DC Drive Bled6c Hm-5109-3e
DC Drive Bled6c Hm-5109-3e
Table of contents
1 Introduction ......................................... 2 7 Connection........................................27
7.1 Connection example.............................. 27
2 Safety precautions .............................. 4 7.2 Connecting the power supply ................ 28
3 Precautions for use............................. 6 7.3 Grounding.............................................. 28
7.4 Connecting the motor and driver ........... 29
4 System configuration .......................... 7 7.5 Connecting the regeneration unit .......... 30
5 Preparation ......................................... 8 7.6 Selecting the I/O signal power supply ... 31
5.1 Checking the product .............................. 8 7.7 Connecting the I/O signals .................... 31
5.2 How to identify the product model........... 8 7.8 Connecting the communication cable ... 36
5.3 Combination tables.................................. 9 7.9 Connection diagram (example) ............. 37
5.4 Names and functions of parts................ 11 8 Operation ..........................................40
6 Installation......................................... 14 8.1 Operation overview................................ 40
6.1 Installation location................................ 14 8.2 Basic operation...................................... 41
6.2 Installation overview .............................. 14 8.3 Setting the acceleration time and
6.3 Installing the combination parallel shaft deceleration time ................................... 43
gearhead ............................................... 15 8.4 Changing the speed .............................. 44
6.4 Installing the round shaft type ............... 16 8.5 Examples of operation patterns............. 44
6.5 Installing the combination type 8.6 Parallel operation................................... 45
hollow shaft flat gearhead ..................... 16 8.7 Setting the FBLⅡcompatible mode and
6.6 Installing a load ..................................... 19 operation................................................ 46
6.7 Permissible overhung load and
9 Extended functions ...........................49
permissible thrust load .......................... 21
6.8 Installing the driver ................................ 22 10 Inspection .........................................49
6.9 Installing the regeneration unit
(accessory)............................................ 24
11 Protection function ............................50
6.10 Installing the external potentiometer 12 Troubleshooting and remedial
(supplied)............................................... 24 actions ..............................................52
6.11 Installing and wiring in compliance with
EMC Directive ....................................... 25 13 Accessories (sold separately) ...........53
1 Introduction
1 Introduction
Before use
This product must be handled by qualified personnel.
Before using motor unit, read 2 “Safety precautions” on p.4 carefully to understand its correct use.
The BLE Series is designed and manufactured for use as an internal component of general industrial equipment.
Do not use it for any other purpose. Oriental Motor will not be liable for whatever damage arises from failure to
observe this warning.
Product overview
The BLE Series is a line of units, each consisting of a compact, high-torque brushless motor and a high-functional
box-type driver.
Each unit has a FBLⅡcompatible mode, so existing users of FBLⅡSeries units can use the BLE Series units with the
same settings.
With the accessory data setter OPX-2A or data editing software MEXE02 (both are sold separately), you can
improve the performance and set operation data/ parameters and motor operations with ease.
• Applicable Standards
Applicable Standards Certification Body Standards File No. CE Marking
UL 1004-1
UL E335369
CSA C22.2 No.100
Motor∗ EN60034-1
EN60034-5
Conform to EN Standards
EN60664-1 Low Voltage Directive
EN60950-1 EMC Directives
UL 508C
UL E171462
CSA C22.2 No.14
Driver
EN 60950-1
Conform to EN Standards
EN 61800-5-1
∗ Thermal class UL/CSA Standards: 105(A), EN Standards: 120(E)
A temperature test has been conducted with a radiation plate. The size, thickness and material of the radiation plates
are as below table.
Model Size [mm (in.)] Thickness [mm (in.)] Material
BLEM23 115×115 (4.53×4.53)∗
BLEM46 135×135 (5.31×5.31) 5 (0.20) Aluminum
BLEM512 165×165 (6.50×6.50)
∗ Electromagnetic brake type: 135×135 mm (5.31×5.31 in.)
• Installation conditions
Motor Driver
Motor is to be used as a component within other Motor is to be used as a component within other
equipment equipment
Overvoltage category:Ⅲ∗ Overvoltage category:Ⅲ∗
Pollution degree: 3 Pollution degree: 2
Protection against electric shock: ClassⅠequipment Protection against electric shock: ClassⅠequipment
∗ Overvoltage category II when EN 60950-1 is applicable.
−2−
1 Introduction
• EMC Directives
This product bears the CE mark under the conditions specified in “Example of motor and driver installation and
wiring” on p.26.Be sure to conduct EMC measures with the product assembled in your equipment by referring to 6.11
“Installing and wiring in compliance with EMC Directive” p.25.
UL RECOGNITION OF DRIVER
Drivers are recognized by UL at following condition.
• Maximum Surrounding Air Temperature 50°C.
• Install device in pollution degree 2 environment.
• Solid state motor overload protection reacts at less than 160% FLA.
• Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000 Arms Symmetrical Amperes, 120 or
240 VAC Maximum Voltage.
• Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the National Electric Code and any additional local codes.
• Use UL Listed Inverse Time Circuit Breaker rated 120 or 240 VAC, 15 A Only.
• Drives have no provision for motor over temperature protection. Motor over temperature protection is required at
end application.
Hazardous substances
RoHS (Directive 2002/95/EC 27Jan.2003) compliant
−3−
2 Safety precautions
2 Safety precautions
The precautions described below are intended to prevent danger or injury to the user and other personnel through safe,
correct use of the product. Please read and understand these precautions thoroughly before using the product.
Handling the product without observing the instructions that accompany a “Warning”
Warning symbol may result in death or serious bodily injury.
Handling the product without observing the instructions that accompany a “Caution”
Caution symbol may result in bodily injury or property damage.
The items under this heading contain important handling instructions that the user
Note should observe to ensure the safe use of the product.
Warning
• Do not use the product in a place exposed to explosive, flammable or corrosive gases or water splashes or near
combustible materials. Doing so may result in fire, electric shock or injury.
• Only qualified personnel should be allowed to perform installation, connection, operation and
inspection/troubleshooting of the product. Handling by unqualified personnel may result in fire, electric shock,
injury or equipment damage.
• Do not move, install, connect or inspect the product while the power is supplied. Perform these operations after
turning off the power. Failure to observe these instructions may result in electric shock.
• The terminals on the driver’s front panel marked with symbol indicate the presence of high voltage. Do
not touch these terminals while the power is on to avoid the risk of fire or electric shock.
• Do not use a non-electromagnetic brake type motor in a vertical application. If the driver’s protection function is
activated, the motor will stop and the moving part of the equipment will drop, thereby causing injury or equipment
damage.
• Do not use the brake mechanism of the electromagnetic brake motor as a safety brake. It is intended to hold the
moving parts and motor position. Doing so may result in injury or damage to equipment.
• If the driver’s protection function has been activated, remove the cause and then reset the protection function.
Continuing to operate the equipment without removing the cause of problem will lead to a motor or driver
malfunction, resulting in injury or equipment damage.
• Use a specified motor (gearhead) and driver combination. Failure to do so may result in fire, electric shock or
equipment damage.
• Use the motor and driver only in class I equipment. Installing them in equipment of other classes may result in
electric shock.
• Install the motor and driver in an enclosure. Failure to do so may result in electric shock or injury.
• When installing the motor and driver, connect their Protective Earth Terminals. Failure to do so may result in
electric shock.
• Securely connect the cables in accordance with the connection examples. Failure to do so may result in fire or
electric shock.
• Do not forcibly bend, pull or pinch the cables. Doing so may result in fire or electric shock.
• Do not machine or modify the motor cable or connection cable. Doing so may result in electric shock or fire.
• Be sure to observe the specified cable sizes. Use of unspecified cable sizes may result in fire.
• Observe the specified screw tightening torque when connecting terminals to the terminal block. Failure to do so
may result in electric shock or equipment damage.
• Always keep the driver’s power supply voltage below the rating. Failure to do so may result in fire or electric
shock.
• When using the electromagnetic brake motor, do not turn the MB-FREE input ON while a load is held in vertical
direction. Otherwise, the holding power of the motor and electromagnetic brake will be lost, causing personal
injury or damage to equipment.
• When using the electromagnetic brake motor in vertical drive (gravitational operation), be sure to operate after
checking the load condition. If a load in excess of the rated torque is applied or the small torque limiting value is
set using a OPX-2A or MEXE02 (accessories), the load may fall. This may result in injury or damage to
equipment.
• Always turn off the power before performing maintenance/inspection. Failure to do so may result in electric shock.
• Do not touch the motor or driver when measuring insulation resistance or performing a dielectric strength test.
Accidental contact may result in electric shock.
• Do not touch the connection terminals on the driver immediately (within 30 seconds or until the CHARGE LED
turns off) after the power is turned off. Residual voltage may cause electric shock.
• Regularly check the openings in the driver for accumulated dust. Accumulated dust may cause fire.
−4−
2 Safety precautions
• Do not disassemble or modify the motor (gearhead) and driver. Doing so may result in electric shock, injury or
equipment damage. Should you require inspection or repair of internal parts, please contact the Oriental Motor
branch or sales office from which you purchased the product.
Caution
• Do not use the product in conditions exceeding the motor (gearhead) or driver specifications. Doing so may result
in electric shock, fire, injury or equipment damage.
• Do not insert an object into the openings in the driver. Doing so may result in fire, electric shock or injury.
• Do not touch the motor (gearhead) or driver during the operation or immediately after the operation has stopped.
Touching a hot motor (gearhead) or driver surface may cause a skin burn(s).
• Do not carry the product by the motor (gearhead) output shaft or any of the cables. Doing so may result in injury.
• Do not place around the motor and driver any object blocking the air flow. Doing so may result in equipment
damage.
• Do not touch the motor output shaft (key groove or pinion) with bare hands. Doing so may result in injury.
• When assembling the motor (pinion shaft) with the gearhead, exercise caution not to pinch your fingers or other
parts of your body between the motor and gearhead. Injury may result.
• Securely affix the motor (gearhead) and driver to their respective mounting plates. Inappropriate installation may
cause the motor/driver to detach and fall, resulting in equipment damage.
• Provide a cover on the rotating part (output shaft) of the motor (gearhead). Failure to do so may result in injury.
• When installing the motor (gearhead) in the equipment, exercise caution not to pinch your fingers or other parts of
your body between the equipment and motor or gearhead. Injury may result.
• Securely install the load on the motor output shaft. Inappropriate installation may result in injury.
• For the I/O signals power supply, use a DC power supply with reinforced insulation on its primary and secondary
sides. Failure to do so may result in electric shock.
• Provide an emergency stop device or emergency stop circuit external to the equipment so that the entire equipment
will operate safely in the event of a system failure or malfunction. Failure to do so may result in injury.
• Immediately when trouble has occurred, stop running and turn off the driver power. Failure to do so may result in
fire, electric shock or injury.
• Do not touch the rotating part (output shaft) during operation. Doing so may result in injury.
• The motor surface temperature may exceed 70 °C (158 °F) even under normal operating
conditions. If the operator is allowed to approach a running motor, attach a warning label as
shown to the right in a conspicuous position. Failure to do so may result in skin burn(s). Warning label
• Use an insulated screwdriver to adjust the internal speed potentiometer, acceleration time potentiometer,
deceleration time potentiometer and switches in the driver. Failure to do so may result in electric shock.
• To dispose of the motor (gearhead) or driver, disassemble it into parts and components as much as possible and
dispose of individual parts/components as industrial waste.
Warning information
A warning label with handling instructions is attached on the driver.
Be sure to observe the instructions on the label when handling the driver.
−5−
3 Precautions for use
• Conduct the insulation resistance measurement or withstand voltage test separately on the
motor and the driver
Conducting the insulation resistance measurement or withstand voltage test with the motor and driver connected may
result in injury or damage to the product.
• Grease measures
On rare occasions, a small amount of grease may ooze out from the gearhead. If there is concern over possible
environmental damage resulting from the leakage of grease, check for grease stains during regular inspections.
Alternatively, install an oil pan or other device to prevent leakage from causing further damage. Oil leakage may lead
to problems in the customer’s equipment or products.
• Use a connection cable (supplied or accessory) when extending the wiring distance between
the motor and driver
• When using the motor in operation such as vertical drive (gravitational operation) or a large
inertial load drive, use an accessory regeneration unit (sold separately).
The driver may be damaged if the regeneration energy generated during vertical drive (gravitational operation) or
sudden starting/stopping of a large inertial load exceeds the allowable limit that can be absorbed by the driver.
The accessory regeneration unit (sold separately) is designed to discharge the regenerated energy, thereby protecting
the driver.
−6−
4 System configuration
4 System configuration
An example of system configuration using the BLE Series electromagnetic brake type is shown below.
Motor
Data editing
Data setter OPX-2A software MEXE02
(accessory) (accessory)
Driver
Or
Connection
cable
Power supply
(supplied or
Make sure power
accessory)
supply voltage does
not exceed the rated
voltage. Motor signal
connector
External control
Circuit breaker Electromagnetic equipment
brake Connect I/O signals.
or
earth leakage connector
breaker
Always connect
a breaker to protect Motor power
the primary circuit. connector
External
potentiometer
Mains filter (supplied)
Use an AC line filter to Connect this to set the
eliminate noise. It effectively motor speed externally.
Or
reduces noise generated from
the power source or driver.
External DC voltage
Connect an appropriate
power supply to set
Regeneration unit the motor speed using
DC voltage.
EPRC-400P (accessory)
Use this regeneration unit
when using the motor in
operation such as vertical
drive (gravitational operation)
or a large inertial load drive.
−7−
5 Preparation
5 Preparation
This chapter explains the items you should check, as well as the names and functions of each part.
−8−
5 Preparation
Standard type
Motor type Model Motor model Gearhead model Driver model
BLE23A S- BLED3A
BLE23C S- BLEM23-GFS GFS2G BLED3C
BLE23S S- BLED3S
BLE46A S- BLED6A
Combination type
BLE46C S- BLEM46-GFS GFS4G BLED6C
parallel shaft gearhead
BLE46S S- BLED6S
BLE512A S- BLED12A
BLE512C S- BLEM512-GFS GFS5G BLED12C
BLE512S S- BLED12S
BLE23A F- BLED3A
BLE23C F- BLEM23-GFS GFS2G FR BLED3C
BLE23S F- BLED3S
Combination type BLE46A F- BLED6A
hollow shaft flat BLE46C F- BLEM46-GFS GFS4G FR BLED6C
gearhead BLE46S F- BLED6S
BLE512A F- BLED12A
BLE512C F- BLEM512-GFS GFS5G FR BLED12C
BLE512S F- BLED12S
BLE23AA- − BLED3A
BLE23CA- BLEM23-A − BLED3C
BLE23SA- − BLED3S
BLE46AA- − BLED6A
Round shaft type BLE46CA- BLEM46-A − BLED6C
BLE46SA- − BLED6S
BLE512AA- − BLED12A
BLE512CA- BLEM512-A − BLED12C
BLE512SA- − BLED12S
−9−
5 Preparation
−10−
5 Preparation
Motor
Illustration shows the electromagnetic brake type.
Motor
Pilot
Output shaft
Protective
Mounting hole
Earth Terminal
(4 locations)
Motor cable
−11−
5 Preparation
Driver
Electromagnetic brake
connector (CN1)∗
CHARGE LED Communication connector (CN3)
−12−
5 Preparation
−13−
6 Installation
6 Installation
This chapter explains the installation location and installation methods of the motor and driver, as well as how to
install a load and external potentiometer. Also covered in this section are the installation and wiring methods that are
in compliance with the relevant EMC Directive.
−14−
6 Installation
C
BLE512 104 (4.09) 40 (1.57) 18 (0.71) 8.5 (0.335)
ØA
ØB indicates the external dimensions of the product.
Drill holes with a minimum diameter of ØB +1 mm (0.04 in.).
4רD
Assembly screws
Model Nominal thread size Tightening torque
BLE23
M2.6 0.4 N·m (3.5 lb-in)
BLE46
BLE512 M3 0.6 N·m (5.3 lb-in)
2. Using the pilot sections of the motor and gearhead as guides, Change the cable
install the gearhead to the motor and tighten the hexagonal position to a desired
socket head screws. 90° direction.
At this time, the motor cable position can be changed to a desired 90°
direction.
When installing the gearhead, slowly rotate it clockwise/
counterclockwise to prevent the pinion of the motor output shaft from
contacting the side panel or gear of the gearhead.
Also confirm that no gaps remain between the motor flange surface and Pilot section
the end face of the gearhead’s pilot section.
Note • Do not forcibly assemble the motor and gearhead. Also, do not let metal objects or other
foreign matter enter the gearhead. The pinion or gear of the motor output shaft may be
damaged, resulting in noise or shorter service life.
• Do not allow dust to attach to the pilot sections of the motor and gearhead. Also, assemble
the motor and gearhead carefully by not pinching the O-ring at the motor’s pilot section. If
the O-ring is crushed or severed, grease may leak from the gearhead.
• The hexagonal socket head screws assembling the motor and gearhead are affixing the
motor and gearhead only temporarily. When installing the gearhead, be sure to use the
supplied hexagonal socket head screws (4 pcs.).
−15−
6 Installation
B
H7
73+0.030
0
BLE46 94 (3.70) 66.47 (2.616) 6.5 (0.256)
(2.8740+0.0012
0 )
83+0.035
0 ØD
BLE512 104 (4.09) 73.54 (2.895) 8.5 (0.335) B
(3.2677+0.0014
0 )
ØC indicates the pilot diameter on the flange.
Note Fit the boss on the gearhead mounting surface into a pilot receiving hole.
Mounting plate
4רC
−16−
6 Installation
Safety cover
mounting screw (M3)
ØD or more
Mounting plate
E 4רC
Flat washer
Spring washer
Hexagonal nut
Note When installing the gearhead by using its rear side as the mounting surface, prevent contact
between the mounting plate and motor by keeping dimension E below the specified value.
−17−
6 Installation
Hexagonal socket
head screw
2. Using the pilot sections of the motor and gearhead as guides, install the motor to the gearhead and
tighten the hexagonal socket head screws.
At this time, the motor cable position can be changed to one of three 90° directions.
Install the motor carefully to prevent the pinion of the motor output shaft from contacting the casing or gear of the
gearhead.
Also confirm that no gaps remain between the motor flange surface and the end face of the gearhead’s pilot
section.
Assembly screws
Model Nominal thread size Tightening torque
BLE23 M4 1.8 N·m (15.9 lb-in)
BLE46 M6 6.4 N·m (56 lb-in)
BLE512 M8 15.5 N·m (137 lb-in)
Note • Do not forcibly assemble the motor and gearhead. Also, do not let metal objects or other
foreign matters enter the gearhead. The pinion or gear of the motor output shaft may be
damaged, resulting in noise or shorter service life.
• Do not allow dust to attach to the pilot sections of the motor and gearhead. Also, assemble
the motor carefully by not pinching the O-ring at the motor’s pilot section. If the O-ring is
pinched, the coupling strength will drop and grease may leak from the gearhead.
• The motor cable position cannot be changed to the direction where the cable faces the
gearhead output shaft, because the gearhead case will obstruct the cable.
−18−
6 Installation
Using a belt
Adjust the motor (gearhead) output shaft to lie parallel with the load shaft and form right angles between the output
shaft/load shaft and the line connecting the centers of both pulleys.
Using a gear
Adjust the motor (gearhead) output shaft to lie parallel with the gear shaft and allow the output shaft to mesh
correctly with the centers of the gear teeth.
Gearhead model name ∗ Output shaft tip screw hole Fixed screw
Spacer
M5
GFS4G
Effective depth 10 mm (0.39 in)
M6
GFS5G
Effective depth 12 mm (0.47 in)
∗ The square box in the gearhead model will contain a value
Screw
representing the gear ratio.
−19−
6 Installation
ØD
Spring washer
Parallel key
Parallel key
Spring washer
Note The safety cover (supplied) cannot be attached due to contact between the safety cover and
hexagonal socket head screw. Take safety measures against rotating part.
−20−
6 Installation
Hexagonal socket
head screw
Spring washer
Retaining ring
Flat washer
Hollow output shaft Flat washer
Spacer
Retaining
ring Load shaft Hexagonal
socket head
screw
Parallel key
Spring washer
Spacer
Parallel key
Load shaft Spacer Spacer
−21−
6 Installation
• Combination type
hollow shaft flat gearhead
Distance from gearhead mounting surface and Permissible
Model
permissible overhung load∗ [N (lb.)] thrust load
Gear ratio 10 mm (0.39 in.) 20 mm (0.79 in.) [N (lb.)]
5, 10 450 (101) [410 (92)] 370 (83) [330 (74)]
BLE23 200 (45)
15 to 200 500 (112) [460 (103)] 400 (90) [370 (83)]
5, 10 800 (180) [730 (164)] 660 (148) [600 (135)]
BLE46 400 (90)
15 to 200 1200 (270) [1100 (240)] 1000 (220) [910 (200)]
5, 10 900 (200) [820 (184)] 770 (173) [700 (157)]
BLE512 15, 20 1300 (290) [1200 (270)] 1110 (240) [1020 (220)] 500 (112)
30 to 200 1500 (330) [1400 (310)] 1280 (280) [1200 (270)]
∗ The values assume a rated speed of 3000 r/min or below. The values in [ ] are based on a rated speed of 4000 r/min.
150 (5.91)
directions, respectively.
Note • Install the driver in an enclosure whose pollution degree is 2 or
above or protection class is IP54 or better.
• Be sure to install (position) the driver vertically. Do not block
the radiation openings.
• Do not install any equipment that generates a large amount of
heat or noise near the driver.
25 (0.98) or more
• If the ambient temperature of the driver exceeds 50 °C
(122 °F), revise the ventilation condition or force-cool the area
around the driver using a fan.
Unit: mm (in.)
Mounting hole
(at the back)
−22−
6 Installation
Mounting holes
(M3, four locations)
Mounting screws
(supplied)
2. Pull the DIN lever down, engage the upper tab of the
DIN rail mounting plate over the DIN rail, and push the Tab
DIN lever until it locks in place.
DIN rail
DIN lever
End plate
−23−
6 Installation
165 (6.50)
Regeneration
unit
EPRC-400P
Ø4.2+ 00.3
(0.165+ 00.012)
Lead wire
Solder (Pass the lead wire
Lead wire through the terminal hole and
give it two or three turns.)
−24−
6 Installation
Applicable Standards
Emission Tests EN 61000-6-4, EN 61800-3 C3
EMI Harmonics Current Test EN 61000-3-2
Voltage Fluctuations Test EN 61000-3-3
EMS Immunity Tests EN 61000-6-2, EN 61800-3 C3
Without effective measures to suppress the electromagnetic interference (EMI) caused by the BLE Series in the
surrounding control system equipment or the electromagnetic spectrum (EMS) generated by the BLE Series, the
function of your mechanical equipment may be seriously affected.
The BLE Series will conform to the EMC Directives if installed/wired using the methods specified below.
Grounding procedure
The cable used to ground the motor, driver, mains filter and power supply cable (shielded cable) must be as thick and
short to the grounding point as possible so that no potential difference is generated. Choose a large, thick and
uniformly conductive surface for the grounding point. Refer to the p.28 for the recommended grounding method.
−25−
6 Installation
Regeneration unit
EPRC-400P
Motor
Regeneration unit Driver
lead wire (0.3 m)∗3
PE
Connection cable
(20 m)∗1∗2
Motor cable∗2 Cable
clamp I/O signals cable (2 m)∗2
AC power
Power supply cable
supply Mains filter External
(2 m)∗2 FG
L potentiometer
N
PE
PE PE
PE
PE
Ground plate (aluminum plate)
PE
∗1 Performance has been evaluated based on connection cable lengths of up to 20 m (65.6 ft.). You can connect up to three
connection cables.
∗2 Shielded cable
∗3 Unshielded cable
−26−
7 Connection
7 Connection
This chapter explains how to connect the driver and motor, I/O signals, and power supply, as well as the grounding
method.
PE
−27−
7 Connection
• Single-phase 100-120 V
Connect the live side to terminal L, and the neutral side to
terminal N. L
• Single-phase 200-240 V
Connect the live side to terminal L, and the neutral side to
terminal N. L
• Three-phase 200-240 V
Connect the R, S and T phase lines to the L1, L2 and L3
R
terminals, respectively.
S
after crimping
• Applicable lead wire: AWG18 to 14 (0.75 to 2.0 mm2)
• Temperature rating of lead wire: 60 °C, 60 or 75 °C, or 75 °C
(140 °F, 140 or 167 °F, or 167 °F) 3.8 (0.15)
• Conductive material: Use only copper wire. or less
Unit: mm (in.)
Circuit breaker
Be sure to connect a circuit breaker to the power line of the driver to protect the primary circuit.
Rated current of protective device: Single-phase input 10 A, three-phase input 5 A
Circuit breaker: Mitsubishi Electric Corporation NF30
7.3 Grounding
Grounding the motor
Connect the Protective Earth Terminal on the motor to the ground near the
motor. Minimize the wiring length of the ground cable.
Tightening torque: 0.8 to 1.0 N·m (7.0 to 8.8 lb-in)
−28−
7 Connection
2 White AWG24
Housing:
5557-02R-210
(Molex)
Terminal:
5556T (Molex)
−29−
7 Connection
Connection cable
This cable (sold separately) is used to extend the wiring distance between the driver and motor. Flexible connection
cables are also available. You can connect up to three connection cables.
• Standard type • Standard type • Electromagnetic brake type • Electromagnetic brake type
Connection cable Flexible connection cable Connection cable Flexible connection cable
Length Length Length Length
Model Model Model Model
[m (ft.)] [m (ft.)] [m (ft.)] [m (ft.)]
1 (3.3) CC01BLE 1 (3.3) CC01BLER 1 (3.3) CC01BLEM 1 (3.3) CC01BLEMR
2 (6.6) CC02BLE 2 (6.6) CC02BLER 2 (6.6) CC02BLEM 2 (6.6) CC02BLEMR
3 (9.8) CC03BLE 3 (9.8) CC03BLER 3 (9.8) CC03BLEM 3 (9.8) CC03BLEMR
5 (16.4) CC05BLE 5 (16.4) CC05BLER 5 (16.4) CC05BLEM 5 (16.4) CC05BLEMR
7 (23) CC07BLE 7 (23) CC07BLER 7 (23) CC07BLEM 7 (23) CC07BLEMR
10 (32.8) CC10BLE 10 (32.8) CC10BLER 10 (32.8) CC10BLEM 10 (32.8) CC10BLEMR
15 (49.2) CC15BLE 15 (49.2) CC15BLER 15 (49.2) CC15BLEM 15 (49.2) CC15BLEMR
20 (65.6) CC20BLE 20 (65.6) CC20BLER 20 (65.6) CC20BLEM 20 (65.6) CC20BLEMR
• Connection method
Connection to the I/O terminals varies depending on the connection method. Refer to p.37.
Connect the regeneration unit before turning on the main power. The regeneration unit does not perform its control
function if connected after the main power has been turned on.
• Regenerative current flows through the two thick lead wires (AWG18: 0.75 mm2) of the regeneration unit. Connect
them to the RG1 and RG2 terminals of the TB1. The applicable crimp terminal is the same as the one used to
connect the power supply. Refer to p.28.
• The two thin lead wires (AWG22: 0.3 mm2) of the regeneration unit are thermostat outputs. Refer to p.31 for the
connection method.
Regeneration unit
EPRC-400P
R: 400 Ω
150 °C (N.C.)
AWG22
Connect
AWG18 to CN5
P.37 to 39
To RG1 and RG2 terminals on TB1
Note If the current consumption of the regeneration unit exceeds the allowable level, the thermostat
will be triggered and a regeneration unit overheat alarm will generate. If a regeneration unit
overheat alarm generates, turn off the power and check the content of the error.
−30−
7 Connection
−31−
7 Connection
13, 15
−32−
7 Connection
Input signals
The signal state represents the “ON: Carrying current” or “OFF: Not carrying current” state of the internal
photocoupler rather than the voltage level of the signal.
• STOP-MODE input
Select how the motor should stop when the FWD input or REV input is turned OFF.
When the STOP-MODE input is ON, the motor stops according to the time set by the deceleration time potentiometer.
STOP-MODE input is OFF, the motor stops instantaneously.
• M0 input
Select how the motor speed is set.
When the M0 input is ON, the motor turns at the speed set by the external potentiometer or external DC voltage.
When the M0 input is OFF, the motor turns at the speed set by the internal potentiometer.
By switching the M0 input, the motor can be operated at two speeds through use of both the external potentiometer
and internal potentiometer. Refer to p.44 for details.
You can set a maximum of eight speeds by changing the assignments of M0 to M2 inputs using the OPX-2A or
MEXE02.
• ALARM-RESET input
This input actuates the driver’s protective function to reset present alarms.
To reset each alarm, be sure to remove the cause of the alarm before switching the ALARM-RESET input.
To reset an alarm, turn both the FWD input and REV input OFF, remove the cause of the alarm, and then turn the
ALARM-RESET input ON (and keep it ON for 10 ms or more). The ALARM-RESET input will not be received if
the FWD input or REV input is ON.
If the alarm cannot be reset with the ALARM-RESET input, turn off the power, wait for at least 30 seconds, and then
turn the power back on.
Stop
Motor operation pattern CW CW
ON
FWD input
OFF
10 ms or more
ON
ALARM-RESET input
OFF
10 ms or more
ON
ALARM-OUT1 input
OFF
∗ The electromagnetic brake locks the moment an alarm generates. The electromagnetic brake can be set to lock after a
free-run stop of the motor using the OPX-2A or MEXE02.
Note • Continuing the operation of the unit without removing the cause of the alarm may result in
equipment damage.
• Overcurrent and EEPROM errors cannot be reset using the ALARM-RESET input.
• MB-FREE input
This input signal is used for the electromagnetic brake type. The operation mode of the electromagnetic brake at
motor standstill is selected.
When the MB-FREE input is ON, the electromagnetic brake will be released.
When the MB-FREE input is OFF, the electromagnetic brake will actuate and hold the shaft in position.
Note The MB-FREE input is disabled while an alarm is present.
• TH input
When using the regeneration unit EPRC-400P, connect the thermostat output of the regeneration unit (normally
closed).
−33−
7 Connection
Output signals
The signal state represents the “ON: Carrying current” or “OFF: Not carrying current” state of the internal
photocoupler rather than the voltage level of the signal.
• SPEED-OUT output
30 pulses are output with each revolution of the motor output shaft synchronously with the motor operation.
The pulse width of output pulse signals is 0.2 ms. You can use the SPEED-OUT output to calculate the motor speed.
1 T
SPEED-OUT output frequency (Hz) =
T
SPEED-OUT output frequency
Motor shaft speed (r/min) = × 60 0.2 ms
30
To display/monitor the speed of the motor output shaft or reduced speed of the gearhead output shaft, connect the
accessory digital speed indicator SDM496 (sold separately). Refer to p.53 for details.
• ALARM-OUT1 output
When the driver’s protective function actuates, the ALARM-OUT1 output turns OFF and the ALARM LED blinks
(normally closed).
The motor coasts to a stop in the case of a standard type. When the motor is an electromagnetic brake type, the motor
stops instantaneously and the electromagnetic brake is actuated to hold the shaft in position.
To reset an alarm, turn both the FWD input and REV input OFF, remove the cause of the alarm, and then turn the
ALARM-RESET input ON (and keep it ON for 10 ms or more). The ALARM-RESET input will not be received if
the FWD input or REV input is ON.
If the alarm cannot be reset with the ALARM-RESET input, turn off the power, wait for at least 30 seconds, and then
turn the power back on.
Stop
Motor operation pattern CW CW
ON
FWD input
OFF
10 ms or more
ON
ALARM-RESET input
OFF
10 ms or more
ON
ALARM-OUT1 input
OFF
∗ The electromagnetic brake locks the moment an alarm generates. The electromagnetic brake can be set to lock after a
free-run stop of the motor using the OPX-2A or MEXE02.
−34−
7 Connection
5.1 kΩ 1.8 kΩ
3
5.1 kΩ 1.8 kΩ
4
5.1 kΩ 1.8 kΩ
5
5.1 kΩ 1.8 kΩ
6
5.1 kΩ 1.8 kΩ
7
5.1 kΩ 1.8 kΩ
8
0V
30 VDC or less
R0 40 mA or less
13
14
R0 40 mA or less
15
16
0V
5.1 kΩ 1.8 kΩ
3
5.1 kΩ 1.8 kΩ
4
5.1 kΩ 1.8 kΩ
5
5.1 kΩ 1.8 kΩ
6
5.1 kΩ 1.8 kΩ
7
5.1 kΩ 1.8 kΩ
8
30 VDC or less 40 mA or less
13
R0
14
40 mA or less
15
R0
16
0V
−35−
7 Connection
−36−
7 Connection
Note Change the setting of the external voltage selector switch (SW2-1) before turning on the main
power supply.
Sink logic
• Using the built-in power supply
In the connection example given below, the motor is operated with a single-phase 100 to 120 V power supply, relays,
switches and other contact switches. For the SPEED-OUT output, supply at least 5 mA of current.
Driver
SPEED-OUT
13
∗
14
15
+17 V ∗
16
ALARM-OUT1
IN-COM0 1
FWD 5.1 kΩ
2
REV
3 ∗Recommended resistance
STOP-MODE 24 VDC:
4 680 Ω to 4.7 kΩ (2 W)
M0 5 VDC:
5
ALARM-RESET 150 Ω to 1.0 kΩ (0.5 W)
6
MB-FREE
7
IN-COM1
12
TH 0V Shielded cable
8
Functional grounding
−37−
7 Connection
Driver
TH Shielded
8
cable
IN-COM1 12
0V Functional
grounding
−38−
7 Connection
Source logic
In the connection example given below, the motor is operated with a single-phase 200 to 240 V power supply based
on transistor sequence connection. For the SPEED-OUT output, supply at least 5 mA of current.
Driver
SPEED-OUT
13
∗
Input signal connection 14
20.4 to 28.8 VDC 15
100 mA or more ∗
16
ALARM-OUT1
FWD 5.1 kΩ
2
REV
3 ∗Recommended resistance
STOP-MODE 24 VDC:
4
M0 680 Ω to 4.7 kΩ (2 W)
5
ALARM-RESET 5 VDC:
6 150 Ω to 1.0 kΩ (0.5 W)
MB-FREE
7
IN-COM0
1
TH
8
Shielded cable
IN-COM1 12
0V
Functional
grounding
−39−
8 Operation
8 Operation
This chapter explains the operations that can be performed with the BLE Series.
−40−
8 Operation
0 20 40 60 80 100
External potentiometer [position]
∗ Refer to p.47 for the characteristics when the FBLⅡcompatible mode is used.
Note Change the setting of the external voltage selector switch SW2-2 before turning on the power.
For the external voltage, use a DC power supply (0 to 5 VDC or 0 to 10 VDC) with reinforced insulation on both the
primary side and secondary side, and use the supplied signal wire [1 m (3.3 ft.)] to connect it to the I/O signal
connector (CN5).
Connect the shield wire of the signal wire to the VL input • External DC voltage vs. speed characteristics
terminal. Make sure the shield wire does not contact other (representative values)
terminals.
Motor shaft speed [r/min]
4000
The input impedance between the VM input and VL input is
approx. 15 kΩ when SW2-2 is ON, and approx. 30 kΩ when 3500 5 VDC
OFF. The VL input is connected to IN-COM1 inside the driver. 3000
2500 10 VDC
CN5
External DC 2000
power supply
1500
10 VM input White White
0 to 5 VDC 1000
11 VL input Yellow Yellow 1 mA or more
500
0 1 2 3 4 5 6 7 8 9 10
External DC voltage [V]
∗ Refer to p.47 for the characteristics when the FBLⅡcompatible mode is used.
Note Be sure to set the external DC voltage to either 5 VDC or less, or 10 VDC or less. When
connecting the external DC power supply, make sure the polarities are correct. If the polarities
are reversed, the driver may be damaged.
−41−
8 Operation
• Operation
When the FWD input is turned ON, the motor turns in the clockwise direction according to the time set by the
acceleration time potentiometer. When the FWD input is turned OFF, the motor stops.
When the REV input is turned ON, the motor turns in the counterclockwise direction according to the time set by the
acceleration time potentiometer. When the REV input is turned OFF, the motor stops.
If the FWD input and REV input are turned ON at the same time, the motor stops instantaneously.
Instantaneous Deceleration
stop stop
Motor operation
ON
FWD input
OFF
ON
REV input
OFF
ON
STOP-MODE input
OFF
Note When using the motor in vertical drive (gravitational operation), although it depends on the load
condition, if operation is performed with the setting below, the motor shaft may momentarily
rotate in the reverse direction (about one-fourth revolution of the motor output shaft) at the time of
starting/stopping the motor.
· When the set rotation speed is low
· When the acceleration time and deceleration time is long
• Stop
Select how the motor should stop when the FWD input or REV input is turned ON.
When the STOP-MODE input is ON, the motor stops according to the time set by the deceleration time potentiometer.
STOP-MODE input is OFF, the motor stops instantaneously.
FWD input REV input STOP-MODE input Motor status
ON OFF − Clockwise rotation
OFF ON − Counterclockwise rotation
ON ON − Instantaneous stop
− − OFF Instantaneous stop
− − ON Deceleration stop
−42−
8 Operation
Sudden start
Gradual start
Sudden stop
Gradual stop
3000 r/min
t1 t2
“Acceleration time (t1)” refers to the time needed for the motor to reach the rated speed (3000 r/min) from the
stationary state.
“Deceleration time (t2)” refers to the time needed for the motor to stop from the rated speed (3000 r/min).
The actual acceleration time and deceleration time vary depending on the conditions of use, load inertia, load torque,
etc. If smooth acceleration operation or deceleration operation is not possible, increase the acceleration time or
deceleration time.
−43−
8 Operation
ON
REV input
OFF
ON
STOP-MODE input
OFF
ON
M0 input
OFF
External potentiometer
Motor operation
Counterclockwise
External potentiometer
Electromagnetic brake operation Release Release
3000 r/min
Motor operation
Counterclockwise
FWD input ON
(Clockwise) OFF
REV input ON
(Counterclockwise) OFF
STOP-MODE input ON
(Deceleration stop/
OFF
Instantaneous stop)
M0 input ON
(Internal potentiometer/
OFF
External potentiometer)
Electromagnetic Lock
brake operation Release
−44−
8 Operation
If the FWD input and REV input are turned ON at the same time, the motor stops instantaneously regardless of the
status of the STOP-MODE input.
Motor operation
Instantaneous Deceleration
CW stop CW stop
ON
FWD input
OFF
ON
REV input
OFF
ON
STOP-MODE input
OFF
2
3 1 Speed setting line
External potentiometer Driver 1 Driver n VRn
VRx 1 kΩ, 1/4 W
VH 470 Ω, 1/4 W VH
VM VM
VL VL
L L
N N
If the number of drivers used is “n,” calculate resistance (VRx) of the external potentiometer using the formula
below:
Resistance (VRx) = 20/n (kΩ), n/4 (W)
Example: If two drivers are used, resistance (VRx) is calculated as 10 kΩ, 1/2 W [20/2 (kΩ), 2/4 (W)].
(Use a resistor of the calculated wattage or more.)
If the speed will vary among the respective motors, make adjustments by connecting a resistor of 470 Ω, 1/4 W to
terminal VM on driver 1 and connecting a variable resistor of 1 kΩ, 1/4 W to driver 2 and subsequent drivers.
−45−
8 Operation
L L
N N
If the number of drivers used is “n,” calculate the current capacity (I) of the external DC power supply using the
formula below:
Current capacity (I) = 1 × n (mA)
Example: If two drivers are used, current capacity (I) is calculated as 2 mA or more [1 × 2 (mA)].
If the speed will vary among the respective motors, make adjustments by connecting a resistor of 470 Ω, 1/4 W to
terminal VM on driver 1 and connecting a variable resistor of 1 kΩ, 1/4 W to driver 2 and subsequent drivers.
−46−
8 Operation
Speed characteristics
· External potentiometer position vs. speed · External DC voltage vs. speed characteristics
characteristics (representative values) (representative values)
3000 3000
2500 2500
5 VDC
2000 2000
10 VDC
1500 1500
1000 1000
500 500
0 20 40 60 80 100 0 1 2 3 4 5 6 7 8 9 10
External potentiometer [position] External DC voltage [V]
SPEED-OUT output
12 pulses are output with each revolution of the motor output shaft synchronously with the motor operation (pulse
width of 0.5 ms).
1 T
SPEED-OUT output frequency (Hz) =
T
SPEED-OUT output frequency
Motor shaft speed (r/min) = × 60 0.5 ms
12
−47−
8 Operation
3000 r/min
Motor operation
Counterclockwise
FWD input ON
(Clockwise) OFF
∗
REV input ON
(Counterclockwise) OFF
STOP-MODE input ON
(Deceleration stop/
OFF
Instantaneous stop)
M0 input ON
(Internal potentiometer/
OFF
External potentiometer)
Electromagnetic Lock
brake operation Release
∗ When switching the FWD input and REV input, provide an interval of at least 10 ms.
Note Make sure each signal remains ON for at least 10 ms.
−48−
9 Extended functions
9 Extended functions
The following functions can be extended using the OPX-2A or MEXE02.
For details, refer to the operating manual for each product.
• A maximum of eight speeds can be set.
• The torque can be limited.
• The assignments of I/O signals can be changed.
• The speed, alarm code and load factor can be displayed.
• I/Os can be monitored.
• Warnings can be output.
• Test operation can be performed.
• Data can be copied.
ON
FWD input
OFF
ON
M2 input
OFF
ON
M1 input
OFF
ON
M0 input
OFF
10 Inspection
It is recommended that the items listed below be inspected regularly after motor operation. If any abnormality is
found, stop using the motor and call our Technical Support Line.
Note • Never measure insulation resistance or conduct a dielectric strength test with the motor and
driver connected. Doing so may damage the motor/driver.
• The driver uses semiconductor elements, so handle it with due care. Electrostatic discharge
can damage the driver.
Inspection items
Confirm that:
• The motor/gearhead mounting screws are not loose.
• The bearing (ball bearing) and other parts of the motor are not generating noise.
• The bearing (ball bearing) and gear meshing parts of the gearhead are not generating noise.
• The motor/gearhead output shaft is not misaligned with the load shaft.
• The cables are free from damage or stress and are securely connected to the driver.
• The openings in the driver are not blocked.
• The driver mounting screws and power connection terminal screws are not loose.
• The power elements and smoothing capacitors in the driver are not generating an abnormal smell or having
abnormalities.
−49−
11 Protection function
11 Protection function
When an alarm generates and the driver's protective function is actuated, the ALARM-OUT1 output will turn OFF.∗
In the case of a standard type, the motor coasts to a stop, and then the holding power of the motor output shaft is lost.
When the motor is an electromagnetic brake type, the motor stops instantaneously and the electromagnetic brake is
actuated to hold the shaft in position.
The ALARM LED blinks at the same time. You can check the type of the alarm by counting the number of times the
ALARM LED blinks.
∗ ON in the FBLⅡcompatible mode
1 2 3 1 2 3
To reset an alarm, be sure to remove the cause of the alarm and then perform one of the following operations:
• Turn the ALARM-RESET input ON for at least 10 ms. (Refer to p.33 for details.)
• Turn off the power, wait for at least 30 sec, and then cycle the power.
Note • Alarms cannot be reset if the FWD input or REV input is ON or the motor is running. Be sure to
stop the motor before resetting any alarm.
• Alarms caused by damage to the motor or driver itself cannot be reset using the method
explained above. Please contact your nearest office.
• Make sure the ALARM-RESET input remains ON for at least 10 ms. If the ON period is too
short, the alarm may not be reset.
• If an external stop alarm generates, the motor stops instantaneously.
Alarm list
Reset using the
No. of ALARM
Alarm name Cause Remedial action ALARM-RESET
LED blinks
input
• Decrease the load.
A load exceeding the rated
• Review the operation pattern
2 Overload torque was applied to the Possible
motor for 5 seconds or more. settings such as the
acceleration/deceleration time.
The motor sensor signal line
experienced an open circuit
Sensor error
during operation, or the signal
connector came off. Check the connection between the
3 Possible
The motor sensor signal line driver and motor.
broke or signal connector
Initial sensor error
came off before the main
power supply was turned on.
• The main power-supply
voltage became higher than • Check the main power supply
the rated voltage by approx. voltage.
20%.
• If this alarm occurs during
• A load exceeding the operation, reduce the load or
4 Overvoltage Possible
allowable gravitational increase the
capacity of the motor is acceleration/deceleration time.
driven or sudden
• Use a regeneration unit.
starting/stopping of a large
inertial load is performed.
The main power-supply • Check the main power supply
voltage became lower than voltage.
5 Undervoltage Possible
the rated voltage by approx. • Check the wiring of the power
40% supply cable.
• Decrease the load.
The rotating speed of the
motor output shaft exceeded • Review the operation pattern
6 Overspeed Possible
approx. 4800 r/min. settings such as the
acceleration/deceleration time.
−50−
11 Protection function
−51−
12 Troubleshooting and remedial actions
−52−
13 Accessories (sold separately)
Regeneration unit
Connect the regeneration unit if gravitational operation or sudden starting/stopping of a large inertial load, will be
repeated frequently.
Model: EPRC-400P
Data setter
This data setter can be used to set or monitor operation data and parameters.
Model: OPX-2A
−53−
• Unauthorized reproduction or copying of all or part of this manual is prohibited.
If a new copy is required to replace an original manual that has been damaged or lost, please contact your nearest Oriental Motor
branch or sales office.
• Oriental Motor shall not be liable whatsoever for any problems relating to industrial property rights arising from use of any
information, circuit, equipment or device provided or referenced in this manual.
• Characteristics, specifications and dimensions are subject to change without notice.
• While we make every effort to offer accurate information in the manual, we welcome your input. Should you find unclear
descriptions, errors or omissions, please contact the nearest office.
• is a registered trademark or trademark of Oriental Motor Co., Ltd., in Japan and other countries.
Other product names and company names mentioned in this manual may be registered trademarks or trademarks of their respective
companies and are hereby acknowledged. The third-party products mentioned in this manual are recommended products, and
references to their names shall not be construed as any form of performance guarantee. Oriental Motor is not liable whatsoever for
the performance of these third-party products.
© Copyright ORIENTAL MOTOR CO., LTD. 2011
• Please contact your nearest Oriental Motor office for further information.