Bulletin SCPb

AUGUST 2018

Specifications, Applications,
Service Instructions & Parts

ENCAPSULATED SOLENOID
COILS AND
BEACON PILOT LIGHTS
Standard Coil with Wire Leads

with 1/2” Fitting or DIN Plug

DIN Plug-in Coil

INTRODUCTION MATERIAL SPECIFICATIONS


All Hansen solenoid valves utilize a one-size Coil: Encapsulated, Class “F” construction
encapsulated, watertight coil. These coils are
Power: 115VAC 50/60Hz
strong and efficient, requiring only 16 watts of
power. All common voltages and frequencies 208/230VAC 50/60Hz
are available. Coils are designed to operate 24VAC 50/60Hz
from 85% to 110% of rated voltage. Pilot light
assemblies are also available. The pilot light 24VDC
assemblies require no additional wiring. Operating Range: 85% - 110% of rated voltage
APPLICATIONS Connections: 1/2” fitting (NPSM), standard
The standard coil connection is a ½” female DIN plug for socket, optional
straight pipe fitting (NPSM) for conduit, with two
CSA & CE Approved
18” long, insulated 18 AWG wire leads plus ground
wire. Coils with a DIN plug or a Quick Disconnect ADVANTAGES
plug are available where codes permit.
Hansen solenoid coils are totally encapsulated.
All coils meet NEMA 3R (IP32) (rainproof) and The new design minimizes corrosion and provides
NEMA 4 (splashproof) requirements. This sealed a clean finish to the product. The watertight
construction can withstand direct contact with Hansen coils are completely interchangeable
splashing or hose-directed water, wind blown with the formerly supplied European/Danish coils
dust or rain, and remain undamaged by the provided the proper Coil Adapter Kit is used. See
formation of ice. coil interchangeability drawings on page 3.

KEY FEATURES Coils have proven reliable for the anticipated


broad ranges of electrical conditions and
One coil fits all valve sizes
temperatures.
Low wattage
Encapsulated, watertight design
Operates on standard voltages
Combination 50/60Hz coil
Can be used with European/Danish coils using
Coil Adapter Kit 70-1104
Easily installed, no tools required
Long life wireless pilot light optional
INSTALLATION LONG LIFE BEACON PILOT LIGHTS
To avoid bending the solenoid tube, remove coil Hansen long life Beacon
from valve before connecting conduit or cable Pilot Lights incorporate
to coil. Make all electrical connections per a tot a lly encapsulate d,
local and national electrical codes. Place coil unique secondary wound
onto solenoid tube. Coil may be rotated 360° to coil and LED light in a
facilitate wiring. compact disc. The pilot
lights require no additional wiring. Simply place
To fasten coil to Hansen solenoid tube (threaded
Beacon Pilot Light and o-ring on top of coil and
top), install o-ring, install coil, install beacon pilot
hand tighten with the Pilot Light Knob. The
light (optional), and hand tighten knob.
Beacon Pilot Light will light when power is flowing
To fasten coil to European/Danish solenoid tube, through the coil. Note: Beacon Pilot Lights are
use Hansen Coil Adapter Kit 70-1104. Remove for AC voltage coils only.
original European/Danish coil and o-ring and
place Hansen coil o-ring and coil onto solenoid SERVICE AND MAINTENANCE
tube. Place adapter clip over coil and push down If coil is suspected of not working, first check
over tube until it snaps in place. Install cap fuses, circuit breakers, control relays and
over clip until it snaps into place. The adapter switches leading to coil to be sure they are
retainer clip can be removed with a blade-type working properly and that power is reaching the
screwdriver. coil. Be sure line voltage is within 85% to 110% of
marked coil rated voltage, see Table 2 below.
ELECTRICAL
The coil will draw 16 watts and properly operate TABLE 2
between 85% and 110% of rated voltage (the
24 Volt coil will draw 19 watts). Typical power Rated Minimum Maximum
consumption for the standard coils is listed in Voltage Voltage (85%) Voltage (110%)
the table below. In the table, the term “INRUSH 115V 98V 126V
AMPS” refers to the high momentary current 208/230V 177V 253V
surge ocurring when the coil is energized. The 24V 20.4V 26.4V
“HOLDING AMPS” (sometimes called running
amps) refers to the continuous current draw Energize the coil; a single metallic “click” signifies
following the inrush. the coil is working. If the “click” is not heard,
To verify correct coil voltage, measure resistance remove knob and hold a small screwdriver against
of coil while coil is at room temperature. See solenoid tube top while coil is energized; a
Table 1 of Resistance Values below. slight magnetic pull should be detected. If not,
check coil winding resistance. Confirm coil is
Coils can be continuously energized without the correct voltage by comparing resistance as
overheating or failure. When coil has been shown in Table 1. Disconnect electrical power
energized for a long period, the surface will and isolate coil from field wiring. Use an Ohm
become hot to the touch; this is normal. Coil meter, or other continuity device, to check the
should only be energized while on solenoid tube; resistance between the two power leads coming
otherwise immediate coil burnout may occur. from the coil. If coil resistance is infinite, replace
coil. Before replacing any coil, the cause of
TABLE 1
failure should be determined and rectified (ie.,
Resistance at missing parts, plugged solenoid tube or plunger,
Frequency Inrush Holding Room worn out parts, over voltage, etc.).
Voltage
(Hertz) Amps Amps Temperature
(Ohms) PRINCIPLES OF OPERATION
60 0.73 0.24 56±6
115VAC
50 0.93 0.31 56±6 When energized, the flow of electricity through
60 (208V) 0.32 0.11 226±23 the coil winding creates a magnetic field. Inside
208/230VAC 60 (240V) 0.41 0.14 226±23 this field is the solenoid tube and plunger. The
50 (230V) 0.47 0.16 226±23 pull of the magnetic field is strong enough to lift
60 3.42 1.14 2±.2
24VAC the plunger off the pilot seat orifice (typical of a
50 4.56 1.52 2±.2
24VDC DC 1.2 1.2 20±2 normally closed solenoid tube and plunger). When
de-energized, the magnetic field is broken and
the plunger returns to close the pilot seat orifice.

SCPb
AUGUST 2018 2
HANSEN SOLENOID COIL INSTALLATION

PILOT LIGHT KNOB

KNOB
BEACON PILOT LIGHT

O-RING

HANSEN FULLY
ENCAPSULATED
COIL WITH
QUICK
DISCONNECT
PLUG
(OBSOLETE)
HANSEN FULLY
ENCAPSULATED
COIL WITH 1/2”
NPSM FITTING HANSEN FULLY
ENCAPSULATED COIL
WITH DIN PLUG

OPTIONAL O-RING

HANSEN SOLENOID TUBE

COIL CLIP ASSEMBLY WITH EUROPEAN DANISH SOLENOID TUBE

HANSEN ADAPTER CAP

HANSEN ADAPTER CLIP

HANSEN COIL

HANSEN O-RING
EUROPEAN DANISH SOLENOID TUBE

SCPb
3 AUGUST 2018
PARTS LIST ORDERING INFORMATION
Standard Coil Kit, 18” Leads
(includes coil, knob and o-ring)
115V 70-1085
230V 70-1086
24AC 70-1087

Standard Coil Kit, 60” Leads


(includes coil, knob and o-ring)
115V 70-1155
230V 70-1156

Plug-in Coil Kit, Less Socket


(includes coil, knob and o-ring)
115V 70-1088
230V 70-1089
24AC 70-1090
24DC 70-1091

Plug-in Coil Kit, with DIN Connector Socket


Item Description Qty Part No. (includes coil, knob and o-ring)
1 Fully Encapsulated Coil 1 Various 115V 70-1092
230V 70-1093
Solenoid Tube/Plunger Kit 1 70-1059 24AC 70-1094
Above kit consists of: 24DC 70-1095
2 Coil Knob 1
3 Solenoid Tube 1
4 Plunger 1 Pilot Light Kit
5 Solenoid Tube O-Ring 1 (includes coil beacon, knob and o-ring)
6 O-Ring 1 (A /C Coils Only)
7 Screws 4 Red 70-1100
Green 70-1102
Also Available: Amber 70-1101
DIN Connector Socket Only 1 70-1130

Coil Adapter Kit for Use on European Danish Valves


CAUTION
70-1104
Coils have been designed specifically for use
with Hansen valves on refrigeration systems.
They can also replace the same size European/
Danish coils. Instructions and related safety
precautions must be completely read and
understood before selecting, using or servicing
coils. Only knowledgeable, trained refrigeration
mechanics should install, operate or service coils.
Stated temperature and pressure limits should
not be exceeded. Do not remove solenoid tube
from valve unless system has been evacuated
to zero pressure. See also Safety Precaution
Sheet supplied with product.

WARRANTY
Hansen electrical and electronic par ts are
guar anteed against defective materials or
workmanship for 90 days F.O.B. factory. All
other components are guaranteed for one year Hansen Technologies Corporation
681 Commerce Street
F.O.B. factory. No consequential damages or Burr Ridge, Illinois 60527 USA
field labor is included. Tel: 630.325.1565 Fax: 630.325.1572 Toll: 866.4HANSEN
Email: [email protected] Web: www.hantech.com
USA ∙ Asia ∙ Europe ∙ India ∙ Latin America ∙ Middle East
© 2018 Hansen Technologies Corporation
SCPb
AUGUST 2018 4