.0
Door - 683 - 683 0.3
Wall - 12,915 - 12,915 5.7
Below-grade Wall - 0 - 0 0.0
Partition - 6,641 - 6,641 2.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 4,684 - 775 5,459 2.4
Subtotal 16,255 50,828 775 67,857 29.8

Internal Gains
People 32,020 2,518 42,866 77,403 34.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 32,020 2,518 42,866 77,403 34.0

Systems
Zone Ventilation 32,758 - 4,751 37,509 16.5
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 15,894 - - 15,894 7.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 48,652 0 4,751 53,403 23.5

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 28,845 - 28,845 12.7
Grand Total 96,927 82,191 48,392 227,509 100.0
System Load Summary AHU 04 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 4852.235 ft3/min
Time at Peak: 4/21 15:00:00
Ventilation: 43.988 ft3/min
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 22.66 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 291.688917
Return: 23.9 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -7,395 - -7,395 -3.7
Glass - Conduction 11,668 - - 11,668 5.8
Glass - Solar - 30,723 - 30,723 15.4
Door - -112 - -112 -0.1
Wall - 3,971 - 3,971 2.0
Below-grade Wall - 0 - 0 0.0
Partition - -4,260 - -4,260 -2.1
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 4,837 - 712 5,548 2.8
Subtotal 16,505 22,927 712 40,143 20.1

Internal Gains
People 32,020 11,222 42,866 86,108 43.1
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 32,020 11,222 42,866 86,108 43.1

Systems
Zone Ventilation 32,766 - 3,998 36,763 18.4
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 12,954 - - 12,954 6.5
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 45,719 0 3,998 49,717 24.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 23,652 - 23,652 11.8
Grand Total 94,244 57,801 47,575 199,620 100.0
System Load Summary AHU 01 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 ft3/min
Time at Peak: null
Ventilation: null ft3/min
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 23.43 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 0.000000
Return: 0.0 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 2,155,617 - 1,366,428,05 1,368,583,67 100.0
5 2
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2
System Load Summary AHU 00 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 ft3/min
Time at Peak: null
Ventilation: null ft3/min
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 17.82 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 0.000000
Return: 0.0 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 2,155,832 - 1,366,564,66 1,368,720,49 100.0
0 2
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 2,155,832 0 1,366,564,66 1,368,720,49 100.0
0 2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 2,155,832 0 1,366,564,66 1,368,720,49 100.0
0 2
System Load Summary AHU 02 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 ft3/min
Time at Peak: null
Ventilation: null ft3/min
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 16.22 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 0.000000
Return: 0.0 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 2,155,617 - 1,366,428,05 1,368,583,67 100.0
5 2
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2
System Load Summary AHU 03 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 ft3/min
Time at Peak: null
Ventilation: null ft3/min
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 18.47 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 0.000000
Return: 0.0 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 2,155,617 - 1,366,428,05 1,368,583,67 100.0
5 2
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2
System Load Summary AHU 04 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 ft3/min
Time at Peak: null
Ventilation: null ft3/min
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null Btu/hr-ft2
Floor Area per Capacity: 0.0000 ft2/kBtu-hr
Outdoor Air Percentage: 22.66 %
TEMPERATURES Airflow per Floor Area: null ft3/min-ft2
Airflow per Capacity: 0.000000
Return: 0.0 C ft3/min-ton
Mixed Air: 0.0 C Number of People: 171.6
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 2,155,617 - 1,366,428,05 1,368,583,67 100.0
5 2
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 2,155,617 0 1,366,428,05 1,368,583,67 100.0
5 2