LX3 Series Installation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

LX3 Series User Manual V2.

LX3 Series User Manual


Safety Precautions
Before installing, operating, and maintaining the micro-programmable control, be sure to
familiarize yourself with this user manual and other related manuals to ensure proper use.
Please use it after you are familiar with the operation method, safety information and all
precautions.
In this manual, safety precautions are classified into two categories: “warning” and “caution”.

Before installation, operation, maintenaning and overhaul of the product, please


be sure to read the user manual and other related manuals to ensure correct use.
Failure to follow the instructions in the manual may result in improper installation
, use and storage of the equipment, which may result in personal injury or even death, and
property damage.

Part 1 Design Precautions


WARNING
To ensure safety system operation, please configure emergency braking circuit, positive
inversion circuit or other similar protection circuit for PLC, which protection circuit can prevent
the damage to PLC or other devices.
●External power supply would break down unexpectedly.
●All outputs will be turned off, as an error be detected by PLC CPU during self-diagnosis, such
as a watch dog timer error. When error cannot be detected, internal protection circuit may be
disabled.
●The output state of relay or transistor in the PLC can’t be controlled, when relay or transistor
is damaged.

Part 2 Installation Precautions


WARNING
●Always make sure to install PLC on vertical plane, not on broadside.
●50mm safe distance must be kept with other devices, and far away
from the high-voltage power line, high-voltage device and the power
equipment.

CAUTION
●Never use the product on condition with dust, oily smoke, conductive dusts, corrosive gas,
flammable gas, vibration or impacts, or expose to high temperature, fire or rain.
●Do not leave anything in the vent. when installation or wiring is completed.
●Always make sure to remove the dust proof sheet from the PLC’s vent when installation or
wiring is completed.

1
LX3 Series User Manual V2.0

Part 3 Wiring Precautions


WARNING
●Before installation and wiring, you must cut off the power.
●Before running, please make sure to attach the cover for terminal on PLC.
●That positive inversion contactor is working on at the same time will be dangerous.
●PLC will be damaged, if the invalid terminal on the PLC being connected with other devices.

CAUTION
●Please follow the instruction to connect with power supply which provided in this manual. The
range of AC source must be from 100V to 240V.
●Please never directly connect terminal with external power supply which is over 24V.
●Separately grounding is recommended.
●The signal input cable and the signal output cable can’t go with the same cable.
●Never put the signal input/output cable and other power cable together.
●It would be safer if the cable within 20m.
Note: The PLC would stop working, if the power-off time is over 10ms. Long-term power failure
or low voltage will cause the PLC to stop working, and the all the output of this PLC will be
OFF. The PLC would continue work automatically with normal power supply.

Part 4 Maintenance Precautions


WARNING
●Never touch the PLC when power is on.
●Never clean up PLC when power is on, which may cause the electric shock.
●The manual should be understood before attempting to install or program.

CAUTION
●Never modify structure of PLC.
●If there is something wrong with our products, please contact Wecon technology company.
●Working with high frequency and large capacity load will shorten service life.
●Please check the following items:
Keep far away from directing sunshine or other heating element, because that would raise
the temperature of PLC.
Make sure there is no dust or electrical dust in the PLC.
Make sure there is no anomaly in the PLC.

Part 5 Maintenance and Overhaul


(1) Regular check
● Whether there are short-lived consumables in the programmable controller.
● For the relay output type, if the output relay operates at abnormally high frequency or drives a lar
ge-capacity load, attention must be paid to its impact on the service life.
● Check with other equipment, please pay attention to the following points.
●Whether there any abnormal rise in temperature inside the machine due to other heating elemen

ts or direct sunlight.
●Whether there is dust or conductive dust intruding into the machine.

●Whether there are any loose wiring and terminals and other abnormalities.

2
LX3 Series User Manual V2.0

Part 6 Module & Product specification

IN

LX 3 V - 2 41 6 MR PWR RUN BAT ERR

OUT

① Mounting hole ⑧ Cover


② Input blocks ⑨ Programming Port COM1(Standard)
③ Output blocks ⑩ RUN/ STOP
④ Output display ⑪ COM2 (Optional)
⑤ Input display ⑫ Socket for additional module
⑥ Power LED ⑬ USB download port
Run LED ⑭ Socket for BD module
Error LED ⑮ Button battery (under the BD module)
⑦ DIN pin installation joint

Part 7 Communication Interface


The LX3V series PLC has two communication port, supporting RS422 (standard) and RS485 (optional).
Pin out of COM1 and COM2
COM1
programming port Pin Signal Description
1 RXD- Received data (negative)
2 RXD+ Received data (positive)
1 2
3 4 5 3 GND Signal ground
6 7 8 4 TXD- Transmitted data (negative)
COM1
5 NC Empty
(Rs422 and RS485 in this (RS 422 standard)
port can’ t be used at the
6 NC Empty
same time) 7 TXD+ Transmitted data (positive)
8 NC Empty
Pin Signal Description
COM1/COM2
A+ 485+ Received data (positive)
(RS 485 optional)
B-
B
485- Received data (negative)

3
LX3 Series User Manual V2.0

② The models of LX3V-0806MX and LX3V-1208MX has RS485 communication port.

COM 2 RS 485 PIN

0 1 2 3
485A
4 5

10 11 12 13
6 7
485B
PWR RUN

BAT ERR

0 1 2 3

4 5 6 7

LX3V-20MX 10 11 12 13

485A
485B
PIN Signal Description
485A 485+ 485+
485B 485- 485-

Part 8 Model

Basic unit

1:1S instruction
2:2N instruction
Default:2N instruction
Output
R: relay A:AC220V
T: transistor D:DC24V

Part 9 Electrical Specification


AC Power Supply
LX3V/ LX3VP/ LX3VE/ LX3VM LX3V/ LX3VP/ LX3VE/ LX3VM
Model
26 points and below above 26 points
Rated voltage AC 100V ~ 240V
Voltage range AC 85V ~ 264V
Rated frequency 50/60HZ
Power outage time continue to work with less than 10ms power outage time
Power fuse 250V 1A 250V 3.15A
Impulse current <20A 5ms/AC100V
Power (W) 20W 50W
Sensor power supply DC 24V 700mA

DC Power Supply

Model LX3V/ LX3VP/ LX3VE/ LX3VM


Rated voltage DC 24V
Voltage range DC 24V±10%
Power fuse 250V 3.15A
Impulse current < 15A 1 ms/AC100V
Power (W) <30W

4
LX3 Series User Manual V2.0

Part 10 Environmental Specifications


Temperature Using:0~55℃ Saving: -20~70℃
Humidity 35~85%RH (no condensation)
JISC0040 standards
Frequency Acceleration Amplitude
DIN rail 10~57Hz -- 0.035mm 10 times of X, Y, Z
Resistance
installed 57~150Hz 4.9m/S2 -- (80 minutes from
to vibration
Directly 10~57Hz -- 0.075mm every direction)
installed 57~150Hz 9.8m/S 2
--
Impact
JISC0041 standard
resistance
Voltage
AC1500V (1 minute)
resistance Confirm with
Insulation JEM- 1021
DC500V is more than 5MΩ
resistance

Grounding

Environment No corrosive gas, combustible gas, or electrical dust.

Part 11 Input Specifications


Model LX3V/ LX3VP/ LX3VE/ LX3VM
Power supply AC power supply, DC output
Input single voltage DC24V ±10%
Input single current 7mA/DC24V (X002 or later, 5mA/DC24V)
Input ON current 4.5mA or more (behind X002, 3.5mA/DC24V)
Input OFF current Less than 1.5mA
About 10ms
Input responding time X000-X005 change D8020 into 0-15ms by the x built-in digital filter
inside
Input single type Contact input or NPN, PNP Open electrode transistor input
Insulated return Optocoupler insulation
Input status When input is on, LED is on

5
LX3 Series User Manual V2.0

24 V
+

S/ S

The picture is NPN connection,


Input circuit if S / S connection 24V negative,
7m A
components X then Positive, namely PNP
connection.

5m A

Part 12 Output Specifications


Model LX3V/ LX3VP/ LX3VE/ LX3VM
Output type Relay Transistor

Load Load

Output circuit
components
Programmable Programmable
External Controllers Controllers
External
power supply
power supply

Power supply Less than AC250V/DC30V DC5~30V


Loop insolation Mechanical insulation Photoelectric coupling insulation
LED lights up when the The LED lights up when the
Action
relay coil is energized optocoupler is driven
0.5A/point, 0.8A/4points,
Resistive 2A/point, 8A/COMx port
Max 0.3A/point (Y0, Y1)
load Inductive 80VA 12W/DC24V, 7.2W/DC24V(Y0,Y1)
General 100W 0.9W/DC24V, 0.9W/DC24V(Y0,Y1)
Leak current -- 0 .1mA/DC30V
Min load DC5V 2mA (reference) --
Response ON About 10ms Less than 0.2ms, 5μs (Y0, Y1)
time OFF About 10ms Less than 0.2ms, 5μs (Y0, Y1)
Out single mode -- NPN mode

Output Circuit Constitutions


●Please put the perceptual load and dc fly-wheel diode in parallel, otherwise it will significantly
reduce the service life of contact.
Reverse voltage of Fly-wheel diode is 5-10 times bigger than the load voltage, positive current
value is higher than load current.

6
LX3 Series User Manual V2.0

DC inductive load
Loa d

output ' s contact of


programmable controller Fly - wheel diode

●If this is AC inductive load, make load and surge absorber in parallel, the noise can be reduced.

AC inductive load
Load

output ' s contact of


programmable controller
surge absorber

●The output contacts of the programmable control are best to use on the same phase side.

in-
phase

●If forward and reverse contactors are close at the same time, it would be very dangerous, like this
load, except to use internal program to do interlock control, on the outside of the programmable
controller must also set the interlock.

interlock
Forward limit
interlock Forward

Reverse limit
Reverse
Warning
output ' s contact of
programmable controller

Part 13 Terminal
Pin LX3V/LX3VP/LX3VE/LX3VM series
L/N AC 100V~240V
24V+/COM Output +24V
Grounding
The empty post, never be connected
Support leakage input (connected to 24V+) or source
S/S
input (connected to COM).
X0-Xn External input terminal
Y0-Yn, COMn Output terminal, Group number

7
LX3 Series User Manual V2.0

Part 14 Installation
Directly installed on the DIN46277 (width 35mm) guide rail. When removing the main unit, gently
pull out the IN rail mounting clip from below.
W

W1

L X 3 V - 1 61 6 M R IN

P WR R UN B AT E RR

99
90
OUT

2 4.5
mounting hole

Use the M4 screw to install the PLC. The distance and the location refer to the right figure.
Model W(mm) W1(mm)
87
LX3V/LX3VP/LX3VE/LX3VM-0806MX 75 61
LX3V/LX3VP/LX3VE/LX3VM-1208MX 75 61
Din rail
LX3V/LX3VP/LX3VE/LX3VM-1212MX 136 123 (35mm)
LX3V/LX3VP/LX3VE/LX3VM-1410MX 136 123
LX3V/LX3VP/LX3VE/LX3VM-1412MX 136 123
LX3V/LX3VP/LX3VE/LX3VM-1616MX 175 161
LX3V/LX3VP/LX3VE/LX3VM-2416MX 175 161
LX3V/LX3VP/LX3VE/LX3VM-2424MX 221 207
LX3V/LX3VP/LX3VE/LX3VM-3624MX 221 207

Part 15 Battery Installation Instructions

1 2 3 4

8
LX3 Series User Manual V2.0

Part 16 The arrangement of terminal for LX3V series


The type of relay and transistor have the same arrangement of terminal. (*The bold line is the
boundary of each group)
<LX3V-0806MX-A>(※Note1)
<LX3V-0806MX-D>(※Note2)
S/S X1 X3 X5 X7
L N X0 X2 X4 X6

COM Y0 COM1 Y3 Y4 485A


24V+ COM0 Y1 Y2 COM2 Y5 485B

<LX3V/LX3VP-1208MX-A>(※Note1)
<LX3V/LX3VP-1208MX-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13
L N X0 X2 X4 X6 X10 X12

COM Y0 COM1 Y3 Y4 Y6 485A


24V+ COM0 Y1 Y2 COM2 Y5 Y7 485B

<LX3V/LX3VP-1212MX-A>(※Note1)
<LX3V/LX3VP-1212MX-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13
L N X0 X2 X4 X6 X10 X12

COM Y0 COM1 Y3 Y4 Y6 COM3 Y11 Y13


24V+ COM0 Y1 Y2 COM2 Y5 Y7 Y10 Y12

<LX3V/LX3VP/LX3VE/LX3VM-1412MX-A>(※Note1)
<LX3V/LX3VP/LX3VE/LX3VM-1412MX-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13 X15
L N X0 X2 X4 X6 X10 X12 X14

COM Y0 COM1 Y3 Y4 Y6 COM3 Y11 Y13


24V+ COM0 Y1 Y2 COM2 Y5 Y7 Y10 Y12

<LX3V/LX3VP/LX3VE/LX3VM-1616MX-A>(※Note1)
<LX3V/LX3VP/LX3VE/LX3VM-1616MX-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13 X15 X17
L N X0 X2 X4 X6 X10 X12 X14 X16

24V+ COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17

<LX3V/LX3VP/LX3VE/LX3VM-2416MX-A>(※Note1)
<LX3V/LX3VP/LX3VE/LX3VM-2416MX-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
L N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26

24V+ COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17

<LX3V/LX3VP/LX3VE/LX3VM-2424MR-A>(※Note1)
<LX3V/LX3VP/LX3VE/LX3VM-2424MT-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
L N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26

24V+ COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 COM7

9
LX3 Series User Manual V2.0

<LX3V/LX3VP/LX3VE/LX3VM-3624MR-A>(※Note1)
<LX3V/LX3VP/LX3VE/LX3VM-3624MT-D>(※Note2)
S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43
L N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42

24V+ COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 COM7

※ Note1 :AC power type, the Land N terminal is power supply terminal, the COM and 24V+ is
transducer supply output.
※ Note2 :DC power type, the COM and 24V+ terminal is power supply terminal.

Notice
The contents of this manual are subject to
change without notice.
R Address: 10 Building, E area, Fuzhou
维控科技 Software park, Fujian, P. R. China ;
WECONTECHNOLOGY Tel: 0086-591-87868869 ;
Email: [email protected] ;
Wecon Technology Fu Zhou Web: www.we-con.com.cn/en ;

WECON_LX3_20230701