The energy audit report summarizes the performance of a water pump and motor located in Ahmad Nagar. Key findings include that the pump is discharging more water than its rated capacity and the power factor indicator (PFI) panel is not working properly. It is recommended to adjust the discharge valve to reduce the flow rate and repair the PFI panel. Additionally, the pump was found to have excessive water leakage from its gland that requires repair. Overall, the report assessed 16 parameters of the pump and motor's operation and found them generally performing within criteria except for the high flow rate and non-functional PFI panel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views2 pages

Ahmad Nagar

The energy audit report summarizes the performance of a water pump and motor located in Ahmad Nagar. Key findings include that the pump is discharging more water than its rated capacity and the power factor indicator (PFI) panel is not working properly. It is recommended to adjust the discharge valve to reduce the flow rate and repair the PFI panel. Additionally, the pump was found to have excessive water leakage from its gland that requires repair. Overall, the report assessed 16 parameters of the pump and motor's operation and found them generally performing within criteria except for the high flow rate and non-functional PFI panel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

ENERGY AUDIT REPORT

Date: 30-03-2023 Pump Data Motor Data


Time : 10:00 pm Make KSB Make Siemens
Location: Ahmad Nagar Rated Discharge ( Q ) 2 cus rated KW 55

Reference # 24112152400120 Rated Head ( H ) 210 ftFrequency 50 C/S


Static water level (m) : 45.8 Discharge Dia. (Dd) Inch 8
Sr. # Parameter Unit Criteria
1 Disch. Pressure (pd) bar > 2 (WASA standard) 0.6
- 20% to +10%
2 Flow (Q) m3/h 221
of Design Flow
3 Pumping Water Level (hpl) m according to design 49
4 Voltage (V) Volt ±10% of rating 393
5 Ampere (A) Amp to be less than 78.0
rated current
6 Power Factor (Cos ø ) Nil > 0.90 0.82
7 Motor Input Power (Pinput) KW according to design 43.5
8 Speed (N) RPM > 1450~ (4 pole) 1487
9 Frict. Losses m Specified 2.25
10 Motor Efficiency (ήm) % Specified 90.0
11 per m^3 consumption kwh/m^3 < 0.30 0.20
12 Motor Vibration (Upper Bearing) mm/s < 5.1 5.4
13 Motor Vibration (Lower Bearing) mm/s < 5.1 3.1
14 Pump vibration (Thrust bearing) mm/s < 5.1 2.3
15 Temperature at (Upper Bearing) ⁰C < (Ambient temp. +40) °C 29.0
16 Temperature at (Lower Bearing) ⁰C < (Ambient temp. +40) °C 32.1
FINDINGS & RECOMMENDATIONS
Excessive water leakage from the pump gland.

Flow is higher than rated capacity. It is recommended to adjust discharge valve.

PFI panel is not working properly.

Mamoona Ishtiaq
SDO (ELECTRICITY), WASA