Chapter 4 Transmission Line Paramters - pptx1
Chapter 4 Transmission Line Paramters - pptx1
Chapter 4
Transmission
Line
MSS
(Voltage Pers.)
(Length Pers.) (Design Pers.)
HV :110 KV -365 KV
EHV : 365 – 800 KV
UHV: above 800 KV
(Run Pers.)
Overhead Underground
MSS
1
12/24/2023
The ACSR conductors are more commonly used as they have following advantages,
4
1. They have low corona loss.
2. Skin effect is to Deduce extent.
3. Due to high mechanical strength, the line span can be increased. This minimizes cost of
erection and maintenance.
4. These conductors are inexpensive as compared to copper conductors having equal Resistance
without reduction in efficiency, useful life span and durability.
The conductors used in transmission system are stranded except for small cross section. These
conductors are electrically in parallel and spiraled together. Due to use of stranded conductors,
the skin effect is Reduced.
NOTE: Skin effect is negligible when the supply frequency is low ( less than 50 Hz) and conductor
diameter is less than 1.0 cm
Skin Effect. The tendency of current to move outward the surface of conductor.
Skin effect depends upon the following factors:
1. Nature of material
2. Diameter of wire
3. Frequency
4. Shape of wire
MSS
2
12/24/2023
5 The conductor size is decided based on its current carrying ability and voltage level on which it is
working. The total number of strands N for n layers of strands in a conductor for uniform each strand
are given by,
𝑵 = 𝟑𝒏𝟐 − 𝟑𝒏 + 𝟏
The overall outer diameter D if the diameter of one strand is d is given by
𝑫 = 𝟐𝒏 − 𝟏 𝒅
INSULATORS: Insulators for transmission lines above 69 kV are typically suspension-type insulators,
that consist of a string of discs constructed of porcelain, toughened glass, or polymer.
MSS
SUPPORT STRUCTURES: Transmission lines employ a variety of support structures. Figure 4.2 shows a self
6 supporting, lattice steel tower typically used for 500- and 765-kV lines. Double-circuit 345-kV lines usually have self-
supporting steel towers with the phases arranged either in a triangular configuration to reduce tower height or in a
vertical configuration to reduce tower width (Figure 4.3). Wood frame configurations are commonly used for voltages
of 345 kV and below (Figure 4.5).
SHIELD WIDES: Shield wires located above the phase conductors protect the phase conductors against lightning. They
are usually high- or extra-high-strength steel, Alumoweld, or ACSR with much smaller cross section than the phase
conductors. The number and location of the shield wires are selected so that almost all lightning strokes terminate on the
shield wires rather than on the phase conductors. Figures 4.2, 4.3, and 4.5 have two shield wires. Shield wires are
grounded to the tower.
MSS
3
12/24/2023
Parameters of
TL
MSS
8 ELECTDICAL FACTODS :
MECHANICAL FACTODS:
Mechanical design focuses on the strength of the conductors, insulator strings, and support structures.
ENVIDONMENTAL FACTODS
Environmental factors include land usage and visual impact.
ECONOMIC FACTODS
The optimum line design meets all the technical design criteria at lowest overall cost, which includes
the total installed cost of the line as well as the cost of line losses over the operating life of the line.
MSS
4
12/24/2023
9 RESISTANCE
DC Resistance: The dc Resistance of a conductor at a specified temperature T is
Resistivity depends on the conductor metal. Annealed cooper is the international standard for measuring
resistivity 𝜌(or conductivity 𝜎, where 𝜎 = 1⁄𝜌) or conductivity. Resistivity of conductor is listed in Table
4.3. As shown, hard-drawn aluminum, which has 61% of the conductivity of the international standard,
has a resistivity at 20 𝐶 ° 𝐶 of 17 Ωcmil/ft. or 2.83 × 10 Ω𝑚.
MSS
10
2. Temperature: 𝜌 =𝜌 ×
10
5
12/24/2023
𝑅 , ° 0.303 𝑅 , ° 0.278
= = 1.003 = = 1.007
𝑅 ° 0.302 𝑅 ° 0.276
Thus, the 60-Hz Resistance of this conductor is about 0.3 to 0.7% higher than the dc Resistance. The variation of
these two ratios is due to the fact that Resistance in Table A.3 is given to only three significant figures. MSS
11
12 CONDUCTANCE
Conductance accounts for real power loss between conductors or between conductors and ground. For
overhead lines, this power loss is due to leakage currents at insulators and to corona. Insulator leakage
current depends on the amount of dirt, salt, and other contaminants that have accumulated on insulators,
as well as on meteorological factors, particularly the presence of moisture. Corona occurs when a high
value of electric field strength at a conductor surface causes the air to become electrically ionized and to
conduct.
INDUCTANCE: SOLID CYLINDRICAL CONDUCTOR
The inductance of a magnetic circuit that has a constant permeability 𝜇 can be obtained by determining the
following:
1. Magnetic field intensity H, from Ampere’s law
2. Magnetic flux density B = 𝜇𝐻
3. Flux linkages λ L = 𝜆/𝐼
4. Inductance from flux linkages per ampere L = 𝜆/𝐼 𝜇 = 𝜇 = 4𝜋 × 10 𝐻/𝑚
𝐼 𝐴 𝑥 𝜋𝑥 𝑥
= = =
𝐼 𝐴 𝑟 𝜋𝑟 𝑟
MSS
12
6
12/24/2023
MSS
13
14
Finally, consider the array of M solid cylindrical conductors shown in Figure . Assume that each
conductor m carries current Im referenced out of the page. Also assume that the sum of the currents is
zero—that is,
MSS
14
7
12/24/2023
15
INDUCTANCE: SINGLE-PHASE TWO-WIRE LINE AND 3-PHASE 3-WIRE
LINE WITH EQUAL PHASE SPACING
MSS
15
𝐷 𝐷 𝐷 …𝐷
𝜆 = 2 × 10 𝐼𝑙𝑛 𝑊𝑏𝑡/𝑚
𝑟 𝐷 𝐷 …𝐷
𝜆 𝐷 𝐷 𝐷 …𝐷 𝐿 + 𝐿 + 𝐿 + ⋯+ 𝐿
𝐿 = = 2 × 10 𝑙𝑛 𝐻 ⁄𝑚 𝐿 = 𝐻 ⁄𝑚
𝐼 ⁄𝑛 𝑟𝐷 𝐷 …𝐷 𝑛
𝜆 𝐷 𝐷 𝐷 …𝐷
𝐿 = = 2 × 10 𝑙𝑛 𝐻 ⁄𝑚
𝐼 ⁄𝑛 𝐷 𝑟 𝐷 …𝐷
𝐿 𝐿 +𝐿 + 𝐿 + ⋯+ 𝐿
𝐿 = = 𝐻 ⁄𝑚
𝑛 𝑛
… … … …
𝐿 = 2 × 10 × 𝑙𝑛 𝐻 ⁄𝑚
… … … …
MSS
16
8
12/24/2023
𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =𝐷 = 0.7788 𝑟
𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =
𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =2r
𝐷 =𝐷 =𝐷 =𝐷 =𝐷 =𝐷 = 2 3r
𝐷 =𝐷 =𝐷 = 4r
𝐺𝑀𝑅 = 𝑟 × 2𝑟 × 2 3r × 4𝑟
MSS
17
×
𝐺𝑀𝐷 = 𝐺𝑀𝐷 = 𝐷 𝐷 𝐷 ;𝐷 𝐷 ;𝐷
𝐺𝑀𝑅 = 𝐷 ×𝐷 ×𝐷 𝐷 ×𝐷 ×𝐷 𝐷 ×𝐷 ×𝐷
18
9
12/24/2023
19
𝐺𝑀𝐷 3.189
𝐿 = 2 × 10 × 𝑙𝑛 = 2 × 10 × 𝑙𝑛 = 4.644 × 10 𝐻 ⁄𝑚 𝑝𝑒𝑟 𝐶𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟
𝐺𝑀𝑅 0.3128
.
𝐿 = 2 × 10 × 𝑙𝑛 = 6.992 × 10 𝐻 ⁄𝑚 𝑝𝑒𝑟 𝐶𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟
.
1 1 1 1
𝜆 = 2 × 10 𝐼 𝑙𝑛 + 𝐼 + 𝐼 𝑙𝑛 = 2 × 10 𝐼 𝑙𝑛 − 𝐼 𝑙𝑛
𝐷 𝐷 𝐷 𝐷
𝐷
= 2 × 10 𝐼 𝑙𝑛 𝑊𝑏𝑡/𝑚
𝐷
𝜆 𝐷
𝐿 = = 2 × 10 𝑙𝑛 𝐻 ⁄𝑚
𝐼 𝐷 MSS
19
20
MSS
20
10
12/24/2023
Solution: The GMD between conductor centers is Dxy= 5 ft. Also, from Table A.3, the GMD of a 4/0 12-strand
copper conductor is Dxx =Dyy=0.01750 ft.
MSS
21
22
Solution: From Table A.4, the GMD of a 1,590,000 cmil 54/3 ACSR conductor is
MSS
22
11
12/24/2023
23 Bundled Conductor
EXAMPLE 4.5: Calculate the inductive reactance of the system given below
From Table A.4, the GMD of a 795,000 cmil 26/2 ACSR conductor is
MSS
23
𝑞 𝑉 𝐹
𝜀𝐸 2𝜋𝑥 = 𝑞 → 𝐸 = 𝑤ℎ𝑒𝑟𝑒 𝜀 = 8.854 × 10 𝑖𝑛 𝑓𝑟𝑒𝑒 𝑠𝑝𝑎𝑐𝑒
2𝜋𝜀𝑥 𝑚 𝑚
𝑞 𝑞 𝐷
𝑉 = 𝐸 𝑑𝑥 = 𝑑𝑥 = 𝑙𝑛
2𝜋𝜀𝑥 2𝜋𝜀𝑥 𝐷
MSS
24
12
12/24/2023
25
𝑞 𝐷 1 𝐷
𝑉 = 𝑙𝑛 𝑣𝑜𝑙𝑡𝑠 𝑉 = 𝑞 𝑙𝑛 𝑣𝑜𝑙𝑡𝑠
2𝜋𝜀 𝐷 2𝜋𝜀 𝐷
1 𝐷 𝐷 𝑞 𝐷 𝐷 𝑞 𝐷. 𝐷 𝑞 𝐷
𝑉 = 𝑞𝑙𝑛 − 𝑞𝑙𝑛 = 𝑙𝑛 = 𝑙𝑛 = 𝑙𝑛
2𝜋𝜀 𝐷 𝐷 2𝜋𝜀 𝐷 𝐷 2𝜋𝜀 𝑟𝑟 𝜋𝜀 𝑟𝑟
𝑞 𝑞 𝜋𝜀 𝜋𝜀
𝐶 = = = = 𝐹⁄𝑚 𝑙𝑖𝑛𝑒 − 𝑡𝑜 − 𝑙𝑖𝑛𝑒
𝑉 𝑞 𝐷 𝐷 𝐷
𝑙𝑛 𝑙𝑛 𝑙𝑛
𝜋𝜀 𝑟𝑟 𝑟𝑟 𝑟
MSS
25
26
F𝐨𝐫 𝟑 − 𝝓 𝟑 − 𝒘𝒊𝒓𝒆 Line with Equal Phase Spacing
With 𝑘 = 𝑎, 𝑖 = 𝑏, 𝑎𝑛𝑑 𝑚 = 𝑎 , 𝑏, 𝑎𝑛𝑑 𝑐
1 𝐷 𝐷 𝐷 1 𝐷 𝑟 𝐷
𝑉 = 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 = 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛
2𝜋𝜀 𝐷 𝐷 𝐷 2𝜋𝜀 𝑟 𝐷 𝐷
= 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛
Similarly With 𝑘 = 𝑎, 𝑖 = 𝑐, 𝑎𝑛𝑑 𝑚 = 𝑎 , 𝑏, 𝑎𝑛𝑑 𝑐
1 𝐷 𝐷 𝐷 1 𝐷 𝐷 𝑟 1 𝐷 𝑟
𝑉 = 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 = 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛 = 𝑞 𝑙𝑛 + 𝑞 𝑙𝑛
2𝜋𝜀 𝐷 𝐷 𝐷 2𝜋𝜀 𝑟 𝐷 𝐷 2𝜋𝜀 𝑟 𝐷
MSS
26
13
12/24/2023
27
4.10 CAPACITANCE: STRANDED CONDUCTORS, UNEQUAL PHASE
SPACING, BUNDLED CONDUCTORS
MSS
27
28
EXAMPLE 4.6 Capacitance, admittance, and reactive power supplied:
single-phase line
A single-phase line operating at 60 Hz consists of two 4/0 12-strand copper conductors with 5 ft spacing
between conductor centers. The line length is 20 miles. determine the line-to-line capacitance in F and the
line-to-line admittance in S. If the line voltage is 20 kV, determine the reactive power in kvar supplied by
this capacitance.
SOLUTION
The GMD between conductor centers is Dxy= 5 ft. Also, From Table A.3, the outside radius of a 4/0 12-
strand copper conductor is
0.552
𝑟= = 0.276 𝑖𝑛 = 0.023 𝑓𝑡
2
𝜋 8.854 × 10
𝐶 = = 5.169 × 10 𝐹/𝑚
𝑙𝑛 5⁄0.023
𝐹 𝑚
𝐶 = 5.169 × 10 × 1609 × 20 𝑚𝑖 = 1.66 × 10 𝐹
𝑚 𝑚𝑖
𝑌 = 𝑗𝜔𝐶 = 𝑗 2𝜋60 1.66 × 10 = 𝑗6.27 × 10 𝑆 𝑙𝑖𝑛𝑒 − 𝑡𝑜 − 𝑙𝑖𝑛𝑒
𝑄 = 6.27 × 10 20 × 10 = 25.1 𝐾𝑉𝐴𝑅
MSS
28
14
12/24/2023
MSS
29
Similar equations for Vab can written for the positions 2 and 3. and same for Vba
and Vca in each positions. Knowing that 𝑉 = we can find that
2𝜋𝜀 Comparing this equation with the
𝐶 = 𝐹 ⁄𝑚 𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙
𝐷 𝐻 𝐻 𝐻 previous we found, a difference of
𝑙𝑛 − 𝑙𝑛
𝑟 𝐻𝐻 𝐻
𝑙𝑛 is seen
Note: the conductors are very high above the ground, then 𝐻 =𝐻 ,𝐻 = 𝐻 and 𝐻 = 𝐻 . Then
𝐻 𝐻 𝐻 ≅ 𝐻 𝐻 𝐻 and we can obtain the previous equation, that is 𝐶 = 𝐹 ⁄𝑚 MSS
𝑡𝑜 𝑛𝑒𝑢𝑡𝑟𝑎𝑙
30
15
12/24/2023
MSS
31
16