0% found this document useful (0 votes)
114 views6 pages

Bitzer Selection Software

This document provides specifications for two semi-hermetic reciprocating compressors, the 2HES-1Y and the 2JES-07Y, that could be used in a refrigeration or air conditioning system. It includes key performance data like cooling capacity, power input, mass flow rate, operating limits, dimensions, and technical details. Considerations are given for using these compressors with different refrigerants and in various temperature applications. The document also provides background on ASERCOM certification of compressor performance data.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views6 pages

Bitzer Selection Software

This document provides specifications for two semi-hermetic reciprocating compressors, the 2HES-1Y and the 2JES-07Y, that could be used in a refrigeration or air conditioning system. It includes key performance data like cooling capacity, power input, mass flow rate, operating limits, dimensions, and technical details. Considerations are given for using these compressors with different refrigerants and in various temperature applications. The document also provides background on ASERCOM certification of compressor performance data.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change.

1/6

Selection: Semi-hermetic Reciprocating Compressors


Input Values
Cooling capacity 3,70 kW
Mode Refrigeration and Air
conditioning
Refrigerant R455A
Reference temperature Dew point temp.
Evaporating SST -5,00 °C
Condensing SDT 35,0 °C
Liq. subc. (in condenser) 0K
Suction gas temperature 20,00 °C
Operating mode Auto
Power supply 400V-3-50Hz
Capacity control 100%
Useful superheat 100%
Result
Compressor 2JES-07Y-40S 2HES-1Y-40S
Capacity steps 100% 100%
Cooling capacity 3,28 kW 4,16 kW
Cooling capacity * 3,28 kW 4,16 kW
Evaporator capacity 3,28 kW 4,16 kW
Power input 1,01 kW 1,27 kW
Current (400V) 2,28 A 2,61 A
Voltage range 380-420V 380-420V
Condenser capacity 4,28 kW 5,43 kW
COP/EER 3,26 3,29
COP/EER * 3,26 3,29
Mass flow 66,7 kg/h 84,7 kg/h
Operating mode Standard Standard
Discharge gas temp. w/o cooling 86,7 °C 86,3 °C

Consider national standards for the use of flammable refrigerants.


*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)

Application Limits 100% 2HES-1, 2JES-07

Legend
additional cooling & suction gas
superheat ≤20K
additional cooling

M1: motor 1

M2: motor 2
BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change. 2/6

Technical Data: 2HES-1Y


Dimensions and Connections
BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change. 3/6

Technical Data
Technical Data
Displacement (1450 RPM 50Hz) 6,51 m³/h
Displacement (1750 RPM 60Hz) 7,86 m³/h
No. of cylinder x bore x stroke 2 x 38 mm x 33 mm
Weight 47 kg
Max. pressure (LP/HP) 19 / 32bar
Connection suction line 16 mm - 5/8''
Connection discharge line 12 mm - 1/2''
Oil type R134a/R407C/R404A/R507A/R407A/R407F BSE32(Standard) | R134a tc>70°C: BSE55 (Option)
Oil type R22 (R12/R502) B5.2 (Option)
Oil type R1234yf BSE32 (Standard) | R1234yf tc>70°C : BSE55 (Option)
Oil type R1234ze BSE55 (Standard) | to>15°C: BSE85K (Option) | tc>70°C:
BSE85K (Option)
Oil type R454C/R455A BSE32 (Standard)
Oil type R515B BSE55 (Standard) | to>15°C: BSE85K (Option) | tc>70°C:
BSE85K (Option)
Motor data
Motor version 2
Motor voltage (more on request) 380-420V Y-3-50Hz
Max operating current 3.8 A
Starting current (Rotor locked) 16.7 A
Max. Power input 2,0 kW
Extent of delivery (Standard)
Motor protection SE-B3(Standard), SE-B2(Option)
Enclosure class IP66
Vibration dampers Standard
Oil charge 1,00 dm³
Discharge shut-off valve Standard
Suction shut-off valve Standard
Available Options
Additional fan Option
Crankcase heater 0..60 W PTC (Option)
Sound measurement
Sound power level (-10°C / 45°C) 64,5 dB(A) @ 50Hz
Sound power level (-35°C / 40°C) 62,5 dB(A) @ 50Hz
Sound pressure level @ 1m (-10°C / 45°C) 56,5 dB(A) @ 50Hz
Sound pressure level @ 1m (-35°C / 40°C) 54,5 dB(A) @ 50Hz
BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change. 4/6

Technical Data: 2JES-07Y


Dimensions and Connections
BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change. 5/6

Technical Data
Technical Data
Displacement (1450 RPM 50Hz) 5,21 m3/h
Displacement (1750 RPM 60Hz) 6,29 m3/h
No. of cylinder x bore x stroke 2 x 34 mm x 33 mm
Weight 47 kg
Max. pressure (LP/HP) 19 / 32bar
Connection suction line 16 mm - 5/8''
Connection discharge line 12 mm - 1/2''
Oil type R134a/R407C/R404A/R507A/R407A/R407F BSE32(Standard) | R134a tc>70°C: BSE55 (Option)
Oil type R22 (R12/R502) B5.2 (Option)
Oil type R1234yf BSE32 (Standard) | R1234yf tc>70°C : BSE55 (Option)
Oil type R1234ze BSE55 (Standard) | to>15°C: BSE85K (Option) | tc>70°C:
BSE85K (Option)
Oil type R454C/R455A BSE32 (Standard)
Motor data
Motor version 1
Motor voltage (more on request) 380-420V Y-3-50Hz
Max operating current 3.7 A
Starting current (Rotor locked) 14.8 A
Max. Power input 1,9 kW
Extent of delivery (Standard)
Motor protection SE-B3(Standard), SE-B2(Option)
Enclosure class IP66
Vibration dampers Standard
Oil charge 1,00 dm³
Discharge shut-off valve Standard
Suction shut-off valve Standard
Available Options
Additional fan Option
Crankcase heater 0..60 W PTC (Option)
Sound measurement
Sound power level (+5°C / 50°C) 63,0 dB(A) @ 50Hz
Sound power level (-10°C / 45°C) 63,5 dB(A) @ 50Hz
Sound power level (-35°C / 40°C) 63,5 dB(A) @ 50Hz
Sound pressure level @ 1m (+5°C / 50°C) 55,0 dB(A) @ 50Hz
Sound pressure level @ 1m (-10°C / 45°C) 55,5 dB(A) @ 50Hz
Sound pressure level @ 1m (-35°C / 40°C) 55,5 dB(A) @ 50Hz
BITZER Software v7.0.0 rev0 16.01.2024 / All data subject to change. 6/6
Semi-hermetic Reciprocating Compressors

Semi-hermetic Reciprocating Compressors


Motor 1 = e.g. 4TES-12 with 12 "HP", primary for air-conditioning (e.g. R22,R407C) and air-conditioning with R134a at high
ambient temperatures.
Motor 2 = e.g. 4TES-9 with 8 "HP", universal Motor for medium and low temperature application (e.g. R404A, R507A, R407A,
R407F) and air-conditioning with R134a
Motor 3 = e.g. 4TES-8, for medium temperature applications and R134a
For more information concerning the application range use the "Limits" button.

Operation modes 4VES-7 to 6FE-44 and 44JE-30 to 66FE-88 with R407F/R407A/R22


CIC = liquid injection with low temperature application, suction gas cooled motor.

ASERCOM certified performance data


The Association of European Refrigeration Component Manufacturers has implemented a procedure of certifying performance
data. The high standard of these certifications is assured by:
* plausibility tests of the data performed by experts.
* regular measurements at independent institutes.
These high efforts result in the fact that only a limited number of compressors can be submitted. Due to this not all BITZER
compresors are certified until now. Performance data of compressors which fulfil the strict requirements may carry the label
"ASERCOM certified". In this software you will find the label at the respective compressors on the right side below the field
"result" or in the print out of the performance data. All certified compressors and further information are listed on the homepage
of ASERCOM.

Condensing capacity
The condensing capacity can be calculated with or without heat rejection. This option can be set in the menu
Program ⟹ Options. The heat rejection is constantly 5 % of the power consumption. The condensing capacity is to be found in
the line Condensing cap. (with HR) resp. Condensing capacity.

Data for sound emission


Data based on 50 HZ apllication (IP-units 60 Hz) and R404A if not declared.
Sound pressure level: values based on free field area conditions with hemisperhical sound emission in 1 meter distance.

General remarks regarding sound data


Listed sound data were measured under testing conditions in our laboratory. For this purpose the free-standing test sample is
mounted on a solid foundation plate and the pipework is connected vibration-free to the largest extend possible. Suction and
discharge lines are fixed in a flexible configuration, such that a transmission of vibrations to the environment can be largely
excluded. In real installations considerable differences might be observed, compared to the measurements in the laboratory.
The airborne sound emitted by the compressor can be reflected from surfaces of the system and this may increase the airborne
sound level measured close to the compressor. Vibrations caused by the compressor are also transferred to the system by the
compressor feet and piping depending on the damping ratio of the fixings. Thus, the vibrations can induce other components to
such an extent that these components contribute to an increase in airborne sound emission. If required, the transfer of
vibrations to the system can be minimized by suitable fixing and damping elements.

You might also like