MMTC - Chiller Equipment Schedule - R0-10-08-2023

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 8

SCHEDULE OF CHILLERS FOR HVAC

Project

COOLER / EVAPORATOR DATA CONDENSER DATA

Quantity (Nos)
COOLING

LOCATION
Min. COP

Working
CAPACITY

Standby
MAX. PR. MAX. PR. DROP
EWT LWT FLOW Fouling Factor EWT LWT FLOW Fouling Factor
Tag.No Compressor DROP (ft) / Mt Remarks
TR IPLV- (°F) (°F) GPM (h.ft2.F/BTU) Ft (°F) (°F) GPM (h.ft2.F/BTU) Ft
100% Load @
ASHRAE Path-
KW AHRI Condition (°C) (°C) M3 / Hr (m2.C/W) M (°C) (°C) M3 / Hr (m2.C/W) M
B

WATER- COOLED CENTRIFUGAL MAGNETIC CHILLER WITH VFD

Centrifugal 600 56.80 42.8 1029 0.0005 20 89.0 99.0 1800 0.001 20
B1_WCC-
Magenetic Basement-1 4 3 1 6.5 9.21
01,02, 03 & 04
Compressor
2106 13.78 6.0 234 0.000088 6 31.67 37.22 409 0.000176 6

Notes:
1 The Chiller capacity must be minimum in terms of Cooling Capacity as given at site condition.
2 Refrigerant shall be R-134a / R-514a
3 Unless & otherwise specified / mentioned, all motors shall be suitable for 415V/3-Ph/50 Hz application
4 Chillers must be supplied with local Isolating Switches
5 Chillers must be fitted with Liquid Isolation Valve for each circuit.
6 Chillers must be factory fitted with flow limit switches for Condenser & Evaporator.
7 Chillers must be supplied with Spring type Vibration Isolators as part of OEM.
8 Vitcualic or Grooved Coupling must be provided for all Inlet / Outlet Water Nozzles
9 Max. permissible Sound pressure shall be 85dBA at 1.5-mt for Water-Cooled chiller, Necessary acoustic jacketing shall be considered for compressor.
10 The selected chillers shall be with VFD drive, Harmonic Filter must be provided.
11 Chillers must comply with Tender Specification as provided separately

723258422.xls / Chiller
Remarks

723258422.xls / Chiller
INPUT/OUTPUT / SOFTWARE SUMMARY FOR CHILLER PLANT OPTIMIZER (CPO)

S/N Description Qty. AI AO DI DO SW Requirement Remarks 3C S

Chiller Plant Optimizer

Location of DDC Panel : Plant Room


@ Basement Floor

A Water Cooled Chillers : 4


3-Working + 1 Standby
Command from BMS PC / DDC to the
1 Chiller On/Off command 4
Chiller microprocessor panel
Chiller Vendor Shall provide the
2 Chiller On/Off status 4 signal from potential free contact. SMS/Email alert module to trigger the
SMS alert in case of trip.
3 Chiller trip status 4 signal from potential free contact.
4 Chiller Auto / Manual status 4 signal from A/M switch
Common chilled water supply / return Chiller vendor shall provide the Temp
5 2 Immersion type temp sensor
header temperatures Sensors
Since chiller manufacturer provides
Individual Chiller Inlet / Outlet
6 Immersion type temp sensor built-in in & out temperatures, this is
Temperature
not required.

Chiller isolation Motorized valves Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
7 4 4
On/Off command & status command and position feedback valves with all accessories.

Condenser Water Inlet Motorized valves Motorized Butterfly Valves with ACMV vendor shall provide butterfly
8 4 4
On/Off command & status On/Off command and position feedback valves with all accessories.

ACMV vendor shall provide flow meter


9 Flow Meter status 4 Flow Meter On/Off status and feedback
with all accessories.

CPO communicates to Pump Logic


Primary Chilled Water Pumps : There Controller (PLC) for readyness (about
PLC supplied by Pump vendor along
B are 3 Nos Chilled Water pumps (3W + 4 4 4 to start) and PLC starts pump based on
with VFD.
1F) with VFD run hour logic. PLC also confirm pump
run / status feed back to CPO

1 AHSRAE Bacnet Communication


2 Header Flow
3 VFD Speed of Chilled Water Pumps 16 ###
4 Other Soft points from PLC 40

Condenser Water Pumps : There are 3 VFD Starters by ACMV vendor


C Nos Condenser Water pumps (3W + 4 Split CPO (IP-65) panel shall be
1F) with VFD provided at Terace level.

ACMV vendor to make electrical


Command from PC / DDC to the provision in the pump panel to execute
1 CDW Pump On/Off command 4
Condenser pumps panel ON/OFF Command for remote
operation

2 CDW Pump On/Off status 4 From Starter NO contact ACMV vendor to provide NO contact

ACMV vendor to provide potential free


3 CDW Pump Auto / Manual status 4 Signal from A/M switch contacts in the pump panel to indicate
A/M selection made in the pump panel

ACMV vendor to provide potential free


4 CDW Pump trip status 4 Signal from potential free contact contacts in the pump panel to indicate
pump trip status (SMS alert).
CDW Pump VFD Speed control and
5 4 4 VFD Panel
feedback

Cooling Towers : There are 3 Nos Cooling Tower supplied along with
D Cooling Towers (3 W + 1 S) 4 VFD Starters by ACMV vendor
Location: Terrace

ACMV vendor to make electrical


Command from PC / DDC to the C.T provision in the starter panel to execute
1 CT fan On/Off command 12
Fan panel ON/OFF Command for remote
operation
ACMV vendor to provide potential free
Through MCC Panel potential free
2 CT fan On/Off status 12 contacts in the starter panel to indicate
contact
ON/OFF status
ACMV vendor to provide potential free
3 CT fan Auto / Manual status 12 Signal from A/M switch contacts in the starter panel to indicate
A/M selection made in the pump panel

ACMV vendor to provide potential free


4 CT Fan Trip Status 12 Signal from potential free contact contacts in the starter panel to indicate
pump trip status (SMS alert)

5 CT Outlet temperature 1 Immersion type temp sensor


Chiller vendor shall provide the
Sensors. The control of the fan speed
with PID loop between the WB Temp &
WB Temp Sensor / Temperature & RH the Approach Temp. Also low Temp
6 Ambient WB Temp. 1 Limit as per the chiller Vendor
Sensor
CT Fan VFD Speed control and
7 12 12 Main MCC Panel
feedback
Chiller Vendor to Provide and install
Condenser Circuit common Supply &
8 2 Immersion type temp sensor immersion type temperature sensor with
Return header temperatures
all accessories.

CT Inlet valve open / close command Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
9 8 8
and status command and position feedback valves with all accessories.

CT Outlet valve open / close command Motorized Butterfly Valves with On/Off ACMV vendor shall provide butterfly
10 8 8
and status command and position feedback valves with all accessories.

Chiller Manufacturer to provide SW


E Chiller Diagnostic Points 4 180
as per tender specification.

AHSRAE Bacnet Communication

Spares 4 4 10 8 40

Total I/O for Chiller Plant Manager 30 20 98 56 276

Note:

Temperature sensors, Bleed off sensors and necessary cabling shall be under ACMV vendor scope and captured in the Low side works BOQ.
Further to above I/O points, Chiller plant optimizer shall provide the following detials in the display from chiller.
1 Differential Pressure Temperature across chiller & header.
2 BTU meter In/Out temp & Flow rate in GPM
3 Individual chiller In/Out temp.
4 Chiller Average current, Line to line voltage, Total power, Power factor, & Frequency
5 COP of chiller & IKW/TR
6 VFD Speed & input Power
7 All chiller soft points to be integrated with CPO.
TECHNICAL DATA SHEET R0
Data must be furnished by tenderer along with offer complete with Annex-1A Annexure-1A
S/No. Description Requirement
S/No. Water cooled Chilling Machine Equipment
1 Unit information / Make
1.01 Country of Origin
1.02 Model No.
1.03 Chiller Certification AHRI / Eurovent
1.04 Nominal Cooling Capacity – at AHRI condition TR/ KW
1.05 No. of compressors per machine (Minimum-2) Nos
1.06 Leaving Water Temperature °C / °F
1.07 Operating Condensing Temperature °C / °F
1.08 Compressor Suction Temperature °C / °F
1.09 Capacity at Design Operating Conditions TR / KW
1.10 Overall Dimension – L x W x H Mt
1.11 Overall Weight Kg
1.12 Operating Refrigerant Charge Kg
1.13 Noise Level at 1.0 Metre from the Unit dB
2 Compressor(s)
2.01 Compressor Type:
2.02 Construction (hermetic/semi hermetic)
2.03 Manufacturer’s Name and Model
2.04 Refrigerant R-134a / R-514a

2.05 Cylinder/Screw data


2.06 Speeds (Operating/Max.) RPM
2.07 Operating condensing and suction temperatures °C / °F
2.08 Capacity at Design conditions TR/kw
2.09 KW at operating conditions KW
2.10 Motor losses %
2.11 Other losses if any %
2.12 Motor intake power Kw
2.13 KW per TR at operating conditions 100% KW/TR
2.14 Capacity control – Range %
2.15 No. of steps of capacity control
3 Capacities and COP & KW/TR as per ARI COP IKW/ TR
condition
3.01 At !00% Capacity or Loading Condition
3.02 At IPLV Condition
3.03 At NPLV (Refer detail sheet as attached & fill up
chart at part load & various outdoor conditions)
3.04 Min COP at AHRI condition at full load as per leed
4 Motors
4.01 Manufacturer’s Name
4.02 Motor KW KW
4.03 Rated current Amps
4.04 Motor efficiency %
4.05 Starting current with type of starter offered Amps
4.06 Model / Frame size
5 Starter (VFD)
5.01 Type VFD
5.02 Make
5.03 Model no.
5.04 Quantity- Nos.
5.05 VFD Rating - Kw.
5.06 Rated Current - Amps.
5.07 Maximum Output - Kw.
5.08 PID Controller provided (Yes / No)
5.09 Interface with BAS
5.10 Fault Indication
5.11 Dimension (mm)
5.12 No. of Steps
5.13 Operating Weight-(Static)-Kg
5.14 Communication Protocal
5.15 Whether single phasing preventer included
5.16 Whether over load relay included
6 Drive
6.01 Type of drive
6.02 Any special requirements
7 Condensers ( Water Cooled)
7.01 Manufacturer’s Name
7.02 Dimensions – L x B x H mm or Dia x Length MM
7.03 Fan Motor ratings kW
7.04 Fan Noise level dB
7.05 No of Fans per Chiller Nos
7.06 Discharge temperature - °C ºC / ºF
7.07 No. of fins / inch in the Condenser coil fns/inch
7.08 Minimum condenser water flow rate CMH / USGPM
7.09 Maximum pressure drop through Condenser MWC / FTWC
7.10 Entering condenser water temperature ºC / ºF
7.11 Leaving condenser water temperature ºC / ºF
7.12 Fouling factor for condenser
7.13
8 Evaporator or Cooler
8.01 Type of Chiller (DX or flooded)
8.02 Shell OD – mm MM
8.03 Overall length – mm MM
8.04 Overall weight – Kg. Kg
8.05 No. of tubes Nos
8.06 Tube OD – mm MM
8.07 Nature of tubes (whether integrally finned or tubes
carry inserts)
8.08 Length of tube between tube sheets - mm MM
8.09 Material of tube
8.10 Material of shell
8.11 Water side surface area . Sq.Mt.
8.12 Refrigerant side surface area Sq.Mt
8.13 Flow rate – Lpm / Gpm LPM/GPM
8.14 Entering water temperature ºC / ºF
8.15 Refrigerant temperature ºC / ºF
8.16 Temperature difference ºC / ºF
8.17 No. of passes Nos
8.18 Tube velocity MPS/FPS
8.19 Pressure drop – Water column Ft. / Mt
9 CPO
9.01 Type
9.02 Make
9.03 Model no.
9.04 Units Communication
9.05 ON/OFF COMMAND
9.06 GROUP SEQUENCING MANAGEMENT
9.07 WEEKLY/HOURLY CHILLER ROTATION
9.08 CRITICAL FAULTS
9.09 ALARMS