The document provides calculations for lighting requirements of various areas of a building including offices, toilets, storage, corridors, stairways and elevators. It determines the number and type of lights needed based on the area, recommended illumination level and lamp efficiency. It also includes cost estimations for electrical installation components.

Uploaded by

SAM tig
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views12 pages

Project Documentation Yyy

The document provides calculations for lighting requirements of various areas of a building including offices, toilets, storage, corridors, stairways and elevators. It determines the number and type of lights needed based on the area, recommended illumination level and lamp efficiency. It also includes cost estimations for electrical installation components.

Uploaded by

SAM tig
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 12

ADAMA SCIENCE AND

TECHNOLOGY UNIVERSITY
ELECTRICAL DESIGN AND
BUILDING ENGINEERING
PROJECT DOCUMENTATION
Group members ID number

1. Mulubrhan Tadesse UGR/25352/14


2. Yishak Mekonnen UGR/25507/14
3.
4. N
5. X
6. X
7. X
8. X
9. X

Submitted to: Mr. Tewodros Asfaw


CONTENTS

1. Calculations
i. Offices
ii. Toilets
iii. storage
iv. Corridor
v. Stairway
vi. Elevator
2. Maximum Load and current rating
3. Expected load
4. Costs
1.CALCULATIONS

I. offices

Office #1

Recommended illumination level(E) = 500 lux

Area to be illuminated (A) =29.8 m2

Total lumens (φ)=E*A→500lux * 29.8m2=14 900

Correction factor (CF) = Maintenance factor(MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 14900/0.48=31,041.67 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS for the offices of :

Efficiency(K):110

Lumen: 4400 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 31,041.67/110= 282.196 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 282.196/40= 7.O5 ≅ 8 LAMPS

Office #2

Recommended illumination level(E) = 500 lux

Area to be illuminated (A) =39.2 m2

Total lumens (φ)=E*A→500lux * 39.2m2=19600 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 19600/0.48=40,833.33Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS for the offices of :


Efficiency(K):110

Lumen: 4400 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 40,833.33/110= 371.12 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 371.12/40= 9.68 ≅ 10 LAMPS

Office #3

Recommended illumination level(E) = 500 lux

Area to be illuminated (A) =29 m2

Total lumens (φ)=E*A→500lux * 29 m2=14,500 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 14,500/0.48=30,208.33 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS for the offices of :

Efficiency(K):130

Lumen: 4400 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 30,208.33 /130= 232.37 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 237.37/40= 5.8 ≅ 6 LAMPS

Office #4

Recommended illumination level(E) = 500 lux

Area to be illuminated (A) =87.4 m2

Total lumens (φ)=E*A→500lux * 87.4 m2=43,700 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 43,700/0.48=91,041.67 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)


Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS for the offices of :

Efficiency(K):170

Lumen: 4400 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 91,041.67 /170= 535.539 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 535.539/40= 13.388 ≅ 14 LAMPS

Office #5

Recommended illumination level(E) = 500 lux

Area to be illuminated (A) =52.7 m2

Total lumens (φ)=E*A→500lux * 29 m2=26,350 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 26,350/0.48=54,895.833 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS for the offices of:

Efficiency(K):180

Lumen: 4400 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 54,895 /180= 304.97 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 304.97/40=7.6 ≅ 8 LAMPS

II.Toilet

Toilet#1

Recommended illumination level(E) = 150 lux

Area to be illuminated (A) =11.4 m2

Total lumens (φ)=E*A→150lux * 11.4 m2=1710 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48
Gross lumens (φG) =(E*A)/CF→ 1710/0.48= 3562.5Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED LIGHTS of:

Efficiency(K):80

Lumen: 1200 lumens

Wattage per lamp (WPL): 15 watts

Therefore TW = 3562.5 /80= 44.531 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 44.531/15= 2.96 ≅ 3 LAMPS

Since there are partitions for the toilet, we divided the number of lamps into two halves of corresponding
areas A1 and A2.

For A1 we have given 2 lamps and the remaining one lamp to A2 to divide for each toilet partitions of 4
watt(approximately)→15w/4= 3.75w ≅ 4w lamp for each toilet seat.

Therefor the total number of lamps for the toilet is 2x 15W lamps and 4x 4W LED light.

Toilet #2

Since it is identical to toilet#1, all calculations for toilet#1 applies to toilet#2.

III. Storage

Recommended illumination level(E) = 200 lux

Area to be illuminated (A) =16.6 m2

Total lumens (φ)=E*A→200lux * 16.6 m2=3320 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→3320 /0.48=6916.67Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used fluorescent Lights for storage of:

Efficiency(K):58

Lumen: 4640 lumens

Wattage per lamp (WPL): 40 watts

Therefore TW = 6916.67/58= 119.252 watts


Number of fixture (lamps)= TW/WPL→ #LAMPS= 119.252/80= 1.49 ≅ 2 LAMPS

IV. Corridor

Recommended illumination level(E) = 200 lux

Area to be illuminated (A) =40.6 m2

Total lumens (φ)=E*A→100lux * 40.6 m2=4060 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→4060 /0.48=8458.3333Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED Lights for corridor of:

Efficiency(K):102.14

Lumen: 1430 lumens

Wattage per lamp (WPL): 14 watts

Therefore TW = 8458.333/102.4 = 82.81 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 82.81/14= 5.915 ≅ 6 LAMPS

V. Stair ways

Recommended illumination level(E) = 200 lux

Area to be illuminated (A) =16.3882 m2

Total lumens (φ)=E*A→150 lux *16.3882 m2=2458.23 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→ 2458.23/0.48=5121.31 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED Lights for stairways of:

Efficiency(K):116.67

Lumen: 1750 lumens

Wattage per lamp (WPL): 15 watts

Therefore TW = 5121.31 /116.67 = 43.89 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 43.89/15= 2.926 ≅ 3 LAMPS

VI. Elevator
Recommended illumination level(E) = 20 lux

Area to be illuminated (A) =3.065 m2

Total lumens (φ)=E*A→20lux * 3.065 m2=61..308 LUMENS

Correction factor (CF) = Maintenance factor (MF) * Utilization factor (UF) → CF = 0.8*0.6=0.48

Gross lumens (φG) =(E*A)/CF→61.308 /0.48=127.725 Lumens

Total watts (TW) = φG/Efficiency of lamp (lumen per watts)

Efficiency of lamp(k)→ lumen per watts

We used LED Lights for elevator of:

Efficiency(K):51

Lumen: 204 lumens

Wattage per lamp (WPL): 4 watts

Therefore TW = 127.725/51 = 2.50 watts

Number of fixture (lamps)= TW/WPL→ #LAMPS= 2.50/4= 0.626 ≅ 1 Lamp/s


Multipurpose building Electricals Installation cost Estimations

Unit price Total cost


Specification Units Quantity
(Birr) (Birr)

Fluorescent
lamp with
holder 36 w
Lightings

LED 4W

LED 40W

LED 15W

LED 14W

one way

two way
Switch

Intermediat

Gang

GPSocket out
let 16
A,220V ,2 Pin
Sockets

SPSocket outlet
25 A,220 ,3pin

waterproof
socket
Junction box
Junction box

65mm for
switch
Junction box
85mm for
socket
Conduit 11 mm
Condu
it
Conduit 13.5
mm

Conduit 16 mm

Circuit breaker
6A

Circuit breaker
10 A

Circuit breaker
16 A
Circuit breaker

Circuit
breaker25 A

Circuit breaker
32 A

Reserve Circuit
breaker 10 A

Reserve Circuit
breaker 16 A

Solid copper
wire 2.5 mm2

Solid copper
Wire

wire 4 mm2

Solid copper
wire 10 mm2

Total cost