0% found this document useful (0 votes)
51 views2 pages

FX Idc1b Kidde Manual Instalacion

The FX-IDC1B Analog Single Input Mini Module is used to connect dry contact initiating devices like alarms to a fire control panel. It operates as an alarm-latching device, sending an alarm signal to the panel when the initiating device contact is closed. The module address is set using two rotary switches and it provides status LEDs visible from the back. It is installed by making wiring connections according to the diagram and setting the address.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views2 pages

FX Idc1b Kidde Manual Instalacion

The FX-IDC1B Analog Single Input Mini Module is used to connect dry contact initiating devices like alarms to a fire control panel. It operates as an alarm-latching device, sending an alarm signal to the panel when the initiating device contact is closed. The module address is set using two rotary switches and it provides status LEDs visible from the back. It is installed by making wiring connections according to the diagram and setting the address.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Figure 1: LED location

FX-IDC1B Analog Single Input


Mini Module Installation Sheet

Operation
The FX-IDC1B Analog Single Input Mini Module is an analog
addressable device used to connect a normally open, alarm,
supervisory, or monitor type dry contact initiating device circuit (IDC) to
a control panel. This module is designed for Class B circuit operation.
The device address is set using the two rotary switches located on the 1 2
front of the module. One device address is required.
1. Red LED: Alarm/active 2. Green LED: Normal
The module is factory set to operate as an alarm-latching device.
When the NO contact of an initiating device is closed, an alarm signal Figure 2: Module address
is sent to the control panel and the alarm condition is latched at the
1
module.
Additional device types are available through front panel programming
or the configuration utility. For additional information, refer to the
documents listed on the control panel label. 5 6 7 89 3
4 5
6
4
3 10 2 7
LEDs 2 11 1 8
1 0 12 0 9
The FX-IDC1B provides two status LEDs. The LEDs are visible from
the back of the module.
1. Insert screwdriver here

Installation Wiring
Install and wire this device in accordance with applicable national and
Wire the device as shown in Figure 3. Be sure to observe the polarity
local codes, ordinances, and regulations.
of the wires.
WARNINGS All wiring is power-limited and supervised.
• This module does not operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards
with the local fire protection specialist.
• This module does not support conventional two-wire smoke
detectors.

Note: The module is shipped from the factory as an assembled unit; it


contains no user-serviceable parts and should not be disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground
faults.
2. Make all wiring connections as discussed in “Wiring” and shown in
Figure 3.
3. Set the module address. Refer to the panel technical reference
manual for a list of valid addresses.
Use a screwdriver to adjust the two rotary switches on the front of
the module. Set the TENS rotary switch (0 through 12) for the 10s
and 100s digit and the ONES rotary switch for the 0 through 9
digit. For example: device address 21, set TENS rotary switch to 2
and set the ONES rotary switch to 1 (see Figure 2).
4. Position the module into the electrical box, behind the device to
which it connects.

P/N 3101081-EN • REV 006 • ISS 22SEP17 1/2


Figure 3: Module wiring

2 3

SLC_OUT – BK ( ) IDC –
5 6 7 89 3
4 5
4 6
7
YE 47 k 
3 10 2
SLC_OUT + 2 11 1 8 OG EOL
1 0 12 0 9
RD (+) IDC +
SLC_IN –
SLC_IN +
4

1 Class A or Class B

1. Refer to the control panel technical reference manual for wiring


specifications
2. Wire nut or other listed splice or terminal block
3. Style B (Class B)
4. Typical NO initiating device

Specifications

Voltage
IDC maximum 10 VDC at 350 µA
Communication line 20.6 V peak-to-peak
maximum
Current
Standby 350 µA
Activated 500 µA

Ground fault impedance 10 kΩ


Initiating device circuit (IDC)
EOL resistor value 47 kΩ, (P/N EOL-47)
Circuit resistance 50 Ω (25 Ω per wire), max.
Circuit capacitance 0.1 µF, max.
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93%, noncondensing at
90°F (32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)

Contact information
For contact information, see www.kiddelifesafety.com
© 2017 Walter Kidde Portable Equipment, Inc.
All rights reserved.

2/2 P/N 3101081-EN • REV 006 • ISS 22SEP17

You might also like