PLY900 Indicator

PLY900 Indicator

Hiya Mechanical Equipment Co., Ltd.

1
PLY900 Indicator

Catalogue

Chapter 1 Main technical indicators and functions-------------------------3

Chapter 2 Panel and Interface description-----------------------------------4

Chapter 3 Installation process description-----------------------------------6

Chapter 4 Calibration and charge mixture operation---------------------6

Chapter 5 MODBUS communication-----------------------------------------9

Chapter 6 Common trouble codes and troubleshooting-------------------16

Chapter 7 Instrument installation size----------------------------------------18

Chapter 8 Attention---------------------------------------------------------------18

2
PLY900 Indicator

Chapter 1 Main technical indicators and functions

1、 Main functions
 A combination of weighing, display, communication, printing and proportioning control.
 With analog, digital double filtering function.
 Automatic error diagnosis, easy to find and solve problems.
 Provide complete material batch control.
 Automatic/manual dosing.
 The batching process can be suspended at any time.
 With automatic zero tracking.
 Can realize automatic reset to power on.
 Automatic zeroing with ingredient start.
 Automatic selection with 4 materials.
 Feel free to modify and print the recipe.
 With manual / automatic setting drop correction function.
 With password permission setting function, easy to manage.
Zero setting range, zero tracking range, overload range.
2、 The main technical indicators
Basic parameters Description
Single row LED digital tube, LED light
Display
indication
Graduation value 1、2、5、10、20、50
Maximum display value 99999
Decimal point display 0、0.0、0.00
Weight unit kg
G.W 1600±300g
Performance
Accuracy ±0.01%FS
Maximum signal input range ±16mv
Sensor interface input impedance ≥20MΩ

3
PLY900 Indicator

Nonlinear error ≦0.002%FS


A/D Conversion speed 10 Times/second
Working parameters
Communication interface form RS485、RS232
Serial port baud rate 4800、9600、19200、115200
Sensor type Resistance strain gauge sensor
Sensor excitation voltage DC 5V
Analog output 4-20ma、0-5v
Switch input parameter 5-12V DC
Working conditions
Power supply voltage range AC 220V (AC175-265V),50Hz/60Hz
Product power <8W
Operating temperature -20℃~60℃
Humidity range ≤90%

Chapter 2 Panel and Interface description

Main display panel and rear structure:

4
PLY900 Indicator

Key Description

Key Description

Press the button in the weighing state,press “start”key,start working.

Press the button in the weighing state,press “stop”key,stop working.

Press the“menu”key in the weighing state 8seconds Enter the setting operation of the
configuration parameters.

In the weighing state,press 5 seconds,Enter the calibration operation。

In the weighing state,press 8 seconds,Enter the ingredient value of the ingredient,


drop the difference, and automatically follow the parameter setting.

After the data is input, press this button and the meter will store the entered value in
memory.

Return to the previous interface function, do not save any parameters when returning.

For example, the tare/zero button is valid only when the 0 button is pressed on the
main page (weighing page), and the zero tare/zero button is directly pressed to zero.
Must be on the main interface, the working state is 0, zero, and tare invalid.
Ten numeric keys for entering set values。Among them, the number keys 2 and 8
Number key
have a page turning function.

Discharge Discharge key,Batching is done in semi-automatic or manual situations ,Press the


key discharge button to activate!

Note: Automatic mode: automatic batching and unloading during work; manual mode: manual discharge
is required during work, and discharge is completed and returned to the main interface; semi-automatic

5
PLY900 Indicator

mode: batching is completed, manual unloading is completed, and unloading is completed automatically.
Semi-manual state: the ingredients are completed, no unloading, return to the main interface.

Chapter 3 Installation process description

1. Before connecting the sensor cable, please check whether the four corners of the sensor on the
weighing hopper are level, and the screw engagement part of the sensor should not exceed the upper
plane of the S-type sensor during installation.
2. Please connect the system three-phase incoming line and motor output line to the controller
reliably.
3. Connect the sensor cable and the hand-held box to the computer-side air connector.
4, the above process can be checked if it is correct, and the formula and calibration scale can be set.

Chapter 4 Calibration and charge mixture operation

4.1Calibration
Calibration;Press“Cal”more than 5 seconds

1、Empty the weighing platform and keep the weighing platform


stable.
2、Press“Cal”more than 5 seconds,The meter automatically jumps to

the interface.
Calibration step
3、 Enter the weight of the interface, in kg.
4、Place the weight on the weighing platform to keep the weighing
platform stable.
5、Click the “Enter” button on the panel to complete the calibration.
4.2 Parameter
Press “Parameter”key show the following table:
Parameter setting,long press the "Parameter" button for more than 5seconds,
No. Parameter Display Range default Remarks
0:Do not display the decimal
1 Decimal point 0-2 0 point
1:Display 1 decimal place

6
PLY900 Indicator

2:Display 2 decimal place


by“↑、↓”Selection parameter
Graduation 1、2、5、10、
2 1 by“↑、↓”Selection parameter
value 20、50
Interval between each
Material
3 3-999s 3 material ingredient.(second)
interval time
Input via numeric keypad
Unloading Indicates the discharge
4 3-999s 1
waiting time control delay time(second)
Interval between each cycle.
5 Cycle interval 3-999s 3 Input via numeric keypad
(second)
Cutting mode selection in
Unloading
6 L/R L automatic mode.
selection
by“↑、↓”Selection parameter.
Unloading perc
7 0-99 00
entage
Unloading dela
8 2-999 002 second
y time
Serial port baud 4800,9600,
9 9600
rate 19200,115200
Zero tracking 0:Do not start zero tracking.
10 0-999g 50g
range Input via numeric keypad
Measuring
11 0-99999 99999 kg
range
Drop 1 setting,
12 Drop 1 setting 0-99999KG 0
Input via numeric keypad
Drop 2 setting,
13 Drop 2 setting 0-99999KG 0
Input via numeric keypad
Drop 3 setting,
14 Drop 3 setting 0-99999KG 0
Input via numeric keypad

7
PLY900 Indicator

Drop 4 setting,
15 Drop 4 setting 0-99999KG 0
Input via numeric keypad
Drop automatically follow
16 Drop following ON/OFF ON the selection,
by“↑、↓”Selection parameter.
0:Manual mode, manual
unloading is required during
work, and unloading is
completed and returned to the
main interface.
1:Automatic mode,
automatic batching and
unloading during work;
17 Operating mode 0;1;2;3 2 2:Semi-automatic mode:
batching completed, manual
unloading, unloading
completed, automatic next
batching
3:Semi-manual state: the
ingredients are completed, no
unloading, return to the main
interface
Note:In the drop manual setting mode, the recipe and drop must be reset each time the decimal point
is changed. If you use the drop to automatically follow, you don't have to reset the drop.

4.2.1、Parameter setting range


Note 1: Index value Unloading The baud rate is selected by ↑ or ↓
Note 2: The ingredients and drop values in each recipe should be reset every time the decimal point is
set.
4.3、Ingredients
4.3.1、Formulation instructions

8
PLY900 Indicator

1、Press“Formula”key more than 5 seconds,in ,by“↑、↓”arrow selection formula


group
2、After selecting the recipe group, click enter.Set in order L1、L2、L3、L4 parameter.After the setting
is completed, click Back to complete the setting.
Note: In the drop manual setting mode, the recipe and drop must be reset each time the
decimal point is changed. If you use the drop to automatically follow, you don't have to reset the
drop.
Note: (1) When the self-calibration drop is not turned on, the drop value will not change. When the
self-calibration drop is on. The drop value will automatically judge the error of the set drop value to
automatically adjust the drop value but will not remember. After the power is turned back on, the drop
value will be restored to the manually set value.
(2) The ingredient switch is judged to stop according to the set difference value of the ingredient
value
4.3.2、Instrument drop setting
Drop setting range
The drop setting range is from 0 to 999 divisions and cannot be greater than one-half of the material's
ingredient setting.

Chapter 5 MODBUS communication

Read parameter request in device: Response:


Add Add
Function code Function code
Number of bytes
High register address High register address
Low register address Low register address
High register address High register address
Low register address Low register address
... ...
CRC low CRC low
CRC high CRC high
Example 1:

9
PLY900 Indicator

Display weighing platform weight:


Request:01 03 00 01 00 02 95 CB
If the weight on the platform is 1 kg now
Return:01 03 04 00 00 03 E8 FA 8D
If the weight on the platform is -1 kg now
Return:01 03 04 FF FF FC 18 BB 1D
Example 2:
Read decimal point:
Request:01 03 00 03 00 01 74 0A
If the decimal point is 1 now
Return:01 03 02 00 01 79 84
Note:
A: Add(initial:01) F: Low number of registers
B: Function code0X03 G: CRC Low
C: High register address H: CRC High
D: Low register address I: Return data description(decimal example)
E: High number of registers

A B C D E F G H I
Signed data-99999
Weight 01 03 00 01 00 02
000—99999000g
Decimal point 01 03 00 03 00 01 0-2
Indexing 01 03 00 04 00 01 1、2、5、10、20、50
Material interval
01 03 00 05 00 01 3-999s
time
Unloading waiting
01 03 00 06 00 01 1-999s
time
Cycle interval time 01 03 00 07 00 01 3-999s
Unloading 0:left unload
01 03 00 08 00 01
direction 1:right unload
Unloading
01 03 00 09 00 01 0-99
percentage

10
PLY900 Indicator

Unloading delay
01 03 00 0A 00 01 2-999s
time
0:4800
1:9600
Baud rate 01 03 00 0B 00 01
2:19200
3:115200
Zero range 01 03 00 0C 00 01 0-9999g
Sensor capacity 01 03 00 0D 00 02 0-99999kg
Drop1 01 03 00 0F 00 02 0-99999000g
Drop2 01 03 00 11 00 02 0-99999000g
Drop3 01 03 00 13 00 02 0-99999000g
Drop4 01 03 00 15 00 02 0-99999000g
Drop5 01 03 00 17 00 02 0-99999000g
Drop6 01 03 00 19 00 02 0-99999000g
Automatic 0:OFF
01 03 00 1B 00 01
adjustment of drop 1:ON
0(Single batch manual
unloading)
1(Automatic unloading
of circulating
ingredients)
Mode 01 03 00 1C 00 01
2(Manual unloading
of circulating
ingredients)
3(Single batch without
unloading)
Current formula 01 03 00 1D 00 01 1-4
Formula1 M1 01 03 00 1E 00 02 0-99999000g
Formula1 M2 01 03 00 20 00 02 0-99999000g
Formula1 M3 01 03 00 22 00 02 0-99999000g
Formula1 M4 01 03 00 24 00 02 0-99999000g

11
PLY900 Indicator

Formula1 M5 01 03 00 26 00 02 0-99999000g
Formula1 M6 01 03 00 28 00 02 0-99999000g
Formula2 M1 01 03 00 2A 00 02 0-99999000g
Formula2 M2 01 03 00 2C 00 02 0-99999000g
Formula2 M3 01 03 00 2E 00 02 0-99999000g
Formula2 M4 01 03 00 30 00 02 0-99999000g
Formula2 M5 01 03 00 32 00 02 0-99999000g
Formula2 M6 01 03 00 34 00 02 0-99999000g
Formula3 M1 01 03 00 36 00 02 0-99999000g
Formula3 M2 01 03 00 38 00 02 0-99999000g
Formula3 M3 01 03 00 3A 00 02 0-99999000g
Formula3 M4 01 03 00 3C 00 02 0-99999000g
Formula3 M5 01 03 00 3E 00 02 0-99999000g
Formula3 M6 01 03 00 40 00 02 0-99999000g
Formula4 M1 01 03 00 42 00 02 0-99999000g
Formula4 M2 01 03 00 44 00 02 0-99999000g
Formula4 M3 01 03 00 46 00 02 0-99999000g
Formula4 M4 01 03 00 48 00 02 0-99999000g
Formula4 M5 01 03 00 4A 00 02 0-99999000g
Formula4 M6 01 03 00 4C 00 02 0-99999000g

Modify the parameters in the device


Request: Response:
Add Add
Function code Function code
Start register address is high Start register address is high
Start register address is low Start register address is low
High number of registers High number of registers
Low number of registers Low number of registers
Number of bytes
High register value

12
PLY900 Indicator

Low register value


High register value
Low register value
CRC low CRC low
CRC high CRC high

Example 1:
Modify the number of decimal places (display two decimal places):
Request:01 10 00 03 00 01 02 00 02 27 A2
Return:01 10 00 03 00 01 F1 C9
Example 2:
Modify the index (display index 5)
Request:01 10 00 04 00 01 02 00 05 67 D7
Return:01 10 00 04 00 01 40 08
Precautions:
1: The maximum setting range of ingredients and drop is related to the decimal point
When the decimal point is 0, the maximum setting range is 0-99999000g.
When the decimal point is 1, the maximum setting range is 0-9999000 grams.
When the decimal point is 2, the maximum setting range is 0-999000 g.
2: After calibrating the zero point, the calibration weight should be calibrated.
3: In the batching process, only start the ingredients, suspend the ingredients, return to the main interface,
the discharge command is valid, and other needs to be effective under the weighing interface.

Note:
A: Add B: function code
C: Start register address is high D: Start register address is low
E: High number of registers F: Low number of registers0
G: Number of bytes H: High register value
I: Low register value J: Write data description (decimal)
A B C D E F G H I J
Device address 01 10 00 00 00 01 02 0-255
Decimal point 01 10 00 03 00 01 02 0-2

13
PLY900 Indicator

1、2、5、10、20、
Indexing 01 10 00 04 00 01 02
50
Material interval
01 10 00 05 00 01 02 3-999s
time
Unloading
01 10 00 06 00 01 02 1-999s
waiting time
Cycle interval
01 10 00 07 00 01 02 3-999s
time
Unloading 0:left unload
01 10 00 08 00 01 02
direction 1:right unload
Unloading
01 10 00 09 00 01 02 0-99
percentage
Unloading delay
01 10 00 0A 00 01 02 2-999s
time
0:4800
1:9600
Baud rate 01 10 00 0B 00 01 02
2:19200
3:115200
Zero range 01 10 00 0C 00 01 02 0-9999g
Sensor capacity 01 10 00 0D 00 02 04 0-99999kg
Drop1 01 10 00 0F 00 02 04 0-99999000g
Drop2 01 10 00 11 00 02 04 0-99999000g
Drop3 01 10 00 13 00 02 04 0-99999000g
Drop4 01 10 00 15 00 02 04 0-99999000g
Drop5 01 10 00 17 00 02 04 0-99999000g
Drop6 01 10 00 19 00 02 04 0-99999000g
Automatic
0:OFF
adjustment of 01 10 00 1B 00 01 02
1:ON
drop
0:Single batch
Mode 01 10 00 1C 00 01 02
manual unloading

14
PLY900 Indicator

1:Automatic
unloading of
circulating
ingredients
2:Manual
unloading of
circulating
ingredients
3:Single batch
without
unloading
Current formula 01 10 00 1D 00 01 02 1-4
Formula1 M1 01 10 00 1E 00 02 04 0-99999000g
Formula1 M2 01 10 00 20 00 02 04 0-99999000g
Formula1 M3 01 10 00 22 00 02 04 0-99999000g
Formula1 M4 01 10 00 24 00 02 04 0-99999000g
Formula1 M5 01 10 00 26 00 02 04 0-99999000g
Formula1 M6 01 10 00 28 00 02 04 0-99999000g
Formula2 M1 01 10 00 2A 00 02 04 0-99999000g
Formula2 M2 01 10 00 2C 00 02 04 0-99999000g
Formula2 M3 01 10 00 2E 00 02 04 0-99999000g
Formula2 M4 01 10 00 30 00 02 04 0-99999000g
Formula2 M5 01 10 00 32 00 02 04 0-99999000g
Formula2 M6 01 10 00 34 00 02 04 0-99999000g
Formula3 M1 01 10 00 36 00 02 04 0-99999000g
Formula3 M2 01 10 00 38 00 02 04 0-99999000g
Formula3 M3 01 10 00 3A 00 02 04 0-99999000g
Formula3 M4 01 10 00 3C 00 02 04 0-99999000g
Formula3 M5 01 10 00 3E 00 02 04 0-99999000g
Formula3 M6 01 10 00 40 00 02 04 0-99999000g
Formula4 M1 01 10 00 42 00 02 04 0-99999000g

15
PLY900 Indicator

Formula4 M2 01 10 00 44 00 02 04 0-99999000g
Formula4 M3 01 10 00 46 00 02 04 0-99999000g
Formula4 M4 01 10 00 48 00 02 04 0-99999000g
Formula4 M5 01 10 00 4A 00 02 04 0-99999000g
Formula4 M6 01 10 00 4C 00 02 04 0-99999000g
Tare(Clear) 01 10 00 4E 00 01 02 00 AA Fixed value
Restore factory se
01 10 00 4F 00 01 02 00 FF Fixed value
ttings
Cal(cal Zero
01 10 00 50 00 01 02 FF FF Fixed value
point)
Cal(cal weight) 01 10 00 50 00 01 02 0-9999kg
Unloading 01 10 00 51 00 01 02 DD DD Fixed value
Starting
01 10 00 52 00 01 02 AA AA Fixed value
ingredients
Pause ingredients 01 10 00 53 00 01 02 BB BB Fixed value
Return to main
01 10 00 54 00 01 02 CC CC Fixed value
interface

Chapter 6 Common trouble codes and troubleshooting

6.1、Error indication
Display content Meaning Solution
Keep the scale stable and re-calibrate
Calibration failed
the scale
More than maximum display Decrease the number of decimal
digits places

Unable to start ingredient, reason:


Set the ingredient value
recipe is not set

Restart the device or restore factory


The system is running abnormally
settings

16
PLY900 Indicator

Turn off the power and connect the


Sensor abnormality
sensor

Exceeding the maximum capacity Replace the large capacity sensor

Ingredients 1 error
An ingredient error indicates that the
Ingredients 2 error weight of the actual ingredient is

Ingredients 3 error greater than or less than one-half of


the set value.
Ingredients 4 error

Note:During the operation of all the buttons, if the operation is wrong, the error LED on the display
panel will be illuminated. If the password is entered incorrectly, press any key and then re-enter. If it is
the start of the ingredient, the error is because the ingredient value is not set.
6.2、Troubleshooting
(1)Failure analysis that cannot be returned to zero after weighing
In the case of ensuring that the sensor output is normal (the scale body is stable), generally the zero
point range setting is too small, and the zero point range should be set larger.
(2)Inaccurate fault analysis
Observe whether the internal code value is stable, whether there is friction in all parts of the sensor,
whether the stabilized power supply is stable, whether the operational amplifier circuit is normal, and
whether the weight of the four-legged weighing pan is averaged using the weight. Further instrumental
analysis or weight correction according to the instructions.
(3)Unable to boot
First determine the problem of non-fuse, power switch, power line and voltage switch, check the
transformer for AC voltage input and AC output. Secondly, check whether the rectifier circuit, the
voltage regulator circuit and the display driver circuit are abnormal. If there is no problem, check
whether the processor and the auxiliary circuit are burnt out.
(4)Show garbled
Remove the original display circuit and change to a normal display circuit to see if it is normal. If
the display is normal, the display circuit has a problem. If it is not normal, check the driver circuit for
faults. Finally, check if the processor shows that the output pin is in a reasonable output range.
(5)Can't be called full
Similar to the situation where it is impossible to return to zero, most of them may be changed due to

17
PLY900 Indicator

the small signal input range or the range setting is not set correctly. According to the method that cannot
be returned to zero, if the problem cannot be found, first check whether the power supply, A/D circuit is
normal, the range setting is normal, and then detect the sensor output.

Chapter 7 Instrument installation size

Chapter 8 Attention

(1) Do not remove the connector on the rear panel of the instrument or replace the sensor when power is
on.
(2) Do not use organic solvents such as hydrocarbons, alcohols, ketones or strong acid or strong alkali
solutions to clean the instrument, so as not to damage the casing, panel and internal components of the
instrument.

18
PLY900 Indicator

※ This equipment cannot be cleaned with organic solvents such as hydrocarbons, alcohols, ketones or
strong acid or alkali solutions to avoid damage to the casing, panels and internal components of the
equipment.
※ This equipment will not accept any repairs or modifications made by you. If
the equipment malfunctions, please follow this manual for troubleshooting or
contact us, otherwise you will lose the right to after-sales service.
※ Do not install in dusty, multi-metal powder.
※ Non-corrosive, explosive gas at the installation site.
※ Installed in a place where there is no direct sunlight or shelter from the rain.

Hiya Mechanical Equipment Co., Ltd.