The Apex 150 is a next generation energy meter designed for precise bulk energy measurement and revenue transactions at power transfer points. It offers flexible and modular communications options to integrate with various AMR/AMI/SCADA systems. The Apex 150 provides 4 quadrant energy measurement, 0.2S accuracy for active and reactive energy, and supports industry standard DLMS and MODBUS protocols. It has multiple communication ports including RS232, RS485, and Ethernet to enable simultaneous data transfer through different networks.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
241 views4 pages

Specifications of Secure ABT Meter Apex150

The Apex 150 is a next generation energy meter designed for precise bulk energy measurement and revenue transactions at power transfer points. It offers flexible and modular communications options to integrate with various AMR/AMI/SCADA systems. The Apex 150 provides 4 quadrant energy measurement, 0.2S accuracy for active and reactive energy, and supports industry standard DLMS and MODBUS protocols. It has multiple communication ports including RS232, RS485, and Ethernet to enable simultaneous data transfer through different networks.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Apex 150 Field Hot pluggable Interoperable

Precision metering series configurable communication communication


installations modules

Bulk energy measurement, modular multi comms options, wall mounted,


long range site configurable

Apex 150, series of next generation energy meter designed for


power transfer points requiring precise measurements and
revenue transactions. Flexible and modular communications
ensure integration with existing AMR/AMI/SCADA systems and
upgrade to future SAS systems. 4 quadrant energy
measurement allows monitoring of generation, transmission
and bulk power transfer point.

Application Feature
Ÿ Metering for availability based tariffs (ABT) and open access Ÿ 0.2S accuracy for active and reactive measurement
systems Ÿ Wide-range dual auxiliary supply with options for AC/DC
Ÿ Energy transfer measurement and reconciliation and self-power (VT powered)
Ÿ Power plants, feeder monitoring, grid substations, Ÿ Power quality features including THD, sag, swell, voltage
wind turbines unbalance and interruption recording
Ÿ On-line monitoring of energy exchange at various Ÿ Dynamic error compensation for CT/VT
interface points Ÿ Transformer/Line loss adjustment (Copper and Iron losses)
Ÿ Energy accounting, automation and system integration Ÿ Intuitive graphical display including vector diagram, wave
forms and bar chart for consumption
Ÿ Remote configuration of communication ports
Benefits
Ÿ Simultaneous DLMS and MODBUS over Ethernet port
Ÿ Minimal integration cost through multiple Ÿ Support of meter reading/display over field replaceable
communication interfaces battery
Ÿ Suitable for diverse applications through wide-range Ÿ Availability of RS232, RS485 and Ethernet ports in a single
voltage, current and auxiliary supply inputs product and capability of simultaneous communication
Ÿ Support of industry standard DLMS and MODBUS meter through all these ports
reading protocols Ÿ Flexible time-of-day tariff, maximum demand support
Ÿ Meter reading and display viewing under power outage with automatic billing dates
Ÿ Field replaceable hot pluggable communication modules Ÿ Meter cover and terminal cover open detection
Ÿ RS232 port compatible with meter-powered modem
Ÿ Best suitable for Interface Energy Meters with 5 minutes
Integration period (field configurable)
Apex 150

The Apex 150 offers various communication modules such as RS232 with output to power up terminal modem, RS485 for multi-drop
connectivity and Ethernet for integrating into communication bus. The communication modules can be hot plugged in field and
locally or remotely configured for IDs, IP addresses. Dual socket support on Ethernet allows for simultaneous communication over
MODBUS and DLMS through different clients. All communication ports can simultaneously transfer data at high speeds.

RS485 and Ethernet port scheme station


Service port 502
for MODBUS

RS232/RS485
Converter
Server

Service port 4059 RS485 Port


for DLMS Online
monitoring system
Network switch
Ethernet port LAN switch
Substation
communication
panel

WAN
Clients

RS485 network

control unit Ethernet network

Digital pulse output


Substation communication panel Digital pulse output

Product options*
Class Power supply 1 Power supply 2 Communication port 1
0.2S Self power 60-240 V AC/DC (±20%) Ethernet
60-240 V AC/DC (±20%) 24-48 V DC (±20%)
none

Communication port 2 Communication port 3 Pulse input / output


RS232 RS232 No pulse I/O
RS485 RS485 4 configurable I/O
4 configurable I/O and 7 fixed pulse O/P
Technical specifications
Electrical
Connection type HV3/HV4
Measurement voltage range 57.7 V or 63.5 V (L-N) for HV4, 100 or 110 V (L-L) for HV3
Measurement current range Ib: 1A or 5A (configurable)*, Imax up to 10A (configurable)*
Frequency 50 Hz ±5%
Burden with auxiliary/self (VT) powered Current circuit: < 0.1 VA/phase @ 1A, < 0.5 VA/phase @ 5A
Voltage circuit in case of Aux power: < 0.1 VA/phase
Voltage circuit in case of internal/self power: < 6 VA/phase
Accuracy Class 0.2S
Maximum overload Voltage 1.5 times of nominal voltage continuously
2 times of nominal voltage for 0.5 second
Maximum overload current 1.5 times of Imax continuously
10 times Imax for 1 second
20 times Imax for 0.5 second

Compliance
Standards* IS 14697
IS 15959 DLMS Indian companion standard, category B

Mechanical
Dimension 292mm x 201mm x 105mm (H x W x D)
Weight 2 kg (+/- 200 gm)

Environmental
Ingress protection IP54
Operating temperature -10 °C to + 60 °C
Limit range of operation -25 °C to + 70 °C
Storage temperature -40 °C to + 80 °C
Temperature coefficient <0.1%/100C

Features
Power supply Dual/single auxiliary supply
Range: 60-240 V AC/DC (±20%), burden: <10VA
Optional range: 24-48 V DC (±20%), burden: <10VA
Display Graphical, with green backlight
Extended temperature range -200C to 700C
Size: 69 x 39 mm (H x W), 128x80 pixels
Pixel size: 0.5 mm²
Max display character size 10 x 5 mm (H x W)
Battery Field-replaceable battery for RTC back up

*For more details, contact your nearest sales office.


Apex 150

Technical specifications
Software
- Data logging:
Maximum 50 parameters configurable
Logging of up to 28 energy channels, with integration period 1 to 60
minutes
80+ parameters available for logging of instantaneous values with
integration period 1 to 60 minutes
~9600 Parameter-days capacity at 30 minute interval
-Configurable parameters:
8 time-of-use tariffs, 16 seasons, 16 day types and 16 time zones, 53 billing
dates
Logging of up to 100 day for daily energy snapshots
7 configurable display sequences along with fixed, auto and sealed button
sequences
40+ events and 10+compartments for event logging
- Logging of up to 15 sets of historical data logging
- Up to 31st individual harmonic component measurement
- Power quality features, including voltage sag, swell, unbalance recording

Inputs and Outputs 7 fixed pulse outputs


4 configurable as pulse inputs/outputs
-Pulse outputs:
Type: Volt-free, 100 mA
Voltage: 48-240 V AC/DC, Option for 24-40 V DC,
Pulse width: 20 - 300 ms
-Configurable as pulse input/output:
Pulse output Type: volt-free, 100mA
Pulse input type: optical isolator
Voltage: 24-240 V AC/DC
-Indicator:
Six LEDs: 2 for metrology, 3 LEDS for Pulse out put and 1 LED for Alarm
Communication
Optical 1107 port
Protocol: DLMS, Baud rate: 1200 – 19200 bps, Half duplex
RS232 port
Built-in supply of 4 V @ 550 mA, Protocol: DLMS,
Baud rate: 1200 –57600 bps, Half duplex
RS485 port
Protocol: configurable DLMS/MODBUS RTU,
Specifications are subject to change without prior notice

Baud rate: 1200 – 57600 bps, Half duplex


Ethernet port
10/100 Mbps, Protocol: DLMS and MODBUS TCP simultaneous client
Full duplex
Connector type: standard RJ45 for all the ports except optical
Accessories (optional) Panel mounting kit/RS232 communication module/
RS485 communication module/Terminal modem/Software
# Electrical, compliance, mechanical, software, features options depend on variant selected.