ANT1

This document contains an HVAC load calculation form for a building located in Balangibang, Albay, Philippines. It calculates the sensible and latent heat loads for rooms and outside air, accounting for factors like solar gain through glass, transmission through walls and the roof, internal heat from people, lighting and equipment, and infiltration. The total calculated heating load is 10,369.64 Btu/hr or 0.86 tons of cooling capacity required.

Uploaded by

mjbicaldo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views1 page

ANT1

This document contains an HVAC load calculation form for a building located in Balangibang, Albay, Philippines. It calculates the sensible and latent heat loads for rooms and outside air, accounting for factors like solar gain through glass, transmission through walls and the roof, internal heat from people, lighting and equipment, and infiltration. The total calculated heating load is 10,369.64 Btu/hr or 0.86 tons of cooling capacity required.

Uploaded by

mjbicaldo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

HVAC LOAD CALCULATION - E20 FORM SHEET

PROJECT
LOCATION BALANGIBANG, POLANGUI, ALBAY
CLIENT DSF
CONSULTANT ENGR. JOEFFREY D. BUSTINERA
126.00
Area or Sun Gain or
Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff.
ROOM HEAT Q= U*A*ΔT
ROOM SENSIBLE HEAT
Solar Gain - Glass Area ΔT U
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00
Glass - SE 12.00 SqFt x 14.00 x 0.94 157.92
Glass - S SqFt x x 0.00
Glass - SW 20.00 SqFt x 57.00 x 0.94 1,071.60
Glass - W SqFt x x 0.00
Glass - NW SqFt x x 0.00
Skylight SqFt x x 0.00
Solar & Transmission Gain - Walls & Roof
Wall - N SqFt x F x 0.00
Wall - NE SqFt x F x 0.00
Wall - E SqFt x F x 0.00
Wall - SE 51.00 SqFt x 30.00 F x 0.38 581.40
Wall - S SqFt x F x 0.00
Wall - SW 61.00 SqFt x 24.50 F x 0.38 567.91
Wall - W SqFt x F x 0.00
Wall - NW SqFt x F x 0.00
Roof 77.50 SqFt x 38.00 F x 0.417 1,227.18
Transmission Gain - Except Walls & Roof
All Glass 29.79 SqFt x 21.80 F x 0.94 610.45
Partition 128.00 SqFt x 16.80 F x 0.45 964.24
Ceiling 81.00 SqFt x 38.00 F x 0.42 1,282.60
Floor 81.00 SqFt x 16.80 F x 0.05 68.04
INFILTRATION AND BY PASSED AIR
Infiltration CFM x 21.80 T.Diff x 1.08 0.00
Outside Air 14.86 CFM x 21.80 x 41.98
Internal Heat
People 2.00 Nos. x 230.00 Btu/Hour Per Person 460.00
Lighting 77.50 SqFt x 1.00 W/SqFt x 3.41 264.28
Equipments 1.00 103.00 Watts x 3.41 351.23
Power kW/Hp x 0.00
Sub Total 7,648.83
Factor 5-15% 1,147.32
Effective Room Sensible Heat 8,796.15 1.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 70.00 Gr/Lb x 0.68 0.00
Outside Air 14.86 CFM x 70.00 Gr/Lb x BFx0.68 84.88
People 2.00 Nos. x 120.00 Btu/Hour Per Person 240.00
Sub Total 324.88
Factor 2.5 - 5% 16.24
Effective Room Latent Heat 341.12 2.00
EFFECTIVE ROOM TOTAL HEAT 9,137.28
OUTSIDE AIR HEAT
Sensible 14.86 CFM x 21.80 F(TD) x CF x 1.08 307.88 3.00
Latent 14.86 CFM x 70.00 Gr/Lb x CF x 0.68 622.46 4.00
OUTSIDE AIR TOTAL HEAT 930.34
GRAND SUB-TOTAL HEAT 10,067.613
Factor 1 - 3% 302.03
GRAND TOTAL HEAT 10,369.64
TMBH 10.37
TKW 3.01
TSMBH 9,104.03
TSKW 2,640.17
TONS=GRAND TOTAL HEAT/12000 0.86