Planning Circular Building Code of Australia 2012 Key Changes 2012 07 27 - Subestaciones Electricas - Class 8
Planning Circular Building Code of Australia 2012 Key Changes 2012 07 27 - Subestaciones Electricas - Class 8
Planning Circular Building Code of Australia 2012 Key Changes 2012 07 27 - Subestaciones Electricas - Class 8
BUILDING SYSTEM
Building regulation advisory note
Circular BS 12 001
Related
• changes to the provisions for wet areas in • AS 1720 ‘Timber structures – Part 1 Design
buildings methods’ - Amendments 1 and 2.
• in Volume Two, removal of the Acceptable • AS 1926 ‘Swimming pool safety:
Construction Practice (ACP) for masonry.
o Part 2 Location of safety barriers for
Other amendments relate to: swimming pools’ - Amendment 2;
• minor technical changes o Part 3 Water recirculation systems’ -
Amendment 1.
• update of referenced documents.
• AS/NZS 3500 ‘Plumbing and drainage – Part 4
Amendments to NSW Variations update references to ‘Heated water services’ - Amendment 2.
reflect current terms and practices and clarify certain
current requirements. • AS 3600 ‘Concrete structures’ - Amendment 1
to the 2009 edition.
Changes to Referenced Documents
• AS 3959 “Construction of buildings in bushfire-
New editions and new references adopted prone areas’ - Amendment 3.
• AS/NZS 1170.2 ‘Structural design actions - • AS 4100 ‘Steel structures’ - Amendment 1.
Part 2 Wind actions’ - 2011 edition with 2002
edition required for determination of design • AS/NZS 4600 ‘Cold-formed steel structures’ -
wind speed (2002 edition retained for 12 Amendment 1.
months transition).
• NASH Standard ‘Residential and low-rise steel
• AS 2870 ‘Residential slabs and footings – framing – Part 1 Design criteria’ - Amendment
Construction - 2011 edition (1996 edition C.
retained for 12 months transition).
• In Volume Two only – AS 4773 ‘Masonry for
• AS/NZS 3666 ‘Air handling and water systems small buildings – Part 1 Design’ - Amendment
of buildings – Microbial control’ - 2011 editions 1.
of:
Deletions
o ‘Part 1 Design, installation and • AS 1038.15 – 1995 ‘Coal and coke – Analysis
commissioning’ and testing, Part 15 Higher rank coal ash and
coke ash – Ash fusibility’ - replaced by ISO
o ‘Part 2 Operation and maintenance’.
540 (see above).
• AS 3700 ‘Masonry structures’ - 2011 edition.
• ARI 460 – 2000 ‘Remote mechanical draft air
• AS 3740 Waterproofing of domestic wet areas’ cooled refrigerant condensers’ - transition with
- 2010 edition: Note also a change of title from AHRI 460 2005 completed.
the previous edition.
• ARI 550/590 – 1998 ‘Water chilling packages
• ISO 540 ‘Hard coal and coke – Determination using the vapour compression cycle’ -
of ash fusibility’ - 2008 edition replaces AS transition with AHRI 550/590 2003 completed.
1038.15 (see below).
• AS 3600 – 2001 ‘Concrete structures’ -
• ABCB ‘Protocol for Structural Software 2011 transition with the 2009 edition completed.
edition - new reference.
• Reference of AS 1288 Amendment 2 has
• In Volume One Only - Education and Care resulted in the deletion of:
Services National Law Act (Vic) - new o ASTM C1279 - 2009 ‘Standard test
reference (equivalent national law act for NSW method for specific stresses on glass’;
referenced in the NSW Footnote of other
legislation). o AS/NZS 2208 - 1996 ‘Safety glazing
materials in buildings’
• In Volume Two only – AS 1397 ‘Continuous
hot dip metallic coated sheet steel and strip- o EN 14179 – 2005 ‘Glass in buildings’ -
coatings of zinc and zinc alloyed with heat soak test for specified glass
aluminium and magnesium’ - 2011 edition: types.
Note also a change of title from the previous
• ABCB Protocol for House Energy Rating
edition (2001 edition retained for 12 month
Software – replaced by a new definition that
transition).
recognises NatHERS as the appropriate
Amendments adopted accreditation scheme for house energy rating
• AS 1288 ‘Glazing in buildings – Selection and software.
installation‘ - Amendment 2. • In Volume Two only
• AS 2159 ‘Piling – Design and installation’ - o AS/NZS 2699 - 2000 ‘Built in
Amendment 1. components for masonry construction
– Part 1 Wall ties – no longer
2/5
Department of Planning & Infrastructure – Building Circular BS 12-001
• Wet areas in buildings (F1.7 and Part 3.8.1) • Minor technical changes
Relevant parts of each volume of the BCA Some minor changes have been made in
have been restructured to include a table of each volume.
requirements for when an element in a wet
area of a building must be waterproof or water Changes made in Volume One of BCA 2012:
resistant. The provision continues to be
applicable to a building of Class 1, 2 and 3 or • Verification Method for emergency lighting
a Class 4 part of a building and requires (EV4.1):
compliance with the newly referenced 2010
edition of AS 3740. A new Verification Method has been included
for verifying if a proposed emergency lighting
In Volume Two, the Acceptable Construction system meets the safe illumination level
Manual has been removed, as AS 3740 no required by the Performance Requirement.
longer stands alone. It must be used in
conjunction with the requirements of the table The Verification Method stipulates lux levels to
and together, form the Acceptable be achieved in various areas and the time
Construction Practice (ACP). All other frames for achieving and maintaining those
previous provisions in the ACP have been levels.
removed.
• Early childhood centres (F2.3, F2.5, F4.2,
GP1.5 and G1.3)
3/5
Department of Planning & Infrastructure – Building Circular BS 12-001
Requirements for facilities in early childhood requirement has been changed from vehicles
centres have been expanded to align with to vehicle ‘spaces’ on the basis that a ‘space’
those aspects of the National Quality is a more defined, measurable concept.
Framework for early childhood education and
care that affect the design and construction of As a consequential amendment, the definition
centres and their facilities. of ‘private garage’ has also been changed to
refer to ‘spaces’.
New provisions include:
• Class 8 electrical network substations
o a new definition that relates to the (ENS) (numerous provisions)
provision of a centre-based education and
care service within the meaning of the Class 8 ENS have been exempted from the
Education and Care Services National BCA requirements for a range of installations
Law legislation. Services that are licensed and facilities, on the basis of the control
or approved under state and territory systems applied to the design and
children's services law are also referenced construction of these buildings through the
national and state-based network provider
o kitchens must restrict the access of
legislation.
children by using child-proof latches
o required nappy change facilities for Class 8 ENS are purpose built, usually
children under three years of age – size, unoccupied and contain hazardous electrical
dimensions and facilities are specified equipment. As water is inappropriate when
dealing with fires in electrical equipment, BCA
o adult hand washing facilities required in
provisions for fire hose reels, hydrants and
kitchen and nappy change areas
sprinklers are affected, among other things.
o the ability to supervise the facility from
specified areas. Note: this provision may The control systems of the network providers
affect the design of an early childhood include measures that compensate for the
centre from its early stages exemptions provided in the BCA.
o sanitary facilities for children to be
The term ‘electrical network substation’ has
accessible from indoor and outdoor play
been defined to provide an understanding of
areas and constructed to meet specified
the intended application of the concessions
requirements
only to substations that meet the specified
o a percentage of the windows in children’s criteria.
rooms to have low sill heights to provide
children with visibility of adjacent areas
and the outside Changes made in Volume Two of BCA 2012:
o the BCA requires the provision of a barrier
• Masonry (Part 3.3)
around an outdoor play area that complies
with AS 1926.1. It also specifies the
AS 4773 Masonry for Small Buildings was
modified application of the standard to
referenced as an Acceptable Construction
ensure the barrier is designed to keep
Manual (ACM) in BCA 2011, and the
children inside the play area. The
Acceptable Construction Practice (ACP)
modification is required, as AS 1926.1
provisions were retained for a 12 month
provides requirements for a barrier to keep
transition.
children out of a swimming pool.
In BCA 2012, the ACP from 3.3.1 to 3.3.4, has
• Carpark ventilation (F4.11) been deleted, following completion of the
transition period. This new reference to AS
Requirements for an atmospheric contaminant 4773 now replaces the ACP and forms an
monitoring system installed in a carpark have alternative ACM to AS 3700.
been relocated from Part J5 to Part F4.
Carpark ventilation requirements are now • Energy Efficiency (Part 3.12)
located with other ventilation requirements
relative to health and safety. In addition to the changes affected in both
volumes as above, in Volume Two, changes to
The provisions have been expanded to allow a the Australian Government’s Renewable
choice of strategies to control the ventilation – Energy Target scheme have resulted in the
a mechanical system of intermittent operation term ‘Renewable Energy Certificate’ being
to provide a minimum number of air changes replaced by the term ‘Small-scale Technology
per hour during a given period or natural Certificate’.
ventilation equivalent to the mechanical rate.
4/5
Department of Planning & Infrastructure – Building Circular BS 12-001
• Referenced documents (NSW This and other Department of Planning & Infrastructure
Specification A1.3 and Part 1.4) building circulars are published on the web at:
http://www.planning.nsw.gov.au/building-system-
The Swimming Pools Act, the Swimming Pools circulars
Regulation, the Environmental Planning and
Assessment Act, the Environmental Planning Authorised by:
and Assessment Regulation and the Rural Susan Budd
Fires Act have been added to the NSW Tables A/Executive Director
of Referenced Documents, due to their
references in the NSW variations.
The Rural Fire Service’s “Planning for Bushfire Important note: This circular does not constitute legal advice. Users are advised to
seek professional advice and refer to the relevant legislation, as necessary, before
Protection” has been deleted from NSW taking action in relation to any matters covered by this circular.
Tables of Referenced Documents as the NSW
Variations were previously amended and the © State of New South Wales through the Department of Planning & Infrastructure
document was no longer referred to. www.planning.nsw.gov.au
Disclaimer: While every reasonable effort has been made to ensure that this
• Footnote: Other legislation affecting document is correct at the time of publication, the State of New South Wales, its
buildings agencies and employees, disclaim any and all liability to any person in respect of
anything or the consequences of anything done or omitted to be done in reliance
References have been updated to reflect new upon the whole or any part of this document.
names of departments and agencies and to
include the new regulating agencies for
plumbing and children’s services.
5/5