State Estimation at All India Level
State Estimation at All India Level
State Estimation at All India Level
Akhil Singhal Harish Kumar Rathour P.K. Agarwal KVS Baba S.K. Soonee
Deputy Manager Chief Manager General Manager Executive Director Chief Executive Officer
POWER SYSTEM OPERATION CORPORATION LIMITED, NEW DELHI, INDIA
Abstract — Indian power system is one of the largest n is the number of measurements.
synchronously operated Power System Networks in the It is the function ‘f’ which is minimized using Weighted
world. It has an installed capacity of about 303 GW. Least Square algorithm.
Indian power system has complex transmission network
along with many cross border connections. It is monitored
State Variables: Voltage and Angle at each node (refer
by a multi-level integrated Supervisory Control & Data fig.1) are the state variables. By estimating these two
Acquisition (SCADA)/ Energy Management System (EMS) parameters, we can calculate line flows, injection, drawls,
installed at many control centres dispersed all over India. etc.
SCADA/EMS of National control centre is integrated with
SCADA/EMS systems of five Regional control centres.
SCADA/EMS systems of Regional control centres in turn
are integrated with SCADA/EMS systems of 32 State
Fig.1: Common Bus diagram showing state variables
control centres.
Real Power, P = V1*V2*sin(θ1- θ2)
It is important to use all real-time tools to help the operator -------------------------
in maintaining the grid in a highly secure and reliable XL
manner. Successful implementation of State Estimator is Reactive Power, Q = V1 2 – V1V2 cos(θ1- θ2)
said to be critical requirement for efficient EMS. An --------------------------------
exercise was taken up by Power System Operation XL
Corporation Limited (POSOCO) with an objective of II. Use of State Estimation in Energy Management
improving the usage of State Estimation in Load Despatch
System at Load Despatch Centres
Centres in India. In this process, it has been interacting
with experts both in India and abroad with the objective of Energy Management System (EMS) is the mechanism to
learning and making continuous improvement. capture “system knowledge” and “situational awareness”
and provide some key indicators to help the Load
Successful running of State Estimation at All India level Despatcher in real-time decision making. EMS tools are
involves maintaining and tuning of a large SCADA and essential for reliable and secure operation of the grid.
Network database. Such a big database needs correction in
topology, device parameters, connectivity model, etc. This EMS applications can be divided into two parts –
paper focusses on all such related issues, its solution and a) Network Applications which includes fault analysis,
impact on State Estimator output. contingency analysis, Powerflow, optimal powerflow,
Keywords – Supervisory Control and Data Acquisition Data Validation (by State Estimation), etc.
(SCADA), National Load Despatch Center (NLDC), b) Generation Applications which includes Unit
Energy Management System (EMS), State Estimator (SE), commitment/scheduling, Reserve/Cost monitoring,
Power Network Applications (PNA). Economic Despatch, etc.
I. Introduction Energy Management System (EMS) has a system of
State Estimation was introduced by Gauss and Legendre computer-aided tools used by operators of electric utility
(around 1800). The basic idea was to “fine tune” State grids to monitor, control and optimize the performance of
Variables (Voltage and Angle at each bus) by minimizing the generation and/or transmission system. The monitor and
the sum of the residual squares. This is the well-known control functions are known as SCADA. This computer
Least Squares (LS) method. The reason for its popularity is technology is also referred to as SCADA/EMS or
easy to understand: At the time of its invention there were EMS/SCADA. The terminology EMS then excludes the
no computers, and the fact that the Least Squares estimator monitoring and control functions, but more specifically
could be computed explicitly from the data made it the only refers to the collective suite of Power Network Applications
feasible approach. State Estimation was applied to Power (PNA) and to the generation control and scheduling
Systems by Schweppe and Wildes in the late 1960s in a applications.
real-time environment. In Load Despatch Centre at National level, thousands of
The basic equations involved are – analog and digital data are acquired in real-time which may
also contain some incorrect data or some data might not be
[z] = H[x] + e getting telemetered due to various reasons such as faulty
f = Σ Wj.ej2 (j=1 to n) RTU, faulty transducers, poor state of potential-free NO/NC
Where, contacts in switching devices, communication failure, etc.
z is the vector of measured state variables.
H is measurement function coefficient matrix.
x is the vector of estimated state variables.
e is the error.
Fig.2: Non-availability of Analog data due to various reasons
Wj is the weight assigned to error ej.
1 of 6
State Estimation provides an estimated value of measurands
for all correctly telemetered/non-telemetered/incorrect data
and hence acts as a cross-check reference helping in Bad
Data detection.
Output of the State Estimator provides Voltage Magnitude
and Angle at each bus and hence gives a base-case for all
the Network Applications and some of the generation
applications to carry out various studies in order to help grid
operator in real-time operation.
2 of 6
and different MW flow. In all such cases the parameters of network based on position of switching devices (i.e. Circuit
ICTs were changed accordingly. Breakers and Isolators). If the output of topology processor
2.3 Correction in Generating Unit Parameters deviates from the actual scenario at the site (due to
incorrect/unavailable status) then output of SE application
In the Network database, the Generating Units need to be would also not of much use and many-a-times would not
properly defined with number of parameters such as give a converged solution.
Maximum/Minimum MW capacity, Maximum/Minimum
MVAR capacity, MVA rating, etc. The generating unit
parameters were taken from the Annual Compendium
Booklet of POSOCO and updated in database.
All these parameters impact the State Estimator Output
considerably. An example is shown in Fig.7.
3 of 6
Another approach is to keep the last good value. Different
vendors may have different approached to handle this.
Whatever approach is chosen one has to look at such device
status & validate them and get the telemetry issue fixed.
Fig.11 further elaborates this approach of correcting the
status information.
Fig.11: Topology correction Fig.13: Incorrect status of bypass switching device of Series
compensation
The status of switching devices with “Good” Quality
remains unchanged. 7. Modeling of Loads and Injections to cater HVDC
connections
5. Topology Estimation
The HVDC lines are generally modeled as Truncated
Topology estimation checks could be performed on network Loads/Injections with the real-time power flow data on the
to find ambiguity with respect to the line flows and status of convertor transformers mapped onto it. The AC filter banks
the corresponding switching devices. Coherency warnings are modeled as a set of Capacitors connected directly to the
generated could be used to tune the network. The threshold bus in order to provide the required MVARs. One of the
for analog data for generating Coherency Warning is kept as examples of +/- 500kV Mundra-Mahendragarh HVDC
50 MW. Bipole is shown in Fig.14.
The drawback of topology estimation checks in NLDC
system is that is does not consider the entire connectivity of
the equipment to the bus. It only checks the coherency with
the switching device (say Line Isolator) directly connected
with the equipment.
6 of 6