Copper DF6000 User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 114

Fire

DF6000 Control Panel


User Manual

Assessed to: ISO 9001:2000


Certification number: 714h/01

Approved to:
EN54-2 1997 & A1;2006
EN54-4:1997 & A1;2002 A2:2006

Document Drg Ref: PR200-04-513-15


Marketing Ref: CC1809a

0832 – CPD – 1060


DF6000 - USER MANUAL

Introduction to the Manual


This manual provides information on the installation, operation and maintenance of the Menvier DF6000
System.

Notice
The operating system of the DF6000 may be revised as a result of enhancements to the system software
or hardware. Revisions to this manual will be issued and supplied on request and should be logged
in the table supplied on the contents page.

Caution
Risk of explosion if battery is replaced by an incorrect type dispose
of the used batteries according to the instructions

Contact

Technical: 01302 303350


Service: 01302 303352
Sales: 01302 303303

2
DF6000 - USER MANUAL

Contents y
Section 1 - System Installation and Design View Faults 59
Introduction 5 Enable / Disable (Others Menu) 59
Project Planning 6 Print 61
System Design Guidelines 7 Lamp Test 62
Compatible Equipment 8 Weekly Test 63
Detectors 9 View Events 64
Callpoints 10 Check Auto Config 65
Beacons and Sounders 11 Replace Device 66
Base Sounder 11 Test Device 67
Stand Alone Sounders 12 Test Zone 68
Loop Powered Beacon 12 Sounder Level Test Mode 69
Compatible Interfaces 13 Global LED Flashing On/Off 70
3 Channel I/O 13 One Man Walk Test 71
1 Channel I/O 14 Load CDR From Laptop 72
Zone Monitor Unit 14 Download CDR To Laptop 73
Shop Monitor Unit 15 Auto Learn 74
Spur Isolator 16 Erase Log 75
4 Way Sounder Circuit Controller 16 System Details 76
Micro Interfaces 17 Analogue Levels 77
Fan Controller Interfaces (FC18 / FC6) 18 Printer Settings 78
Equipment Compatiblity 19 Change Panel Number 79
System Overview 20 Number of Panels In Network 80
Technical Specification 22 Screen Cover 81
Optional Functions as per EN54 Pt 2 & 4 24 Programming I/O and Sounders 82
Optional Functions Not Approved to EN54 Pt 2 & 4 28 Sound Settings 83
Cable and Wiring 29 Change Date/Time 84
Installation 30 Change Address Text 85
Fixing Details 31 Change Zone Text 86
External Connections 32 Change Panel Text 87
Networking 33 Configure Zones 88
Inputs/Outputs 34 Change User Code 89
Maintainance 36 Add Zone 90
Delete Zone 91
Section 2 - Panel Assembly Information Add Device 92
Attaching Panel Door 38 Delete Device 93
Installing Optional Screen Door 39 Configure Heat Detectors 94
Replacing Printer Paper Roll 40 Network 95
Password Protection 96
Section 3 - Commissioning
Commissioning Mode 42 Section 5 - Appendix
Configuration 43 Spur Isolator 98
Panel Fault Finding 44 4 Way Sounder Controller 99
Protocol 45 Zone Monitor Unit 100
PC Comissioning Software 46 Shop Monitor Unit 101
1 Way Input Output Unit 102
Section 4 - Panel Controls And Indicators Detector Base Wiring 103
System Indicators 50 System Wiring 104
Panel Layout 51 IP66 Wall Sounder 105
Touch Screen Display 52 Internal Wall Sounder 106
Panel Operation 53 Base Sounder 107
Public (Access Level 1) 54 3 Way Input Output Unit 108
Evacuate (Access Level 2) 55 Loop Powered Beacon 109
Silence Alarms 56 Callpoint 110
Mute Buzzer 57 EN54 Product Spec Label 111
Reset 57 Battery Disposal Instructions 112
Pre Alarms 58 CE Marking 113
Disabled Devices 58

3
DF6000 - USER MANUAL

Section 1
System Installation and Design

4 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Introduction
DF6000 provides all of the sophisticated features required of a leading edge analogue addressable fire
system along with the simple operation and neat installation demanded by installers and building users.

The panel can be flush or surface mounted and the generously sized metal back box allows ample
facilities for rear or top cable entries. It is available in single two and four loop versions, with or without an
integral printer.

In addition both passive and fully functional repeater panels are available.

A comprehensive range of ancillary devices is available to operate with DF6000, including optical,
ionisation, photo-thermal and heat detectors, base mounted and stand alone sounders (including an IP67
version) a loop powered beacon and a wide range of input and output interfaces.

Each of the DF6000 system components has been specifically designed to operate as part of a DF6000
system, this provides an assurance that the panel, the detectors, the interfaces and the ancillaries are all
fully compatible with each other and that the full range of system functionality is supported by each
device.

Each loop of a DF6000 panel can accommodate up to 200 addresses. To comply with EN54
requirements no more than 512 addresses should be connected to a single panel. Each panel can
indicate upto 96 zones. Panels are available with upto 4 detection loops, up to 126 panels can be
networked together to form a single system capable of operating with over 32,000 devices.

Note:
Network systems fall outside the scope of EN54.

Section 1 - System Installation and Design 5


DF6000 - USER MANUAL

Project Planning
The following is a typical program and timetable for a DF6000 installation project, once the initial order
has been received:

1. Project Meeting
Installer and user to be present; system specifications, schematic diagram and proposed circuit drawing
to be available. DF6000 Installation and Commissioning Guide to be provided.

2. Equipment Fix
Typically 2 week's notice is required for equipment to be delivered. Cable to be installed and bases/back
boxes to be fitted. Then fire detectors, callpoints, alarm sounders, isolator units and interface units to be
installed.

3. Address Schedule
Schedule of sensor locations to be completed by installer and returned to enable system programming.

4. Auto Learn
Fire panel/repeater panels to be installed and terminated. System to be powered up by installer and auto
learn mode activated (see Auto Learn section). System to be tested and verified by installer, prior to final
commissioning.

5. Final Commissioning
Minimum 2 weeks notice is required from receipt of address schedule and commission request form.
Cooper Fire service engineer to attend site implement/oversee the final commissioning procedures (see
commissioning section), in conjunction with the installer.

6 Section 1 - System Installation and Design


DF6000 - USER MANUAL

System Design Guidelines


Guidelines
Systems should to the relevant local standards and codes of practice, for the UK this is BS5839 Pt 1.
DF6000 meets all the relevant requirements of BS5839 Pt 1: 2002. Installation planning is simplified by
the fact that every addressable DF6000 device contains an integral short circuit isolator. Care must be
taken to ensure that local standards requirements regarding aspects such as loop coverage, area
covered by a single spur and cable specification are observed.

There may be certain applications in which deviations from the code may be necessary and these must
be listed on the commissioning certificate. (See commissioning section).

Loop Lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the DF6000
motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must be
included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors,
down to manual callpoints) must be included. Remember to include these especially when taking loop
lengths from plan drawings.

Loop Loading - Total Number of Addresses


The total number of addresses per loop is 200. this includes detectors, callpoints and all other
addressable items (e.g. MPU, MIO, loop repeaters etc.) When designing systems its recommended that
allowances are made for future expansion, Short circuit isolators are incorporated into every DF6000 loop
device, including Smoke detectors, heat detectors, sounders, callpoints and interfaces. Therefore, no
further fault protection is required, in the event of a single fault, none of the devices connected to the loop
will fail to operate as the fault will be isolated by the two adjacent devices. Spur connected devices
downstream of a cable fault will cease to function.

DF6000/PR Repeater Panels


Each repeater unit requires one address and consumes no more current from the loop than a smoke
detector. The repeater also requires a local mains supply and incorporates battery backup.

Loop Loading System Verification


Unless a loop loading calculation has already been carried out, please contact our technical support
department (01302 303350), before starting installation to verify that a proposed loop loading
arrangement is acceptable.

Section 1 - System Installation and Design 7


DF6000 - USER MANUAL

Compatible Equipment

DF6000 system components


Order Code Description Dimensions (mm)
DF6000/1 1 Loop DF6000 Panel 495 W x 400 H x 180 D
DF6000/2 2 Loop DF6000 Panel 495 W x 400 H x 180 D
DF6000/4 4 Loop DF6000 Panel 495 W x 400 H x 180 D
DF6000/1/P 1 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D
DF6000/2/P 2 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D
DF6000/4/P 4 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D
DF6000/1/G 1 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D
DF6000/2/G 2 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D
DF6000/4/G 4 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D
DF6000/1/P/G 1 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D
DF6000/2/P/G 2 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D
DF6000/4/P/G 4 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D
DF6000/COV Hinged protective cover kit
DF6000/PR Passive repeater for DF6000
MAS850 Sounder Base 102 Dia x 40 D
MASC Cover for MAS850 102 Dia x 13 D
MASB870 Base Sounder Beacon 114 Dia x 36 D
MASB870-NT Base Beacon 114 Dia x 36 D
MAS850LPS Wall Sounder 105 L x 105 H x 95 D
MAS850LPS/WP IP66 Wall sounder 108 L x 108 H x 103 D
MAB870 Addressable Beacon 95 Dia x 50 D
MBG813 Surface / Flush Callpoint 85 L x 85 W x 53 D
MBG817 Weatherproof Callpoint 108 L x 108 W x 65 D
MIO324 3 Channel I/O Device 147 L x 88 W x 57 D
MIO324T 3 Channel I/O Device 1 Address 147 L x 88 W x 57 D
MIO324S 3 Channel I/O Device reset on silence 147 L x 88 W x 57 D
MIO1240 1 Channel Output Unit (mains rated) 180 L x 130 H x 60 D
MIU871 Zone Monitor Unit 150 L x 89 H x 58 D
MIU871/ IS Zone Monitor Unit Intrinsically Safe 150 L x 89 H x 58 D
MSU840 Shop Unit Interface 150 L x 89 H x 58 D
MSI850 Spur Isolator 112 L x 41 H x 33 D
MPU424 4 Way Sounder Circuit Controller. 300 L x 300 H x 74 D
MAB800 Common Mounting Base For Analogue Detectors 104 Dia x 22 D
MAP820 Optical Smoke Detector 101 Dia x 33 D
MAH830 Multi Mode Heat Detector 101 Dia x 43 D
MAOH850 Combined Photo Thermal Detector 101 Dia x 43 D
MIU872 Micro Zone Monitor Unit 63 L x 35 H x 18.5 D
MCIM-C Micro Callpoint Input Module 63 L x 35 H x 18.5 D
MCOM-S Micro Sounder Output Module 63 L x 35 H x 18.5 D
MCOM-R Micro Output Module Resetable 63 L x 35 H x 18.5 D
MICM-NF Micro Analogue Non Fire Input Module 63 L x 35 H x 18.5 D

8 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Detectors
Analogue Photoelectric Detector - MAP820
This is the most commonly used detector and is
most suitable for detecting slow burning fires. The
status LED can be programmed to either be
permanently off under normal conditions or to
pulse in order to confirm that it is in
communication with the DF6000 control panel.

Analogue Photo/thermal Detector - MAOH850


This is a new addition to the Menvier range of
detectors. It is the ideal detector for a multi-use
environment as it has an excellent response to
smouldering and fast burning fires. Photo/thermal
detectors can be programmed for thermal only
operation at certain times of day. The status LED
can be programmed to either be permanently off
under normal conditions or to pulse in order to
confirm that it is in communication with the
DF6000 control panel.

Analogue Heat Detector - MAH830


Heat detectors are suitable for dusty environments
or environments where smoke is likely to be
present under normal operating conditions. The
MAH830 can be programmed to operate in A1R,
BS or CS mode of operation depending on the
required application and sensitivity requirements.
The status LED can be programmed to either be
permanently off under normal conditions or to
pulse in order to confirm that it is in
communication with the DF6000 control panel.

Section 1 - System Installation and Design 9


DF6000 - USER MANUAL

Callpoints - MBG813 / MBG817


The range of purpose designed callpoints for DF6000 consists of a surface callpoint, a flush callpoint and
a surface weatherproof callpoint. A range of accessories is available including a hinged protective cover,
resettable element kit and a flush bezel. The status LED can be programmed to either be permanently off
under normal conditions or to pulse in order to confirm that it is in communication with the DF6000
control panel.

Flush mounted callpoint Surface mounted callpoint Weatherpoof callpoint


MBG813 MBG813 MBG817

10 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Sounders and Beacons


A wide range of loop powered sounders and beacons are available to operate with DF6000 consisting of
a combined sounder base with a maximum output of 95 dB(A), a standalone sounder with a maximum
output of 100 dB(A) that is available in standard or weatherproof versions and a stand alone loop
powered beacon.

For applications where a discreet dedicated sounder is required, a cover plate is available for the white
base mounted sounder enabling it to be used as a stand alone wall or ceiling mounted sounder.

All of these devices are fully programmable via the sophisticated DF6000 multi stage cause and effect
programming facilities.

All sounders have multiple selectable volume settings, the volume setting is controlled globally by the
DF6000 panel and so can be altered without needing to access the sounder. Alternatively individual
sounders can be set through the Menvier programming utility.

Base Sounder - MAS850


The MAS850 has been designed specifically to complement the latest generation of Menvier soft
addressed detectors. it consists of a first fix bracket, and a main body which clips onto the bracket
incorporating the sounder and a detector mounting base in a single composite assembly.

Base sounder
MAS850

Base sounder with detector fitted Base sounder with MASC fitted
MAS850 MAS850

After the body has been clicked into place and connected, a detector or front cover is then added to
complete a very simple quick and neat installation. The cover enables the MAS850 to be used as a
discreet stand alone wall or ceiling mounted device. The sounder base design incorporates a mechanism
that can be activated if required to lock either the detector or the cover into place to prevent unauthorised
removal.

Section 1 - System Installation and Design 11


DF6000 - USER MANUAL

Stand Alone Sounders -


MAS850LPS / MAS850LPSWP
Stand alone sounders are ideal for applications
where greater sound outputs are required than can
be achieved with a base sounder or for
applications requiring a higher level of resilience or
ingress protection. Two different versions are
available standard version and an IP66 rated
version.
Stand alone sounder
Loop Powered Beacon - MAB870 MAS850LPS
A loop powered flashing beacon is available for
applications where visual alarm indication is
required such as areas of high ambient noise or
buildings which are used by people who are hard
of hearing.

Base Sounder Beacon - MASB870


Loop powered base sounder with a built in beacon
where both sound and visual alarms are required.
Taking 1 address

Base Beacon - MASB870-NT Stand alone sounder - weatherproof


Loop powered base beacon where visual alarm MAS850LPSWP
without sound are required. Taking 1 address.

Loop powered beacon


MAB870

Loop powered beacon


MASB870-NT

12 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Compatible Interfaces
DF6000 has been designed to be suitable for a wide range of applications, various interfaces have been
developed to enable the simple integration of other fire systems or building control and safety systems.
The following devices are available:

3 Channel I/O device - MIO324


MIO324 has 3 input channels and 3 output channels, it is used to monitor up to 3 separate inputs from
equipment such as sprinkler flow switches and also to provide 3 separately controlled volt free output
contacts which are intended to be used to control external equipment such as air handling plant or
access control systems. All inputs and outputs operate completely independently of each other and can
be programmed using the sophisticated cause and effect capabilities of DF6000 to operate either globally
or in response to activation of specific devices or specific inputs. Inputs are monitored for open and short
circuits, a specific resistance is required to activate an alarm condition, fully open or short circuit
conditions are monitored and generate a system fault signal. Inputs are suitable for use as fire signal
inputs such as from a sprinkler flow switch, however they can also be used to monitor non fire inputs
such as external keyswitches. Outputs are rated to switch a maximum of 1A resistive at 30 V dc.
MIO324 fixes to a standard, deep, double gang back box and can be either surface or semi recess
mounted.

MIO324T
This unit is identical in build to the MIO324 but this has been designed to take 3 addresses (this can be
expensive in terms of outputs because it replies as 3 x 3 Channel I/O's), this means that text information
can be allocated to each channel. It also allows each individual input and output to be disabled (by
address). The maximum number of addressable MIO324T per loop is 6.

MIO324S
Once again this unit is identical with the MIO324 only taking 1 address. The programming is the same as
the MIO324. This unit was designed so that the relay outputs reset on silence rather than full reset, thus
enabling the user to interface this device with other fire panels and hence prevents locking up. The
maximum number of addressable MIO324S per loop is 20.

3 channel I/O device


MIO324 / MIO324T / MIO324S

Section 1 - System Installation and Design 13


DF6000 - USER MANUAL

1 Channel I/O device with mains rated switching capability (MIO1240)


MIO1240 is a single channel input / output unit, the output is capable of switching up to 8 A at 230 V ac.
Commonly used for applications such as door release controls and plant shut down signalling the input is
monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully
open or short circuit conditions are monitored and generate a system fault signal. The input is suitable for
use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non
fire inputs such as an external keyswitch.

1 channel I/O device


MIO1240

Zone monitor unit (MIU871)


MIU871 is designed to enable a zone of compatible conventional detectors and callpoints to be
connected into the DF6000 loop, it is compatible with up to 20 Menvier conventional detectors
connected via FXN520 bases. Please refer to local standards e.g. BS5839 Pt1:2002 for details of the
maximum allowable area to be covered by a single spur / zone. MIU871 fixes to a standard, deep, double
gang back box and can be either surface or semi recess mounted. When semi recessed only the front
section protrudes giving a maximum 29mm depth.

MIU871/IS
Similar to the above but the detection zone has been programmed to accept a Zener barrier and zone of
intrinsically safe detectors. End of line for this zone now becomes 6K8 and the diode in the detector base
must be removed.

Zone monitor unit


MIU871 / MIU871/IS

14 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Shop Unit Interface - MSU840


MSU840 accepts a zone of conventional detectors plus an unlimited number of callpoints which can be
connected to the same input as the detectors or a separate callpoint input if required. There is also a
facility to connect a power supply, which can then be monitored for fault.

In addition it has the facility to connect two circuits of conventional polarised sounders, which are
monitored by means of an end of line resistor and powered in alarm conditions from the external power
supply. The sounder circuits can be programmed to operate in pulsed, continuous or time delayed mode.

Please refer to local standards e.g. BS5839 Pt 1:2002 for details of the maximum allowable area to be
covered by a single spur / zone.

Note: This unit must always be used with a 24 V power suply

Shop unit Interface


MSU840

Section 1 - System Installation and Design 15


DF6000 - USER MANUAL

Spur Isolator - MSI850


Enables soft addressing to work when the loop contains spurs, it controls the addressing operation so
that when the system reaches a spur, all devices on the spur are allocated an address before it continues
addressing the loop. The device also incorporates a short circuit isolator. Because each device contains a
short circuit isolator only 1 is required at the start of each spur. MSI850 is mounted on a standard deep
double gang back box (supplied) please refer to BS5839 Pt 1:2002 f

Spur Isolator
MSI850

4 Way Sounder Circuit Controller - MPU424


MPU424 provides power for 4 separately controllable conventional sounder circuits, each circuit can be
separately programmed. MPU424 is designed to greatly simplify installation in applications where
specialist sounders or beacons are required since it powers the sounders and allows full control of the
sounder operation without having to wire the sounder back to the DF6000 control panel.

A 4 way unit takes up a single address but each circuit can be independently controlled. An MPU424 unit
requires a local un-switched 230 V supply and incorporates a back up battery to 24 hours of standby
operation followed by a minimum of 30 minutes of full alarm ringing. A standby of 72 hours can be
achieved at the expense of reduced load capability.

4 Way sounder circuit controller


MPU424

16 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Micro Interfaces
A range of micro interfaces modules are also available:

MCIM
Is a competitively priced input module, designed to enable a Menvier panel to accept input signals from
external devices such as key switches and sprinkler flow switches. It is extremely compact
and therefore ideal for incorporation into other equipment. The maximum number of addressable MCIM per
loop is 20.

MCOM
Is a competitively priced output module, designed to enable a Menvier panel control external devices such
as door holders or access control systems. It is extremely compact and therefore ideal for incorporation
into other equipment. The maximum number of addressable MCOM per loop is 20.

MIU872
Is a compact single zone input, soft addressed, microinterface, incorporating integral short circuit isolators.
It is fully compatible with the current range of Menvier analogue fire detection panels. It is suitable for
interfacing a zone of up to 20 conventional Menvier detectors onto a Menvier analogue fire panel. It will
operate with any Menvier conventional detector in configuration with a schottky diode type base.

MCIM-C (Identified as a Callpoint)


Is a compact input module used to accept input signals from external equipment such as beam detectors,
flow switches, valve monitor switches etc. The maximum number of sounder devices per loop is 200.

MCOM-S (Identified as a Sounder)


Is a compact single channel output unit. This device is identified as a sounder output by a Menvier
addressable panel. The maximum number of sounder devices per loop is 60.

MCOM-R
Is a compact output module used to control or signal external equipment which require removal of power
for reset purposes. The maximum number of addressable MCOM-R per loop is 20.

MICM-NF
Is a compact single channel input unit. This device is identified as a non-fire input module by the Menvier
addressable panel. The maximum number of addressable MICM-NF per loop is 200. Complex cause and
effect can still be achieved using the latest site installer software without any indication on the panel.
However the action will still be seen in the event log. Ideally suited for non fire applications.

Micro interfaces
MCIM / MCOM / MIU872 / MCIM-C / MCOM-S / MCOM-R / MICM-NF

Section 1 - System Installation and Design 17


DF6000 - USER MANUAL

Fan Controller Interfaces (FC18 / FC6)


FC18 and FC6 Interface is designed to work with the Menvier range of analogue fire alarm control panels,
providing the capability to control and display the status of AHU fans.

FC18 and FC6 Interface is connected to a Menvier analogue addressable fire alarm control panel by
means of the comms loop, utilizing only one address whilst providing the ability to monitor and control up
to six AHU Fans.

Each FC6 and FC18 Interface incorporates its own CPU specifically configured to control the relevant
input and output logic making programming quick and easy via the ‘CAPPER’ software or site installer.

Using the CAPPER software or site installer, each individual Fan Control channel on the FC6 is
programmed to an output and feedback input field device to control and monitor the status of an AHU
fan.

Features
> Convenient loop mounting
> Comprehensive LED display
> Surface/rack mounting options
> Key operated auto/manual operation
> Comprehensive software cause and effect

Fan controller interface


FC18
Fan controller interface
FC6

18 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Equipment Compatibility
Detectors
Loop wired detectors must be of the Menvier 800 series soft addressed analogue type. FXN500 series
conventional detectors can be connected via an MIU871 interface. The connection of other detector
types via an MIU871 interface is not recommended.

Callpoints
Loop wired callpoints must be the Menvier 800 series soft addressed analogue type, FX200 series
conventional callpoints can be connected via an MIU871 interface. The connection of other callpoint
types via an MIU871 interface is not recommended.

Sounders
Loop powered addressable sounders must be of the Menvier 800 series soft addressed analogue type.
Conventional sounders can also be connected either to the conventional sounder circuits at the panel or
to the loop via a MPU424 addressable sounder controller interface providing they meet the following:
1. They are suitable for operation between 18 V and 28 V.
2. They are polarised and suppressed.
3. The total alarm load is less than the rating of the panel / alarm power interface.
Note:
It is possible to use devices outside these requirements if they are supplied with power from a separate
source and switched via a suitable relay.

Relay circuits
Additional relays can be added to the DF6000 system by using either MIO1240 or MIO324 relay units.
Relays / Auto-dialers and auxiliary equipment A wide variety of relays and other equipment can be
connected to the DF6000 system, but you should note the following constraints:
1. DF6000 provides monitored outputs to drive fire and fault relays mounted in external equipment.
External relays should be suppressed. If a non-suppressed relay is used then a diode can be
connected. to suppress any reverse EMF on the release of the relay which might cause the panel to
malfunction.
2. A 24 V dc output is provided at the panel to make it easy to connect ancillary equipment. Although the
panel can supply a continuous quiescent load of up to 30 mA, BS5839 precludes this practice and
any ancillary equipment you connect should only consume power in the alarm or fault mode to meet
the requirements of BS5839.

Additional instructions for electromagnetic compatibility


When used as intended this product complies with EMC Directive (89/336/EEC) and the UK EMC
regulations 1992 (SI 2372/1992) by meeting the limits set by the standards BS5406 (Pt 2 & 3) 1988,
EN50130-4 immunity and EN 61000-6-3 emission requirements. The following installation guidelines
must be followed.
1. External cables must be connected using the cable entries or knockouts provided.
2. When routing external cables inside the product they must be
a) Kept as short as possible
b) Routed close to the housing
c) Kept as far as possible from the electronics
Any modifications other than those stated in this manual, or any other use of this product may cause
interference and it is the responsibility of the user to comply with the EMC and low voltage directives.

Section 1 - System Installation and Design 19


DF6000 - USER MANUAL

System Overview
Simple User Interface
The main element of the user interface with DF6000 is a large (120mm x 90mm visible area) touch screen
display, which provides comprehensive user information and also acts as a multifunctional keypad.

Comprehensive context sensitive help information is provided throughout the menus to assist unfamiliar
users with system operation.

The DF6000 touch screen display automatically reconfigures to suit the selected function, for example, if
the change device text menu option is selected, the touch screen is automatically formatted as a full
QWERTY keyboard to enable fast and simple text entry.

The use of the touch screen display enables a wide range of user and engineering facilities to be
incorporated into the panel whilst still offering simple operation.

As well as a large format LCD display providing full system status information, the panel incorporates 96
traditional zone indication LED's to provide clear information about the status and spread of a fire even to
a user who is completely unfamiliar with the operation of the system.

In addition there are a number of system status LED's designed to give clear status information to non
technical users.

User Configuration And Maintenance Facilities


DF6000 has comprehensive facilities for on site system configuration, whereby the user can add or
remove simple devices or change device text directly via the panel, without the need for a service
engineer to visit site. For initial configuration or major system changes special PC configuration software
is available enabling Cooper Lighting and Safety personnel to do this more efficiently than can be
achieved using the system screen. Exiting configurations can be uploaded to the PC so that changes can
be made to the existing system rather than having to revert to initial files.

Sophisticated Sounder Control Facilities


DF6000 has the ability to support highly complex ringing pattern requirements. Multistage cause and
effect programming is possible whereby each addressable sounder or output interface can be
programmed independently if required and can be set to respond to specific addresses, specific
detection zones, specific panels on a networked system or standard global ringing.

The panel supports 3 separate sets of programming per sounder and each stage can be triggered
differently For example, if a single detector is triggered the panel can be programmed such that the
sounder nearest to the detector operates immediately and continuously, the remaining sounders in the
affected zone operate in pulsed mode and the other sounders delay for a selectable period to allow the
cause of the alarm to be investigated before global ringing commences.

20 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Spur Tolerant Soft Addressing


DF6000 utilises intelligent soft addressing technology to greatly simplify the installation and
commissioning processes. Once the system has been installed and the autolearn menu selected, the
DF6000 control panel will automatically scan the detection loops and allocate each device with an
address number corresponding with its position on the loop, this avoids the traditional need for manual
addressing of the system devices which is time consuming and provides a potential for error.

A major innovation with DF6000 is the ability to incorporate spurs of analogue devices which are fed from
the main loop by utilising a spur isolator. Whenever the panel detects a spur, it breaks from allocating
address numbers to the loop wired devices, allocates address numbers to each of the devices on the
spur in sequence and then continues to address the devices on the main loop. Every DF6000 analogue
device incorporates an integral short circuit isolator ensuring maximum system integrity. A single short
circuit will not disable any loop-mounted devices, the isolators in the devices each side of the short circuit
will operate and the DF6000 control panel will drive communication from both ends of the loop. The spur
isolator also incorporates a short circuit isolator such that in the event of a short circuit on the spur, the
integrity of the main loop will not be compromised. Please refer to local standards e.g. BS5839 Pt1:2002
for details of the maximum allowable are to be covered by a single spur.

Simple Future Expansion


DF6000 is designed to ensure simplicity of future expansion. If an additional device is added after the
system has been programmed, the DF6000 will allocate the next available address, it will not alter any of
the existing address numbers allocation thus enabling simple updating of as fitted drawings etc. Similarly
if a device is removed, the relevant address is saved as a spare address for future use, the addresses of
the remaining devices are not altered.

Integral Power Supply and Battery


The DF6000 panel is designed for ease of installation, the power supply and battery are integral to the
main control panel so only a single panel is required even on large 4 loop systems.

Optional Printer
DF6000 panels are available with optional built in printers. Where a printer is fitted, it is housed behind a
printer cover door, which can be opened by means of a special tool (supplied) to provide simple and safe
access to the printer paper roll without exposure to any live equipment. Paper replacement is extremely
simple due to the drop in loading method and auto feed printer design, the paper roll is simply dropped
into the purpose designed cradle and the end of the roll is then offered up to the printer, which will then
automatically load the paper ready for use. The printer can be set to either print automatically or to print
on demand When a printer is not fitted, a removable, flush fitting blanking plate is used to cover the
printer paper aperture to enhance the appearance of DF6000 and to preserve its ingress protection
rating.

Optional Hinged Lockable Cover


With a standard panel, access to all panel functions is controlled by a series of pass codes, which are
entered via the touch screen display, for maximum security, a facility is built into the DF6000 to enable the
user to alter the user pass code as required. For applications where a high level of resilience is required, a
clear hinged lockable front cover is available which allows the screen and all of the system status
indicators to be clearly seen but prevents access without first unlocking the cover. A single concealed
locking mechanism provides access to both the printer door and the optional display cover where a
hinged cover is fitted, additional buttons are provided to scroll the display and to silence the fault buzzer
without opening the lockable cover

Section 1 - System Installation and Design 21


DF6000 - USER MANUAL

Technical Specification

Power Supply (Approved EN54 pt 4)


Mains
Nominal voltage 230 Vac + 10%, -15%
Nominal current 75mA
Maximum current 750mA
Input fuse R1 NTC SG39 Imax 4 Amp
Output voltage including tolerances 26 V = 18.5 to 29.5 V
26 V RAW = 18.5 V to 29.5 V
5 V Output = 4.6 V to 5.5 V
Ripple voltages 26 V = 800m V
26 V RAW = 800m V
5 V Output = 430m V
Maximum loadings 26 V O/P = 0.98A
26 V RAW O/P = 1.7A
5 V = 0.5A
Standby current (4 loops loaded) 26 V = 280 mA
26 V RAW = 150 mA
26 V = 280 mA
26 V RAW = 150 mA
5 V = 43 mA
DF6000 is protected by an internal thermal device, this requires no maintenance
* I max a, I max b and I min = Current as specified in BSEN54-4 Published 2006 (amendments 1 and 2)
Batteries
Number of batteries 2
Manufacturer YUASA NP12-12
Capacity 12 Ah
Battery fuse 6.3A Anti-Surge (F4)
Maximum battery current 3.5 Amps
Standby current (mA) 175 (4 loops), 125 (2 loops)
Maximum charging current to the batteries 1.0amp
Float voltage 27.4 V
Final voltage 21.0 V
Charging characteristics Constant voltage with 0.970A
limit with temperature
compensation
Maximum current drawn from the batteries (when the mains is not available) 3.5Amps
Deep discharge protection 20.6 V
Battery Internal Impedance Fault >0.5 ohms
Inputs
Addressable loops
Max number 1-4
Max loop load per loop 220 ma
Max number of addressable devices per Loop 200
Class change Operated by external volt free contact

22 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Outputs
Conventional sounder circuits
Number of sounder circuits 4
Total sounder Load 1.5 Amps
Sounder circuit fuses (F1/2/3/4) 1.6 Amp (Quick Blow)
End of line resistor 6k8
Fire Protecting Equipment
Max load 60 ma
Fused (PTC3) 100mA polyswitch
End of line resistor 6k8
Fault Routing Equipment
Max load 30 ma
Fused (PTC1) 100mA polyswitch
End of line resistor 6k8
Auxiliary Relays - The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max load 24 V 1 Amp
Fuse (PTC4) 1.35 Amps polyswitch
Auxiliary 24 V Supply
Nominal voltage 24 V ±10%
Fuse (PTC5) 100 mA polyswitch
Maximum current 30 mA
This output is not to be used for fire protecting equipment or fire alarm routing equipment any power taken from the
alarm system will effect the standby duration
RS485 Port - Serial output port for driving DF6000 repeater panels, mimics etc.. This output is short circuit protected
Max cable length 2 Km
Min recommended cable size 1mm² (Screened)
RS232 Port - Serial output port for driving DF6000 repeater panels, mimic etc. This output is short circuit protected
Printer (Optional)
Type High speed thermal
Number of characters per line 40
Type of paper 58mm x 46mm Thermal Roll
Replacement paper roll order code ADF6PRINTERPAPER
Mechanical Specification
Weight incl batteries 18kg, excl batteries 9kg
Dimensions (standard batteries) 495mm(L) x 395mm(H) x 180mm(D)
Type of material (backbox) Mild Steel (power coated)
Type of material (Facia) PC/ABS
Flammability rating UL 94 V0
Total number of knockouts 51
Diameter of knock out 20mm
Anti-Tamper cover (optional) Weight : 250g
Material used : Poly Carbonate
Flammability rating : UL 94 5VA

Terminal Blocks: Do not use excessive force when tightening the screws on the terminal block
Risk of explosion if battery is replaced by an incorrect type dispose of the used batteries
according to the instructions

Section 1 - System Installation and Design 23


DF6000 - USER MANUAL

Optional Functions as per EN54 Pt 2 & 4


DF6000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected as
required

Panel Outputs

Panel Sounders: (option 7.8 EN54 Pt 2)


Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the
connections are observed at all times and end of line resistors (6K8 5%) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp All outputs are fused with 1.6 Amp Glass fuse
Alarm devices should be spread equally across the 4 sounder circuits.
WARNING: Do not exceed the rated output current

Output Fire Alarm Routing Equipment (option 7.9 EN54 Pt 2)


This output, which is fused, and monitored using a 6.8k end of line resistor, is used for the automatic
transmission of the fire signals to fire alarm routing equipment (e.g. fire brigade). It operates by providing
24 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a resettable polyswitch.
Class change and test conditions do not operate this output. If operated under a fire alarm condition, the
indication will be displayed on the Touch screen display and will remain until the fire alarm is reset. Ensure
the polarity of the connections are observed at all times and end of line resistors (6k8 5%)
are fitted for correct operation.

Output to Fire Alarm Protecting Equipment (option 7.10 EN54 Pt 2)


This output, which is fused, and monitored using a 6.8k end of line resisters used for the transmission of
the fire signals to controls for automatic fire protecting equipment (e.g. Door released units etc). It
operates by providing 24 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a
resettable. polyswitch. Class change and test conditions do not operate this output. If operated under a
fire alarm condition, this output remains energised until the fire alarm is reset. Ensure the polarity of the
connections is observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.

Output to Fault Warning Routing Equipment (option 9.4.1c EN54 Pt 2)


This output, which is fused and monitored using 6.8k end of line resistor, is used for the
transmission of fault signals to fault warning routing equipment This output is monitored using 6k8
end of line resistor and it current limited to 30 mA.Under normal condition it operates by providing
12 V dc which can be connected directly to a 12 V auxiliary device (relay). It is current limited to 30 mA.
Under fault conditions or even if the DF6000 is powered down, this output will be switch to OV.
Ensure the polarity of the connections is observed at all times and end of line resistors (6k8 5%)
are fitted for correct operation.

Delays to Outputs (option 7.11 of EN54 Pt 2)


The DF6000 has the option to delay the operation of panel sounders, the fire routing equipment output
and the fire protecting equipment. This delay is selectable using the DF6000 site installer download
software .The delay is configurable in increments of 1 minute up to a maximum of 10 minutes.
This delay can be enabled and disabled at access level 2. The DF6000 has the facility for a specific
callpoint to override this delay by programming this callpoint via an input interface to provide an evacuate
signal using DF6000 site Installer.

24 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Dependencies on More Than One Alarm Signal - Type C (option 7.12.3 of EN54 Pt 2)
The DF6000 has the facility to inhibit the operation of the output sounders, output to fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using DF6000 site installer software.

Alarm Counter (option 7.13 EN54 Pt 2)


The panel records the number of instances that it enters the fire alarm condition. This is abbreviated in the
touch screen by "AC" and it is displayed in the fire window at access level 2. This counter can only be
reset by the manufacturer.

Optional Auxiliary Board VDS Requirement (option not required by EN54)


This board can be connected to an extinguishing system as well as a fire brigade control panel.
This board has been tested and approved in according with DIN14661 and DIN 14675.

Input / Outputs to Fire Brigade Panel

Outputs
Output 1: Fire Protecting Equipment Operated "Extinguishing On"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire protecting equipment (option 7.10 of EN54 Pt 2).
Output 2: Fire Routing Equipment Operated "Fire Brigade Link"
This output is ON in alarm condition to indicate that the DF6000 control and indicating
equipment has operated the fire routing equipment (option 7.9 of EN54 Pt 2).
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire protecting equipment has been disabled either by
the DF6000 control and indicating equipment or the fire brigade panel.

Section 1 - System Installation and Design 25


DF6000 - USER MANUAL

Output 4: Disablement of the Fire Routing Equipment


This output is ON to indicator that the fire routing equipment has been disabled either by the
DF6000 Control and indicating equipment or the fire brigade panel.
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the DF6000 control and indicating equipment is in alarm
condition. This output will remain on for at least 15mins after reset or when the reset has
been activated from the fire alarm brigade panel
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the DF6000
control and indicating equipment or the rire brigade panel

Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment if the DF6000. Once the FRE is
disabled from this interface, it can never be enabled from the DF6000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment of the DF6000. Once the FRE is
disabled from this interface, it can never be enabled from the DF6000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the DF6000. The disablement of sounders from
the fire brigade panel can be re-abled from the DF6000 control panel only when the system
is not Alarm State.

26 Section 1 - System Installation and Design


DF6000 - USER MANUAL

German Interface Electrical Characteristics

Inputs
The inputs are designed to be actioned in one of two ways, see list below:

First: A change in logic state ie. switch toggled on / off.


Second: Logic pulse ie. nominal state logic high, then logic low > 200mS then return to logic high.

all inputs are held high via a weak pull up (logic high), the action of short circuiting any of the five inputs to
there respective 0v will result in a logic low.

1: reset -> logic pulse


2: FRE relay test -> logic pulse
3: FPE disable -> logic state change
4: FRE disable -> logic state change
5: Acoustic disable -> pulse logic

Monitored Inputs
In Fault / Extinguisher Active

-> End Of Line resistor 3K3.


-> 680 Ohm across input to actiavte input

Relay Outputs

Normal status -> Input sees a 3K3 resistor.


Active status -> Input sees a 680 ohm resistor.

Outputs
1: Extinguisher released -> output high 26 V
2: FRE operated
3: FPE disabled
4: FRE disabled
5: Panel in fire, will remain on after panel soft reset for > 15 minutes, or extinguish immediately with
interface reset
6: Disable all sounders.

Section 1 - System Installation and Design 27


DF6000 - USER MANUAL

Optional Functions Not Approved to EN54 Pt 2 & 4


Italian Mode: (option not required by EN54 Pt 2)
This mode can be programmed at access level 3. This relates to points 12.2(a) and 12.2(b) of the Internal
Italian Ministerial Decree 9th April 1994 which states that in the event of a fire detection from 2 or more
detectors or from an MCP there should be a 2 minute delay before output activation otherwise in the
event of a fire detection from any one detector there should be a 5 minute delay before output activation,
provided that the fire event is not acknowledged. These delays apply to siren activation as well as the
shutting down/activation of other external equipment and additionally the legislation states that these
delays should be adjustable depending on the type of activity being carried out within the building.

For example, if there was a fire detected from a single detector then we should start a 5-minute
(adjustable) delay (T2). If however a fire is detected from a second detector or a call-point the delay
should automatically revert to 2 minutes (adjustable) (T1). In this scenario the value of (T1) is critical. To
keep things simple, let's assume that we set T1 = 2 minutes and T2 = 5 minutes.

Swedish Mode (option not required by EN54 Pt 2)


This mode is programmed at access level 3. One of the Swedish requirements is that access level 2 and
3 is only avalailabe by the access of the keyswitch. The key switch is wired to the class change input.

Commission per Loop (option not required by EN54 Pt 2)


This mode is programmed at access level 3. This allows the commissioning engineer to auto learn one
loop at the time

Alarm Verification (option not required by EN54 Pt 2)


This mode is programmed at access level 3.This has the flexibility to delay the activation of detectors by
30 seconds. In the event of an alarm from a detector, the led of the detector will be illuminated and no
alarm will be displayed on the panel. The detectors are checked continuously for 30 seconds. If after this
time, the detector is still in alarm, the output will be activated otherwise the detector will be reset.

Timer T1/T2 (option not required by EN54 Pt 2)


This mode is set on at access level 3 and is a commonly used by eastern european countries.

In the event of a fire the timer T1 can be set from 0 to 3 min where the alarm will be displayed on the
panel and no output activation, if during this time the alarm is acknowledged then timer T2 can be set
from 0-10 min where the alarm can be investigated and alarm reset. However if timer T1 and T2 time out
during alarm activation, the outputs will be activated.

Timer T1/T2 with callpoint Override (option not required by EN54 Pt 2)


This is similar to the above except a callpoint alarm will activate the output instantly

28 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Cable and Wiring


Only the cable types listed below are allowable for loop connections.
1. Enhanced Fire TUF
2. Fire TUF™
3. FP200
4. MICC

When choosing your preferred cable type, you must take note of the following cable and wiring
requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 2 km
3. Maximum volt drop must be limited to 7 V.
4. The conductors should be 1.5mm minimum an no larger than 2.5mm
5. Multicore cable should not be used for detector wiring.
6. Different loops should NEVER be run within the same cable.
7. Loop feeds and returns should never be used within the same cable.

Cable Resistance

Core Diameter Typica l FP200 Resistance


1.0mm² 18.1 Ohms/km/Core
1.5mm² 12.1 Ohms/km/Core
2.5mm² 7.41 Ohms/km/Core
4.0mm² 4.61 Ohms/km/Core

Cable Anchorage
The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably located knockout
feed the cable through the gland and bolt the gland to the DF6000 backbox as shown. Secure the cable
to the side of the box using the cable clip provided.

NOTE: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event
of accidental switching on of the mains supply.

Section 1 - System Installation and Design 29


DF6000 - USER MANUAL

Installation
the panel should be installed in a clean, dry, reasonably well ventilated place, and not in direct sunlight.
Temperatures in excess of 40°C and below 5°C may cause problems, if in doubt consult Cooper Lighting
and Safety. The panel should be located away from any potential hazard, in a position where it is readily
accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a
permanent entrance. Mount the panel to the wall using the drill template provided. Do not drill through the
panel to the wall as dust will contaminate the circuitry.

Installation Guide
! Never carry out insulation tests on cables connected to electronic equipment.
! DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS
! Always use the correct type of cables specifically designed for the operation of fire detection and
alarm circuits.
! Always adhere to volt drop limitation when sizing cables
! Always observe polarity throughout. Non colour coded conductors should be permanently identified.
! Screen continuity must be maintained throughout the entire loop circuit including at each junction
point and at each device, terminals are provided on each device to facilitate this.
! The screen should be earthed at the connection point provided at the DF6000 panel and not at any
other point. Both the loop start and the loop end must be connected to the appropriate earthing
points. Care must be taken to avoid connecting the screen to the earthed body of any metal devices,
enclosures or cable containment. The screen or drain wire of the loop cables should not be
considered as safety earth and therefore should not be connected to terminals marked with the earth
symbol, except at the panel, and should not be insulated with green and yellow sleeving.
! DF6000 utilises intelligent soft addressing technology to greatly simplify the installation and
commissioning processes. Once the system has been installed and the autolearn menu selected, the
DF6000 control panel will automatically scan the detection loops and allocate each device with an
address number corresponding with its position on the loop, this avoids the traditional need for
manual addressing of the system devices which is time consuming and provides a potential for error.
! It is of vital importance that accurate details are kept of the exact wiring route in order to determine
which address has been allocated to each device.

30 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Fixing Details
Read all the installation instructions before commencing with the installation. The installation of this panel
must be carried out by a suitably qualified /trained person. Theinstallation must comply with IEE wiring
regulations and with BS5839 Pt 1 2002 The electronic components within the fire panel are Static
Sensitive. Do not touch the electronics directly.

Mounting the Backbox


The DF6000 can be flush mount or surface mounted.

1. Surface Mount: Drill four holes and fix the backbox to the wall.

2. Flush Mount: The backbox requires a hole 364 x 472 with a depth of 117mm (standard battery /
backbox ) or 217 mm if deep backbox is used.

Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands.

479mm
400mm

227mm
364mm
309mm

117mm

132mm 472mm

Section 1 - System Installation and Design 31


DF6000 - USER MANUAL

External Connections (Mains Supply)


The mains supply should be installed in accordance with the current edition of the IEE wiring regulations.
Connection to the mains supply must be via an isolating device (e.g. an isolating fuse rated at 3Amps
maximum) reserved solely for the fire alarm system. The cover should be coloured red and labelled “FIRE
ALARM - DO NOT SWITCH OFF”. The isolating protective device should be secure from unauthorised
operation and ideally installed in a securely closed box with a breakable cover.

An additional warning label should be provided, depending on whether:

1. The isolating protective device is fed from the live side of the main isolating device in which case the
label on the isolating protective device, should read in addition - “WARNING: THIS SUPPLY REMAINS
ALIVE WHEN THE MAIN SWITCH IS TURNED OFF”. A further label should be placed on the main
isolating device reading “WARNING: THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH
IS TURNED OFF.

Or

2. If the isolating protective device is fed from the dead side of the main isolating device, a label should
be fixed to the main isolating device reading “WARNING: THIS SWITCH ALSO CONTROLS THE
SUPPLY TO THE FIRE ALARM SYSTEM”.

Distributed Power Supplies


The above also applies to any distributed power supply (i.e. mains connections for DF6000/PR repeat
units MPU424 relay units, etc.)

Cable Segregation
All cables for the fire alarm system should be segregated from any other cables/wiring/services.

Wiring configurations
Spurs can be taken off the loop in the following ways:

1. MIU871 Addressable Interface - Allows up to 20 conventional smoke detectors and unlimited FX201 /
203 callpoints.
2. Direct Loop Spur Wiring - Allows a zone of analogue detectors and callpoints to be directly spurred off
the loop

Note: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event
of accidental switching on of the mains supply.

32 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Networking
Up to 126 DF6000 panels or passive repeaters can be networked together to operate as a single
networked system. To achieve this each panel must be fitted with a network card (supplied at additional
cost.)

When operating as a networked system all fire and fault event information is displayed at every panel,
silencing and resetting of alarms can also be carried out from any panel on a networked system if panels
are suitably configured.

Networked panels are connected using a loop topology illustrated, or radial.

Networked panels can be used as active repeaters, alternatively a low cost passive repeater is available.
This can either be connected a loop of an individual panel or it can be connected to the network. The
recommended network cable for the network connection between panels is an enhanced Firetuf cable
Manufactured by Draka cables (part number 910234). Screen continuity must be maintained throughout
the entire network circuit including at each junction point. The screen should only be earthed at the
connection point provided at the first panel and not at any other point. The screen or drain wire of the
network cable should not be considered as a safety earth and therefore should not be connected to
terminals marked with the earth symbol, except at the panel, and should not be insulated with green and
yellow sleeving.

Where the network cable passes between buildings, screen continuity should not be maintained from
building to building. A booster device must however be used irrespective of cable length and should be
fitted at a suitable point in the link between buildings. The cable screen should be connected to the earth
of one panel in each building.

Network Cable

Power System Charge Battery


ON FIRE General
FAUL T DISABLE
System
FAUL T
System
TEST FA UL T FAUL T CF3000 ANALOGUE ADDRESSABLE FIRE P ANE L Power
ON FIRE General
FA UL T
System
DISABLE
System
FA UL T
System
TEST
Charge
FA UL T
Battery
FAUL T CF3000 ANALOGU E A DDRESSABLE FIRE P PAANEL
NE L

Zone s Zone s
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72 61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84 73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96 85 86 87 88 89 90 91 92 93 94 95 96

Designed to EN54 parts 2 & 4 Designed to EN54 parts 2 & 4

A B X Y
Network
Card
(Panel 1)

A B X Y Network
Card
(Panel 2)

Section 1 - System Installation and Design 33


DF6000 - USER MANUAL

Input/Outputs
Panel Inputs
Class Change: (option not required by EN54)
A pair of terminals are provided for class change. By shorting these terminals together (e.g. switch, time
clock) the alarm will sound (panel sounders + loop sounders only). The panel will not indicate a fire. The
alarm will cancel when the short circuit is removed. If the short circuit is not removed the alarms will not
cancel.
WARNING: No voltage should be applied to this input
class change

-
+

Switch/Contactorb timer etc.


(Apply NO voltage)

Panel Outputs
Panel Sounders: (option 7.8 EN54 Pt 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the
connections are observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp all outputs are fused with 1.6 Amp glass fuse
alarm devices should be spread equally across the 4 sounder circuits.
WARNING: Do not exceed the rated output current

All sounders must be polarised

Both sounder circuits must


be terminated with a
6800 Ohm end of line resistor

Output Fire Alarm Routing Equipment


(option 7.9 EN54 Pt 2)
This output, which is fused and monitored using a 6.8k end of line resistor, is used for the automatic
transmission of the fire signals to fire alarm routing equipment (e.g. fire brigade). It operates by providing
12 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a resettable polyswitch.
Class change and test conditions do not operate this output. If operated under a fire alarm condition, the
indication will be displayed on the touch screen display and will remain until the fire alarm is reset. Ensure
the polarity of the connections are observed at all times and end of line resistors (6k8 5%) are fitted for
correct operation.

34 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Output to Fire Alarm Protecting Equipment (option 7.10 EN54 Pt 2)


This output, which is fused and monitored using 6.8k end of line resistor is used for the transmission of
the fire signals to controls for automatic fire protecting equipment (e.g. Door release units etc).It operates
by providing 24 V output to an auxiliary device (e.g. relay).

It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do not
operate this output. If operated under a fire alarm condition, this output remains activated until the fire
alarm is reset. Ensure the polarity of the connections is observed at all times and end of line resistors (6k8
5%) are fitted for correct operation. All activated devices must be polarised.

Output to Fault Warning Routing Equipment (option 9.4.1c EN54 Pt 2)


This output, which is fused and monitored using 6.8k end of line resistor is used for the transmission of
fault signals to fault warning routing equipment This output is monitored using 6k8 end of line resistor and
it current limited to 30 mA.

Under normal conditions it operates by providing 24 V dc which can be connected directly to a 24 V


auxiliary device (relay). It is current limited to 30 mA. Under fault conditions or even if the DF6000 is
switched off, this output will switch to 0 V. Ensure the polarity of the connections is observed at all times
and end of line resistors (6k8 5%) are fitted for correct operation.

Auxiliary Relay (option not required by EN54)


This output is a volt free contact, which is protected by a polyswitch. It is rated at 24 V 1 Amp. If operated
under a fire alarm condition , this output will remain energised until the fire alarm is reset.

Auxiliary DC Output (option not defined by EN54)


A 24 V dc output is provided. This output is protected by a polyswitch. This output can be used to power
fire or fault auxiliary equipment. Please ensure that all equipments connected to this output will only draw
current when a fire condition exists.
WARNING: Do not exceed the rated output current

Mimic Output (option not required by EN54)


This RS485 output is used to send data to a mimic display or a repeater panel. The maximum distance is
2 km.

Section 1 - System Installation and Design 35


DF6000 - USER MANUAL

Maintainance
Daily Inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault indication. Notify any faults
to a system supervisior.

Weekly Test
Check indicators. Press supervisor mode on the top left of the touch screen. Enter passcode. Select
“others” tab. Press the button labeled weekly test, confirm you wish to perform the test and the amber
“System Test” LED will light. The panel will stay in the weekly test mode for 5mins before resetting. During
the weekly test, trigger a smoke detector or callpoint and check the fire panel registers the device and
illuminates the correct zonal indicator. Trigger a different device every time a weekly test is performed
ensuring devices are tested in rotation until all have been checked. It is advisable to develop a detailed a
building plan highlighting devices and locations to aid testing. The panel will reset automatically once the
5mins have elapsed. If no devices are triggered during the weekly test the panel will abort the test and
reset after 5mins. Record weekly test in the table provided in the log book.

Quarterly Test
Check all previous log book entries and verify that remedial action has been taken. Carry out the weekly
test. Visually examine the batteries and their connections, by loosening the screws behind printer door
and opening the hinged front from the right hand side. Disconnect the mains supply and check that the
batterry is capable of supplying the alarm sounders, by operating a callpoint.

Annual Test
As weekly test and quarterly test above. Additionally test all sensors and callpoints and check operation.

Every 2-3 Years


Replace or return the smoke detectors for cleaning to ensure correct operation and freedom from false
alarms. Special equipment is required for cleaning smoke detectors. Consult Cooper Lighting and Safety.

Every 5 Years
Replace sealed lead acid battery.

Cleaning
When cleaning the panel, use a moist cloth. Do not use solvents or harsh abrasives.

Printer Paper Order Code

Servicing: Cooper Lighting and Safety can offer a regular servicing contract.
Cooper Lighting and Safety
Service Division,
Wheatley Hall road
Doncaster
DN2 4NB.
Telephone: 01302 303352 Web: www.cooperfire.com

36 Section 1 - System Installation and Design


DF6000 - USER MANUAL

Section 2
Panel Assembly Information

Section 2 - Panel Assembly Information 37


DF6000 - USER MANUAL

Attaching the Door


The door is designed as a drop on fit. Offer the door up to the back box in the open position as shown
below. Align the hinges and lower the door onto the hinge pins. Check the hinges are secure.

38 Section 2 - Panel Assembly Information


DF6000 - USER MANUAL

Installing a Hinged Cover


An option hinged cover is available as an optional extra item for DF6000. This can be fitted as standard
equipment prior to despatch or retro-fitted later. The method for fitting a cover is shown below.

Insert the bottom peg of the


hinged cover into the panel as
shown and close the hinged cover
followed by the printer door. Next
from the back of the panel insert
second peg though the hole
shown below and push into the
hinged cover

Section 2 - Panel Assembly Information 39


DF6000 - USER MANUAL

Fitting Printer Paper Roll


Open the printer access door on the right hand side of the panel using the key provided. Drop the paper
roll into the paper holder and feed paper into the printer. The printer will then automatically pull the paper
through if the panel is powered up. Tear off the excess paper them close and secure the printer access
door. Please note for paper feed to operate correctly, paper end must be straight

New paper roll simply drops into the holder.

Push paper underneath the roller as


shown until printer automatically
loads the paper. Tear off excess
paper and close the printer
compartment door.

40 Section 2 - Panel Assembly Information


DF6000 - USER MANUAL

Section 3
Commissioning

Section 3 - Commissioning 41
DF6000 - USER MANUAL

Commissioning Mode
Walk test mode allows a single engineer to test the various detectors and callpoints on a system without
always having to return to the panel either to reset the system or silence the alarms. When in
COMMISSIONING MODE, the system operates as normal except that when a detector or callpoint goes
into alarm, the alarms only operate for a few seconds and then will silence. The panel then tries to reset
the device automatically and, if successful, the alarms are operated again for a few seconds and the
installation engineer can move on to the next detector. After a full test has been carried out the engineer
can check the order in which the detectors/callpoints were operated using the DISPLAY LOG mode. This
information can also be printed on the optional printer.

When the panel is in “Walk Test Mode” the control panel inserts a different code into the log and also onto
the print-out. This is to distinguish between when a device has been tested in “Walk Test Mode” and
when a device has been triggered while in normal operation.

The following differences will occur:

1. When in the LOG mode, "One man walk test”" will appear on the display followed by the address text
and device type.
2. On the printout a “One man walk test” message will appear will appear followed by the address text
and device type.
3. During a real fire “FIRE !” Will appear on the display followed by the address text and device type.

42 Section 3 - Commissioning
DF6000 - USER MANUAL

Configuration
DB Level Check
DF6000 includes the facility to test and set the system sounders with the minimum amount of
disturbance. In sounder test mode, the sounders will sound for 30 seconds on then 30 seconds off. This
facility can be accessed via the engineering menu.

Detector LED Flashing


The DF6000 detector flashing function is used to allow a visual inspection and confirmation that the fire
panel is in communication with the installed system devices. This facility can be accessed via the
engineering menu and can be switched on or off at any time as required.

Up/downloading using PC Software


The PC Software enables the address, location text, device type and any comments to be downloaded to
the DF6000 panels.

The software can download to all 126 networkable panels.

The PC is connected to each panel on the network in turn. All data for the panel is downloaded.

For networked systems, panels are identified by panel number, P1, P2 etc.

Powe r System System Charge Battery


ON FIRE General
FAUL T DISABL E
System
FAUL T TEST FAUL T FAUL T

Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96

Section 3 - Commissioning 43
DF6000 - USER MANUAL

Panel Fault Finding

V = +5.5V ± 0.5V (No Printer Attached)


NO

= O/C Normal S/C Fire


RELAY

C
AUX

= S/C Normal O/C Fire


- NC
RELAY
FAULT

V = 12V No Fault 0V (short CCT) Fault


+
-
+ 24V
O/P

V = 28.5V (No Load Connected)


+ 0V
FIRE R/E

V = -O.6V-No Fire 28V Fire

} No Fires
+26V

See Scope Plots for


-
FIRE P/E

V = -O.6V-No Fire 28V Fire Monitoring Condition


+
S+

V = 22V (Device Fitted) 0V (Unused)


S-
LOOP 1

F-

V = 22V (Device Fitted) 0V (Unused)


F+
S+
S-

= As Above
LOOP 2

F-
F+
LOOP CIRCUITS

S+
S-
LOOP 3

= As Above
F-
F+
S+
S-
LOOP 4

= As Above
-F-
F+
CHANGE
CLASS

V = 28V (Open Circuit, No Input)


+
+

= -0.6V Mon +28V Fire (Depends on Programming)


1 -

V
CIRCUIT 1
SOUNDER

}
+

See Scope
2 -

V = -0.6V Mon +28V Fire (Depends on Programming)


Plots
for
+
1 -

V = -0.6V Mon +28V Fire (Depends on Programming) Monitoring


CIRCUIT 2
SOUNDER

Conditions
+
2 -

V = -0.6V Mon +28V Fire (Depends on Programming)


Tx
Rx

}
MODEM/PC
Rs232

CTS RTS

V -9V Static Conditions


V 0V (No Data)
V 9V
V 0V
OV
Tx+ Tx-
REPEATER
MIMIC

V =0V (No Data)

44 Section 3 - Commissioning
DF6000 - USER MANUAL

Protocol Format
Normal Communications to Devices:
With the command bits set for the 'Normal' command and the MSB of the 3 mode bits set at 0, this
shortened version of the normal communications to each device allows the analogue reply or status from
each device to be read. This format of communication is generally used throughout all background
supervision of the addressable loop.

Alarm Interrogate Command:


This command is seen by all devices on the loop, so no address byte is required, and is periodically sent
out during normal communications. This command allows any device experiencing an alarm condition to
respond, with callpoints given the highest priority, reporting their address. This causes the control panel
to break off from general background supervision of the loop and focus directly on the device in question.

Full Protocol Format:


With the command bits set for the 'Normal' command and the MSB of the 3 mode bits set at 1, the long
version of the normal communications can be sent to any device. This would normally be done by the
panel following a response to the alarm Interrogate command, allowing the panel to check the device
address, ID and confirm that the analogue reply, or status, is truly an alarm condition before actioning the
panel sounder outputs, for example.

Viewing the Voltage and Current waveforms at the panel:

Loop 1: Using a digital storage oscilloscope, connect one channel to R34 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 1, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe.

Loop 2: Using a digital storage oscilloscope, connect one channel to R36 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 2, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe

Panel to Device Device to Panel

1.1 ms
300us

2ms 300us

24v
typ
7.5v
0v

Command Mode
Response ID Flags A
Start Byte 1 Byte 2 Byte 3
Parity

8 bits 5 bits 3 bits

Loop Current

Each Packet of Comms above must be separated by a gap of 20ms minimum where the line is held at 24v

Section 3 - Commissioning 45
DF6000 - USER MANUAL

PC Comissioning Software

Device Input Programming

Fire panel reports fire from device.


Fault panel reports fault from device.
Reset panel resets.
Silence silence all currently active sounders.
Pre-Alarm panel reports pre-alarm from device.
Non-Latching device won't latch in alarm condition, used in conjunction with isolates.

Isolate Zone / Address


User can define between zones or addresses to be isolated on activation of the device. The isolate list
button enables the user to enter upto 8 unique zones or addresses.

If non-latching has been enabled, Isolated devices can be un-isolated as the triggered device returns to
normal operation. (a callpoint keyswitch is an example for this application).

46 Section 3 - Commissioning
DF6000 - USER MANUAL

PC Comissioning Software

Device Outputs

Delay Configuration
The output of a device when triggered can be delayed - based on a user defined value in minutes.
This programming option is enabled when a value other than zero is entered inside the 'Delay' window.

MCP Override
This option is a manual intervention override, when enabled (check in box) the delay can be overridden
from any callpoint on the loop when triggered.

Section 3 - Commissioning 47
DF6000 - USER MANUAL

PC Comissioning Software

Panel Outputs

Dependency Type C
Each panel output can be assigned a unique list of zones derived from the zones available on the
loop, to activate this output, two unique zones from this list have to be in fire or alternatively any
zone outside this list will trigger the output also. When the 'Coincidence' box is checked - the
'Allocate device' button allows the user to populate this list.

48 Section 3 - Commissioning
DF6000 - USER MANUAL

Section 4
Panel Controls and Indicators

Section 4 - Panel Controls and Indicators 49


DF6000 - USER MANUAL

Panel Controls and Indicators


1. System LED’s 1 2 3 4
2. Zonal LED’s
3. Touch Screen Display
4. Printer Access Door
5. Slot for Optional Printer

Powe r System System Charge Battery


ON FIRE General
FAUL T DISABL E
System
FAUL T TEST FAUL T FAUL T

Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96

1 2 3 4 5 6 7 8 9 10 11

Power General System Power Sounder System System FRE Extinguisher Delay
ON FIRE FAUL T FAUL T FAUL T Disabl e DISABLE TEST Disable ACTIV ATED ACTIVE
Faul t Faul t

Zones

LED Name Function Action


1 Power On Shows Panel is On Check Indicator is Illuminated
2 Fire Indicators Panel has Detected a Fire Impliment Fire Action Procedure
3 General Fault Monitors Devices for Faults e.g. Smoke detectors/Sounders Report to System Supervisor
4 System Fault Monitors Fire Panel for Faults Report Fault to Service Dept
5 Power Fault Monitor Internal Battery Charger Report Fault to Service Dept
6 Sounder Monitors Sounder Circuits/Indicates Disablement of this Output Report Fault to Service Dept
7 System Disable Part of the System has been Disabled Report to System Supervisor
8 System Test Supervisor/Engineer is Testing the System Check with System Supervisor
9 FRE Monitors the FRE Circuit/Indicates Disablement of this Output Report Fault to Service Dept
10 Extinguisher Activated Display Activatiion of Extinguishers (If Option Fitted) Check with System Supervisor
11 Delay Active Delays on Outputs Active Check with System Supervisor

50 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Panel Controls and Indicators


1. Log Book Storage 1 2
2. Insert Supervisor Key Here
3. Printer
4. Paper Roll Storage

Power System System


ON FIRE General
FAUL T DISABLE
System
FAUL T TEST
Charge
FAUL T
Battery
FAUL T

Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96

3 2 4

1. Optional Hinged Cover


2. Scroll Up
3. Mute Buzzer
4. Scroll Down
2
3
4

Section 4 - Panel Controls and Indicators 51


DF6000 - USER MANUAL

Touch Screen Display


Supervisor Fire Pre Faults Disabled
FRE Off 0 Alarms 0 0 / Test

Systems Healthy
XX Zones Acitve

Tuesday
dd-mm-yyyy

16:25.25
BST On

The touch screen is a multi-function display consisting 320 x 240 dots featuring high intensity
backlighting. In normal operation, the display indicates as above with the backlighting off.

During an event on the system the display shows the FIRST EVENT and LAST EVENT plus other events
as space allows.

The last 2 lines are normally used to display the total number of events, but they are also used for
scrolling fire conditions, faults, pre alarms or disabled devices independently or for displaying a reduced
menu when in fire condition.

When an event occurs the touch screen backlighting comes on unless there is a mains
power supply fault.

Use the touch screen to scroll through all active events on the system by using the SCROLL UP and
SCROLL DOWN buttons (available at access level 1). You can display the contents of the log and also
view details of any fires, faults, pre-alarms,faults or disablements. When displaying the system menu on
the touch screen, the last 5 lines of the display are shown in reverse text.

52 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Panel Operation
DF6000 is operated via a backlit touch screen. The default fire screen is shown below. From this screen
all the panels functions can be operated. The first time you touch the screen the backlight will illuminate
the panel.

Supervisor Fire Pre Faults Disabled


FRE Off 0 Alarms 0 0 / Test

Systems Healthy
XX Zones Acitve

Tuesday
dd-mm-yyyy

16:25.25
BST On

Pressing a field will highlight it and forward to the next screen as shown below.

Touch the screen here to view details

Supervisor Fire Pre Faults Disabled Supervisor Fire Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE Off 1 Alarms 0 0 / Test

First Fire Meeting Room 1, Building 1, 1st floor


Loop: 1, Zone: 2, Type: Optical (150)

Systems Healthy
10 Zones Acitve
Total Fires = 1 Print All Help

Tuesday Tuesday
dd-mm-yyyy dd-mm-yyyy

16:25.25 16:25.25
BST On BST On

Section 4 - Panel Controls and Indicators 53


DF6000 - USER MANUAL

Public (Access Level 1)


Public access level does not require an access code and allows anybody to review the functions outlined
below.

Public access level


Supervisor Fire Pre Faults Disabled
FRE Off 0 Alarms 0 5 / Test

Systems Healthy
10 Zones Acitve

Tuesday
dd-mm-yyyy

16:25.25
BST On

Supervisor Fire Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE off 0 Alarms 6 6 / Test
Show Show Show Show
First Fire 12:26:23 Device 1, Zone 1 Addresses Zones I/O Test Zone
Lp: 1, Ad:1, Z:1, Opto/thermal, [69]
Print All Help

Total Fires = 1 Print All Help 001 Device 2, Zone 1


Loop 1, Zone: 1, Type : Opto/thermal

002 Device 3, Zone 1


Loop 1, Zone: 1, Type : Opto/thermal
Tuesday
dd-mm-yyyy 003 Device 4, Zone 1
Loop 1, Zone: 1, Type : Opto/thermal

16:25.25 004 Device 5, Zone 1


BST On Loop 1, Zone: 1, Type : Opto/thermal

Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 0 Alarms 6 0 / Test FRE off 0 Alarms 6 5 / Test

Print All Help Print All Help

001 03-Jun-03 12:51 Warning! : Device 1 001 03-Jun-03 12:51 Fault! : Device 1
Lp: 1, Ad: 1, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 1, Z: 1, Opto / Thermal [0]

002 03-Jun-03 12:51 Warning! : Device 2 002 03-Jun-03 12:51 Fault! : Device 2
Lp: 1, Ad: 2, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 2, Z: 1, Opto / Thermal [69]

003 03-Jun-03 12:51 Warning! : Device 3 003 03-Jun-03 12:51 Fault! : Device 3
Lp: 1, Ad: 3, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 3, Z: 1, Opto / Thermal [69]

004 03-Jun-03 12:51 Warning! : Device 4 004 03-Jun-03 12:51 Fault! : Device 4
Lp: 1, Ad: 4, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 4, Z: 1, Opto / Thermal [69]

005 03-Jun-03 12:51 Warning! : Device 5 005 03-Jun-03 12:51 Fault! : Device 5
Lp: 1, Ad: 5, Z: 1, Opto / Thermal [69] Lp: 1, Ad: 5, Z: 1, Opto / Thermal [69]

54 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Evacuate (Access Level 2)


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode Passcode and select “Evacuate” on the menu at the top of the screen.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Others
View
Faults
View
View Fires Disabled
View Pre
AC = 0
Alarms

Pre-alarm = Some smoke / heat but below fire threshold


these warnings will appear and disappear

Select “Yes” to evacuate the building.

Supervisor
FRE Off

This will activate ALL sounders


and activate all panel relays
Do you wish to continue?

Yes No

Section 4 - Panel Controls and Indicators 55


DF6000 - USER MANUAL

Silence Alarms
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode Passcode and select “Silence Alarms” button as the top of

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

View Fires Others


AC = 0 View
View Pre
View Faults
Alarms
Disabled

I/O Zone: 0

Address: 0

Touch button to view list

Select “yes” to silence Alarm.

Supervisor
FRE Off

This will silence ALL sounders


Do you wish to continue?

Yes No

56 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Mute Buzzer
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode and Select “Mute Buzzer” from the Top Menu

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

View Fires
AC =19 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Reset
Enter the Supervisor Mode and Select “Reset” from the top Menu. Select “Yes” to reset the panel.

Supervisor Silence Mute Supervisor


Evacuate Reset
FRE off Alarms Buzzer FRE Off

View Fires
View Pre Others
AC =19
Alarms View
Disabled View
Faults The panel will reset
Do you wish to continue?
001 14:22:49
Mains Failure

Yes No
Faults = Short circuits, broken detectors etc.
To remove faults from this list:
1) Fix Fault
2) Reset Panel

Section 4 - Panel Controls and Indicators 57


DF6000 - USER MANUAL

Pre-Alarms
Enter the Supervisor Mode and Select “Pre-Alarms” tab.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Others
View
Faults
View
View Fires Disabled
View Pre
AC = 0
Alarms

Pre-alarm = Some smoke / heat but below fire threshold


these warnings will appear and disappear

A pre-alarm is shown when a detector appears to register heat or smoke but in a quantity that is
insufficient to warrant an alarm. Pre-alarm may indicate a build up of dirt in a smoke detector which can
be interpreted by the detector as smoke presence.

Disabled Devices
Enter the Supervisor mode and Select the “Disabled” tab.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

View Fires Others


AC = 0 View
View Pre
View Faults
Alarms
Disabled

I/O Zone: 0

Address: 0

Touch button to view list

The individual buttons show which devices and the number of devices which have been disabled. Press
one of the buttons to display detailed information for a particular category

58 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Faults
Enter Supervisor Mode Passcode and select “Faults” tab.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
View Pre Others
AC = 0
Alarms View
Disabled View
Faults

Pre-alarm = Some smoke / heat but below fire threshold


These warnings will appear and disappear

Enable/Disable (Others Menu)


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode

Enter the Supervisor Mode passcode and select the “Others” tab.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Section 4 - Panel Controls and Indicators 59


DF6000 - USER MANUAL

Enable/Disable (Others Menu) Cont.


The Enable/Disable feature allows the operator to disable part or a whole system by the sub menus
shown on the left.

Supervisor Silence Mute


Evacuate Reset
FRE Off Alarms Buzzer

Network Enable / Disable

Enable / Disable Zone

Enable / Disable I/O

Enable All

Enable / Disable Address

Exit

Supervisor Silence Mute Supervisor Silence Mute


Evacuate Reset
FRE Off Alarms Buzzer FRE Off Evacuate Alarms Buzzer
Reset

Show Show Show Show


Exit Fire Routing: Enabled
All Detectors Alarms I/O Units
001 Device 1, Zone 1
Loop 1, Zone 1, Type: Optical / Thermal
Enable Fire Protection: Enabled

002 Device 2, Zone 1 Delayed: Enabled


Disable
Loop 1, Zone 1, Type: Optical / Thermal

003 Device 3, Zone 1 Aux Realy: Enabled Fire Relay: Enabled


Disable
Loop 1, Zone 1, Type: Optical / Thermal

004 Device 4, Zone 1 Fault Realy: Enabled


Enable
Loop 1, Zone 1, Type: Optical / Thermal

005 Device 5, Zone 1 Disable Exit


Loop 1, Zone 1, Type: Optical / Thermal

Supervisor Silence Mute Supervisor


Evacuate Reset
FRE Off Alarms Buzzer FRE Off

Exit Touch “Enabled” button to Disable


Touch “Disabled” button to Enalbe

Zone 001 Zone 1 Enable Enable all devices?

Zone 002 Zone 2 Disable Do you want to continue?

Zone 003 Zone 3 Disable

Yes No
Zone 004 Zone 4 Enable

60 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Print
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode and Select the “Others” Tab. Press “Print”

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Select the Information You wish to Print from the Buttons Listed.

Service Silence Mute


Evacuate Reset
FRE off Alarm Buzzer

Print All Log Records Print Fire Log

Print last 10 Log Records Print Fault Log

Print Disablement Print Test Log

Print Current Faults

Print Current Files Exit

Section 4 - Panel Controls and Indicators 61


DF6000 - USER MANUAL

Lamp Test
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode and Select the “Others” Tab. Press “Lamp Test”

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Supervisor
FRE Off

Lamp Test

LED’s will light in


numerical order

Yes No

62 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Weekly Test
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode. Select the others tab as
shown below. Press Weekly test.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Weekly test is now in progress.

Supervisor
FRE Off

* Features outside EN54 spec

Weekly Test
Weekly Test Awaiting alarm signal
Do you want to continue?
Will rest after 4 minutes

Yes No Cancel

The panel will automatically return to the system healthy screen once the weekly test has been
completed.

Section 4 - Panel Controls and Indicators 63


DF6000 - USER MANUAL

Viewing Events
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode Passcode. Select the “Others” tab and press View Log.

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Use the scroll bar to view the list of upto 1000 events.

Supervisor Silence Mute Events can be sorted


Evacuate Reset
FRE off Alarms Buzzer by selecting from the
Newest Oldest Exit
sort option menu.

Show Show Show Show


All Fires Faults Tests
001 Monday 13-Jan-2004 08:34:12
Hard Reset

002 FIRE! Lobby, [Optional] (Ana=150)


Building 1, Ground flour, Panel 1, Loop1, device 1

003 Monday 06-Nov-2000 11:22:12


Soft Reset

004 Monday 13-Nov-2001 11:22:12 Fault


Panel 1, Loop1, device 1

005 Monday 18-Feb-2001 22:20:18


Mains or battery failure

The DF6000 event log stores up to 1000 events including, fires, faults, resets and address changes.
Once the maximum 1000 events has been reached DF6000 will automatically overwrite the oldest event
every time a new event is stored. The event log can only be reset by an approved service engineer.

64 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Check Auto Config


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the passcode.

Enter the Supervisor Mode and Select the “Others” Tab. Press Check Auto Config. This feature will scan
the loop and pinpoint the exact location of any break in the loop wiring and will also identify any changes
in the loop configuration (e.g. New devices added or changed device types).

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Supervisor
FRE Off

Check Auto Config

Replace Device

Exit

Supervisor
FRE Off

Check
Auto Config

Yes No

Section 4 - Panel Controls and Indicators 65


DF6000 - USER MANUAL

Replace Device
Replace device enables an existing device to be replaced with a new device without losing the existing
text and sounder programming. Replace a single device then use use the replace device menu to allocate
an existing address to the new device

Supervisor Silence Mute


Evacuate Reset
FRE off Alarms Buzzer

Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others

Enable / Disable Weekly Test Send Log to PC

Print Veiw Log Check Config.

Lamp Test Send Analogue Value to PC

Supervisor
FRE Off

Check Auto Config

Replace Device

Exit

Supervisor Supervisor
FRE off FRE off

Select a Loop Enter Loop 1 Address

Loop 1 0 1 2 3
Loop 2
Del 4 5 6

Exit Exit OK 7 8 9

66 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Test Device (Access Level 3)


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the service mode touch the supervisor button and enter engineer passcode.

Service Mute Enter the Service


Exit Reset
FRE off Buzzer mode. Select “Test”.
Commission

Configure

Test

Enable/Disable Address

Service Mute Select the


Exit Reset
FRE off Buzzer “Test Device” button.
Test Device

Test Zone

Sounder Level Test Mode

Globle Flashing LED on/ff

One Walk Walk Test

Touch row to select device to test.


Service Exit Reset
FRE off

Touch row to test


Show Show Show Show
All Detectors Alarms Relay Test Devises
001 Lobby, Building 1, 1st Floor
Loop 1, Zone 2, Type: Optical Loop 1, Address 1
002 Main Reception, Building 1, 1st Floor
Loop 1, Zone 2, Type: Optical
Yes No
003 Storage / archive, Building 1, 1st Floor
Loop 1, Zone 2, Type: Optical

004 Meeting Room 1, Building 1, 1st Floor


Loop 1, Zone 2, Type: Optical

Section 4 - Panel Controls and Indicators 67


DF6000 - USER MANUAL

Test Zone
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode, Select “Test” and on the Screen Shown Below Press “Test Zone”

Service Mute
Exit Reset
FRE off Buzzer

Test Device

Test Zone

Sounder Level Test Mode

Globle Flashing LED on/ff

One Walk Walk Test

Service Exit Reset


FRE off

Touch “_” Button to place a zone into test mode


Touch “_” Button to remove a zone into test mode

Zone 001 Building 1, Ground _

Zone 002 Building 1, 1st Floor Test

Zone 003 Building 1, 2nd Floor _

Zone 004 packing & Stores _

_
Zone 005 Building 2, Basement

68 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Sounder Level Test Mode


Enter the Service Mode and Select Test. From the Test Menu Select “Sounder Level Test Mode”

Service Mute Service Mute


Exit Reset Exit Reset
FRE off Buzzer FRE off Buzzer

Commission Test Device

Test Zone
Configure

Sounder Level Test Mode


Test
Globle Flashing LED on/ff

Enable/Disable Address One Walk Walk Test

Sound Level Test Mode

Do you want to continue?

Yes No

Sound Level Test Mode

All sounders will now pulse


15 seconds on, 30 seconds off

Touch “Stop” button to stop test

Stop

Section 4 - Panel Controls and Indicators 69


DF6000 - USER MANUAL

Global Flashing LED On/Off


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Test.

Service Mute If global LED flashing is


Exit Reset
FRE off Buzzer set to on, all device
LED’s will pulse
Commission
intermittently to
confirm correct
Configure communication.

Test

Enable/Disable Address

Service Mute Select “Global Flashing


Exit Reset
FRE off Buzzer LED On/Off” from the
Test Menu Screen.
Test Device

Test Zone

Sounder Level Test Mode

Globle Flashing LED on/ff

One Walk Walk Test

Global Flashing LED’s

Flashing Off

70 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

One Man Walk Test


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Test.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute Select “One Man


Exit Reset
FRE off Buzzer Walk Test” from the
Test Menu Screen.
Test Device

Test Zone

Sounder Level Test Mode

Globle Flashing LED on/ff

One Walk Walk Test

* Features outside EN54 spec

One Man Walk Test


One Man Walk test
Awaiting Alarm Signal
Do you want to continue?

Yes No Stop

Section 4 - Panel Controls and Indicators 71


DF6000 - USER MANUAL

Commission: Load CDR from Laptop


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute Select “Load CDR


Exit Reset
FRE Off Buzzer from Laptop” from the
Commission Menu”
Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

After pressing “Yes”


click commission on
the PC download
software.
Load CDR from Laptop

This will erase the current CDR Important:


Do you want to continue? Do not click
commission before
Yes No pressing “Yes” on the
“Load CDR” screen.

72 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Commission: Download CDR to Laptop


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute Select “Download CDR


Exit Reset
FRE Off Buzzer from Laptop” from the
Load CDR from Laptop Analogue Level
Commission Menu
Screen.
Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Download CDR to Laptop

Start PC Program

Press “OK” to continue


Or “Cancel” to Exit

Ok Cancel

Section 4 - Panel Controls and Indicators 73


DF6000 - USER MANUAL

Commission: Auto Learn


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Select “Auto Learn”


from the Configure
Menu Screen.
Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Service
Important:
Exit Auto Learn
FRE off Activating autolearn
will erase all existing
Do you want to continue? programming, text
and configuration
No data.

Pre- Addressed Auto Learn

Yes - Autolearn All Loops

74 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Erase Log
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute Select “Erase Log


Exit Reset
FRE Off Buzzer and Reset” from the
Configure Menu
Load CDR from Laptop Analogue Level
Screen.
Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

This will delete all log entries

Do you want to continue?

Yes No

Section 4 - Panel Controls and Indicators 75


DF6000 - USER MANUAL

System Details
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission, then Press “System Details”.

Service Mute Service Mute


Exit Reset Exit Reset
FRE off Buzzer FRE Off Buzzer

Commission Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings


Configure
Auto Learn Change Panel Number

Number of Panel
Test Erase Log and Reset
in Network

Systems Detail Screen Cover

Enable/Disable Address
Load Logo From PC Italian Mode

Service Service
Print Exit Reset Print Exit Reset
FRE Off FRE Off
Program V3.02.01 Loop 1 Loop 2 Loop 3 Loop 4
Program Data 22/01.08
CDR V0.5 Optical 0 0 0 0
CDR Checksum 0xF7D95E Ionisation 13 14 0 0
Loop Controller 1 V2.1.4 Thermal A1R 0 0 0 0
Loop Controller 2 V0.0.0 Opto / Thermal 0 0 0 0
Panel Number 0 Thermal BS 0 0 0 0
Total Panels 1 Thermal CS 2 1 0 0
Total Addresses 13 Alarm 0 0 0 0
Total Zones 4 I / O Units 0 0 0 0

Page 1 Page 2 Page 3 Page 4 Page 5 Page 1 Page 2 Page 3 Page 4 Page 5

Service
Print Exit Reset
FRE Off
Loop 1 Loop 2 Loop 3 Loop 4

SCU 0 0 0 0
Voice Annunciator 13 14 0 0
Repeater 0 0 0 0
ZMU / {SUM 0 0 0 0
Beam Detector 0 0 0 0
Technical Timer 2 1 0 0
Access Control 0 0 0 0
Emerg.Light.Module 0 0 0 0
Carbon Monoxide 0 0 0 0

Page 1 Page 2 Page 3 Page 4 Page 5

76 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Analogue Level
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission then press “Analogue Levels”.

Service Mute Service Mute


Exit Reset Exit Reset
FRE off Buzzer FRE Off Buzzer

Commission Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings


Configure
Auto Learn Change Panel Number

Number of Panel
Test Erase Log and Reset
in Network

Systems Detail Screen Cover

Enable/Disable Address
Load Logo From PC Italian Mode

Service Note:
Exit Goto Reset
FRE Off Go to command can
Show Show Show Show Show be used to jump to a
All Detectors Optical Ionisation Thermal
specific address
001 Device 1, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal

002 Device 2, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

003 Device 3, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

004 Device 4, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

005 Device 5, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

Enter Address
..............................

Loop 1 0 - 13
1 2 3
Loop 2 0-0 4 5 6
Loop 3

8 9
0-0

Loop 4 0-0
7
Cancel
ok 0
Section 4 - Panel Controls and Indicators 77
DF6000 - USER MANUAL

Printer Settings
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission then press “Printer settings”.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute
Exit Reset
FRE Off Buzzer

Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log and Reset
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Service
Exit Reset
FRE Off

Auto

Request

78 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Change Panel Number


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission then press “Change Panel Number”

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute
Exit Reset
FRE Off Buzzer

Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log and Reset
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Change Panel Number


0..............................
1 2 3
4 5 6
7 8 9
Cancel
ok 0
Section 4 - Panel Controls and Indicators 79
DF6000 - USER MANUAL

Number of Panels in Network


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission then press “Number of Panels in Network”

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute
Exit Reset
FRE Off Buzzer

Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log and Reset
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Number of Panels
In Network
1.............................. 1 2 3
4 5 6
7 8 9
Cancel
ok 0
80 Section 4 - Panel Controls and Indicators
DF6000 - USER MANUAL

Screen Cover
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Commission then press “Screen Cover”

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute
Exit Reset
FRE Off Buzzer

Load CDR from Laptop Analogue Level

Dowload CDR to Laptop Printer Settings

Auto Learn Change Panel Number

Number of Panel
Erase Log and Reset
in Network

Systems Detail Screen Cover

Load Logo From PC Italian Mode

Service
Exit Reset
FRE Off

Installed

Not Required

Section 4 - Panel Controls and Indicators 81


DF6000 - USER MANUAL

Programming I/O and Sounders


To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.

Enter the Service Mode and Select Configure.

Service Mute
Exit Reset
FRE off Buzzer

Commission

Configure

Test

Enable/Disable Address

Service Mute Select “Programming


Exit Reset
FRE Off Buzzer I/O and Sounders””
Programming I/O from the Configure
Add/Delete
and Sounders Menu Screen.
Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode Day / Night

Service Mute Press panel outputs -


FRE Off Exit Reset
Buzzer
Note:
Panel Outputs T1/T2
Interface
Alarm Verification Feature
Inputs/Interface
Auxiliary Board
Outputs are only
HMO FRE Double Knock Override used in certain
export markets
Sounder Tone

82 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Sound Settings
Touch sound settings.

Service Exit Reset


FRE Off

Sound Settings

Selections from the screens below will become the global settings for all loop sounders.
Service Exit Service Exit
Reset Reset
FRE Off FRE Off

Volume
This will efffect all sounders

Volume Low

Medium

Sound High

Service Exit Service Exit


Reset Reset
FRE Off FRE Off

Volume
This will efffect all sounders

Volume Slow Loop

Two Tone

Sound Continuous

Section 4 - Panel Controls and Indicators 83


DF6000 - USER MANUAL

Change Date/Time
Enter the Service Mode and Select Configure. Select Change Date/Time.

Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Set the Time Using the Buttons Shown Below.


Service
OK Cancel Reset
FRE Off

Current Time: +1 + 10 +1
Hour Minutes Minute
10:10:04 -1 - 10 -1
Hour Minutes Minute

BST On
+1 + 10 +1
Current Date: Day Month Year

Wednesday -1 - 10 -1
dd-mmm-yyyy Day Month Year

84 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Change Address Text


Enter the Service Mode and Select Configure. Select “Change Text”

Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Press “Change Address Text”


Service Mute
Exit Reset
FRE off Buzzer

Change Address Text

Change Zone Text

Change Panel

Select the Address you wish to change and edit using the keyboard
Service
FRE Off
Exit Reset Name for address 1

Show Show Show Show Address 1


...........................................................................
All Detectors Alarms I/O Units
001 Device 1, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal
1 2 3 4 5 6 7 8 9 0
002 Device 2, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal
Q W E R T Y U I O P
003 Device 3, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal A S D F G H J K L
004 Device 4, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal CAPS Z X C V B N M , .
005 Device 5, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal OTHER SPACE OK CANCEL

Section 4 - Panel Controls and Indicators 85


DF6000 - USER MANUAL

Change Zone Text


Enter the Service Mode and Select Configure. Select “Change Text”

Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service Mute Press


Exit Reset
FRE off Buzzer “Change Zone Text”
Change Address Text

Change Zone Text

Change Panel

Select the Address you wish to change and edit using the keyboard
Supervisor Reset
FRE Off Enter the name for zone 2
Zone 2
..........................................................
Exit

Zone 001 Zone 1


1 2 3 4 5 6 7 8 9 0
Zone 002 Zone 2
Q W E R T Y U I O P
Zone 003 Zone 3
A S D F G H J K L
Zone 004 Zone 4
CAPS Z X C V B N M , .
OTHER SPACE OK CANCEL

86 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Change Panel Text


Enter the Service Mode and Select Configure. Select “Change Text”

Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service
Press
Exit Reset
FRE off “Change Panel Text”

Change Address Text

Change Zone Text

Change Panel

Correct Panel Text


DF6000
..........................................................

1 2 3 4 5 6 7 8 9 0
Q W E R T Y U I O P

A S D F G H J K L

CAPS Z X C V B N M , .
OTHER SPACE OK CANCEL

Section 4 - Panel Controls and Indicators 87


DF6000 - USER MANUAL

Configure Zones
Enter the Service Mode and Select Configure. Select “Configure Zones”

Service Mute
FRE Off Exit Reset
Buzzer
Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service
Select Zone into which
Exit Reset
FRE Off device will be added
Touch row to configure

Zone 001 Zone 1

Zone 002 Zone 2

Zone 003 Zone 3

Zone 004 Zone 4

Service Touch the dash to


Exit Goto Reset
FRE Off move the device into
Show Show Show Show Show the selected zone.
All Detectors Alarms I/O Units Selected
001 Device 1, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal In Zone

002 Device 2, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal In Zone
003 Device 3, Zone 1
Loop: 1, Zone 1, Type: Opto / Thermal In Zone

004 Device 4, Zone 2 _


Loop: 1, Zone 2, Type: Opto / Thermal

005 Device 5, Zone 2 _


Loop: 1, Zone 2, Type: Opto / Thermal

88 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Change User Code


Enter the Service Mode and Select Configure. Select “Change User Code”

Service
FRE Off Exit Reset

Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service Mute Please Enter Code


Exit Reset
FRE Off Buzzer
..............................

New Code
1 2 3
Change Engineering Code ..............................

Verify New Code


4 5 6
Change User Code
..............................
7 8 9
Cancel
ok 0

Passcode is not correct. Verification is incorrect. New password accepted.


No change made No change made Save

Ok Ok Ok

Section 4 - Panel Controls and Indicators 89


DF6000 - USER MANUAL

Add Zone
Enter the Service Mode and Select Configure. Select “Add Zone”

Service Mute
FRE Off Exit Reset
Buzzer

Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service Exit Reset


FRE Off

Add Zone

Delete Zone

Add Device

Delete Device

Add Zone?

Yes No

90 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Delete Zone
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Zone”

Service Exit Reset


FRE Off

Add Zone

Delete Zone

Add Device

Delete Device

Service
Select Zone to be
Reset
FRE Off Deleted
Exit Touch row to delete

Zone 001 Zone 1

Zone 002 Zone 2

Zone 003 Zone 3

Zone 004 Zone 4

Confirm or Cancel
Deletion

Add Zone 2?

Yes No

Section 4 - Panel Controls and Indicators 91


DF6000 - USER MANUAL

Add Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Add Device”

Service Exit Reset


FRE Off

Add Zone

Delete Zone

Add Device

Delete Device

Service
Select a Loop to Add a
Reset
FRE Off New Device
Loop 1

Loop 2

Loop 3

Loop 4

Exit

Confirm New
Device and Loop

Loop 2

Scanning Loop

Exit

92 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Delete Device
Enter the Service Mode and Select Configure, select “Add/Delete” then “Delete Device”

Service Exit Reset


FRE Off

Add Zone

Delete Zone

Add Device

Delete Device

Service
Select a Device to
Exit Goto Reset
FRE Off Delete
Touch row to delete

001 Device 1, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

002 Device 2, Zone 2


Loop: 1, Zone 2, Type: Opto / Thermal

003 Device 3, Zone 1


Loop: 1, Zone 2, Type: Opto / Thermal

004 Device 4, Zone 2


Loop: 1, Zone 2, Type: Opto / Thermal

005 Device 5, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

Confirm or Cancel
Deletion

Delete device 3?

Device 3
Loop 1, Address 3. Device Type Opto / Thermal

Yes No

Section 4 - Panel Controls and Indicators 93


DF6000 - USER MANUAL

Configure Heat Detectors


Enter the Service Mode and Select Configure. Select “Configure Heat Detectors”

Service Mute
FRE Off Exit Reset
Buzzer

Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service
Select a Device to
Exit Goto Reset
FRE Off Configure
Touch row to delete

001 Device 1, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

002 Device 2, Zone 2


Loop: 1, Zone 2, Type: Opto / Thermal

003 Device 3, Zone 1


Loop: 1, Zone 2, Type: Opto / Thermal

004 Device 4, Zone 2


Loop: 1, Zone 2, Type: Opto / Thermal

005 Device 5, Zone 1


Loop: 1, Zone 1, Type: Opto / Thermal

Select appropriate detector class

Service Reset
FRE Off

Thermal A1R

Thermal BS

Thermal CS

Exit

94 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Network
Enter the Service Mode and Select Configure. Select “Network”, This menu defines whether messages
are broadcast across the network or remain local.

Service Mute
FRE Off Exit Reset
Buzzer

Programming I/O
Add/Delete
and Sounders

Change Date/Time Configure Heat Detectors

Change Text Network

Configure Zones Language

Change Passcode

Service
FRE Off Exit Receive message over network

Reset Network

Evacuate Network

Silence Network

Fire Network

Fault Network

Pre-Alarm Network

Service Silence Mute Service Silence Mute


FRE Off Evacuate Reset FRE Off Evacuate Reset
Alarms Buzzer Alarms Buzzer

Exit Exit

Network Filter Panel 001 Enable

Configure Zones Panel 002 Enable

Panel 003 Enable

Section 4 - Panel Controls and Indicators 95


DF6000 - USER MANUAL

Password Protection
The Menvier DF6000 system has password protection which restricts access to the DISABLE Menu and
to TEST/COMMISSIONING MODE. The password is a four digit code and the default number is 2214 for
access level two and 143243 for access level 3. The password entry screen is accessed via the
supervisor mode button. Press supervisor mode and the password entry screen will be displayed, type in
the passcode and press Ok. If the wrong password is entered 3 times further access to the
system is denied.

Service
FRE Off

Please enter code: 1 2 3


..............................

4 5 6
7 8 9
Cancel
ok 0

96 Section 4 - Panel Controls and Indicators


DF6000 - USER MANUAL

Section 5
Appendix

Section 5 - Appendix 97
DF6000 - USER MANUAL

Spur Isolator - MSI850


Installation
1. Fit the unit in position.
2. Connect the unit according to the diagram below.

Notes:
A spur isolator must be used when making spurs from the analogue addressable panel loop. Without this
unit, the self addressing features of the system will not function correctly.

No addressing of the interface is required. See control panel operation for details.

Standard Connections

Out

+
Analogue
No end of line
addressable m resistor required
loop m
In
Spur
+
+

Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. For maximum spur length / load see BS5839 Pt 1:2002.
3. This unit can only be used with Menvier MAB800 and JSB FXN720 detector bases and compatible
detectors.

98 Section 5 - Appendix
DF6000 - USER MANUAL

4 Way Sounder Controller - MPU424


Installation
1. Remove the cover of the unit.
2. Fit the back-plate in position and pass the wires into it taking care not to damage the circuit board.
3. Connect the unit according to the diagram below.

Notes:
No addressing of the interface is required. See control panel operation for details. This unit requires a
permanent 230 V ac supply.

Standard Connections
6k8 6k8 6k8 6k8

Analogue
addressable loop

230V AC Mains

Fire Relay
N/O C N/C

L N E E + - E + - E + - E + - E - + E - +
OUT IN

+
+
BATT
Back up
- battery
-

Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistors must always be fitted, even if the sounder circuits are unused

Section 5 - Appendix 99
DF6000 - USER MANUAL

Zone Monitor Unit - MIU871


Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting backbox.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.

Notes:
No addressing of the interface is required. See control panel operation for details.

Standard Connections

EOLM-1

12K

- Out +
- In +
Analogue addressable loop - Out +
- In +

E - + E - + E - + E - +

Out In Callpoint Detector


Loop zone zone

Callpoints can be connected with


detectors on detector zone if preferred

Notes:
1. This unit can only be used with JSB FXN520 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt 1:2002 for aone coverage.
5. Maximum number of callpoints allowed is unlimited.
6. Detector zone end of line device is EOLM-1 (supplied)
7. Callpoint zone has end of line resistor

100 Section 5 - Appendix


DF6000 - USER MANUAL

Shop Monitor Unit - MSU840


Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting backbox.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.

Notes:
No addressing of the interface is required. See control panel operation for details.

Standard Connections

24V dC output
EOLM-1 power supply unit

12K 12K Fault contact 24V


6K8
N/O O/P

- Out +
- In +
- +
Analogue addressable loop 12K
- Out +
- In +

E - + E - + E - + E - + N/O C N/C + - + - E - +

Out In Detector Fire + - E + - 24V


Loop Callpoint External
zone zone Relay 1 2 PSU External
Sounder Monitor PSU
Input

Callpoints can be connected with


detectors on detector zone if preferred

Notes:
1. This unit can only be used with FXN520 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt 1:2002 for zone coverage.
5. Maximum number of callpoints allowed is unlimited.
6. Detector zone end of line device is EOLM-1
7. Callpoint zone has end of line resistor

Section 5 - Appendix 101


DF6000 - USER MANUAL

1 Way Input / Output Unit - MIO1240


Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.

Notes:
No addressing of the interface is required. See control panel operation for details.

Standard Connections

5K6

22K
Analogue addressable loop

Volt-Free Output
230V rated

E - + E - + - + E C N/C N/O

In Out
Spur Input

Only connected cable screen to its adjacment earth terminal.


The end of line resistor must always be be fitted, even if the spur is unused.

WARNING: Segregate mains cable from other connections to this unit. 230 V Relay output is un-
fused. Ensure that the 230 V supply feeding this unit is adequately protected

Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.

102 Section 5 - Appendix


DF6000 - USER MANUAL

Detector Base Wiring - MAB800


Supply Voltage 18 - 30 V dc
Cable Size 0.5 - 2.5mm²
Recommended cable types FIRETUF,FP200 or MICC
Mounting hole centres 50 - 80mm

Wiring Hints
1. Each terminal is suitable for clamping up to 2 wires
2. Clamping of 2 wires of very different diameters under one screw is not recommended.
3. Suitable for mounting to mounting boxes with 50-80mm fixing centres. General If difficulty is
experienced when mounting the detector, this may be due to the following:
4. Wiring causing an obstruction - move or shorten wires.
5. Although the base is tolerant to uneven mounting surfaces, a very uneven surface may cause the base
to deform when the mounting screws are tightened down - loosen screws to reduce this or slide base
to a more flat position.

WARNING: Do not use high voltage testers when detectors or control panel are connected to the
system.

+VIN remote indicator


LED (optional)

4 4
S+
Analogue addressable

Loop start
fire alarm panel

S- 3 3

1 1
F-
Loop finish

F+ 2 2

- VE COM IN - VE COM OUT

earth screen of cable to be continuous between detectors

Attention: If using the outer connection on terminal 2, ensure the operation of the switch
is not impeded and that there no shorts between terminal 2 and the switch contact.

Ensure that the cable does not short onto the contact

Section 5 - Appendix 103


DF6000 - USER MANUAL

Any 300 series analogue sensor can be connected to the loop

Section 5 - Appendix
NO C NC - + - + 0V - +26V - + S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ - + + 1 -- + 2 -- + 1- + 2 Tx Rx CTS RTS OV Tx+ Tx-
System Wiring
AUX Fault +24V Loop 1 Loop 2 Loop 3 Loop 4 Sounder Sounder MODEM/PC MIMIC
Fire R/E Fire P/E
Relay Relay O/P Class Circuit 1 Circuit 2 R&232 Repeater
Loop Circuits Change

104
DF6000 - USER MANUAL

Weatherproof Wall Sounder - MAS850LPS/WP


Installation
1. Drill required holes for the cable gland fixing
2. Drill out the required fixing holes
3. Fix to mounting surface using two suitable screws

Standard Connections

WARNING: Do not use high voltage testers if any equipment is connected to the system. earth
screen must be continuous along entire length of loop.

In Out
E - + E - +

Analogue addressable loop

Section 5 - Appendix 105


DF6000 - USER MANUAL

Internal Wall Sounder - MAS850/LPS


Installation
1. Fix to mounting surface using two suitable screws - the rear gasket fits underneath the base and the
sounder gasket fits inside the base.

Standard Connections

WARNING: Do not use high voltage testers if any equipment is connected to the system. earth
screen must be continuous along entire length of loop.

Note:
Care should be taken to ensure the cable does not put stress on the circuit board

In Out
E - + E - +

Analogue addressable loop

106 Section 5 - Appendix


DF6000 - USER MANUAL

Base Sounder - MAS850 + MASC


Supply Voltage 17 ~ 32 V dc
Cable Size / type 0.5 ~ 2.5mm/ FIRETUF, FP200 or MICC
Standby current < 320 uA
Operating temperature -10 to +55 degrees C (95%RH)
Sound output @ +/-3dB (set by panel) Low volume: 84 dB @ <4 mA
Medium volume: 92 dB @ <8 mA
High volume: 95 dB @ <12 mA
Tones (set by panel) Continuous 910 Hz
Pulsed: 910 Hz / 0 Hz pulse 1 Hz
Two tone: 610 Hz / 910 Hz @ 1 Hz cycle
Slow whoop: 500-1200 Hz in 3.5 seconds / 0.5secs gap

- +- + - +- +
S+
Analogue addressable

Loop start
fire alarm panel

S-

F-
Loop finish

F+

Section 5 - Appendix 107


DF6000 - USER MANUAL

3 Way Input / Output Unit - MIO324


Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.

Notes:
No addressing of the interface is required. See control panel operation for details.

Standard Connections

5K6 5K6 5K6

22K 22K 22K

Analogue addressable loop

Outputs
E - + E - + - + - + - + N/O C N/C N/O C N/C N/O C N/C

In Out Inputs
Loop

Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
3. Monitored inputs can detect open or short circuit faults.
4. Output relays are volt-free contacts and are not monitored.

108 Section 5 - Appendix


DF6000 - USER MANUAL

Loop Powered Beacon - MAB870


Connection Details
Earth screen of cable to be continuous between beacons

WARNING: Do not use high voltage testers if any equipment is connected to the system.

Standard Connections

In Out
E - + E - +

Loop in Loop out

Analogue addressable loop

Section 5 - Appendix 109


DF6000 - USER MANUAL

Callpoint - MBG813 / MBG817

Standard Connections

In Out
E - + E - +

Loop in Loop out

Analogue addressable loop

110 Section 5 - Appendix


DF6000 - USER MANUAL

EN54 Product Spec Label


Note: X=2 on a 2 Zone Panel / X=4 on a 4 Zone Panel

Label: D6K XB
PR200-04-517-01

Label: D6K XA
PR200-04-518-01

Powe r System System Charg e Battery


ON FIRE General
FAUL T DISABL
DISABLE E
System
FAUL T TEST FAUL T FAUL T

Zones
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60
61 62 63 64 65 66 67 68 69 70 71 72
73 74 75 76 77 78 79 80 81 82 83 84
85 86 87 88 89 90 91 92 93 94 95 96

Note: If the panel is recessed this label must be placed on the front of the panel

Section 5 - Appendix 111


DF6000 - USER MANUAL

Battery Disposal Instructions


Although batteries contain lead and small amounts of antimony and arsenic, they are safe if handled
according to the accompanying guide. The battery cells must not be dismantled as this involves several
hazards, which are best handled under controlled conditions, using specialised equipment. No attempt
should be made to repair any batteries; they should be treated as disposable when they have outlived
their use. Batteries must be disposed of in accordance with current waste disposal and pollution
legislation and in particular; The Environment Protection Act 1990, Special Waste Regulation 1996. It is
recommended that the following authorities are contacted before any attempt is made to dispose of
batteries; Environment Agency Local office, Local Authority Environmental Health or Waste Handling
department.

112 Section 5 - Appendix


DF6000 - USER MANUAL

CE Marking

CE RTIF CE RTIF
ON IC
ON IC

I
AT

AT
PR E V E NT

P R E V E NT
LPCB LPCB
I ON B OA

I ON B OA
SS

SS
R

R
LO D D
LO

0832 – CPD – 1060 714h/01 0832 – CPD – 1060 714h/01

Cooper Lighting and Safety Ltd Cooper Lighting and Safety Ltd
Wheatley Hall Road Wheatley Hall Road
Doncaster Doncaster
South Yorkshire South Yorkshire
DN2 4NB DN2 4NB

09 09

EN 54-2 1997 & A1:2006 EN 54-4 1997 & A1:2002 A2:2006

DF6000 DF6000
Control and indicating equipment for fire detection and fire Power supply equipment for fire detection and fire alarm
alarm systems for buildings systems for buildings
EN 54-2 Clause

Options Provided Other technical data: see Doc. PR200-04-513 held by the
manufacturer
7.8 Output to fire alarm devices
7.9.1 Output to fire alarm routing equipment
7.10.1 Output to automatic fire protection equipment (type A)
7.10.2 Output to automatic fire protection equipment (type B)
7.11 Delays to outputs
7.12.3 Dependencies on more than one alarm signal-Type C
7.13 Alarm counter
8.9 Output to fault routing equipment
9.5 Disablement of each point
10 Test condition

Other technical data: see Doc. PR200-04-513 held by the


manufacturer

Section 5 - Appendix 113


Head Office
Sales
Tel: 01302 303999
Fax: 01302 303333
Email: [email protected]

Technical
Tel: 01302 303350
Fax: 01302 303332
Email: [email protected]

Export
Tel: 01302 303334
Fax: 01302 303345
Email: [email protected]

Service
Tel: 01302 303352
Fax: 01302 303332
Email: [email protected]

Web: www.cooperfire.com

Head Office
Cooper Lighting and Safety Ltd
Wheatley Hall Road
Doncaster
South Yorkshire
DN2 4NB

CC1809

You might also like