Man Service Letter
Man Service Letter
Man Service Letter
SL2018-668/KNB
December 2018
Concerns
Owners and operators of MAN B&W
two-stroke marine diesel engines.
Type: MC/MC-C and ME/ME-C
Dear Sir or Madam
Summary
We have recently received reports of malfunctioning starting air Correct maintenance of starting air
systems that led to rupture of the starting air manifold. Based on system to avoid any ruptures
our findings in these cases we would like to emphasise the im-
portance of correct and timely overhaul of the starting air system
and of the main engine in order to minimise the risk of suffering
personal injuries or causing damage to the engine. Correct and
timely maintenance is to be carried out according to the instruc-
tion manual delivered with the engine.
Yours faithfully
Head office (& po. address) PrimeServ Production Forwarding & Receiving MAN Diesel & Turbo
MAN Energy Solutions Teglholmsgade 41 Teglholmsgade 35 Teglholmsgade 35 Branch of MAN Energy Solutions
Teglholmsgade 41 2450 Copenhagen SV 2450 Copenhagen SV 2450 Copenhagen SV SE, Germany
2450 Copenhagen SV Denmark Denmark Denmark CVR No.: 31611792
Denmark Phone: +45 33 85 11 00 Phone: +45 33 85 11 00 Phone: +45 33 85 11 00 Head office: Teglholmsgade 41
Phone: +45 33 85 11 00 Fax: +45 33 85 10 49 Fax: +45 33 85 10 17 Fax: +45 33 85 10 16 2450 Copenhagen SV, Denmark
Fax: +45 33 85 10 30 [email protected] [email protected] [email protected] German Reg.No.: HRB 22056
[email protected] Amtsgericht Augsburg
www.man-es.com
Service Letter SL2018-668/KNB
Normally, only a single bursting disc will be found rup- The bursting disc must be exchanged and the starting
tured, and the branch pipe as well as the starting air air valve must be overhauled at the earliest opportunity if
valve will have been heated up by the combustion gas- the bursting disk has ruptured.
5
6
8 Bursting cap
Explosion in the starting air system Open drain pipes (gravity drain)
In the worst case an explosion in a starting air manifold
may lead to rupture of the manifold. Such incidents pose a
serious potential threat to property and persons, and may
even result in bodily injuries and/or fatal casualties. Proper
and timely maintenance can prevent such incidents.
If the drains are blocked, a combustible mixture may be Fig. 2: Main starting air valve
trapped inside the manifold or the branch pipes and thus
become a hazard, see Fig. 4.
Fig. 4: Starting air pipe bend after main starting air valve towards
engine
The most likely reason for the unintended combustible mixtures can be one of the below or a combination:
If an oily substance is present, the origin of the substance must be found and remedied as soon as possible.
Any fuel leakage from fuel valves or pipings on the cylinder cover must be remedied as soon as possible.
In case of a defect O-ring the starting air valve must be overhauled as soon as possible.
The below shown Figure shows an example of an open drain modified in a way that obstructs the intended
draining of the manifold by means of gravity. Any kind of modification to the drain pipe is prohibited for safety
reasons as modifications may increase the risk of blocking the pipes or create a water-lock in the pipe.
Fig. 7: Fluoro rubber O-ring, green Fig. 8: Silicone rubber O-ring, red (NOT to be used)
Proposal for regular onboard routine check to prevent Test procedure for checking of external air leakage
failures in the starting air system, as a supplement to from starting air valves for MC/MC-C engines
normal start-up inspections and procedures:
– Prepare the engine for start.
– The drain point positioned at the starting air manifold – The engine control is shifted to manual control at the
must always be open to ensure free drainage based engine side console.
on gravity. – The air supply for the starting air distributor is “cut
off” on the starting air distributor valve handle.
At engine start-up – 1 person is located at the engine side console.
Immediately after starting the engine, listen for a – At least 1 person is positioned on top of the engine to
“hissing sound” from the drain points when venting check for leakages.
the starting air manifold from 30 bar pressure to 0. – Press the start bottom on the engine side console
and check that the shaft is not rotating.
At “Finished with engine”
Visually inspect the area below the drainpipes for water If the shaft rotates partly, a starting air valve is leaking
or oily substance. Check by poking a steel rod through – Press the start button and keep it active when the
the pipe and watch for overpressure and fluids. tightness from starting air valves and the complete
starting air system has been checked for leakages.
Visually inspect for fuel leakage during daily routine
watch. Check that the drain from the cylinder cover is All starting air valves are to be checked for leakages
open and working properly. from the sealing in the cylinder cover.
Before start-up of engine This test can also be made with the engine in C/R control
The drain groove in the cylinder cover around the with good communication lines between
starting air valve may be filled with water (only for the involved persons.
starting air valves mounted on the top surface of cyl-
inder cover). See also General overview of Starting Air System page 7.
General overview of Starting Air System (valid for both MC/-MC-C and ME/ME-C engines)
Test procedure for checking of external air leakage from starting air valves for ME/ME-C engines
This MOP test procedure describes how to pressurise the main starting air pipe with closed starting air valves during
engine standstill and stand-by condition, ready to start.
Fig. 9: Engine in standby condition – Ready to start without any start blockings or shutdowns.
Fig. 10: Close shut-off valve to starting air distributer – Note: Engine Not Ready/Start blocked.
Fig. 11: Select test function of three (3) solenoid valves – marked yellow above.
Fig. 12: Valve test function will appear – Note: Close Valve is activated (blue shadow around).
Fig. 13: Test: Open Slow Turn Pilot Valve – Check for external air leakages – Close Valve.
Fig. 14: Test: Open main starting valve (A or B) – Check for external air leakages – Close valve.