PR502 Datasheet
PR502 Datasheet
PR502 Datasheet
Features:
! Ramp / Soak Control
! 4+4 Digits, 7 Segment LED Dual Display
! LED Status Indicator : Relay ON, Tune, Alarm, Manual
! 4 Front Panel Control buttons
! TC / RTD Input, Analog Input
! ON - OFF / PID Control
o
! C / oF Selectable
! 10 Programs, 16 Steps Each
! Alarm at Each Step
48 x 48mm ! Memory Retention
Certifications :
Display 4+4 Digits 7 Segment LED Dual Display Control Action 1) PID Control with Auto tuning
Height of Upper Display : 10mm 2) ON-OFF Control
Height of Lower Display : 7mm Proportional Band (P) 0.0 to 400.0o
LED Indications Relay ON, Alarm, Manual mode, Tune Integral Time (I) 0 to 3600 sec
Derivative Time (D) 0 to 200 sec
Input Specifications Alarm
Modes Deviation high, Deviation low, Band, Full scale
Inputs Thermocouple (J, K, T, R, S, C, E, B, N, L, U, W,
high, Full scale low, Sensor break
Platinel II), RTD (PT100)
DC Analog inputs (-5 to 56mV, 0 to 10V, Operation Absolute / Deviation mode
0 to 20mA) Hysteresis Programmable
Resolution 1 / 0.1o for TC / RTD only Hold / Standby mode Programmable
( Fixed 1° resolution for R & S type TC)
Annuniator Programmable
Decimal point position selectable :
1 / 0.1 / 0.01 / 0.001 for analog input Reset Action Programmable - Automatic or Latched
Indication Accuracy For TC inputs : 0.25% of F.S. ±1o
Probe Break Action Upscale
For R & S type TC inputs : 0.5% of F.S. ±2o Profile
(20 min of warm up time for TC inputs)
For RTD input : 0.1% of F.S. ±1o No. of Profiles 10
For Analog input : ±0.5%, ±1 digit No. of Steps 16 each
(F.S. = Full Scale) Ramp/Soak Time Range 0.01 to 99.59 Hrs : Min
o
Temperature Unit C / oF Selectable Target Temperature Range SPLL to SPHL
Input Filter (FTC) 1 to 99 sec Other Profile Parameters Link profiles, Programmable repeat cycle,
Sampling time 200 ms Power down resume / Reset options, Deviation
hold, Alarm at each step with settable alarm
duration
Output Specifications
Mechanical Specifications
www.selec.com 1
PR502 Temperature Controller - Profile
PR502-0-0-0-CE
45mm
RELAY RELAY 85-270V AC/DC
46mm
48mm
Accessories (Optional)
Standard SELEC accessories that can be used with this product.
Terminal Connections
Adapter plate
1) AP7248 : Plastic adapter plate, used to mount 1 / 16 DIN (cutout size 48 x 48)
Instrument into existing (72 x 72) cutout size.
2) AP9648 : Plastic adapter plate, used to mount 1 / 16 DIN (cutout size 48 x 48)
Instrument into existing (96 x 96) cutout size.
3) AP4896-4848-G-C : Plastic adapter plate, used to mount 1 / 16 DIN
(cutout size 48 x 48) Instrument into existing (48 x 96)
cutout size.
www.selec.com 2