0% found this document useful (0 votes)
1K views3 pages

Transformer Core Design

The document describes the design of a 25 kVA, 3-phase, core type distribution transformer with an 11000/433 V rating and 50 Hz frequency. The design calculations determine the core dimensions, window dimensions, yoke dimensions and frame dimensions based on the transformer rating and design parameters. The core is designed with a flux density of 1.0 Tesla and the dimensions are approximated and displayed.

Uploaded by

Amit Dipankar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views3 pages

Transformer Core Design

The document describes the design of a 25 kVA, 3-phase, core type distribution transformer with an 11000/433 V rating and 50 Hz frequency. The design calculations determine the core dimensions, window dimensions, yoke dimensions and frame dimensions based on the transformer rating and design parameters. The core is designed with a flux density of 1.0 Tesla and the dimensions are approximated and displayed.

Uploaded by

Amit Dipankar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

%Design a 25 kVA, 11000/433 V, 50 Hz, 3 phase, delta/star, core type, oil

%immersed natural cooled distribution transformer. The transformer is


%provided with tapping ±2 1/2 ±5 % on the HV winding. Maximum temperature
%not to exceed 450 C with mean temperature rise of oil 350C.

%%%%%%%%%%%%%%%%%%%%%%% DESIGN OF TRANSFORMER CORE %%%%%%%%%%%%%%%%%%%%%%

clc
clear all
%Initialization of known parameters
Q=25; %kVA rating of transformer
kV=11; %kV rating of transformer
f=50; %Rated frequency in Hz

%Code for window design


K=0.45; %(For a 3-phase core type distribution transformer)
Et=K*sqrt(Q); %Voltage per turn
fluxMAX=Et/(4.44*f); %Maximum Flux in Webers
B=1.0; %Assumed flux density in Tesla
Ai=fluxMAX/B; %Net Core Area in m^2
Ki=0.9; %Stacking Factor
Agi=Ai/Ki; %Gross Core Area in m^2
Kc=0.56; %(For crcuciform core)
d=sqrt(Ai/Kc); %Diameter of the circumscribing circle %%Ceil
a=0.85*d; %Lamination-length in m
b=0.53*d; %Lamination-width in m
Kw=8/(30+kV); %%Window space factor
Kw=0.75*Kw;
J=2.3; %Current density in A/mm^2(For oil immersed natural
cooling)
Aw=Q*10^3/(3.33*f*Kw*B*Ai*J); %Window Area
Ww=sqrt(Aw/2.5); %Window-width in mm
Hw=2.5*Ww; %Window-Height in mm

%Code for yoke design


Agy=Agi*1.2; %Gross Yoke Area in m^2
Ay=Ai*1.2; %Net Yoke Area in m^2
By=B/1.2; %Flux density in yoke in T
Wy=a; %Yoke-width in m
Hy=Agy/a; %Yoke-height in m

%Code for frame design


Hf=Hw/1000+2*Hy; %Frame-width in m
Wf=2*Ww/1000+3*a; %Frame-height in m

%Approximation of theoretical dimensions


a=round(1000*a);
b=round(1000*b);
d=round(1000*d);
Ww=ceil(1*Ww);
Hw=ceil(1*Hw);
Wy=ceil(1000*Wy);

1
Hy=ceil(1000*Hy);
Wf=ceil(1000*Wf);%Frame width in mm
Hf=ceil(1000*Hf);%Frame height in mm

%Code for display of outputs


fprintf("Transformer rating in KVA: %5.2f kVA\n", Q);
fprintf("Rated frequency : %d Hz\n", f);
fprintf("K for core typedistribution transformer : %5.2f\n", K);
fprintf("Voltage per turn : %5.3f V\n", Et);
fprintf("Max flux in the core : %5.5f Wb\n", fluxMAX);
fprintf("Assummed flux density : %5.3f T\n", B);
fprintf("Net core area : %5.2f mm^2\n", Ai*10^6);
fprintf("Stacking factor : %5.1f\n", Ki);
fprintf("Gross core area : %5.2f mm^2\n", Agi*10^6);
fprintf("kc for CRUCIFORM core : %5.2f\n", Kc);
fprintf("Diameter for circumscribing circle : %5.3f mm\n", d);
fprintf("Dimension for laminations : a=%5.3f mm and b=%5.3f mm\n", a, b);
fprintf("Kv Rating: %5.2f kV\n", kV);
fprintf("Window space factor: %5.3f\n", Kw);
fprintf("Height Window: %5.3f\n", Hw);
fprintf("Width of Window: %5.3f\n", Ww);
fprintf("Net area of the Yoke: %5.2f mm^2\n", Ay*10^6);
fprintf("Gross area of the Yoke: %5.2f mm^2\n", Agy*10^6);
fprintf("Flux density in yoke: %5.3f T\n", By);
fprintf("Depth of the yoke: %5.3f mm\n", Wy);
fprintf("Height of the yoke: %5.3f mm\n", Hy);
fprintf("Height of the Frame: %5.3f mm\n", Hf);
fprintf("Width of the Frame: %5.3f mm\n", Wf);

%Code for plotting of transformer core


Rdraw(0,0,Wf,Hf);
hold;
title("Cross-Sectional View of designed transformer");
Rdraw(a,Hy,Ww,Hw);
Rdraw(2*a+Ww,Hy,Ww,Hw);
axis([-150 1.2*Wf -100 1.2*Hf]);

Transformer rating in KVA: 25.00 kVA


Rated frequency : 50 Hz
K for core typedistribution transformer : 0.45
Voltage per turn : 2.250 V
Max flux in the core : 0.01014 Wb
Assummed flux density : 1.000 T
Net core area : 10135.14 mm^2
Stacking factor : 0.9
Gross core area : 11261.26 mm^2
kc for CRUCIFORM core : 0.56
Diameter for circumscribing circle : 135.000 mm
Dimension for laminations : a=114.000 mm and b=71.000 mm
Kv Rating: 11.00 kV
Window space factor: 0.146
Height Window: 332.000
Width of Window: 133.000
Net area of the Yoke: 12162.16 mm^2

2
Gross area of the Yoke: 13513.51 mm^2
Flux density in yoke: 0.833 T
Depth of the yoke: 115.000 mm
Height of the yoke: 119.000 mm
Height of the Frame: 569.000 mm
Width of the Frame: 609.000 mm
Current plot held

Published with MATLAB® R2022b

You might also like