Mutual Compensation
Mutual Compensation
Abstract—Mutual coupling of multi-circuit lines affects The input to the relay point is the phase voltages and line
distance relay measurements during earth faults which include currents transformed with the help of voltage and current
zero sequence currents. The difficulty stems from the fact that transformers. When a fault occurs on the protected line, the
the lines are mutually coupled in their zero-sequence circuits. fault currents and voltages are monitored at the protection
This effect can cause distance protection on healthy circuits to
relay. The voltage drop along the line is equal to the product
mal-operate under fault conditions when mutual coupling was
not considered and when calculating impedance protection of the fault current Ie and the impedance fault Za.
settings. The multi-circuit lines need not be of the same voltage
levels to experience mutual coupling, and some coupling exists
even for lines that are not on the same tower. This paper studies Va
the effects of mutual coupling on parallel transmission lines and
how different system configurations affect the protection relay S R
settings. Finally, the paper describes using simulations the VS
effects off mutual coupling compensation to evaluate the CT Za
performance of the protection system.
VT
Ie
Keywords—Mutual Coupling, Mutual Compensation, Earth Fault
Fault, Distance Protection. Va=0
Z<
Relay
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.
The apparent impedance seen by the relay for an earth fault
in phase a is: where:
is the depth of penetration in the ground
f is the frequency in Hz
is the specific resistance in Ω/m
Dab is spacing in meters between the two conductors.
= (3)
+
Alternatively, Zmo can be measured using test equipment
when a line is out of service.
where:
Za is the relay phase to earth impedance For the typical case of parallel lines A and B, connected
Vph-e is the phase to earth short-circuit voltage at the at the local and remote busbars, as shown in Fig 2, the
relay located on the faulted phase apparent impedance Za of line A seen by the ground distance
Iph is the short-circuit current in the faulted phase function for an earth fault in phase a is [7]:
Ie is the earth fault current.
.
The correct operation of earth fault elements in distance 3. 2 −
= . + . (5)
relays is highly dependent on the correct application of k0. 1+
Various relays vendors have different forms of naming,
defining and applying these factors [4]. For the protection of phase to earth faults, a measuring
error occurs. This error appears because the parallel line earth
II. GENERAL CONSIDERATION FOR PARALLEL LINES current (Ie-b = 3I0) which induces a voltage Ie-b × (Zm0 /3) into
the fault loop.
The most common problems concerning distance
protection of parallel lines ending at the same bus without From equation (5) it can be deduced [5]:
mutual compensation can be summarised as follows [5] :
• The error is proportional to the mutual coupling
• A tendency to underreach when both lines A and B factor Zmo/3ZL1.
are energised. • The error increases with the parallel line earth
• A tendency to overreach when one of the lines is current Ie-b in relation to the relay current Iph-a+k0Ie-a.
disconnected and earthed at both ends. • The relay underreaches when the parallel current
Ie-b is in phase with Iph-a and Ie-a.
l
• The relay overreaches when Ie-b and Iph-a /Ie-a have
opposite signs.
S Line B Ie-b , Iph-b R
VS VR
Simulations demonstrate that a relay, using fixed settings
to protect 85% of the total line length, protects at a specific
Line A Ie-a , Iph-a Zm0
moment only 50 % of the line, while at another moment its
actual coverage is more than 100 %, depending on the power
Z< F system configuration [8].
x l-x
For lines having only one supply at one end of the line,
Fig 2. Parallel circuit fed from both ends these values become even worse. The actual coverage is so
widespread that the relay settings must be adapted to the
The coupling impedance Zmo between the zero-sequence operation mode of the double circuit line.
systems of two lines with an earth-wire is estimated using the
following equation [6]: In the following analysis, different scenarios and
switching states of the parallel line system and the measured
impedances are discussed. In each case for a fault at the end
of the parallel line, with the following assumptions are made:
Ω
= . + . . (4)
4 • The phase current and zero-sequence current of the
protected line are equal (Iph-a=3I0)
• The parallel line residual current is equal to the
= 4 . 10 Ω. residual current of the protected line.
= 658
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.
A. Double-circuit lines with Lines A and B operated in C. Double-circuit lines with Line B disconnected (one or
parallel both ends isolated)
Network 1 Network 2
Line B
Line A
Network 1 Network 2
Line B
S R
Line B
VS VR
Zmo
Line A
Zm0
Line A
Z< F
Fig 4. Parallel circuit switched off and earthed on both ends Fig 6. Mutual compensation using the zero-sequence current from line B into
the ground distance relay in line A
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.
The compensate earth factor can be calculated using:
TABLE II. DISTANCE RELAY PROTECTION SETTING PARAMETERS
1 Grading +Rreach +Rph-ph +Xph-e Time delay
= −1 (9) (Reach) Ω Ω Ω (s)
3
Zone 1 (85%) 6.12 2.29 8.23 0.0
Zone 2 (120%) 8.64 2.50 9.72 0.4
1 Zone 3 (300%) 21.60 3.54 11.61 0.7
= −1 (10)
3
The mutual earth factor can be calculated using: Within DigSilent PowerFactory, and using the IEC 60909
method, an SLG fault was performed at 75% and 85% of line
1 A with the parallel line energised and de-energised, from
= −1 (11) where the relay is.
3
1
= −1 (12)
3
= . . (13)
The distance protection relay slot shown in Fig 7, included Fig 9. R-X Plot for SLG fault at 85% of line A, with line B disconnected
a CT-Mutual measuring input to which the earth current of
the parallel line was connected. With line A compensated and line B disconnected, the
relay of the energised circuit measures the fault impedance
correctly. The relay correctly operated for a fault in zone 1.
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.
It was observed that the fault (75%), this time determined
by the relay to be outside of zone 1. This is due to the Mutual
Coupling Effect.
Fig 13. R-X Plot for an SLG fault at 75%, with both line A and B connected
An SLG fault is applied at 75% of line A. Line B is now and fault resistance of 18Ω with compensation
connected. Mutual compensation has been applied.
F. Analysis of an SLG at 75% on line A, with line B,
disconnected and earthed with a fault resistance of 18Ω.
(No mutual compensation applied)
An SLG fault is applied at 75% of line A. Line B is now
disconnected and earthed. Mutual compensation has been
removed.
Fig 11. R-X Plot for an SLG fault at 75% of line A, with both line A and B
connected
Fig 14. R-X Plot for SLG fault at 75%, with both line A and B connected
and fault resistance of 18Ω with no compensation
D. Analysis of an SLG at 75% on line A and B connected.
(No mutual compensation) It was observed that the fault (75%), this time determined
by the relay to be outside of zone 1. This is due again to the
To see the effect of the mutual coupling on the relay Mutual Coupling Effect.
impedance measurement without the proper compensation,
the “Mutual Earth Factor” values were set to zero.
Alternatively, the reference CT in the adjacent line can be IV. CONCLUSION
disconnected. Distance relays must be compensated against the coupling
present between parallel lines. This will otherwise affect the
measured impedance under earth fault conditions.
Compensation the mutual effects of parallel lines by
referencing the residual current from the parallel line into the
distance relay of the protected line is complex and can lead to
incorrect operation and testing. Also, there are many system
configurations that will defeat this method of compensation.
It is also impossible to compensate this way when several
lines are in parallel or when a line is out of service.
In some cases, the overhead line positive and zero
sequence impedances are measured as part of the
Fig 12. R-X Plot for an SLG fault at 75%, with both line A and B, connected
with no compensation commissioning tests of an overhead line. The actual
measurement of the fault-loop impedance is the best way to
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.
ensure that the distance relay settings are correct. Where 2008), 17-20 March 2008 2008, pp. 649-653, doi:
10.1049/cp:20080115.
measured line impedance data is available, this should be
used in preference to the calculated or simulated impedances. [4] E. Sorrentino, "Comparison of five methods of compensation for the
Line impedances and k factors are critical for a fully ground distance function and assessment of their effect on the resistive
reach in quadrilateral characteristics," International Journal of
operational distance protection relay. The recommended Electrical Power & Energy Systems, vol. 61, pp. 440-445, 2014/10/01/
method to determine the settings for distance protection 2014, doi: https://doi.org/10.1016/j.ijepes.2014.03.049.
relays requires a thorough knowledge of the relay’s reach, [5] CIGRE, "Modern Distance Protection Functions and Applications,"
and its k factors in order to provide proper protection. 2008. [Online]. Available: https://e-cigre.org/publication/359-modern-
distance-protection-functions-and-applications
REFERENCES
[6] Siemens, "Applications for SIPROTEC Protection Relays," 2005.
[1] J. Holbach, V. Vadlamani, and Y. Lu, "Issues and Solutions in Setting
a Quadrilateral Distance Characteristic," in 2008 61st Annual [7] A. G. Worldwide, Network Protection & Automation Guide. Alstom
Conference for Protective Relay Engineers, 1-3 April 2008 2008, pp. Grid, 2011.
89-104, doi: 10.1109/CPRE.2008.4515049.
[8] A. G. Jongepier and L. v. d. Sluis, "Adaptive distance protection of a
[2] V. Sellwood, U. Klapper, M. Kruger, and S. Kaiser, "A new technique double-circuit line," IEEE Transactions on Power Delivery, vol. 9, no.
for setting distance protection and fault location by measurement of 3, pp. 1289-1297, 1994, doi: 10.1109/61.311155.
transmission line system impedance characteristics," in The 8th IEE
[9] DIgSILENT, Distance Tutorial, 2017. [Online]. Available:
International Conference on AC and DC Power Transmission, 28-31
http://www.digsilent.de.
March 2006 2006, pp. 197-199, doi: 10.1049/cp:20060040.
[3] P. J. Moore, K. Muhalhel, and C. Booth, "Distance relay behaviour on
mixed voltage, double circuit lines," in 2008 IET 9th International
Conference on Developments in Power System Protection (DPSP
Authorized licensed use limited to: Middlesex University. Downloaded on November 02,2020 at 16:09:42 UTC from IEEE Xplore. Restrictions apply.