Sup 602s Signal Isolator User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1.

Performance Introduction as required, see the product label for  Distribution output voltage:

details; Open circuit voltage≤26V;


Provide an isolated working power supply to
 Input impedance: Full-load voltage≥23V
the transmitter, and detect the current in the
DC: about 100Ω In case of full-load 20mA output,
circuit and output current or voltage signal via
User’s Manual of In case of 0(1)V~5V input, ≥1MΩ; in voltage≥17.5V
isolation and transmission at the same time.
Current/Voltage Input case of 0V~10V input, ≥2MΩ  Accuracy of isolated transmission:
The input, output and power supply terminals
 Allowed output signal: ±0.1%F∙S(25℃±2℃)
Signal isolator are isolated from each other, characterized
Active current: 0(4)mA~20mA; 0mA~  Temperature drift: 40ppm/℃
by the advantages such as fast response,
10mA;  Response time: ≤0.5s
low power consumption and good
Passive current: 4mA~20mA; Dielectric strength (leakage current
temperature characteristics.
DC voltage: 0(1)V~5V; 0V~10V; 1mA, with test time of 1 minute):
This product adopts smart design, provided
Other signal types may be customized ≥1500VAC (among input/output/power
with many advanced technologies such as
as required, see the product label for supply)
internal digital adjustment, no potentiometer
the specific signal types;  Dielectric strength (leakage current
and zero-point auto-calibration. Through
 Output load capacity: 1mA, with test time of 1 minute):
matching with various types of instruments
Active: 0(4)mA~20mA:≤500Ω;0mA~ ≥1500VAC (among input/output/power
and DCS, PLC and other devices, the
10mA: ≤1kΩ supply)
product has been widely used in major
Passive: RL≤【(U-3)/0.02】Ω;U refers  Insulation resistance: ≥100MΩ
projects in petroleum, petrochemical,
www.supmea.com
to the circuit service voltage (among input/output/power supply)
[email protected]
manufacturing, power, metallurgy and other
Voltage: 0(1)V~5V:≥1MΩ; 0V~  EMC: EMC conforms to IEC61326-3
Supmea Automation Co.,Ltd. industries.
Add:5th floor,Building 4,Singapore Hangzhou 10V:≥2MΩ;  Power supply: DC 18~32V (typical
Science Technology Park,No. 6 street, Hangzhou 2. Technology Parameters Other load demands may be value 24V DC)
Economic Development Area,Hangzhou
 Allowed input signal: customized as required, see the  Full-load power(In case of 24V DC) :
310018,China
Current: 0(4)mA~20mA; 0mA~10mA; product label for details. Single-channel output 0.6W
Version
Voltage: 0(1)V~5V; 0V~10V;  Output ripple: Double-channel full-load output 1.5W
U-YAP602S-MYEN1
Other signal types may be customized ≤5mVrms(load 250Ω)
3. Wiring Diagram:  PWR:Power indicator (green). When  Please install it as vertically as possible

The instrument is powered, it lights up to facilitate heat dissipation inside the

all the time. instrument.

 OUT1、OUT2:Channel input signal

status indicator, red, corresponding to 9 10 9 10 9 10 9 10 9 10


7 8 7 8 7 8 7 8 7 8
5 6 5 6 5 6 5 6 5 6
channel 1 and channel 2 respectively.
PWR PWR PWR PWR PWR

The indicator does not light up during


ALM ALM ALM ALM ALM

Code Meaning
normal operation; the indicator flashes PRO PRO PRO PRO PRO

1 4~20mA
in case of input signal failures of
1 2 1 2 1 2 1 2 1 2

2 1~5V 3 4 3 4 3 4 3 4 3 4

3 0~10mA corresponding channel; the indicator


4 0~5V
lights up all the time when the input
5 0~10V Vertical Installation Diagram
signal of corresponding channel is out
6 0~20mA
of range. 6. Considerations
4. Wiring Diagram:
There shall not be strong vibration and the
4. Operational Environment
electromagnetic interference exceeding the
 Ambient temperature during operation:
intensity of Type 3 industrial field in the
5. Outline Dimensions
−20℃~+60℃
IEC61000-4 series from the signal terminal,
Width × Height × Depth
 Allowed relative humidity during
(12.7mm×110mm×118.9mm) power supply terminal and space at the
operation: 10%RH~90%RH(40℃)
installation location, and there shall be no
 Allowed atmospheric pressure during
harmful substances having serious
operation: 80kPa~106kPa
corroding effect on the metallic and plastic
 Allowed ambient temperature during
parts in the operational environment.
storage and transportation: −40℃~

+80℃
7. Other Descriptions
In case of any unconformities between the
5. Installation Method
contents in this instruction manual and the
 35mm guide-rail type installation.
information of website and samples, etc., this
Please position stably and firmly.
instruction manual shall prevail.