MMTC - Chiller Equipment Schedule - R0-10-08-2023
MMTC - Chiller Equipment Schedule - R0-10-08-2023
MMTC - Chiller Equipment Schedule - R0-10-08-2023
Project
Quantity (Nos)
COOLING
LOCATION
Min. COP
Working
CAPACITY
Standby
MAX. PR. MAX. PR. DROP
EWT LWT FLOW Fouling Factor EWT LWT FLOW Fouling Factor
Tag.No Compressor DROP (ft) / Mt Remarks
TR IPLV- (°F) (°F) GPM (h.ft2.F/BTU) Ft (°F) (°F) GPM (h.ft2.F/BTU) Ft
100% Load @
ASHRAE Path-
KW AHRI Condition (°C) (°C) M3 / Hr (m2.C/W) M (°C) (°C) M3 / Hr (m2.C/W) M
B
Centrifugal 600 56.80 42.8 1029 0.0005 20 89.0 99.0 1800 0.001 20
B1_WCC-
Magenetic Basement-1 4 3 1 6.5 9.21
01,02, 03 & 04
Compressor
2106 13.78 6.0 234 0.000088 6 31.67 37.22 409 0.000176 6
Notes:
1 The Chiller capacity must be minimum in terms of Cooling Capacity as given at site condition.
2 Refrigerant shall be R-134a / R-514a
3 Unless & otherwise specified / mentioned, all motors shall be suitable for 415V/3-Ph/50 Hz application
4 Chillers must be supplied with local Isolating Switches
5 Chillers must be fitted with Liquid Isolation Valve for each circuit.
6 Chillers must be factory fitted with flow limit switches for Condenser & Evaporator.
7 Chillers must be supplied with Spring type Vibration Isolators as part of OEM.
8 Vitcualic or Grooved Coupling must be provided for all Inlet / Outlet Water Nozzles
9 Max. permissible Sound pressure shall be 85dBA at 1.5-mt for Water-Cooled chiller, Necessary acoustic jacketing shall be considered for compressor.
10 The selected chillers shall be with VFD drive, Harmonic Filter must be provided.
11 Chillers must comply with Tender Specification as provided separately
723258422.xls / Chiller
Remarks
723258422.xls / Chiller
INPUT/OUTPUT / SOFTWARE SUMMARY FOR CHILLER PLANT OPTIMIZER (CPO)
Chiller isolation Motorized valves Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
7 4 4
On/Off command & status command and position feedback valves with all accessories.
Condenser Water Inlet Motorized valves Motorized Butterfly Valves with ACMV vendor shall provide butterfly
8 4 4
On/Off command & status On/Off command and position feedback valves with all accessories.
2 CDW Pump On/Off status 4 From Starter NO contact ACMV vendor to provide NO contact
Cooling Towers : There are 3 Nos Cooling Tower supplied along with
D Cooling Towers (3 W + 1 S) 4 VFD Starters by ACMV vendor
Location: Terrace
CT Inlet valve open / close command Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
9 8 8
and status command and position feedback valves with all accessories.
CT Outlet valve open / close command Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
10 8 8
and status command and position feedback valves with all accessories.
Spares 4 4 10 8 40
Note:
Temperature sensors, Bleed off sensors and necessary cabling shall be under ACMV vendor scope and captured in the Low side works BOQ.
Further to above I/O points, Chiller plant optimizer shall provide the following detials in the display from chiller.
1 Differential Pressure Temperature across chiller & header.
2 BTU meter In/Out temp & Flow rate in GPM
3 Individual chiller In/Out temp.
4 Chiller Average current, Line to line voltage, Total power, Power factor, & Frequency
5 COP of chiller & IKW/TR
6 VFD Speed & input Power
7 All chiller soft points to be integrated with CPO.
TECHNICAL DATA SHEET R0
Data must be furnished by tenderer along with offer complete with Annex-1A Annexure-1A
S/No. Description Requirement
S/No. Water cooled Chilling Machine Equipment
1 Unit information / Make
1.01 Country of Origin
1.02 Model No.
1.03 Chiller Certification AHRI / Eurovent
1.04 Nominal Cooling Capacity – at AHRI condition TR/ KW
1.05 No. of compressors per machine (Minimum-2) Nos
1.06 Leaving Water Temperature °C / °F
1.07 Operating Condensing Temperature °C / °F
1.08 Compressor Suction Temperature °C / °F
1.09 Capacity at Design Operating Conditions TR / KW
1.10 Overall Dimension – L x W x H Mt
1.11 Overall Weight Kg
1.12 Operating Refrigerant Charge Kg
1.13 Noise Level at 1.0 Metre from the Unit dB
2 Compressor(s)
2.01 Compressor Type:
2.02 Construction (hermetic/semi hermetic)
2.03 Manufacturer’s Name and Model
2.04 Refrigerant R-134a / R-514a