Lec 3
Lec 3
Lec 3
3
Weekly Schedule
Week 1 Introduction to the electric power system, review of phasors and three-phase power
Week 2 Models for transformers, generators, and loads
Week 3 Per unit system of calculations: Selection of base and change in the base of per unit quantities, node equations, one-
line diagram and Problem Solution
Week 4 Bus admittance matrix: Importance and formulation
Week 5 Bus admittance matrix: Problem solution
Week 6 Load Flow Analysis: Importance, Static load flow equations, Gauss-Seidel Method
Week 7 Load Flow Analysis: Application of Gauss-Seidel Method for load flow studies and Problem Solution using GS method
Week 8 Load Flow Analysis: Newton Raphson Method, Application of Newton Raphson Method for Load Flow Studies
4
Synchronous Generator Model
• Field winding and armature winding have same number of poles
• Field winding excitation typically requires 0.2% to 3% of generator
rated output power
• Field winding is placed on the rotor while armature winding on stator
• Field winding is either excited by a DC generator (exciters) or AC
generator (brushless excitation)
• The generator excitation system on the field winding control the
reactive power flow.
• Rotor type can be cylindrical or salient. 70% of generators have
cylindrical rotors. Typical rating is 150 MVA to 1500 MVA.
5
Synchronous Generator Model
• Two pole three phase
generator is shown below
• Stator (armature) winding
contain three coils aa’, bb’, cc’
displaced by 120 degree
• Rotor (field) winding is rr’
• Rotor is excited to produce
airgap flux f per pole
revolving at constant angular
velocity
• Flux linkage with coil aa’ is
6
Synchronous Generator Model – Voltage Induced
• The induced voltage in aa’ is
• In normal conditions
generator operates
synchronous with power grid
8
Synchronous Generator Model – Currents
• Due to synchronization with
grid, three phase balanced
currents are in armature
9
Synchronous Generator Model
• Excitation voltage
• Armature resistance
• Synchronous
Reactance
10
Transformer Model
The voltage E1 across
the primary of ideal
trafo represents the
rms voltage induced in
the primary winding by
the mutual flux f
12
Transformer Model
V1’ is the supply phase voltage referred to the high voltage side
V2’ is the load phase voltage referred to the high voltage side
Assume
14
Voltage Control of Transformers, Example 3.6
A three-phase transmission line is feeding
from a 23 / 230-kV transformer at its
sending end . The line is supplying a 150-
MVA , 0.8 power factor load through a step-
down transformer of 230 / 23 kV . The
impedance of the line and transformers at
230 kV is 18 + j60 Ohm. The sending end
transformer is energized from a 23-kV
supply . Determine the tap setting for each
transformer to maintain the voltage at the
load at 23 kV
15
Per-Unit System
1. Procedure is very similar to 1f except we use a 3f
2. VA base, and use line to line voltage bases
a. Pick a 3f VA base for the entire system,
b. Pick a voltage base for each different voltage level, VB. Voltages are line
to line.
c. Calculate the impedance base
VB2, LL ( 3 VB, LN ) 2 VB2, LN
ZB
S B3f 3S 1Bf S 1Bf
16
Per-Unit System
4. Calculate the current base, IB
17
Thank you!