Copper DF6000 User Manual
Copper DF6000 User Manual
Copper DF6000 User Manual
Approved to:
EN54-2 1997 & A1;2006
EN54-4:1997 & A1;2002 A2:2006
Notice
The operating system of the DF6000 may be revised as a result of enhancements to the system software
or hardware. Revisions to this manual will be issued and supplied on request and should be logged
in the table supplied on the contents page.
Caution
Risk of explosion if battery is replaced by an incorrect type dispose
of the used batteries according to the instructions
Contact
2
DF6000 - USER MANUAL
Contents y
Section 1 - System Installation and Design View Faults 59
Introduction 5 Enable / Disable (Others Menu) 59
Project Planning 6 Print 61
System Design Guidelines 7 Lamp Test 62
Compatible Equipment 8 Weekly Test 63
Detectors 9 View Events 64
Callpoints 10 Check Auto Config 65
Beacons and Sounders 11 Replace Device 66
Base Sounder 11 Test Device 67
Stand Alone Sounders 12 Test Zone 68
Loop Powered Beacon 12 Sounder Level Test Mode 69
Compatible Interfaces 13 Global LED Flashing On/Off 70
3 Channel I/O 13 One Man Walk Test 71
1 Channel I/O 14 Load CDR From Laptop 72
Zone Monitor Unit 14 Download CDR To Laptop 73
Shop Monitor Unit 15 Auto Learn 74
Spur Isolator 16 Erase Log 75
4 Way Sounder Circuit Controller 16 System Details 76
Micro Interfaces 17 Analogue Levels 77
Fan Controller Interfaces (FC18 / FC6) 18 Printer Settings 78
Equipment Compatiblity 19 Change Panel Number 79
System Overview 20 Number of Panels In Network 80
Technical Specification 22 Screen Cover 81
Optional Functions as per EN54 Pt 2 & 4 24 Programming I/O and Sounders 82
Optional Functions Not Approved to EN54 Pt 2 & 4 28 Sound Settings 83
Cable and Wiring 29 Change Date/Time 84
Installation 30 Change Address Text 85
Fixing Details 31 Change Zone Text 86
External Connections 32 Change Panel Text 87
Networking 33 Configure Zones 88
Inputs/Outputs 34 Change User Code 89
Maintainance 36 Add Zone 90
Delete Zone 91
Section 2 - Panel Assembly Information Add Device 92
Attaching Panel Door 38 Delete Device 93
Installing Optional Screen Door 39 Configure Heat Detectors 94
Replacing Printer Paper Roll 40 Network 95
Password Protection 96
Section 3 - Commissioning
Commissioning Mode 42 Section 5 - Appendix
Configuration 43 Spur Isolator 98
Panel Fault Finding 44 4 Way Sounder Controller 99
Protocol 45 Zone Monitor Unit 100
PC Comissioning Software 46 Shop Monitor Unit 101
1 Way Input Output Unit 102
Section 4 - Panel Controls And Indicators Detector Base Wiring 103
System Indicators 50 System Wiring 104
Panel Layout 51 IP66 Wall Sounder 105
Touch Screen Display 52 Internal Wall Sounder 106
Panel Operation 53 Base Sounder 107
Public (Access Level 1) 54 3 Way Input Output Unit 108
Evacuate (Access Level 2) 55 Loop Powered Beacon 109
Silence Alarms 56 Callpoint 110
Mute Buzzer 57 EN54 Product Spec Label 111
Reset 57 Battery Disposal Instructions 112
Pre Alarms 58 CE Marking 113
Disabled Devices 58
3
DF6000 - USER MANUAL
Section 1
System Installation and Design
Introduction
DF6000 provides all of the sophisticated features required of a leading edge analogue addressable fire
system along with the simple operation and neat installation demanded by installers and building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample
facilities for rear or top cable entries. It is available in single two and four loop versions, with or without an
integral printer.
In addition both passive and fully functional repeater panels are available.
A comprehensive range of ancillary devices is available to operate with DF6000, including optical,
ionisation, photo-thermal and heat detectors, base mounted and stand alone sounders (including an IP67
version) a loop powered beacon and a wide range of input and output interfaces.
Each of the DF6000 system components has been specifically designed to operate as part of a DF6000
system, this provides an assurance that the panel, the detectors, the interfaces and the ancillaries are all
fully compatible with each other and that the full range of system functionality is supported by each
device.
Each loop of a DF6000 panel can accommodate up to 200 addresses. To comply with EN54
requirements no more than 512 addresses should be connected to a single panel. Each panel can
indicate upto 96 zones. Panels are available with upto 4 detection loops, up to 126 panels can be
networked together to form a single system capable of operating with over 32,000 devices.
Note:
Network systems fall outside the scope of EN54.
Project Planning
The following is a typical program and timetable for a DF6000 installation project, once the initial order
has been received:
1. Project Meeting
Installer and user to be present; system specifications, schematic diagram and proposed circuit drawing
to be available. DF6000 Installation and Commissioning Guide to be provided.
2. Equipment Fix
Typically 2 week's notice is required for equipment to be delivered. Cable to be installed and bases/back
boxes to be fitted. Then fire detectors, callpoints, alarm sounders, isolator units and interface units to be
installed.
3. Address Schedule
Schedule of sensor locations to be completed by installer and returned to enable system programming.
4. Auto Learn
Fire panel/repeater panels to be installed and terminated. System to be powered up by installer and auto
learn mode activated (see Auto Learn section). System to be tested and verified by installer, prior to final
commissioning.
5. Final Commissioning
Minimum 2 weeks notice is required from receipt of address schedule and commission request form.
Cooper Fire service engineer to attend site implement/oversee the final commissioning procedures (see
commissioning section), in conjunction with the installer.
There may be certain applications in which deviations from the code may be necessary and these must
be listed on the commissioning certificate. (See commissioning section).
Loop Lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the DF6000
motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must be
included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors,
down to manual callpoints) must be included. Remember to include these especially when taking loop
lengths from plan drawings.
Compatible Equipment
Detectors
Analogue Photoelectric Detector - MAP820
This is the most commonly used detector and is
most suitable for detecting slow burning fires. The
status LED can be programmed to either be
permanently off under normal conditions or to
pulse in order to confirm that it is in
communication with the DF6000 control panel.
For applications where a discreet dedicated sounder is required, a cover plate is available for the white
base mounted sounder enabling it to be used as a stand alone wall or ceiling mounted sounder.
All of these devices are fully programmable via the sophisticated DF6000 multi stage cause and effect
programming facilities.
All sounders have multiple selectable volume settings, the volume setting is controlled globally by the
DF6000 panel and so can be altered without needing to access the sounder. Alternatively individual
sounders can be set through the Menvier programming utility.
Base sounder
MAS850
Base sounder with detector fitted Base sounder with MASC fitted
MAS850 MAS850
After the body has been clicked into place and connected, a detector or front cover is then added to
complete a very simple quick and neat installation. The cover enables the MAS850 to be used as a
discreet stand alone wall or ceiling mounted device. The sounder base design incorporates a mechanism
that can be activated if required to lock either the detector or the cover into place to prevent unauthorised
removal.
Compatible Interfaces
DF6000 has been designed to be suitable for a wide range of applications, various interfaces have been
developed to enable the simple integration of other fire systems or building control and safety systems.
The following devices are available:
MIO324T
This unit is identical in build to the MIO324 but this has been designed to take 3 addresses (this can be
expensive in terms of outputs because it replies as 3 x 3 Channel I/O's), this means that text information
can be allocated to each channel. It also allows each individual input and output to be disabled (by
address). The maximum number of addressable MIO324T per loop is 6.
MIO324S
Once again this unit is identical with the MIO324 only taking 1 address. The programming is the same as
the MIO324. This unit was designed so that the relay outputs reset on silence rather than full reset, thus
enabling the user to interface this device with other fire panels and hence prevents locking up. The
maximum number of addressable MIO324S per loop is 20.
MIU871/IS
Similar to the above but the detection zone has been programmed to accept a Zener barrier and zone of
intrinsically safe detectors. End of line for this zone now becomes 6K8 and the diode in the detector base
must be removed.
In addition it has the facility to connect two circuits of conventional polarised sounders, which are
monitored by means of an end of line resistor and powered in alarm conditions from the external power
supply. The sounder circuits can be programmed to operate in pulsed, continuous or time delayed mode.
Please refer to local standards e.g. BS5839 Pt 1:2002 for details of the maximum allowable area to be
covered by a single spur / zone.
Spur Isolator
MSI850
A 4 way unit takes up a single address but each circuit can be independently controlled. An MPU424 unit
requires a local un-switched 230 V supply and incorporates a back up battery to 24 hours of standby
operation followed by a minimum of 30 minutes of full alarm ringing. A standby of 72 hours can be
achieved at the expense of reduced load capability.
Micro Interfaces
A range of micro interfaces modules are also available:
MCIM
Is a competitively priced input module, designed to enable a Menvier panel to accept input signals from
external devices such as key switches and sprinkler flow switches. It is extremely compact
and therefore ideal for incorporation into other equipment. The maximum number of addressable MCIM per
loop is 20.
MCOM
Is a competitively priced output module, designed to enable a Menvier panel control external devices such
as door holders or access control systems. It is extremely compact and therefore ideal for incorporation
into other equipment. The maximum number of addressable MCOM per loop is 20.
MIU872
Is a compact single zone input, soft addressed, microinterface, incorporating integral short circuit isolators.
It is fully compatible with the current range of Menvier analogue fire detection panels. It is suitable for
interfacing a zone of up to 20 conventional Menvier detectors onto a Menvier analogue fire panel. It will
operate with any Menvier conventional detector in configuration with a schottky diode type base.
MCOM-R
Is a compact output module used to control or signal external equipment which require removal of power
for reset purposes. The maximum number of addressable MCOM-R per loop is 20.
MICM-NF
Is a compact single channel input unit. This device is identified as a non-fire input module by the Menvier
addressable panel. The maximum number of addressable MICM-NF per loop is 200. Complex cause and
effect can still be achieved using the latest site installer software without any indication on the panel.
However the action will still be seen in the event log. Ideally suited for non fire applications.
Micro interfaces
MCIM / MCOM / MIU872 / MCIM-C / MCOM-S / MCOM-R / MICM-NF
FC18 and FC6 Interface is connected to a Menvier analogue addressable fire alarm control panel by
means of the comms loop, utilizing only one address whilst providing the ability to monitor and control up
to six AHU Fans.
Each FC6 and FC18 Interface incorporates its own CPU specifically configured to control the relevant
input and output logic making programming quick and easy via the ‘CAPPER’ software or site installer.
Using the CAPPER software or site installer, each individual Fan Control channel on the FC6 is
programmed to an output and feedback input field device to control and monitor the status of an AHU
fan.
Features
> Convenient loop mounting
> Comprehensive LED display
> Surface/rack mounting options
> Key operated auto/manual operation
> Comprehensive software cause and effect
Equipment Compatibility
Detectors
Loop wired detectors must be of the Menvier 800 series soft addressed analogue type. FXN500 series
conventional detectors can be connected via an MIU871 interface. The connection of other detector
types via an MIU871 interface is not recommended.
Callpoints
Loop wired callpoints must be the Menvier 800 series soft addressed analogue type, FX200 series
conventional callpoints can be connected via an MIU871 interface. The connection of other callpoint
types via an MIU871 interface is not recommended.
Sounders
Loop powered addressable sounders must be of the Menvier 800 series soft addressed analogue type.
Conventional sounders can also be connected either to the conventional sounder circuits at the panel or
to the loop via a MPU424 addressable sounder controller interface providing they meet the following:
1. They are suitable for operation between 18 V and 28 V.
2. They are polarised and suppressed.
3. The total alarm load is less than the rating of the panel / alarm power interface.
Note:
It is possible to use devices outside these requirements if they are supplied with power from a separate
source and switched via a suitable relay.
Relay circuits
Additional relays can be added to the DF6000 system by using either MIO1240 or MIO324 relay units.
Relays / Auto-dialers and auxiliary equipment A wide variety of relays and other equipment can be
connected to the DF6000 system, but you should note the following constraints:
1. DF6000 provides monitored outputs to drive fire and fault relays mounted in external equipment.
External relays should be suppressed. If a non-suppressed relay is used then a diode can be
connected. to suppress any reverse EMF on the release of the relay which might cause the panel to
malfunction.
2. A 24 V dc output is provided at the panel to make it easy to connect ancillary equipment. Although the
panel can supply a continuous quiescent load of up to 30 mA, BS5839 precludes this practice and
any ancillary equipment you connect should only consume power in the alarm or fault mode to meet
the requirements of BS5839.
System Overview
Simple User Interface
The main element of the user interface with DF6000 is a large (120mm x 90mm visible area) touch screen
display, which provides comprehensive user information and also acts as a multifunctional keypad.
Comprehensive context sensitive help information is provided throughout the menus to assist unfamiliar
users with system operation.
The DF6000 touch screen display automatically reconfigures to suit the selected function, for example, if
the change device text menu option is selected, the touch screen is automatically formatted as a full
QWERTY keyboard to enable fast and simple text entry.
The use of the touch screen display enables a wide range of user and engineering facilities to be
incorporated into the panel whilst still offering simple operation.
As well as a large format LCD display providing full system status information, the panel incorporates 96
traditional zone indication LED's to provide clear information about the status and spread of a fire even to
a user who is completely unfamiliar with the operation of the system.
In addition there are a number of system status LED's designed to give clear status information to non
technical users.
The panel supports 3 separate sets of programming per sounder and each stage can be triggered
differently For example, if a single detector is triggered the panel can be programmed such that the
sounder nearest to the detector operates immediately and continuously, the remaining sounders in the
affected zone operate in pulsed mode and the other sounders delay for a selectable period to allow the
cause of the alarm to be investigated before global ringing commences.
A major innovation with DF6000 is the ability to incorporate spurs of analogue devices which are fed from
the main loop by utilising a spur isolator. Whenever the panel detects a spur, it breaks from allocating
address numbers to the loop wired devices, allocates address numbers to each of the devices on the
spur in sequence and then continues to address the devices on the main loop. Every DF6000 analogue
device incorporates an integral short circuit isolator ensuring maximum system integrity. A single short
circuit will not disable any loop-mounted devices, the isolators in the devices each side of the short circuit
will operate and the DF6000 control panel will drive communication from both ends of the loop. The spur
isolator also incorporates a short circuit isolator such that in the event of a short circuit on the spur, the
integrity of the main loop will not be compromised. Please refer to local standards e.g. BS5839 Pt1:2002
for details of the maximum allowable are to be covered by a single spur.
Optional Printer
DF6000 panels are available with optional built in printers. Where a printer is fitted, it is housed behind a
printer cover door, which can be opened by means of a special tool (supplied) to provide simple and safe
access to the printer paper roll without exposure to any live equipment. Paper replacement is extremely
simple due to the drop in loading method and auto feed printer design, the paper roll is simply dropped
into the purpose designed cradle and the end of the roll is then offered up to the printer, which will then
automatically load the paper ready for use. The printer can be set to either print automatically or to print
on demand When a printer is not fitted, a removable, flush fitting blanking plate is used to cover the
printer paper aperture to enhance the appearance of DF6000 and to preserve its ingress protection
rating.
Technical Specification
Outputs
Conventional sounder circuits
Number of sounder circuits 4
Total sounder Load 1.5 Amps
Sounder circuit fuses (F1/2/3/4) 1.6 Amp (Quick Blow)
End of line resistor 6k8
Fire Protecting Equipment
Max load 60 ma
Fused (PTC3) 100mA polyswitch
End of line resistor 6k8
Fault Routing Equipment
Max load 30 ma
Fused (PTC1) 100mA polyswitch
End of line resistor 6k8
Auxiliary Relays - The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max load 24 V 1 Amp
Fuse (PTC4) 1.35 Amps polyswitch
Auxiliary 24 V Supply
Nominal voltage 24 V ±10%
Fuse (PTC5) 100 mA polyswitch
Maximum current 30 mA
This output is not to be used for fire protecting equipment or fire alarm routing equipment any power taken from the
alarm system will effect the standby duration
RS485 Port - Serial output port for driving DF6000 repeater panels, mimics etc.. This output is short circuit protected
Max cable length 2 Km
Min recommended cable size 1mm² (Screened)
RS232 Port - Serial output port for driving DF6000 repeater panels, mimic etc. This output is short circuit protected
Printer (Optional)
Type High speed thermal
Number of characters per line 40
Type of paper 58mm x 46mm Thermal Roll
Replacement paper roll order code ADF6PRINTERPAPER
Mechanical Specification
Weight incl batteries 18kg, excl batteries 9kg
Dimensions (standard batteries) 495mm(L) x 395mm(H) x 180mm(D)
Type of material (backbox) Mild Steel (power coated)
Type of material (Facia) PC/ABS
Flammability rating UL 94 V0
Total number of knockouts 51
Diameter of knock out 20mm
Anti-Tamper cover (optional) Weight : 250g
Material used : Poly Carbonate
Flammability rating : UL 94 5VA
Terminal Blocks: Do not use excessive force when tightening the screws on the terminal block
Risk of explosion if battery is replaced by an incorrect type dispose of the used batteries
according to the instructions
Panel Outputs
Dependencies on More Than One Alarm Signal - Type C (option 7.12.3 of EN54 Pt 2)
The DF6000 has the facility to inhibit the operation of the output sounders, output to fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using DF6000 site installer software.
Outputs
Output 1: Fire Protecting Equipment Operated "Extinguishing On"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire protecting equipment (option 7.10 of EN54 Pt 2).
Output 2: Fire Routing Equipment Operated "Fire Brigade Link"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire routing equipment (option 7.9 of EN54 Pt 2).
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire protecting equipment has been disabled either by
the DF6000 control and indicating equipment or the fire brigade panel.
Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment if the DF6000. Once the FRE is
disabled from this interface, it can never be enabled from the DF6000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment of the DF6000. Once the FRE is
disabled from this interface, it can never be enabled from the DF6000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the DF6000. The disablement of sounders from
the fire brigade panel can be re-abled from the DF6000 control panel only when the system
is not Alarm State.
Inputs
The inputs are designed to be actioned in one of two ways, see list below:
all inputs are held high via a weak pull up (logic high), the action of short circuiting any of the five inputs to
there respective 0v will result in a logic low.
Monitored Inputs
In Fault / Extinguisher Active
Relay Outputs
Outputs
1: Extinguisher released -> output high 26 V
2: FRE operated
3: FPE disabled
4: FRE disabled
5: Panel in fire, will remain on after panel soft reset for > 15 minutes, or extinguish immediately with
interface reset
6: Disable all sounders.
For example, if there was a fire detected from a single detector then we should start a 5-minute
(adjustable) delay (T2). If however a fire is detected from a second detector or a call-point the delay
should automatically revert to 2 minutes (adjustable) (T1). In this scenario the value of (T1) is critical. To
keep things simple, let's assume that we set T1 = 2 minutes and T2 = 5 minutes.
In the event of a fire the timer T1 can be set from 0 to 3 min where the alarm will be displayed on the
panel and no output activation, if during this time the alarm is acknowledged then timer T2 can be set
from 0-10 min where the alarm can be investigated and alarm reset. However if timer T1 and T2 time out
during alarm activation, the outputs will be activated.
When choosing your preferred cable type, you must take note of the following cable and wiring
requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 2 km
3. Maximum volt drop must be limited to 7 V.
4. The conductors should be 1.5mm minimum an no larger than 2.5mm
5. Multicore cable should not be used for detector wiring.
6. Different loops should NEVER be run within the same cable.
7. Loop feeds and returns should never be used within the same cable.
Cable Resistance
Cable Anchorage
The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably located knockout
feed the cable through the gland and bolt the gland to the DF6000 backbox as shown. Secure the cable
to the side of the box using the cable clip provided.
NOTE: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event
of accidental switching on of the mains supply.
Installation
the panel should be installed in a clean, dry, reasonably well ventilated place, and not in direct sunlight.
Temperatures in excess of 40°C and below 5°C may cause problems, if in doubt consult Cooper Lighting
and Safety. The panel should be located away from any potential hazard, in a position where it is readily
accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a
permanent entrance. Mount the panel to the wall using the drill template provided. Do not drill through the
panel to the wall as dust will contaminate the circuitry.
Installation Guide
! Never carry out insulation tests on cables connected to electronic equipment.
! DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS
! Always use the correct type of cables specifically designed for the operation of fire detection and
alarm circuits.
! Always adhere to volt drop limitation when sizing cables
! Always observe polarity throughout. Non colour coded conductors should be permanently identified.
! Screen continuity must be maintained throughout the entire loop circuit including at each junction
point and at each device, terminals are provided on each device to facilitate this.
! The screen should be earthed at the connection point provided at the DF6000 panel and not at any
other point. Both the loop start and the loop end must be connected to the appropriate earthing
points. Care must be taken to avoid connecting the screen to the earthed body of any metal devices,
enclosures or cable containment. The screen or drain wire of the loop cables should not be
considered as safety earth and therefore should not be connected to terminals marked with the earth
symbol, except at the panel, and should not be insulated with green and yellow sleeving.
! DF6000 utilises intelligent soft addressing technology to greatly simplify the installation and
commissioning processes. Once the system has been installed and the autolearn menu selected, the
DF6000 control panel will automatically scan the detection loops and allocate each device with an
address number corresponding with its position on the loop, this avoids the traditional need for
manual addressing of the system devices which is time consuming and provides a potential for error.
! It is of vital importance that accurate details are kept of the exact wiring route in order to determine
which address has been allocated to each device.
Fixing Details
Read all the installation instructions before commencing with the installation. The installation of this panel
must be carried out by a suitably qualified /trained person. Theinstallation must comply with IEE wiring
regulations and with BS5839 Pt 1 2002 The electronic components within the fire panel are Static
Sensitive. Do not touch the electronics directly.
1. Surface Mount: Drill four holes and fix the backbox to the wall.
2. Flush Mount: The backbox requires a hole 364 x 472 with a depth of 117mm (standard battery /
backbox ) or 217 mm if deep backbox is used.
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands.
479mm
400mm
227mm
364mm
309mm
117mm
132mm 472mm
1. The isolating protective device is fed from the live side of the main isolating device in which case the
label on the isolating protective device, should read in addition - “WARNING: THIS SUPPLY REMAINS
ALIVE WHEN THE MAIN SWITCH IS TURNED OFF”. A further label should be placed on the main
isolating device reading “WARNING: THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH
IS TURNED OFF.
Or
2. If the isolating protective device is fed from the dead side of the main isolating device, a label should
be fixed to the main isolating device reading “WARNING: THIS SWITCH ALSO CONTROLS THE
SUPPLY TO THE FIRE ALARM SYSTEM”.
Cable Segregation
All cables for the fire alarm system should be segregated from any other cables/wiring/services.
Wiring configurations
Spurs can be taken off the loop in the following ways:
1. MIU871 Addressable Interface - Allows up to 20 conventional smoke detectors and unlimited FX201 /
203 callpoints.
2. Direct Loop Spur Wiring - Allows a zone of analogue detectors and callpoints to be directly spurred off
the loop
Note: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event
of accidental switching on of the mains supply.
Networking
Up to 126 DF6000 panels or passive repeaters can be networked together to operate as a single
networked system. To achieve this each panel must be fitted with a network card (supplied at additional
cost.)
When operating as a networked system all fire and fault event information is displayed at every panel,
silencing and resetting of alarms can also be carried out from any panel on a networked system if panels
are suitably configured.
Networked panels can be used as active repeaters, alternatively a low cost passive repeater is available.
This can either be connected a loop of an individual panel or it can be connected to the network. The
recommended network cable for the network connection between panels is an enhanced Firetuf cable
Manufactured by Draka cables (part number 910234). Screen continuity must be maintained throughout
the entire network circuit including at each junction point. The screen should only be earthed at the
connection point provided at the first panel and not at any other point. The screen or drain wire of the
network cable should not be considered as a safety earth and therefore should not be connected to
terminals marked with the earth symbol, except at the panel, and should not be insulated with green and
yellow sleeving.
Where the network cable passes between buildings, screen continuity should not be maintained from
building to building. A booster device must however be used irrespective of cable length and should be
fitted at a suitable point in the link between buildings. The cable screen should be connected to the earth
of one panel in each building.
Network Cable
Zone s Zone s
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72 61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84 73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96 85 86 87 88 89 90 91 92 93 94 95 96
A B X Y
Network
Card
(Panel 1)
A B X Y Network
Card
(Panel 2)
Input/Outputs
Panel Inputs
Class Change: (option not required by EN54)
A pair of terminals are provided for class change. By shorting these terminals together (e.g. switch, time
clock) the alarm will sound (panel sounders + loop sounders only). The panel will not indicate a fire. The
alarm will cancel when the short circuit is removed. If the short circuit is not removed the alarms will not
cancel.
WARNING: No voltage should be applied to this input
class change
-
+
Panel Outputs
Panel Sounders: (option 7.8 EN54 Pt 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the
connections are observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp all outputs are fused with 1.6 Amp glass fuse
alarm devices should be spread equally across the 4 sounder circuits.
WARNING: Do not exceed the rated output current
It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do not
operate this output. If operated under a fire alarm condition, this output remains activated until the fire
alarm is reset. Ensure the polarity of the connections is observed at all times and end of line resistors (6k8
5%) are fitted for correct operation. All activated devices must be polarised.
Maintainance
Daily Inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault indication. Notify any faults
to a system supervisior.
Weekly Test
Check indicators. Press supervisor mode on the top left of the touch screen. Enter passcode. Select
“others” tab. Press the button labeled weekly test, confirm you wish to perform the test and the amber
“System Test” LED will light. The panel will stay in the weekly test mode for 5mins before resetting. During
the weekly test, trigger a smoke detector or callpoint and check the fire panel registers the device and
illuminates the correct zonal indicator. Trigger a different device every time a weekly test is performed
ensuring devices are tested in rotation until all have been checked. It is advisable to develop a detailed a
building plan highlighting devices and locations to aid testing. The panel will reset automatically once the
5mins have elapsed. If no devices are triggered during the weekly test the panel will abort the test and
reset after 5mins. Record weekly test in the table provided in the log book.
Quarterly Test
Check all previous log book entries and verify that remedial action has been taken. Carry out the weekly
test. Visually examine the batteries and their connections, by loosening the screws behind printer door
and opening the hinged front from the right hand side. Disconnect the mains supply and check that the
batterry is capable of supplying the alarm sounders, by operating a callpoint.
Annual Test
As weekly test and quarterly test above. Additionally test all sensors and callpoints and check operation.
Every 5 Years
Replace sealed lead acid battery.
Cleaning
When cleaning the panel, use a moist cloth. Do not use solvents or harsh abrasives.
Servicing: Cooper Lighting and Safety can offer a regular servicing contract.
Cooper Lighting and Safety
Service Division,
Wheatley Hall road
Doncaster
DN2 4NB.
Telephone: 01302 303352 Web: www.cooperfire.com
Section 2
Panel Assembly Information
Section 3
Commissioning
Section 3 - Commissioning 41
DF6000 - USER MANUAL
Commissioning Mode
Walk test mode allows a single engineer to test the various detectors and callpoints on a system without
always having to return to the panel either to reset the system or silence the alarms. When in
COMMISSIONING MODE, the system operates as normal except that when a detector or callpoint goes
into alarm, the alarms only operate for a few seconds and then will silence. The panel then tries to reset
the device automatically and, if successful, the alarms are operated again for a few seconds and the
installation engineer can move on to the next detector. After a full test has been carried out the engineer
can check the order in which the detectors/callpoints were operated using the DISPLAY LOG mode. This
information can also be printed on the optional printer.
When the panel is in “Walk Test Mode” the control panel inserts a different code into the log and also onto
the print-out. This is to distinguish between when a device has been tested in “Walk Test Mode” and
when a device has been triggered while in normal operation.
1. When in the LOG mode, "One man walk test”" will appear on the display followed by the address text
and device type.
2. On the printout a “One man walk test” message will appear will appear followed by the address text
and device type.
3. During a real fire “FIRE !” Will appear on the display followed by the address text and device type.
42 Section 3 - Commissioning
DF6000 - USER MANUAL
Configuration
DB Level Check
DF6000 includes the facility to test and set the system sounders with the minimum amount of
disturbance. In sounder test mode, the sounders will sound for 30 seconds on then 30 seconds off. This
facility can be accessed via the engineering menu.
The PC is connected to each panel on the network in turn. All data for the panel is downloaded.
For networked systems, panels are identified by panel number, P1, P2 etc.
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
Section 3 - Commissioning 43
DF6000 - USER MANUAL
C
AUX
} No Fires
+26V
F-
= As Above
LOOP 2
F-
F+
LOOP CIRCUITS
S+
S-
LOOP 3
= As Above
F-
F+
S+
S-
LOOP 4
= As Above
-F-
F+
CHANGE
CLASS
V
CIRCUIT 1
SOUNDER
}
+
See Scope
2 -
Conditions
+
2 -
}
MODEM/PC
Rs232
CTS RTS
44 Section 3 - Commissioning
DF6000 - USER MANUAL
Protocol Format
Normal Communications to Devices:
With the command bits set for the 'Normal' command and the MSB of the 3 mode bits set at 0, this
shortened version of the normal communications to each device allows the analogue reply or status from
each device to be read. This format of communication is generally used throughout all background
supervision of the addressable loop.
Loop 1: Using a digital storage oscilloscope, connect one channel to R34 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 1, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe.
Loop 2: Using a digital storage oscilloscope, connect one channel to R36 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 2, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe
1.1 ms
300us
2ms 300us
24v
typ
7.5v
0v
Command Mode
Response ID Flags A
Start Byte 1 Byte 2 Byte 3
Parity
Loop Current
Each Packet of Comms above must be separated by a gap of 20ms minimum where the line is held at 24v
Section 3 - Commissioning 45
DF6000 - USER MANUAL
PC Comissioning Software
If non-latching has been enabled, Isolated devices can be un-isolated as the triggered device returns to
normal operation. (a callpoint keyswitch is an example for this application).
46 Section 3 - Commissioning
DF6000 - USER MANUAL
PC Comissioning Software
Device Outputs
Delay Configuration
The output of a device when triggered can be delayed - based on a user defined value in minutes.
This programming option is enabled when a value other than zero is entered inside the 'Delay' window.
MCP Override
This option is a manual intervention override, when enabled (check in box) the delay can be overridden
from any callpoint on the loop when triggered.
Section 3 - Commissioning 47
DF6000 - USER MANUAL
PC Comissioning Software
Panel Outputs
Dependency Type C
Each panel output can be assigned a unique list of zones derived from the zones available on the
loop, to activate this output, two unique zones from this list have to be in fire or alternatively any
zone outside this list will trigger the output also. When the 'Coincidence' box is checked - the
'Allocate device' button allows the user to populate this list.
48 Section 3 - Commissioning
DF6000 - USER MANUAL
Section 4
Panel Controls and Indicators
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
1 2 3 4 5 6 7 8 9 10 11
Power General System Power Sounder System System FRE Extinguisher Delay
ON FIRE FAUL T FAUL T FAUL T Disabl e DISABLE TEST Disable ACTIV ATED ACTIVE
Faul t Faul t
Zones
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
3 2 4
Systems Healthy
XX Zones Acitve
Tuesday
dd-mm-yyyy
16:25.25
BST On
The touch screen is a multi-function display consisting 320 x 240 dots featuring high intensity
backlighting. In normal operation, the display indicates as above with the backlighting off.
During an event on the system the display shows the FIRST EVENT and LAST EVENT plus other events
as space allows.
The last 2 lines are normally used to display the total number of events, but they are also used for
scrolling fire conditions, faults, pre alarms or disabled devices independently or for displaying a reduced
menu when in fire condition.
When an event occurs the touch screen backlighting comes on unless there is a mains
power supply fault.
Use the touch screen to scroll through all active events on the system by using the SCROLL UP and
SCROLL DOWN buttons (available at access level 1). You can display the contents of the log and also
view details of any fires, faults, pre-alarms,faults or disablements. When displaying the system menu on
the touch screen, the last 5 lines of the display are shown in reverse text.
Panel Operation
DF6000 is operated via a backlit touch screen. The default fire screen is shown below. From this screen
all the panels functions can be operated. The first time you touch the screen the backlight will illuminate
the panel.
Systems Healthy
XX Zones Acitve
Tuesday
dd-mm-yyyy
16:25.25
BST On
Pressing a field will highlight it and forward to the next screen as shown below.
Supervisor Fire Pre Faults Disabled Supervisor Fire Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE Off 1 Alarms 0 0 / Test
Systems Healthy
10 Zones Acitve
Total Fires = 1 Print All Help
Tuesday Tuesday
dd-mm-yyyy dd-mm-yyyy
16:25.25 16:25.25
BST On BST On
Systems Healthy
10 Zones Acitve
Tuesday
dd-mm-yyyy
16:25.25
BST On
Supervisor Fire Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE off 0 Alarms 6 6 / Test
Show Show Show Show
First Fire 12:26:23 Device 1, Zone 1 Addresses Zones I/O Test Zone
Lp: 1, Ad:1, Z:1, Opto/thermal, [69]
Print All Help
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 0 Alarms 6 0 / Test FRE off 0 Alarms 6 5 / Test
001 03-Jun-03 12:51 Warning! : Device 1 001 03-Jun-03 12:51 Fault! : Device 1
Lp: 1, Ad: 1, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 1, Z: 1, Opto / Thermal [0]
002 03-Jun-03 12:51 Warning! : Device 2 002 03-Jun-03 12:51 Fault! : Device 2
Lp: 1, Ad: 2, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 2, Z: 1, Opto / Thermal [69]
003 03-Jun-03 12:51 Warning! : Device 3 003 03-Jun-03 12:51 Fault! : Device 3
Lp: 1, Ad: 3, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 3, Z: 1, Opto / Thermal [69]
004 03-Jun-03 12:51 Warning! : Device 4 004 03-Jun-03 12:51 Fault! : Device 4
Lp: 1, Ad: 4, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 4, Z: 1, Opto / Thermal [69]
005 03-Jun-03 12:51 Warning! : Device 5 005 03-Jun-03 12:51 Fault! : Device 5
Lp: 1, Ad: 5, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 5, Z: 1, Opto / Thermal [69]
Enter the Supervisor Mode Passcode and select “Evacuate” on the menu at the top of the screen.
Others
View
Faults
View
View Fires Disabled
View Pre
AC = 0
Alarms
Supervisor
FRE Off
Yes No
Silence Alarms
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.
Enter the Supervisor Mode Passcode and select “Silence Alarms” button as the top of
I/O Zone: 0
Address: 0
Supervisor
FRE Off
Yes No
Mute Buzzer
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.
Enter the Supervisor Mode and Select “Mute Buzzer” from the Top Menu
View Fires
AC =19 View Pre
Alarms View
Disabled View
Faults Others
Reset
Enter the Supervisor Mode and Select “Reset” from the top Menu. Select “Yes” to reset the panel.
View Fires
View Pre Others
AC =19
Alarms View
Disabled View
Faults The panel will reset
Do you wish to continue?
001 14:22:49
Mains Failure
Yes No
Faults = Short circuits, broken detectors etc.
To remove faults from this list:
1) Fix Fault
2) Reset Panel
Pre-Alarms
Enter the Supervisor Mode and Select “Pre-Alarms” tab.
Others
View
Faults
View
View Fires Disabled
View Pre
AC = 0
Alarms
A pre-alarm is shown when a detector appears to register heat or smoke but in a quantity that is
insufficient to warrant an alarm. Pre-alarm may indicate a build up of dirt in a smoke detector which can
be interpreted by the detector as smoke presence.
Disabled Devices
Enter the Supervisor mode and Select the “Disabled” tab.
I/O Zone: 0
Address: 0
The individual buttons show which devices and the number of devices which have been disabled. Press
one of the buttons to display detailed information for a particular category
Faults
Enter Supervisor Mode Passcode and select “Faults” tab.
Fires
View Pre Others
AC = 0
Alarms View
Disabled View
Faults
Enter the Supervisor Mode passcode and select the “Others” tab.
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Enable All
Exit
Yes No
Zone 004 Zone 4 Enable
Print
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Press “Print”
Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Select the Information You wish to Print from the Buttons Listed.
Lamp Test
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.
Enter the Supervisor Mode and Select the “Others” Tab. Press “Lamp Test”
Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Lamp Test
Yes No
Weekly Test
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode. Select the others tab as
shown below. Press Weekly test.
Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Weekly Test
Weekly Test Awaiting alarm signal
Do you want to continue?
Will rest after 4 minutes
Yes No Cancel
The panel will automatically return to the system healthy screen once the weekly test has been
completed.
Viewing Events
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.
Enter the Supervisor Mode Passcode. Select the “Others” tab and press View Log.
Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Use the scroll bar to view the list of upto 1000 events.
The DF6000 event log stores up to 1000 events including, fires, faults, resets and address changes.
Once the maximum 1000 events has been reached DF6000 will automatically overwrite the oldest event
every time a new event is stored. The event log can only be reset by an approved service engineer.
Enter the Supervisor Mode and Select the “Others” Tab. Press Check Auto Config. This feature will scan
the loop and pinpoint the exact location of any break in the loop wiring and will also identify any changes
in the loop configuration (e.g. New devices added or changed device types).
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Replace Device
Exit
Supervisor
FRE Off
Check
Auto Config
Yes No
Replace Device
Replace device enables an existing device to be replaced with a new device without losing the existing
text and sounder programming. Replace a single device then use use the replace device menu to allocate
an existing address to the new device
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Replace Device
Exit
Supervisor Supervisor
FRE off FRE off
Loop 1 0 1 2 3
Loop 2
Del 4 5 6
Exit Exit OK 7 8 9
Configure
Test
Enable/Disable Address
Test Zone
Test Zone
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode, Select “Test” and on the Screen Shown Below Press “Test Zone”
Service Mute
Exit Reset
FRE off Buzzer
Test Device
Test Zone
_
Zone 005 Building 2, Basement
Test Zone
Configure
Yes No
Stop
Test
Enable/Disable Address
Test Zone
Flashing Off
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Test Zone
Yes No Stop
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Number of Panel
Erase Log
in Network
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Number of Panel
Erase Log
in Network
Start PC Program
Ok Cancel
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Number of Panel
Erase Log
in Network
Service
Important:
Exit Auto Learn
FRE off Activating autolearn
will erase all existing
Do you want to continue? programming, text
and configuration
No data.
Erase Log
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Number of Panel
Erase Log
in Network
Yes No
System Details
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode and Select Commission, then Press “System Details”.
Number of Panel
Test Erase Log and Reset
in Network
Enable/Disable Address
Load Logo From PC Italian Mode
Service Service
Print Exit Reset Print Exit Reset
FRE Off FRE Off
Program V3.02.01 Loop 1 Loop 2 Loop 3 Loop 4
Program Data 22/01.08
CDR V0.5 Optical 0 0 0 0
CDR Checksum 0xF7D95E Ionisation 13 14 0 0
Loop Controller 1 V2.1.4 Thermal A1R 0 0 0 0
Loop Controller 2 V0.0.0 Opto / Thermal 0 0 0 0
Panel Number 0 Thermal BS 0 0 0 0
Total Panels 1 Thermal CS 2 1 0 0
Total Addresses 13 Alarm 0 0 0 0
Total Zones 4 I / O Units 0 0 0 0
Page 1 Page 2 Page 3 Page 4 Page 5 Page 1 Page 2 Page 3 Page 4 Page 5
Service
Print Exit Reset
FRE Off
Loop 1 Loop 2 Loop 3 Loop 4
SCU 0 0 0 0
Voice Annunciator 13 14 0 0
Repeater 0 0 0 0
ZMU / {SUM 0 0 0 0
Beam Detector 0 0 0 0
Technical Timer 2 1 0 0
Access Control 0 0 0 0
Emerg.Light.Module 0 0 0 0
Carbon Monoxide 0 0 0 0
Analogue Level
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode and Select Commission then press “Analogue Levels”.
Number of Panel
Test Erase Log and Reset
in Network
Enable/Disable Address
Load Logo From PC Italian Mode
Service Note:
Exit Goto Reset
FRE Off Go to command can
Show Show Show Show Show be used to jump to a
All Detectors Optical Ionisation Thermal
specific address
001 Device 1, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal
Enter Address
..............................
Loop 1 0 - 13
1 2 3
Loop 2 0-0 4 5 6
Loop 3
8 9
0-0
Loop 4 0-0
7
Cancel
ok 0
Section 4 - Panel Controls and Indicators 77
DF6000 - USER MANUAL
Printer Settings
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode and Select Commission then press “Printer settings”.
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Service Mute
Exit Reset
FRE Off Buzzer
Number of Panel
Erase Log and Reset
in Network
Service
Exit Reset
FRE Off
Auto
Request
Enter the Service Mode and Select Commission then press “Change Panel Number”
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Service Mute
Exit Reset
FRE Off Buzzer
Number of Panel
Erase Log and Reset
in Network
Enter the Service Mode and Select Commission then press “Number of Panels in Network”
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Service Mute
Exit Reset
FRE Off Buzzer
Number of Panel
Erase Log and Reset
in Network
Number of Panels
In Network
1.............................. 1 2 3
4 5 6
7 8 9
Cancel
ok 0
80 Section 4 - Panel Controls and Indicators
DF6000 - USER MANUAL
Screen Cover
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode and Select Commission then press “Screen Cover”
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Service Mute
Exit Reset
FRE Off Buzzer
Number of Panel
Erase Log and Reset
in Network
Service
Exit Reset
FRE Off
Installed
Not Required
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Enable/Disable Address
Sound Settings
Touch sound settings.
Sound Settings
Selections from the screens below will become the global settings for all loop sounders.
Service Exit Service Exit
Reset Reset
FRE Off FRE Off
Volume
This will efffect all sounders
Volume Low
Medium
Sound High
Volume
This will efffect all sounders
Two Tone
Sound Continuous
Change Date/Time
Enter the Service Mode and Select Configure. Select Change Date/Time.
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Current Time: +1 + 10 +1
Hour Minutes Minute
10:10:04 -1 - 10 -1
Hour Minutes Minute
BST On
+1 + 10 +1
Current Date: Day Month Year
Wednesday -1 - 10 -1
dd-mmm-yyyy Day Month Year
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Change Panel
Select the Address you wish to change and edit using the keyboard
Service
FRE Off
Exit Reset Name for address 1
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Change Panel
Select the Address you wish to change and edit using the keyboard
Supervisor Reset
FRE Off Enter the name for zone 2
Zone 2
..........................................................
Exit
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Service
Press
Exit Reset
FRE off “Change Panel Text”
Change Panel
1 2 3 4 5 6 7 8 9 0
Q W E R T Y U I O P
A S D F G H J K L
CAPS Z X C V B N M , .
OTHER SPACE OK CANCEL
Configure Zones
Enter the Service Mode and Select Configure. Select “Configure Zones”
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Service
Select Zone into which
Exit Reset
FRE Off device will be added
Touch row to configure
Service
FRE Off Exit Reset
Programming I/O
Add/Delete
and Sounders
Change Passcode
New Code
1 2 3
Change Engineering Code ..............................
Ok Ok Ok
Add Zone
Enter the Service Mode and Select Configure. Select “Add Zone”
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Add Zone
Delete Zone
Add Device
Delete Device
Add Zone?
Yes No
Delete Zone
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Zone”
Add Zone
Delete Zone
Add Device
Delete Device
Service
Select Zone to be
Reset
FRE Off Deleted
Exit Touch row to delete
Confirm or Cancel
Deletion
Add Zone 2?
Yes No
Add Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Add Device”
Add Zone
Delete Zone
Add Device
Delete Device
Service
Select a Loop to Add a
Reset
FRE Off New Device
Loop 1
Loop 2
Loop 3
Loop 4
Exit
Confirm New
Device and Loop
Loop 2
Scanning Loop
Exit
Delete Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Device”
Add Zone
Delete Zone
Add Device
Delete Device
Service
Select a Device to
Exit Goto Reset
FRE Off Delete
Touch row to delete
Confirm or Cancel
Deletion
Delete device 3?
Device 3
Loop 1, Address 3. Device Type Opto / Thermal
Yes No
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Service
Select a Device to
Exit Goto Reset
FRE Off Configure
Touch row to delete
Service Reset
FRE Off
Thermal A1R
Thermal BS
Thermal CS
Exit
Network
Enter the Service Mode and Select Configure. Select “Network”, This menu defines whether messages
are broadcast across the network or remain local.
Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders
Change Passcode
Service
FRE Off Exit Receive message over network
Reset Network
Evacuate Network
Silence Network
Fire Network
Fault Network
Pre-Alarm Network
Exit Exit
Password Protection
The Menvier DF6000 system has password protection which restricts access to the DISABLE Menu and
to TEST/COMMISSIONING MODE. The password is a four digit code and the default number is 2214 for
access level two and 143243 for access level 3. The password entry screen is accessed via the
supervisor mode button. Press supervisor mode and the password entry screen will be displayed, type in
the passcode and press Ok. If the wrong password is entered 3 times further access to the
system is denied.
Service
FRE Off
4 5 6
7 8 9
Cancel
ok 0
Section 5
Appendix
Section 5 - Appendix 97
DF6000 - USER MANUAL
Notes:
A spur isolator must be used when making spurs from the analogue addressable panel loop. Without this
unit, the self addressing features of the system will not function correctly.
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Out
+
Analogue
No end of line
addressable m resistor required
loop m
In
Spur
+
+
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. For maximum spur length / load see BS5839 Pt 1:2002.
3. This unit can only be used with Menvier MAB800 and JSB FXN720 detector bases and compatible
detectors.
98 Section 5 - Appendix
DF6000 - USER MANUAL
Notes:
No addressing of the interface is required. See control panel operation for details. This unit requires a
permanent 230 V ac supply.
Standard Connections
6k8 6k8 6k8 6k8
Analogue
addressable loop
230V AC Mains
Fire Relay
N/O C N/C
L N E E + - E + - E + - E + - E - + E - +
OUT IN
+
+
BATT
Back up
- battery
-
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistors must always be fitted, even if the sounder circuits are unused
Section 5 - Appendix 99
DF6000 - USER MANUAL
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
EOLM-1
12K
- Out +
- In +
Analogue addressable loop - Out +
- In +
E - + E - + E - + E - +
Notes:
1. This unit can only be used with JSB FXN520 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt 1:2002 for aone coverage.
5. Maximum number of callpoints allowed is unlimited.
6. Detector zone end of line device is EOLM-1 (supplied)
7. Callpoint zone has end of line resistor
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
24V dC output
EOLM-1 power supply unit
- Out +
- In +
- +
Analogue addressable loop 12K
- Out +
- In +
E - + E - + E - + E - + N/O C N/C + - + - E - +
Notes:
1. This unit can only be used with FXN520 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt 1:2002 for zone coverage.
5. Maximum number of callpoints allowed is unlimited.
6. Detector zone end of line device is EOLM-1
7. Callpoint zone has end of line resistor
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
5K6
22K
Analogue addressable loop
Volt-Free Output
230V rated
E - + E - + - + E C N/C N/O
In Out
Spur Input
WARNING: Segregate mains cable from other connections to this unit. 230 V Relay output is un-
fused. Ensure that the 230 V supply feeding this unit is adequately protected
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
Wiring Hints
1. Each terminal is suitable for clamping up to 2 wires
2. Clamping of 2 wires of very different diameters under one screw is not recommended.
3. Suitable for mounting to mounting boxes with 50-80mm fixing centres. General If difficulty is
experienced when mounting the detector, this may be due to the following:
4. Wiring causing an obstruction - move or shorten wires.
5. Although the base is tolerant to uneven mounting surfaces, a very uneven surface may cause the base
to deform when the mounting screws are tightened down - loosen screws to reduce this or slide base
to a more flat position.
WARNING: Do not use high voltage testers when detectors or control panel are connected to the
system.
4 4
S+
Analogue addressable
Loop start
fire alarm panel
S- 3 3
1 1
F-
Loop finish
F+ 2 2
Attention: If using the outer connection on terminal 2, ensure the operation of the switch
is not impeded and that there no shorts between terminal 2 and the switch contact.
Ensure that the cable does not short onto the contact
Section 5 - Appendix
NO C NC - + - + 0V - +26V - + S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ - + + 1 -- + 2 -- + 1- + 2 Tx Rx CTS RTS OV Tx+ Tx-
System Wiring
AUX Fault +24V Loop 1 Loop 2 Loop 3 Loop 4 Sounder Sounder MODEM/PC MIMIC
Fire R/E Fire P/E
Relay Relay O/P Class Circuit 1 Circuit 2 R&232 Repeater
Loop Circuits Change
104
DF6000 - USER MANUAL
Standard Connections
WARNING: Do not use high voltage testers if any equipment is connected to the system. earth
screen must be continuous along entire length of loop.
In Out
E - + E - +
Standard Connections
WARNING: Do not use high voltage testers if any equipment is connected to the system. earth
screen must be continuous along entire length of loop.
Note:
Care should be taken to ensure the cable does not put stress on the circuit board
In Out
E - + E - +
- +- + - +- +
S+
Analogue addressable
Loop start
fire alarm panel
S-
F-
Loop finish
F+
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Outputs
E - + E - + - + - + - + N/O C N/C N/O C N/C N/O C N/C
In Out Inputs
Loop
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
3. Monitored inputs can detect open or short circuit faults.
4. Output relays are volt-free contacts and are not monitored.
WARNING: Do not use high voltage testers if any equipment is connected to the system.
Standard Connections
In Out
E - + E - +
Standard Connections
In Out
E - + E - +
Label: D6K XB
PR200-04-517-01
Label: D6K XA
PR200-04-518-01
Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96
Note: If the panel is recessed this label must be placed on the front of the panel
CE Marking
CE RTIF CE RTIF
ON IC
ON IC
I
AT
AT
PR E V E NT
P R E V E NT
LPCB LPCB
I ON B OA
I ON B OA
SS
SS
R
R
LO D D
LO
Cooper Lighting and Safety Ltd Cooper Lighting and Safety Ltd
Wheatley Hall Road Wheatley Hall Road
Doncaster Doncaster
South Yorkshire South Yorkshire
DN2 4NB DN2 4NB
09 09
DF6000 DF6000
Control and indicating equipment for fire detection and fire Power supply equipment for fire detection and fire alarm
alarm systems for buildings systems for buildings
EN 54-2 Clause
Options Provided Other technical data: see Doc. PR200-04-513 held by the
manufacturer
7.8 Output to fire alarm devices
7.9.1 Output to fire alarm routing equipment
7.10.1 Output to automatic fire protection equipment (type A)
7.10.2 Output to automatic fire protection equipment (type B)
7.11 Delays to outputs
7.12.3 Dependencies on more than one alarm signal-Type C
7.13 Alarm counter
8.9 Output to fault routing equipment
9.5 Disablement of each point
10 Test condition
Technical
Tel: 01302 303350
Fax: 01302 303332
Email: [email protected]
Export
Tel: 01302 303334
Fax: 01302 303345
Email: [email protected]
Service
Tel: 01302 303352
Fax: 01302 303332
Email: [email protected]
Web: www.cooperfire.com
Head Office
Cooper Lighting and Safety Ltd
Wheatley Hall Road
Doncaster
South Yorkshire
DN2 4NB
CC1809