Installation Instructions
December 11, 2017
Mounting Information
Always mount the room unit vertically.
Unit Set-up
• Use the bottom and middle pins for 0 to 10V. a. Install the two room unit mounting screws
provided, but do not tighten.
NOTE: If the jumper is missing or removed, the
output voltage will default to b. Level the room unit base plate for appearance
0 to 10V. only.
c. Tighten the two mounting screws to the room
NOTE: The factory default for displayed temperature unit base plate.
units is °F. To change the display to °C, snip the
wire jumper (0 Ohm resistor R64) on the back of CAUTION:
the PCA. Over-tightening may cause the room unit
base plate to crack or bend.
4. Continue with Drywall Mounting (No Rough-in),
Typical, Steps 6 through 8, and Unit Set-up.
Page 3 of 4
Document No. 129-104
Installation Instructions
December 11, 2017
CAUTION:
To prevent equipment damage, do the
following:
If the room unit is powered by AC:
• AC Supply must be type NEC Class 2
and earth grounded at the secondary
neutral.
• Room Unit ACN (GND) must be
connected to the controller common.
• If the controller has a floating common,
that common must be connected to the
same earth ground point as the controller
AC supply.
If the room unit is powered by isolated
DC: Figure 6. Typical Wiring Base.
• Where power is current limited up to 300 (All terminals may not be present.)
mA, it is not required to earth ground the
Pin No. Function
controller isolated common.
Units with Blank Front
• Room Unit DC-(GND) must be connected 1 DC+ or ACH
to the controller common.
2 DC- or ACN (GND)
3 Temp Output
CAUTION: 4 Humidity Output
Follow manufacturer’s Installation 5* Passive Temp
Instructions and Wiring Guidelines for 6* Passive Temp Common
connecting the controller to the Room Units with Display
Unit. 1 DC+ or ACH
2 DC- or ACN (GND)
For Siemens Controllers: 3 Temp Output
• APOGEE Controllers with common already 4 Humidity Output
earth grounded are TXIO used on PXC 5* Passive Temp
Modular, PXC Compact 36 Expansion and 6* Passive Temp Common
P1 BIM or PTM used on MBC and RBC. 7 Setpoint Output
These do not require the earth ground wire
8 Override
to be connected to the controller.
9 Override Common
• APOGEE Controllers with floating common * Not available on “SS” models.
are PXC Compact 16/24/36, MEC, PXM,
LON TEC and PPM. These require the NOTE: If active temperature (0 to 5V/0 to 10V/4 to
earth ground wire to be connected to the 20 mA) (Pin 3) rather than passive/resistive
controller.
temperature is used, Passive Temp Common
(Pin 6) does not need to be terminated.
The installation is now complete.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. APOGEE is a registered trademark or Siemens Industry, Inc. Other product or company names mentioned herein
may be the trademarks of their respective owners. © 2017 Siemens Industry, Inc.
Siemens Industry, Inc. Your feedback is important to us. If you have Document No. 129-104
Building Technologies Division comments about this document, please send them Printed in the USA
1000 Deerfield Parkway to [email protected] Page 4 of 4
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000