Two Way Slab Analysis
Two Way Slab Analysis
1. Introduction:-
The direct design method consists of a set of rules for distributing moments to slab
and beam sections in a two-way slab system.
l
0.1l
Figure 01: Column offset at a distance of 0.1l from the basic rectangular grid.
(v) All loads must be due to gravity only (N/A to un-braced laterally loaded frames,
mats or pre-stressed slabs).
(vi) Service (unfactored) live load ≤ 2 (service dead load).
(vii)For panels with beams between supports on all sides, relative stiffness of the
beams in the two perpendicular directions:
l122
2l12
Shall not be less than 0.2 nor greater than 5.0.
Page 1 of 33
Direct Design Method
Where α is the ratio of flexural stiffness of beam section to flexural stiffness of width
of slab bounded laterally by centerlines of adjacent panels (if any) on each side of the
beam.
flexural stiffness of beam
=
flexural stiffness of slab
4Ecb Ib / l 4Ecb Ib
= =
4Ecs Is / l 4Ecs Is
Ecb = Modulus of elasticity of beam concrete
Esb = Modulus of elasticity of slab concrete
Ib = Moment of inertia of uncracked beam
Is = Moment of inertia of uncracked slab
The width of slab is bounded laterally by centerline of adjacent panels on each side of
the beam (figure 02).
hf hf
hw hw
bw
(a) Section for Ib(Edge beam) (c) Section for Ib(Interior beam)
(b) Section for Is (Edge beam) (d) Section for Is (Interior beam)
Page 2 of 33
Direct Design Method
l1 l1 l1
ne a
l
P
l
Interior Frame EW2 2
ln
N
l2
Half middle strip
ri
0.25l1 or 0.25l2 Column Inte ame
(Whichever is less) strip oFrr 3
EW
Middle
l2
strip
eri
0.25l1 or 0.25l2 Column strip Ext me
ofrra
(Whichever is less) 4
EW
(a)
l1
ln l1
(b)
Figure 03: Slab system divided into EW and NS frames.
Page 3 of 33
Direct Design Method
(iii)Column Strip (ACI 13.2.1): Column strip is a design strip with a width on each
side of a column centerline equal to 0.25l2 or 0.25l1, whichever is less. Column strip
includes beams, if any.
(iv) l1: l1 is the length of span in direction that moments are being determined, measured
center-to-center of supports.
(v) l2: l2 is the length of span transverse to l1, measured center-to-center of supports.
(vi) Middle strips (ACI 13.2.2): Middle strip is a design strip bounded by two column
strips.
4. Distribution of Moments:-
(i) Total static Moment, Mo (ACI 13.6.2): The total static moment for a span length
ln and width l2 of a given frame is given by ACI equation 13-3 as:
w l l2
M0 = u 2 n
(ACI 13 - 3)
8
Where,
Page 4 of 33
Direct Design Method
Figure 04: Equivalent square section for supporting members, ACI fig 13.6.2.5.
(ii) Longitudinal Distribution of Static Moment (ACI 13.6.3): For a typical interior
panel, the total static moment is divided into positive moment 0.35Mo and negative
moment of 0.65Mo.
For an exterior panel, the total static moment is dependent on the type of restraint
at the outside edge.
ACI table 13.6.3.3 as shown in figure 05 of this document can be used for
longitudinal distribution. Alternatively, figure 06 of this document can also be used.
Page 5 of 33
Direct Design Method
First
Exterior Interior Interior
1 No restraint
2 Full restraint
3 Slab with
beam between
supports
4 Edge beam
only (no other
beam)
5 No beams
Note that the longitudinal moment values mentioned are for the entire width of the
equivalent building frame i.e., the width of two half column strips and two half-
middle strips of adjacent panels.
Page 6 of 33
Direct Design Method
Where, C is the torsional constant of the edge beam. This is roughly equal to the
polar moment of inertia of edge beam and is given as:
C =∑[1–0.63{x/y}×x3y/3] = [1 – 0.63{x1/y1}×x 13y1/3] + [1 – 0.63{x2/y2}×x23y2/3]
Where, “x” is the shorter side of the rectangle and “y” is the longer one.
Slab
y2
y1 x2
x1
Beam
Figure 07: Cross-section of torsional member (edge beam) for calculation of βt.
Page 7 of 33
Direct Design Method
Page 8 of 33
Direct Design Method
Page 9 of 33
Direct Design Method
l2 l2 /2
l1/4 or l2 /4
(whichever
is smaller)
l2 /2
l2
Mp= Mp=
Panel moment
Column strip
Middle strip
Figure 10: Summary of longitudinal & lateral distribution for slabs without
beams.
Page 10 of 33
Direct Design Method
b. For αm > 2:
Figure 11: Table for minimum thickness of slabs without interior beams.
Page 11 of 33
Direct Design Method
Additionally, slab systems with αm < 0.2 shall also fulfill the following requirements:
• For slabs without drop panels meeting ACI 13.3.7.1 and 13.3.7.2,
hmin = 5 in
• For slabs with drop panels meeting ACI 13.3.7.1 and 13.3.7.2,
hmin = 4 in
ACI 13.3.7.1 — Drop panel shall extend in each direction from centerline of support
a distance not less than one-sixth the span length measured from center-to-center of
supports in that direction.
ACI 13.3.7.2 — Projection of drop panel below the slab shall be at least one-quarter
the slab thickness beyond the drop.
Page 12 of 33
Direct Design Method
• In the case of flat plates/slabs, it is clear that the middle-strip positive moments (for
example) are larger in the long direction than the short direction, exactly the
opposite of the situation for the slab with stiff beams. In the column strips, positive
and negative moments are larger in the long than in the short direction. On this
basis, the designer is led to place the long-direction negative and positive bars, in
both middle and column strips, closer to the top or bottom surface of the slab,
respectively, with the larger effective depth.
• If column-line beams are added and if their stiffness is progressively increased for
comparative purposes, it will be found that the short-direction slab moments
gradually become dominant, although the long-direction beams carry larger
moments than the short-direction beams.
• The best guide in specifying steel placement order in areas where stacking occurs
is the relative magnitudes of design moments obtained from analysis for a particular
case, with maximum d provided for the bars resisting the largest moment. No firm
rules can be given. For square slab panels, many designers calculate the required
steel area based on the average effective depth, thus obtaining the same bar size and
spacing in each direction.
• In case of DDM standard bar cut off points from figure 13 of this document are
used as recommended in ACI code, figure 13.3.8.
• ACI 13.3.8.5 requires that all bottom bars within the column strip in each direction
be continuous or spliced with Class A splices (1.0 ld, For development length see
ACI 12.2.3 or Nelson 13th Ed, page 172 chapter 5) or mechanical or welded splices.
At least two of the column strip bars in each direction must pass within the column
core and must be anchored at exterior supports (ACI 13.3.8.5).
Page 13 of 33
Direct Design Method
• Alternatively, either layer of steel may be placed in two bands parallel to the sides
of the slab. The positive and negative reinforcement, in any case, should be of a
size and spacing equivalent to that required for the maximum positive moment in
the panel, according to ACI 13.3.6.
Page 14 of 33
Direct Design Method
Page 15 of 33
Direct Design Method
Design Pb.1: Design the slab shown below (Follow the Direct Design Method for the
slab analysis).
Data Given:
A 75′ × 60′ building, divided into nine (9) panels using beams supported at their ends
on columns. Each panel is 20′ × 25′.
fc′ = 4 ksi
fy = 60 ksi
Height of building = 10′
Column dimensions = 14″ × 14″
Live load = 144 psf
20'-0"
Page 16 of 33
Direct Design Method
Solution: -
Check if the slab system satisfies all the limitations for Direct Design Method.
1) There must be a minimum of three continuous spans in each direction.
2) The panels must be rectangular, with the ratio of the longer to shorter spans
within a panel not greater than 2.
3) The successive span lengths in each direction must not differ by more than one
third of the longer span.
4) Loads must be due to gravity only and the service live load must not exceed 2
times the service dead load.
5) If beams are used on the column lines, the relative stiffness of the beam in the two
perpendicular directions, given by the ratio αl2/l1, must be in between 0.2 and 5.0.
6) Columns may be offset a maximum of 10 percent of the span in the direction of
the offset from either axis between centerlines of the successive columns.
Page 17 of 33
Direct Design Method
hw= 13"
hw= 13"
bw= 14"
bw= 14"
Note: -
IIS25 = Moment of inertia (MOI) of 25′ long interior slab.
IES25 = Moment of inertia (MOI) of 25′ long exterior slab.
IIS20 = Moment of inertia (MOI) of 20′ long interior slab.
IES20 = Moment of inertia (MOI) of 20′ long exterior slab.
IBINT = Moment of inertia of interior beam.
IBEXT = Moment of inertia of exterior beam.
α INT25 = Ratio of MOI of interior beam to MOI of 25′ long interior slab.
α EXT25 = Ratio of MOI of exterior beam to MOI of 25′ long exterior slab.
α INT20 = Ratio of MOI of interior beam to MOI of 20′ long interior slab.
α EXT20 = Ratio of MOI of exterior beam to MOI of 20′ long exterior slab
αm = (α INT25 + 2 × α INT20+ α EXT25)/4 {for panel A as shown in fig. 14}
= (2.7 + 2.2 + 2.2 + 3.9)/4 = 2.75
β = larger clear span / smaller clear span
= [{25 – (2 × (14/2)/12)}]/ [{20 – (2 × (14/2)/12)}] = 23.8 / 18.8 = 1.27
Page 18 of 33
Direct Design Method
25' 25'
Static Moment Mo (ft-k) 476 476
Exterior Interior
Section Positive Negative Positive Negative
Negative Negative
Distribution Factor,
0.16 0.57 0.7 0.65 0.35 0.65
ACI 13.6.3 (D.F)
Longitudinal Moment
77 272 334 310 167 310
(L.M) = Mo x D.F
Page 19 of 33
Direct Design Method
77 ft-k
77 ft-k
20" hf =7"
14"
C = 11210
Page 20 of 33
Direct Design Method
25' 25'
Static Moment M of beam (ft-k) 17 17
Exterior Interior
Section Positive Negative Positive Negative
Negative Negative
Distribution Factor (D.F) 0.16 0.57 0.7 0.65 0.35 0.65
Moment due to self weight
3 10 12 12 6 12
(MDSB) = M x D.F (ft-k)
Beam moment from slab (MDS)
61 188 230 214 115 214
(ft-k)
Total Moment (ft-k) 64 198 242 226 121 226
Page 21 of 33
Direct Design Method
B4 B3 B3 B4
B2 B2
C1 C2 C2 C1
B1 B1
C3 C4 C4 C3
B1 B1
C3 C4 C4 C3
C1 C2 C2 C1
B2 B2
B4 B3 B3 B4
Figure 18: Beam and Column plan.
Page 22 of 33
Direct Design Method
25'
RDL 53.3 k 53.3 k 53.3 k
1.42'
Vint = 60.59 k
10.81'
Vcr, int =54.52 k
45°
20'
B1 B1
25' 25'
Static Moment Mo (ft-k) 252 252
Exterior Interior
Section Positive Negative Positive Negative
Negative Negative
Distribution Factor(D.F) 0.16 0.57 0.7 0.65 0.35 0.65
Longitudinal Moment
40 144 176 164 88 164
(L.M) = Mo x D.F
40 ft-k
40 ft-k
Negative 0.81 x 164 = 133 0.85 x 133= 113 0.15 x 133 = 20 0.19 x 164 = 31
Interior
Positive 0.81 x 88 =71 0.85 x 71 = 61 0.15 x 71 = 11 0.19 x 88 = 17
Interior
0.81 x 176=143 0.85 x 144= 121 0.15 x 144 = 22 0.19 x 176 = 33
negative
Exterior Positive 0.81 x 144 =117 0.85 x 117= 99 0.15 x 117 = 18 0.19 x 144= 27
Exterior
0.88 x 40 =35 0.85 x 35 =30 0.15 x 35 = 5 0.12 x 40 = 5
negative
Note: Coefficients for lateral distribution have been taken from graph A.4, using αl2/l1, βt, and l2/l1.
Note: ACI 13.6.5.1 states that “Beams between supports shall be proportioned to
resist 85 percent of column strip moments if α1l2/l1 is equal to or greater than 1.0”.
20" hf =7"
14"
C = 11210
Figure 21: βt calculation.
25' 25'
Static Moment M of beam (ft-k) 17 17
Exterior Interior
Section Positive Negative Positive Negative
Negative Negative
Distribution Factor (D.F) 0.16 0.57 0.7 0.65 0.35 0.65
Moment due to self weight
3 10 12 12 6 12
(MDSB) = M x D.F
Beam moment from slab (MDS) 30 99 121 113 61 113
Total T.M 33 109 132 125 67 125
1.42'
Vint =32.16 k
10.74'
Vcr, int =28.9k
B2 B2
Step No 4: Design.
(1) Design of slab strips.
A. E-W Interior slab strip:
d = 5.5"
hf = 7"
ds = hf – 1 = 7 – 1 = 6″
dl = ds – bar dia = 6 – (4/8) = 5.5″ (for # 4 bar)
Asmin = 0.0018bhf (for fy = 60 ksi) = 0.0018 × 12 × 7 = 0.151 in2 (ρmin = 0.0023, in
terms of actual effective depth)
Now, Equation used to calculate (ρ) in (table 1.4) is as follows:
Mu = Φfyρbdl2{1-0.59ρfy/fc′) = 0.9 × 60 × ρ × 12 × 5.52 × {1-0.59 x ρ x 60/4}
After solving the above equation for ρ, we get:
ρ = [19602 ± √{(196022) - (4 x 173477.7 x Mu′ x 12)}]/2(173477.7)…….(A)
ds = hf – 1 = 7 – 1 =6″
dl = ds – bar dia = 6 – (4/8) = 5.5″ (for # 4 bar)
Asmin = 0.0018 × 12 × 7 = 0.151 in2 (ρmin = 0.0023, in terms of actual effective
depth)
Now, Equation used to calculate (ρ) values is as follows:
Mu = Φfyρbdl2{1-0.59ρfy/fc′} = 0.9 × 60 × ρ × 12 × 5.52 × {1-0.59 × ρ × 60/4}
After solving the above equation for ρ
ρ = [19602 ± √ {(196022) – (4 × 173477.7 × Mu′ × 12)}]/2(173477.7)
B2
B1
20'
20'
20'
B4
# 4 @ 9" c/c (T) # 4 @ 9" c/c (T) # 4 @ 9" c/c (T)
25'
# 4 @ 12" c/c (B)
Step No 5: Detailing.
PLAN
B3
A A
B4
B
Direct Design Method
#4 @ 12" c/c
#4 @ 12" c/c
Direct Design Method
18.83' 18.83'
SECTION A-A
#4 @ 12" c/c
#4 @ 9" c/c
#4 @ 12" c/c #4 @ 12" c/c
23.83' 23.83'
SECTION B-B