Heat Pumps On Roof Level (1: 100) : Fan Schedule

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES

1. ALL DUCTWORK TO BE MANUFACTURED FROM GALVANISED


SHEET METAL AND INSTALLED IN ACCORDANCE WITH SABS
BACK DRAFT DAMPER 1238 AND SABS 0173. DUCT SIZES INDICATE CLEAR INTERNAL
DIMENSION. ROUND DUCTING TO BE OF THE SPIRAL WOUND
TYPE UNLESS INDICATED OTHERWISE.
2. AIR CONDITIONED SUPPLY AIR DUCTING, INCLUDING FLEXIBLES,
TO BE EXTERNALLY INSULATED WITH 25mm FRK UNLESS
WL-1 OTHERWISE SHOWN. RETURN AIR DUCTING AND PLENUM BOXES TO
SVL-1 SVL-1 1860 L/s BE EXTERNALLY INSULATED. RETURN AIR FLEXIBLE DUCTING
WL-2 NEED NOT BE INSULATED AND IS TO BE SIZED AND ROUTED
6000 L/s 6000 L/s 1250x600
600x600 NOT TO EXCEED 10Pa PRESSURE DROP. EXPOSED SUPPLY AIR
2000x600 2000x600 DUCTING WITHIN THE CONDITIONED SPACE NEED NOT BE
INSULATED UNLESS SPECIFICALLY REQUESTED. ALL
1 INSULATION IS TO TO BE INSTALLED IN ACCORDANCE WITH SABS
1238. EXTERNAL DUCTWORK SHALL BE INSULATED, USING 25mm
THICK RIGID PREFORMED POLY-ISOCYNURATE (PIC) SECTIONS
RC RC HAVING A DENSITY OF 32Kg/m, AND SHALL BE FINISHED WITH TWO
F-1 COATS OF POLYESTER RESIN REINFORCED WITH 300g
EXISTING FAN ASSEMBLY, BUT WITH TG-1 FIBREGLASS CHOPSTRAND. THIS SHALL BE SANDED SMOOTH
NEW TRANSFER PIECE AND SVF-1 SVF-1 AND COATED WITH RESIN RICH TOPCOAT PIGMENTED TO THE
COLOUR AS SPECIFIED. THE INSULATION SHALL BE INSTALLED SO
WEATHER LOUVRE AS TO PREVENT WATER PONDING ON TOP OF DUCTING.
ATT-1 3. FLEXIBLE DUCTING TO HAVE A CLASS 1 FIRE RATING
COMPLYING WITH SABS 0177 PART 3, TO BE EUROFLEX OR
CC-1.1 TG-1 TG-1 EQUAL, AND TO BE MORE THAN 1,5m IN LENGTH. ENDS ARE
TG-1 TG-1 TO BE SEALED AND FIXED WITH JUBILEE TYPE CLAMPS.
4. DAMPERS ARE TO BE OF THE OPPOSED BLADE TYPE AND FITTED
SAD-1 SF-1 THIS SPACE IS A RETAIL SHOP (F2) WITH A MANUAL LOCKING QUADRANT. ROUND DUCT DAMPERS
Ø200 ARE TO BE OF THE UNITEX TYPE WITH LOCKING QUADRANTS.
AND DOES NOT FORM PART OF THIS 5. FILTERS FOR FRESH AIR DIRECT FROM THE OUTSIDE ARE TO BE OF
SUBMISSION THE WP77 WASHABLE PANEL TYPE, 50mm THICK, HOUSED IN EASILY
ATT-1
SAD-2 CC-2.1 CC-2.2 SAD-2 1 ACCESIBLE FILTER FRAME. RETURN AIR FILTERS AND FILTERS FOR
FRESH AIR ARE TO BE OF WASHABLE MATT TYPE HOUSED IN A
MOVE EXISITNG TOILET EXTRACTION Ø200 250x300 Ø250 Ø250 SUITABLE FRAME. TEMPORARY FILTERS ARE TO BE USED DURING
TESTING. A SPARE SET OF FILTERS IS TO BE SUPPLIED AT
DUCT TO THE LEFT HAND SIDE OF REF PIPING TO OUTDOOR UNITS ON HANDOVER.
THE ROOM TO MAKE SPACE FOR ROOF REVEL 6. ALL GRILLES, DIFFUSERS AND LOUVRES ARE TO BE AS SET
OUT IN THE SCHEDULES OR EQUAL AND APPROVED. RETURN
NEW SMOKE EXTRACTION.

Ø250

Ø250
Ø200
AIR GRILLES TO BE DUCTED HIDEAWAYS ARE TO BE FITTED
2 WITH PLENUM BOXES WHERE SHOWN THAT ARE SUITABLY
SIZED TO ACCOMODATE THE FLEXIBLE DUCT CONNECTION TO
TG-1 THE AC UNIT AND ALLOW FREE FLOW IF DISC VALVES ARE
TO BE USED IN LIEU OF EXTRACT GRILLES, THESE ARE TO BE

850x300
OF THE STEEL TYPE NO SMALLER THAN 150mm DIAMETER.
U/C U/C
7. SOUND AND VIBRATION DEADENING EQUIPMENT IS TO BE PROVIDED
EXISTING MECHANICAL VENTILATION SAD-1 WHERE INDICATED AND/OR REQUIRED. ALL OUTDOOR SPLIT
400x300 250x300 AND VRV UNITS ARE TO BE ISOLATED FROM THE STRUCTURE BY
IN TOILETS. Ø200 TICO PADS. THOSE MOUNTED ON THE GROUND ARE TO BE
BOLTED TO 300x300 PAVING SLABS OR LOCATED ON SUITABLE AND
SIZED CONCRETE PLINTHS AND THOSE MOUNTED ON WALLS, TO BE
ADD BURGULAR FIXED TO UNISTRUT BRACKETS. FLEXIBLE COLLARS ARE TO BE
TG-1 CC-1.2 TG-1 BARS BEHIND USED BETWEEN SUPPLY AIR DUCTING AND DUCTED HIDE-AWAY
LOUVRE UNITS WICH ARE TO BE ISOLATED FROM THE STRUCTURE BY
SAD-1 RUBBER MOUNTS. SMALL TUBE AND BOX FANS ARE TO BE ISOLATED
EXISTING MECHANICAL VENTILATION FROM STRUCTURE BY RUBBER MOUNTS AND FROM THE DUCTWORK

450x300
Ø200 HP-1 HP-2 BY ACOUSTIC FLEXIBLE DUCTING. ALL OTHER FANS ARE TO BE
IN MALE ABLUTIONS. MOUNTED ON SPRING MOUNTS AND ISOLATED FROM THE
2 8.
DUCTWORK BY FLEXIBLE COLLARS.
ALL HVAC EQUIPMENT AND DUCTING TO BE HUNG AS HIGH
WL-3 AS POSSIBLE, THE AC CONTRACTOR IS TO LIASE WITH THE
RC 1000x2500
OTHER TRADES ON SITE TO CO-ORDINATE WITH THE OTHER
300x300 Ø250 SERVICES.
9. CONDENSATE DRAINS TO BE TRAPPED AT AC INDOOR UNITS AND
RUN TO NEAREST FOUL SEWER OR CONNECTION POINT
REF PIPING TO FLOOR ABOVE. U/C U/C PROVIDED BY THE PLUMBER AT A FALL GREATER THAN
RC 3 1:80. CONDENSATE DRAINS FROM OUTDOOR UNITS TO BE RUN
TO NEAREST FULL-BORE. PIPING TO BE 40mm PVC WITH
RC CC-1.3 INSPECTION POINTS WHERE REQUIRED TO ENABLE ACCESS TO ALL
TG-1 TG-1
PH-30 CABLE FIRE Ø200 PIPEWORK FOR CLEANING. PIPING TO BE SUPPORTED AT 750mm

Ø250
CENTRES. ALL DRAINS TO BE TESTED PRIOR TO
RATED CABLE COMMISSIONING OF THE AIR CONDITIONING UNITS. HEAT
SV-3 MAKE-UP AIR ELECTRO-MECH PUMP TYPE UNITS ARE TO BE PROVIDED WITH DRAIN PANS
SAD-1 VENTILATOR. DIMENSIONS 1000mm X FOR THE OUTDOOR UNITS.
Ø200 2500mm. OPEN ON RECEIPT OF FIRE
10. REFRIGERATION PIPING TO BE RUN AS SHOWN ON CABLE TRAYS
SUPPORTED AT MAX 2000mm CENTRES. PIPE INSULATION TO BE
EXISTING MECHANICAL VENTILATION SIGNAL. EN 12101 CERTIFIED FOR ARMAFLEX AF, AT LEAST 13mm THICK, ON BOTH SUCTION AND
IN FEMALE ABLUTIONS. LIQUID LINES FOR HEAT PUMPS. ALL INSULATION JOINTS TO BE
CC-2.3 U/C U/C U/C SMOKE SYSTEMS. GLUED, TAPED AND SEALED. THE CABLE TRAY CARRYING THE
SAD-2 CC-2.4 SAD-2 REFRIGERATION PIPING IS TO BE FIXED AS HIGH AS POSSIBLE
Ø250 Ø250 UNDER THE HVAC DUCTING AND EQUIPMENT WITHOUT TOUCHING.
PIPEWORK EXPOSED TO THE ELEMENTS IS TO BE
PROTECTED BY GALVANISED STEEL COVERS. UNPROTECTED
RC CONNECTIONS TO THE OUTDOOR UNITS MAY NOT EXCEED
DRIP TRAY REQUIRED BELOW MW-1 MW-1 3 500mm AND MUST BE PROTECTED WITH CANVASS
WRAPPING COATED WITH FOSTER SEALFAS 30-36.
MIDWALLS. 11. ALL SUPPORT STEELWORK, INCLUDING HANGER RODS AND
TG-1 TG-1 TG-1 TG-1 BRACKETS MUST BE GALVANISED. STEELWORK EXPOSED TO THE
Ø150 DV-1 DV-1 Ø100 DV-1 ELEMENTS MUST BE HOT DIP GALVANISED AFTER ALL
FABRICATION WORK IS COMPLETE. FASTENERS ARE TO BE
GALVANISED AND WHERE EXPOSED TO THE ELEMENTS ARE TO BE
CONTROL PANEL FOR SMOKE STAINLESS STEEL. FIXING SCREWS FOR GRILLES AND
VENTILATIONS FANS (SVF-1). REQ = 4 LOUVRES ARE TO BE STAINLESS STEEL. ALL DISSIMILAR METALS
ARE TO BE GALVANICALLY ISOLATED FROM EACH OTHER BY NYLON
5.0 KW / 3* (RUN) SPACERS.
12. ALL EQUIPMENT, DUCTING AND PIPING EXPOSED TO THE
ELEMENTS TO BE PAINTED. ALL OUTDOOR UNIT COILS TO BE
TREATED AS PER SPECIFICATION.
E F G

HEAT PUMPS ON ROOF LEVEL ( 1: 100 )


THIS SPACE IS A COMBINATION OF
RETAIL SHOPS (F2) AND OFFICES
(G1) AND DOES NOT FORM PART OF
THIS SUBMISSION

5
2 LEGEND
22033- H - 001
ELECTRICAL ISOLATOR

O.B.D. - OPPOSED BLADE DAMPER

DOOR GRILLE

FRESH AIR PANEL FILTER

FLEXIBLE COLLAR

A B SOUND ATTENUATOR

DUFFUSER

FAN

CEILING CASSETTE AC UNIT


6
L2_Second Storey MID WALL SPLIT AC UNIT
L2_Soffit
L2_ Second Storey
16574
16375 DUCTED HIDE AWAY AC UNIT
15224
U/C UNDERCUT DOOR GRILLE BY 25MM

RC AIR CONDITIONING REMOTE CONTROL

REFRIGERANT PIPING
MW-1
L1_First Storey REMOTE WIRING
CONDENSATE PIPING
MW-1 13400 L1_Soffit
L1_First Storey
12975L0_Susp.12050
Ceiling
Ground Floor Ceiling
12400
11225

7 L0_Ground Storey
L0_Ground Storey
10000
8650
C 06/10/22 FOR COUNCIL APPROVAL MNS DU
No DATE DESCRIPTION DRW CHK
REVISION SCHEDULE
A B C D E F G
CONSULTING ENGINEER

ECSA 20160394 06/10/2022


GROUND FLOOR ( 1: 100 )
DIRK UYS PR ENG No DATE

CLIENT

FAN SCHEDULE
STATIC NORMAL / TIMERS SIGNATURE DATE
FAN DESCRIPTION MAKE / MODEL FLOW (L/S) PRESSURE (Pa) ACCESSORIES QTY POWER INPUT (RUN) EMERGENCY 07:00-18:00 FIRE INTERLOCK
SVF-1 SMOKE VENTILATION FAN AMS LCS0804GA3/2.4 6000 150 300° FOR 60 MIN EN 12101 CERTIFIED 2 2.4KW / 4.8A / 3* E N Y
SF-1 SUPPLY AIR FAN AMS APG05064AP10/.6 1860 220 VSD SPEED DRIVE 1 0.6 KW / 1.5A / 3* N Y Y
FOR COUNCIL APPROVAL
CONSULTANT
DIFFUSER AND GRILLE SCHEDULE
ITEM No DESCRIPTION MAKE OR SIM AP TYPE AND SIZE FLOW RATE (L/S) ACCESSORIES QTY
SVL-1 SMOKE VENTILATION LOUVRE EUROPAIR 2000 X 600 WL 6000 WM,EPC, BURGULAR BARS 2
WL-1 WEATHER LOUVRE EUROPAIR 1250 X 600 WL 1860 WM,EPC, BURGULAR BARS 1 SECTION 2-2 SHOWING MW-1
SAD-1 SUPPLY AIR DIFFUSER BRIAN RICKARD ⌀200 CCD 200 - 4 OUTDOOR UNITS BELOW CONCRETE Unit 8, First Floor, 16 Plein Street, Durbanville, 7550
DV-1 DISK VALVE EUROPAIR ⌀150 DVK 20 WHITE 3
STAIR ( 1: 100 ) www.fmwe.co.za | [email protected] | 084 5636 434
ATT-1 ATTENUATION AMS 900W X 600H X 1200L 1860 - 2
CLIENT
F-1 FILTER MACS PLEAT 1250 X 600 WP 1860 WASHABLE PLEATED FILTER + FILTER FRAME 1
TG-1 TRANSFER GRILLE EUROPAIR 1200 X 600 VARIES - 14
SAD-2 SUPPLY AIR DIFFUSER BRIAN RICKARD ⌀250 CCD 250 - 4
WL-2 WEATHER LOUVRE EUROPAIR 600 X 600 WL VARIES WM,EPC, BURGULAR BARS 1
WL-3 WEATHER LOUVRE EUROPAIR 1000 X 2500 WL 12000 WM,EPC 1
SV-3 SMOKE ELECTRO-MECHANICAL VENTILATOR EUROPAIR 1000 X 2500 12000 EN 12101 CERTIFIED, ELECTROMECHANICAL ACTUATOR 1

PROJECT
AIR-CONDITIONING INDOOR SCHEDULE
PROPOSED ADDITIONS AND
ITEM No DESCRIPTION MAKE/MODEL QTY POWER INPUT (RUN) NORMAL/EMERGENCY FIRE INTERLOCK ALTERATIONS TO AN EXISTING
MW-1 MIDWALL SAMSUNG AR18TSHZAWK 2 FROM OUTDOOR UNIT E Y BUILDING AT CURRO JEWEL CITY
CC-1.1 CEILING CASSETTE SAMSUNG AM112NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y ON ERF 1145 & 459, GAUTENG.
CC-1.2 CEILING CASSETTE SAMSUNG AM112NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y
CC-1.3 CEILING CASSETTE SAMSUNG AM112NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y
CC-2.1 CEILING CASSETTE SAMSUNG AM128NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y DRAWING DESCRIPTION
CC-2.2 CEILING CASSETTE SAMSUNG AM128NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y
C:\Temp\drawings\dwg imports\18005 - H - 002 - Rev 0.dwg

CC-2.3 CEILING CASSETTE SAMSUNG AM128NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y


CC-2.4 CEILING CASSETTE SAMSUNG AM128NN4DEH/EU 1 INDOOR = 0.1 KW/1* N Y
GROUND FLOOR, HVAC PLAN

AIR-CONDITIONING OUTDOOR SCHEDULE


ITEM No DESCRIPTION MAKE/MODEL QTY POWER INPUT (RUN) NORMAL/EMERGENCY FIRE INTERLOCK
DATE SCALE ORIGINAL SIZE
HP-1 VRV HEAT PUMP SAMSUNG AM140KXVAGH 1 12.0 KW / 3* N Y
HP-2 VRV HEAT PUMP SAMSUNG AM180KXVAGH 1 15.0 KW / 3* N Y 26/09/22 AS SHOWN A0
MW-1 MIDWALL SPLIT UNIT SAMSUNG AR18TSHZAWK 2 1.8KW / 1* E Y
DRAWING NUMBER REV
22033- H - 001 C