FOREWORD
This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C,
N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared on
the basis of the recognized standards, scientific publications, technical documents, accumulated
knowledge and experiences in petroleum industries at national and international levels.
Iranian Petroleum Standards are prepared by Iranian Petroleum Standards Organization reviewed
and amended by the relevant technical standard committees to incorporate acceptable comments
made by oil, gas and petrochemical experts.
Standards are finally approved by the “Standards High Council” of Iranian Ministry of Petroleum.
Iranian Petroleum Standards (IPS) are subject to amendment withdrawal, if required, thus the latest
edition of IPS shall be applicable.
Any comment or recommendation submitted to the “Iranian Petroleum Standards Organization” will
be evaluated in the relevant technical committee and will be considered in the next revision, upon
approval.
GENERAL DEFINITIONS:
“COMPANY” : Refers to one of the related and/or affiliated companies of the Iranian Ministry of
Petroleum such as National Iranian Oil Company, National Iranian Gas Company, National
Petrochemical Company etc.
“PURCHASER” : Means the “Company “ Where this standard is part of direct purchaser order by
the “Company”, and the “Contractor” where this Standard is a part of contract documents.
“VENDOR” and “SUPPLIER” : Refers to firm or person who will supply and/or fabricate the
equipment or material.
“WILL” : Is normally used in connection with the action by the “Company” rather than by a
contractor, supplier or vendor.
FOR
FIRST EDITION
MARCH 2004
This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner.
Neither whole nor any part of this document may be disclosed to any third party, reproduced, stored in
any retrieval system or transmitted in any form or by any means without the prior written consent of the
Iranian Ministry of Petroleum.
Mar. 2004 IPS-M-IN- 250(1)
1. SCOPE ............................................................................................................................................ 2
2. REFERENCES ................................................................................................................................ 2
3. UNITS.............................................................................................................................................. 4
4. SYSTEM REQUIREMENT .............................................................................................................. 4
4.1 General..................................................................................................................................... 4
4.2 System Architecture ............................................................................................................... 4
4.3 System Configuration............................................................................................................. 4
4.4 System Security ...................................................................................................................... 5
4.5 Sy stem Continuity................................................................................................................ 7
4.6 Alarm Handling........................................................................................................................ 7
5. SYSTEM HARDWARE REQUIREMENTS ..................................................................................... 8
5.1 Communication System ......................................................................................................... 8
5.2 Controllers ............................................................................................................................. 10
5.3 Process Interface and Data Acquisition System ............................................................... 12
5.3.1 General............................................................................................................................ 12
5.3.2 Process interface modules........................................................................................... 12
5.3.3 Data acquisition system................................................................................................ 14
5.4 Man-Machine Interface (MMI)............................................................................................... 15
5.5 System Cabinets and Consoles Structure ......................................................................... 26
5.6 Data Highway Interface to Automation Computer System ............................................... 28
5.7 Interface to Programmable Logic Controllers (PLC)......................................................... 29
5.8 Electrical Requirements ....................................................................................................... 29
6. SOFTWARE REQUIREMENTS.................................................................................................... 30
7. DOCUMENT AND DRAWINGS REQUIREMENT ........................................................................ 32
8. TRAINING ..................................................................................................................................... 36
9. SERVICE AND PARTS AVAILABILITY....................................................................................... 37
10. SHOP TESTS FOR DCS ............................................................................................................ 37
APPENDICES:
1
Mar. 2004 IPS-M-IN- 250(1)
1. SCOPE
This Standard specification defines the minimum requirements for functions, hardware, and
firmware/software of DCS employed in Iranian Petroleum Industries projects. The detailed
requirements will be specified for each individual project as a supplement to this Standard
specification.
Note: This is a revised version of the standard specification for distributed control system (DCS), which is issued
as revision (1). Revision (0) of the said standard specification is withdrawn.
2. REFERENCES
Throughout this Standard the following dated and undated standards/codes are referred to. These
referenced documents shall, to the extent specified herein, form a part of this standard. For dated
references, the edition cited applies. The applicability of changes in dated references that occur
after the cited date shall be mutually agreed upon by the company and the vendor. For undated
references, the latest edition of the referenced documents (including any supplements and
amendments) applies.
BS 381C, shade 217 "Colours for Identification, Coding and Special Purposes"
2
Mar. 2004 IPS-M-IN- 250(1)
3
Mar. 2004 IPS-M-IN- 250(1)
Equipment"
3. UNITS
This Standard is based on International System of Units (SI), unless otherwise specified.
4. SYSTEM REQUIREMENT
4.1 General
4.1.1 The DCS shall be totally distributed digital process control and data acquisition system with
shared display. The CS shall preferably be of "open system type" according to ISO 7498-1.
4.1.2 The DCS shall be furnished with a unified data-base enabling implementation of all types of
control strategies. Basic system shall be made of four building block subsystems naming
communication system. The system shall be configured hierarchical architecture capable of
integrating into higher automation levels as illustrated in Appendix A.
The Distributed Control System shall provide both geographical and functional distribution by
means of highly optimized modular architecture for simple, cost effective future expansions. The
following levels shall be incorporated into the DCS architecture.
This level shall cover all microprocessor based controller files, input/output connection terminals,
A/D and D/A converters, and signal conditioning circuits. Each module in distributed architecture
shall include a microprocessor with it’s own firmware and data-base. Each building block module
shall be task partitioned and shall be tailored to perform a specific dedicated task, such as; process
interface, control strategy implementation, data highway interface, etc. Each task shall be
performed in each block independently of other blocks.
Interconnection between controllers and shared display shall be implemented by means of a data
highway which shall be a part of basic system’s communication network.
The next level above the process control level just described is process supervision level. At this
level, operator interface to the process and to the higher levels will be performed.
4.3.1 The DCS system shall be comprised of a family of hardware and software to implement all
types of process control systems. The system shall provide a distributed intelligence architecture
with shared display, in a manner to combine; operator interfaces, process controllers and
input/output modules into an operating integrated system effective at the loop, unit and plant control
levels.
4.3.2 DCS modules shall be integrated together through a data bus oriented communication link
system. Alternatively, communication link employing IEEE 802.3 and/or IEEE 802.4 standards may
be proposed.
4
Mar. 2004 IPS-M-IN- 250(1)
4.3.3 The system configuration shall basically comprise of the following building block sub-systems :
- Communication system
-Data highway ports for interfacing with PLC’S & Batch sequence control
4.3.4 The system shall be structured so that a physical separation between the safety oriented
functions and process control related functions can be easily achieved.
4.3.5 The system shall be sized to contain 40% spare I/O capacity, 20% of them installed in the
system, unless otherwise specified. The system shall maintain the same real-time system response,
and shall maintain an adequate traffic load within communication network after full expansion.
4.4.1 General
The security of the instrumentation system shall be confirmed by all precautions necessary to
ensure that the control will continue uninterrupted, in case of equipment breakdown.
These precautions shall include minimally back-up redundant modules, manual mode on controllers
that allow manual operation, should the normal operating modes (i.e. computer, cascade,
automatic) be unavailable. The following security procedures are mentioned, as a minimum,
preference will be granted to systems with more reliable security measures.
4.4.2.1 The system design shall be based on highly modular components at all levels using the
state of the art technology.
4.4.2.2 The following points shall be considered in the system design by hardware and
software/firmware configurations:
- Function distribution shall be used to minimize the consequences in the event of a failure
occurrence in the system and to simplify maintenance.
- The system display shall be divided in hierarchical pages, with each level of the hierarchy
providing more detail information about a specific item or area in a manner that the
following levels to be available for the operation of the process.
Level 1: Overview display of overall plant status with arriving alarm annunciation.
Level 3: Portions of the process area (depending on the size of process area), with arriving
alarm indication.
Level 5: Single loop or point detail display showing process value, set-point, tuning
parameters and all information about the loop.
5
Mar. 2004 IPS-M-IN- 250(1)
4.4.2.3 The system shall also provide a dynamic display hierarchy based on alarm priorities to ease
quick access to the highest priority alarm for the process area involved.
4.4.3 Reliability
4.4.3.1 The reliability for DCS shall establish measuring guidelines to determine compliance with
requirements set forward in this standard specification and shall indicate risk as well as need for
redundancy, fail-safe design, spare part stocking, and any other protective measures available.
Details of definition and equations are included in Appendix B.
4.4.3.2 Software reliability aspects of the system should be discussed and approved by Company.
4.4.3.3 The equations indicated in Appendix B shall be used by the DCS vendor to perform detail
calculations report of his proposed system Availability and shall be submitted by his bid proposal to
the Company.
4.4.3.4 The reliability report, in addition to the Availability result, shall contain the following:
- The assumptions
- A data table listing all equipment failure rates (or probabilities of failure) and restoration
times with reference to the data source.
The system shall be fault tolerant to achieve the availability measures mentioned herein and the
system shall utilize the following failure recovery measures to exceed 99.9% availability minimally.
4.4.4.1 Redundancy
The operator will be considered as ultimate back-up for the control of the process, but such a
measure shall not be considered in availability estimation stated here-to-fore. Such a capability shall
fulfill the following requirements:
6
Mar. 2004 IPS-M-IN- 250(1)
4.4.4.3 Maintainability
- The modules of the DCS shall be designed, in a manner to be replaced without hampering
regular operations.
- Repair policy shall be based on replacing Printed Circuits boards from a small quantity of
recommended spare boards. The vendor shall have the capability to provide complete
After-Sales-Services for repairing the cards and to provide enough spare Printed Circuits
cards for ten years, minimally.
- The distributed control system shall continuously monitor itself for failure of it’s
components (modules, processors, buses, etc.) and shall provide prompt advice to the
operator when a failure is detected, by means of, automatic self-diagnostics program. All
devices operating within the DCS shall be under continuous surveillance by self-diagnostic
programs.
- Upon any malfunctioning, a designated back-up device shall be switched into operation
automatically.
- System overloads such as memory capacity, scan rate etc., shall be alarmed at the
operator console. The status of failed module(s) shall be made available as a hard copy
print-out.
- The system shall be equipped with suitable diagnostic software and hardware to locate
and identify faults and malfunctions with details such as; time of failure occurrence,
identities of faulty devices, major components malfunctioning and the back-up system which
are activated automatically.
System shall be provided with off-line diagnostic programs to perform a through detailed check of
the equipment. The Vendor shall submit detailed description of his off-line diagnostic programs with
his proposal to be evaluated by the Company. Diagnostic program shall be capable to perform
integrity checks to determine if a hardware or software error has occurred in the system.
The system shall have continuity of design and updating, that is; the system shall be capable to
accept all new developments and updating of the system without any need to obsolete the existing
system in favor of the new one.
4.6.1* Alarm annunciation shall not cease without acknowledgment when points return to normal.
4.6.3* The Alarm Silence Key shall immediately silence the audible annunciation of any alarm.
Note*:
4.6.4 Acknowledgment of any alarm shall be inhibited until sufficient detail is presented on the
display to identify the nature of the problem to the Operator (e.g. Detail Display or Group Display
including the annunciating alarm points).
7
Mar. 2004 IPS-M-IN- 250(1)
4.6.5 A means of quickly and easily guiding the Operator to displays of annunciating points must be
provided. This could be a list of displays with unacknowledged alarms or a key for directly
accessing the appropriate displays.
4.6.6 A quick and easy mean for inhibiting and restoring all configured annunciation capabilities of
any Operator Station at a time must be provided. Access must be restricted to authorized
Engineering Personnel only. This requirement will allow same configuration to be used for all
Operator Stations while permitting authorized Engineering personnel to randomly select the
Operator console to be used for alarm annunciation.
- Communication system
- Controllers
- Man-Machine-Interface (MMI)
The hardware units shall be manufacturer standard as "Off the Shelf" items.
5.1.1 General
Communication links of the DCS shall basically conform to Manufacturer Automation Protocol
(MAP). Preference will be given to International Organization for Standardization (ISO), Open
System Interface (OSI) data communication concept as outlined in Section 2 here-to-fore.
The communication media shall consist of fully redundant cable trunk running plant-wide to transfer
data between different process controllers and shared display operator stations. Connection
between components shall be made by means of flexible drop cables branched off the main cable.
5.1.2.1 The trunk cable may be made of semi-rigid, coaxial or fiber optic cables, as required.
5.1.2.2 The shields of all trunk and drop cables shall provide an effective shielding factor of 100%.
5.1.2.3 Redundant trunk bus media shall be provided for the DCS. These redundant media shall
function correctly for all DCS data communication demands independent of the main trunk.
5.1.2.4 Separate connectors shall be provided for jabber-inhibit monitoring for each communication
media. Received signal source selection circuit shall be capable of selecting any one of the
redundant media automatically and it shall be possible to enable or disable each single transmitter
independently of the other redundant transmitter when the source of received signal is one of the
redundant media.
8
Mar. 2004 IPS-M-IN- 250(1)
5.1.2.5 The physical layer design entity shall be, such that; the probability of a communication error,
causing malfunction of other controllers connected to the medium to be less than 10-6 (bit error
rate).
5.1.2.6 The link media shall provide total electrical isolation between plant areas, to minimize the
ground loop problems.
5.1.2.7 The media shall not be prone to problems arising due to moisture and corrosion.
5.1.2.8 Provision shall be made for the redundant link medium to operate normally without upsetting
overall operation or requiring any modifications in the link, in case that; any number of connected
modules fail or for removing and replacing any connected device.
5.1.2.9 The communication link shall be capable to service in hazardous area classified
environment.
5.1.2.10 The communication interface cards in each sub-system shall be galvanically isolated from
the Bus.
5.1.2.11 The communication interface card shall also be provided with a hardware timer which
disables communication, if transmission time exceeds abnormal values.
5.1.2.12 Bus control shall preferably be performed by token passing or CSMA/CD method in
accordance with one of the following standards:
IEEE 802.3
IEEE 802.4
IEEE 802.5
ISA/S 72.01
5.1.2.13 The access cycle time to the Bus will be dependent on communication load and the
number of system equipment connected to the Bus, but anyhow in all circumstances, this access
time shall not be greater than 500 m Sec.
5.1.2.14 All communication failure shall be reported suitably to the operator station. Such failures
shall be logged in the system’s diagnostics list. Continuous communication routine shall detect the
communication system failure for alarming and switching to the redundant medium automatically.
5.1.2.15 Request for internal DCS information exchanges shall be generated from one of the
following sources:
- Status changes
5.1.2.16 In periods with high communication load, the system shall consider priority for alarm
transmissions over system information request.
5.1.2.17 The data protocol used shall safeguard against false data transmission and shall detect
transmitted data errors.
9
Mar. 2004 IPS-M-IN- 250(1)
5.1.3.1 Necessary interfaces shall be provided in the system to link 16 data highways in Bus, Ring
or Star architecture or any combination of them, as a minimum.
5.1.3.2 Routing of data among multiple highways shall be handled, in a manner that; error detection
on one communication path results an intelligent re-routing along other possible communication
paths.
5.1.3.3 Multiple highways shall preferably work on the basis of IEEE 802.4 or IEEE 802.5 (ISO
8802.4 and ISO 8802.5 respectively) standard.
5.2 Controllers
The system shall perform the conventional control strategies by dedicated microprocessor based
digital controllers capable of being installed in control building or field auxiliary rooms. The following
points shall be fully met as a minimum:
5.2.1 The controller shall be micro-processor based digital type using at least 16 bit industrial type
microprocessor to provide multifunction process control.
5.2.2 Scaling, filtering, conversion to engineering units and alarm checking of analog measurement
values shall also be included through standard predefined functional blocks.
5.2.3 Special function blocks shall be made available for floating point calculations. All control
calculations and reporting shall preferably be performed by floating point arithmetic to avoid scaling
problems. Measured values, as well as, calculated variables shall be accessible to these calculation
function blocks.
5.2.4 Executive routines and control logic shall be stored, by suitable Read Only Memory (ROM), in
a manner that; setting values and tuning constants are not lost or altered if the module fails or when
a power surge or power interruption occurs.
5.2.5 Control routines shall permit on-line changes to be made in any parameter of the controller,
including reassignment of input or output signals. This task shall not affect the operation of other
loops implemented in the same microprocessor and shall not create any plant control upsets.
5.2.6 Output and set-point tracking shall be automatic and shall be available for all types of
controllers for bumpless transfer of mode changes.
5.2.7 Each controller module shall have a dedicated data-base, containing information on the
performance of the device and the status and history of the process variable in non-volatile memory
for protection against power outages.
5.2.8 Control modules shall function autonomously, in a manner that, failure of one of them does
not take others out of service.
5.2.9 Controller set-points and output ramping speeds shall be adjustable through operator console
or portable maintenance terminal.
5.2.10 Controllers shall be equipped with the following modes of operation minimally, selectable
from the operator console:
a) Manual
10
Mar. 2004 IPS-M-IN- 250(1)
b) Automatic
- The set-point will be the output from another controller or the same controller
loaded with another control algorithm. Bumpless transfer between different modes
shall be provided in the controllers.
5.2.11 Autodiagnostics shall be run in the controllers to detect sensor faults (bad PV) or operations
out of tolerances, as well as, failure of component blocks, such as:
- Memories
- Power regulators
5.2.12 When the above mentioned problems identified by the autodiagnostic routines, the system
shall place the affected loops in a safe state to prevent any incorrect final element positioning. The
detected error shall trigger appropriate alarms, diagnostics codes, and status displays at control
centre, and pertinent Printed Circuits card(s).
5.2.13 In the event of entire controller failure, the system shall reassign the contained loops to the
back up controllers or to the operator station, automatically. The latest valid command shall be held
during switch-over to avoid process upsets.
5.2.14 Controller parameters shall be checked to prevent entering of unreasonable values by the
operator and to detect erratic signals obtained from other loops. The checked parameters, in
addition to, the set-points, shall include:
- Output limits
5.2.15 During the program modifications, all process outputs shall be placed on hold and
parameters shall be checked with unreasonable entries alarmed.
5.2.16 Each controller block within a controller card shall be capable to accept customer selected
equations or algorithms, without affecting other loops via operator console.
5.2.17 The controller including the back-up shall have a real-time database to perform actual control
and monitoring functions. The data stored in this database shall be, minimally, as follows:
- Operating parameters, such as; the current process value, set-point, valve output, and
mode (automatic or manual)
- Tuning parameters including values, such as gain, reset, derivative, and alarm trip-points.
5.2.18 The variety of controller card to perform all control functions shall be limited types to ease the
maintenance and spare parts stocking of the system. The vendor shall furnish detail technical
document for his proposed controllers to be evaluated by purchaser.
11
Mar. 2004 IPS-M-IN- 250(1)
5.2.20 Special indicators shall be incorporated in the design of printed circuit boards to ensure rapid
detection of malfunctions and current status by maintenance personnel to be used for isolation of
failures and performing the repairs. These indicators may be Light-Emitting-Diodes (LED) on the
circuit cards to reduce the need for test equipment.
5.2.21 Controllers shall be capable of being replaced while the system is powered up without
requiring any other controller in the system to be shut-down.
5.2.22 On-Line control configuring capability shall be considered for the controllers, with no need to
take them off-line.
5.2.23 The controllers shall be capable to be operated durably in wide ranges of; temperature,
humidity, dust, atmospheric corrosion, and contamination, if requested.
5.3.1 General
The DCS shall provide a comprehensive set of I/O conversions to interface with all types of
standard analog and digital input/output signals encountered in the process. The requirements for
this kind of interface will be specified under "process interface modules".
In addition to process interface modules, a "data acquisition system" shall be furnished with serial
data communication to DCS-BUS, to achieve a truly integrated process control system with all
packaged unit instrumentations in the plant, if specified.
5.3.2.1 The process interface modules shall be capable of interfacing with the following types of
input signals from field sensors and transmitters.
e) Pulse inputs from turbine-meters, rotational speed measurements, etc. in the range of 0-
1 or 0-10 Volts at frequency range of 1-2000 Hz.
f) Floating dry contacts, with 24 V dc power supply by a source external to the process
interface.
5.3.2.2 The input cards shall be solid state electronics employing the state of the art technology.
5.3.2.3 Digital input/output cards shall have LED On/Off status indication for all inputs/outputs.
5.3.2.4 Any input or output card shall be replaceable without turning-off the power to the system or
disturbing the operation of the rest of the system, in any way.
5.3.2.5 Light Emitting Diodes (LED) shall be provided in process interface cards for indication of
12
Mar. 2004 IPS-M-IN- 250(1)
errors occurring within the unit and for confirmation of correct operation of the system.
5.3.2.6 The input/output cards shall perform all necessary conversions, such as; A/D, D/A, code
conversion, filtering, etc. required to perform interfacing to the process.
5.3.2.7 The process interface card electronics shall convert all low level input signals to standard 1
to 5 volts and apply any necessary conditioning, such as:
5.3.2.8 The vendor shall quote conversion repeatability and accuracy of A/D and D/A in his proposal
to be evaluated for each specific application. The sampling rate shall be suitable for scanning time
of 100 msec. for each individual control loop.
5.3.2.9 The input/output circuitry shall be provided with suitable over-voltage protection.
5.3.2.10 The I/O system shall supply the operating power to the field instruments connected to DCS
via power supply units installed in the same cabinet.
5.3.2.11 The I/O system shall provide required electrical isolation, noise rejection, transient
suppression, to ensure clean, accurate information to the controllers for monitoring and control.
Signal conditioning, isolation, and surge protection for analog and discrete I/O shall be preferably
performed by signal conditioning modules mounted on the termination panels.
5.3.2.12 The I/O system cabinets shall contain high quality terminals to allow easy installation of
field wiring and labeling of terminations.
5.3.2.13 The I/O system shall be capable to be operated durably in wide ranges of temperature,
humidity, dust, atmospheric corrosion, and contaminants which are present in typical oil industry
installation. The specific environmental condition will be specified for each project.
5.3.2.14 In hazardous locations where isolation or energy limitation to field devices are essential,
the I/O system shall be capable to be equipped with safety barriers inside the termination cabinet.
5.3.2.15 The I/O system termination panels shall be separated from the I/O electronics to provide
enough space for ease of wiring installation. The termination panel shall be located at the sides of
the cabinets.
5.3.2.16 Redundant I/O system shall be provided for critical loops using the back-up I/O to keep the
process running, if the primary one is damaged or malfunctioning , unless otherwise specified.
5.3.2.17 Fuses and relays of the I/O card shall be readily accessible and can be changed without
disrupting service of any other channels.
5.3.2.18 All non-intrinsically safe circuits shall be provided with suitable fuse protection in the
termination block.
5.3.2.19 The I/O system shall be equipped with multiple channel signal conditioning cards to
perform scanning, filtering, and alarm implementation on all field instrument analog measurements
for each group of I/O cards.
13
Mar. 2004 IPS-M-IN- 250(1)
The card shall provide the following features on per channel basis:
5.3.2.20 The overall accuracy of I/O system shall be 0.2% F.S. minimally subject to the following
conditions:
- The stated accuracy shall apply individually to each input/output pair with the system
operating at a data rate up to the maximum rate for all I/O channels.
5.3.2.21 Any electronic components located on the I/O system modules shall be capable of
operation with the specified performance during repeated shock loading of 1.0 g trapezoidal pulse
of 30 m Sec. duration.
5.3.2.22 The data cable and cable attached connectors shall be capable of surviving at a repeated
shock loading of 7.0 g trapezoidal pulse of 30 m Sec. duration.
5.3.2.23 I/O system component modules located on test slot shall be capable of operation within the
specified performance during exposure to sinusoidal vibration of 2.5 mm. peak-to-peak at
frequencies from 10 to 60 Hz., with 0.5 g maximum acceleration.
5.3.2.24 All calibration parameters of the I/O cards shall be handled using software without any
need for any potentiometers on the I/O card. As a result, replacement of an I/O card shall not
require any recalibration.
5.3.2.25 Connection of I/O system to controllers shall be made by 16-bit Industry Standard
Architecture (ISA) Bus, Extended Industry Standard Architecture (EISA) 32-bit Bus preferably or
manufacturer’s proprietary Bus link.
5.3.2.26 When a field transmitter falls or its output raises above 22 MA, the I/O system module shall
detect and segregate the fault without any affect on other input of the same module.
In order to achieve a complete integrated process control system, the DCS shall be equipped with
suitable data acquisition sub-system to provide gateways expanding the control system data-base,
by linking other devices to the data highway.
5.3.3.1 The data acquisition shall employ an independent interface card to provide translation of
acquired signals to DCS data link format and allows RS-232C or current loop connection to foreign
devices, such as:
- Programmable Logic Controllers (PLC) - Gas Chromatographs and any other process
analyzers.
- Data loggers
14
Mar. 2004 IPS-M-IN- 250(1)
- Weigh scales
5.3.3.2 The data acquisition system electronics shall employ fully modular design using state of the
art technology.
5.3.3.3 The data acquisition system shall enable the operator to use the DCS console to monitor a
programmable controller and control its specified functions through the pertinent PLC interface card.
5.3.3.4 The data acquisition system device shall check all input variables for over-range and under-
range limits and transmit relevant alarm signal to the DCS.
5.3.3.5 The data acquisition system shall be equipped with auto diagnostics routine for checking
correct operation of the electronics and producing pertinent alarm signals to the operator console
via the data highway.
5.3.3.6 Digital inputs and outputs shall be electrically isolated from internal electronic circuits by
dedicated devices, such as optocouplers. Fuses shall be provided for protection of the cards, if
specified.
5.4.1 General
5.4.1.1 Each MMI station shall consist of two independent consoles, two printers, one hard copy
device, two redundant hard disc drives, and two dual diskette drives minimally. The exact number of
consoles and accessories will be indicated in architectural configuration sheet for each project.
5.4.1.2 The MMI stations shall permit access in different levels, such as:
- Operator: The station shall provide possibility to have rapid access to all video pages
defined for the engaged operator and shall provide access to all MMI functions necessary to
perform the control of the process.
- Supervisor: The station shall provide access to all consoles of the system connected,
with possibility to monitor and define the responsibilities of each operator station by the
supervisor.
- Engineer: The station shall provide possibility of start-up and control of particular
diagnostic programs, modifying the configuration data, creating new video pages and new
control loops by means of a password, if employed.
5.4.1.3 The operator station shall acknowledge all operator actions and indicate acceptance or
rejection, in order to, circumvent problems arising by incorrectly pushed buttons, improper entry of
point tags or data. For each continuous control loop, the operator interface must allow the operator
to perform all of the normal control functions and monitoring the results of these actions.
5.4.1.4 All variables shall be referred by their pertinent tag number through a data base entry
interactively. The following man-machine functions shall be provided in all operator stations;
- The frequently used operator functions such as; start/stop, controller mode selection, set-
point adjustment, output adjustment, etc., shall be provided with dedicated functional keys.
- It shall be possible to have access to the various DCS sub-systems by any operator
15
Mar. 2004 IPS-M-IN- 250(1)
console.
5.4.1.5 The following human engineering factors shall be minimally foreseen in the consoles design:
- Monitor color saturation and light intensity shall be continuously variable and adjustable,
and shall be made accessible to the operator by suitable means.
- The scan frequency and power supply filtering design shall be, in a manner that,
stroboscopic effects arising between room fluorescent lighting and screen up-dating be
negligible.
- New monitor display pages invocation shall be completed in one second maximally, static
data acquired from disk shall be invoked in three seconds maximally.
- Each station shall be equipped with electronic bleeper for audible alarm annunciation. The
bleepers shall preferably be of variable intensity type for identification of selective alarms.
5.4.1.6 The monitoring system shall support user selectable colors for defining colors of process
variables, set-points, outputs, messages, etc. A minimum of 16 colors shall be available.
5.4.1.7 Selectable strip chart recorders shall be provided for all loops shown on P & ID or indicated
in the function list. The operator shall be provided with the possibility to select each of the specified
variables and address them to the pertinent recorder by the keyboard at his own discretion.
5.1.4.8 Automatic time synchronization shall be provided among monitor consoles by real-time
clock. The real-time clock shall be crystal type independent of line frequency.
5.4.1.9 Devices operating within the DCS shall be under continuous surveillance by diagnostic
routines. In the event of malfunction detection, the operator shall be alerted at the console and the
malfunctioning device. System over-loads, such as memory capacity, scan rate, etc., shall be
alarmed at the operator station.
5.4.1.10 The MMI stations shall be microprocessor based using 32-bit microprocessor to operate in
the multiprocessor environment. The microprocessors shall employ standard EISA Bus preferably
for communication between processors,. The processors shall employ an efficient real-time
operating system as an environment for application software.
5.4.2.1 Each console in an operator station shall be fully independent of others and shall be stand
alone type, with it’s own electronic circuits and dedicated peripherals, CPU and memory. The
operator console shall minimally contain the following devices:
- Dual 3½" high-density, 1.44 Mbyte diskette drive (diskette drives for all consoles may be
located in a unified compartment)
16
Mar. 2004 IPS-M-IN- 250(1)
The consoles shall be fully interchangeable, in a manner that, a failure in any single console does
not affect the performance of the operator station.
5.4.2.2 The operator consoles design shall be according to the best human engineering factors, to
reduce the instances and effects of human errors, and shall be easy to operate.
5.4.2.3 The operator console shall perform basically the following functions:
- Manipulation of control set-point and alarm setting values and also manual, auto, or
cascade operation.
- Performing hourly, shift end, daily and monthly average and historical trends.
menu display, overview display for at least 64 loops per display page, unit display
for at least 32 loops, group display for not more than 8 variables, detail displays,
trend group displays for 8 variables, single trend displays, interactive, color dynamic
control configuration graphic displays, alarm summary display with list of displays,
alarm processing and display, controller tuning trend displays (protected by
password), system self-diagnostic displays, system hardware status displays, real
and historical trends, guide message display, help message display.
5.4.2.4 The overview display variables shall be represented by bar-graphs having a length
proportional to their deviation value from the standard setting on a simplified graphic representation
of the process. Alarm signals shall also b e presented for each variable at bottom side of the
screen. Each alarm point shall have the tag number and status, shown in conjunction with the
deviation indication.
5.4.2.5 Group display shall be displayed by pertinent information, such as; tag number, engineering
unit, set-point, process variable, etc., as well as, pre-alarm, alarm status, and information on the
setting values of the alarms, in a manner, to allow the operator to modify the alarm settings. This
information shall also be displayed by bar-graph indications and color coding for visual recognition.
Other information pertinent to each loop, such as; loop status (i.e. AUTO/MANUAL), and loop
description (i.e. GAS FLOW) shall be made available on this type of displays.
5.4.2.6 Detail display shall show a bar-graph and tabular representation of the actual value of
manipulated variable, control variable, set-point and relevant engineering information pertinent to a
specific loop for each operating loop connected to the control system.
- At this level of display hierarchy, the engineering units and configuration values shall be
allowed to be changed, by means of, password or hardware keylock to restrict unauthorized
access to the loop tuning constants, process variable zero and span, alarm limits and any
other configuration details, such as; algorithms, signal types, or input sources.
- The following detail status condition displays shall be accessed by the operator for all
discrete signals:
17
Mar. 2004 IPS-M-IN- 250(1)
a) Type of device;
b) Tag-number;
d) Failure to operate;
i) Alarm setting;
j) Configuration data;
-The following commands shall be available to the operator through functional keyboard for
analog variables pertaining to each loop:
1) Up (open)
2) Down (close)
5.4.2.7 Trend display shall support trends for one, two or three variables simultaneously on the
monitor screen with the loop tag-number enabling the operator to monitor the inter-relation between
variables (measured variables, calculated values, setpoints, and discrete inputs or states). The
display time base shall be selectable within 20 minute period up to 24 hours and trends shall be
automatically saved on the operator station magnetic disc media. The process variables specified in
the function lists shall be sampled and the instantaneous values shall be stored at intervals of
maximally ten second periods. The stored data shall be reproducible on the printer automatically
once per eight hour shift and at any time according to the operator request.
5.4.2.8 Trending displays shall be made available for all specified loops in P&ID and the DCS
function lists. The display shall have range expansion and compression, zero suppression and
elevation, timebase compression and expansion.
- Data shall be updated on point-by-point basis to ensure availability of a stored data at any
time.
- Trend data points shall be connected with a continuous trace provided in accordance with
pixel resolution of the monitor.
- Continuous scale expansion in 1% increments shall be provided for the operator enabling
him to change the display scaling (i.e. going from 0-100% to 25-50%).
18
Mar. 2004 IPS-M-IN- 250(1)
5.4.2.9 Dynamic graphic configured displays shall be considered for the system. These displays
shall be fully interactive.
- The displays shall be organized in partitioned overlapped pages, in a manner that, each
display page contains process information and related instrumentation for up to 64 unique
tags, each having multiple dynamic variables presentation.
- The organization of different graphic display pages shall be hierarchical according to the
following levels:
a) Overall process;
b) Status of equipment such as; pumps, On-Off valves, packaged equipment, etc;
- The following interactive operations shall be made available to the operator by display
pages;
a) Commands for turning On or Off the pumps, On-Off valves, packaged equipment
etc.
- The graphics shall be programmed by vendor based on ISA S5.3 for instrument symbols
and ANSI Y32.11 for process symbols. Vendor shall prepare the graphics, on the basis of
the simplified graphic display schematics supplied to him for the project after contract
award. Multiple color coding (8 colors) shall be provided to indicate alarm points and
operating status of motors, fans, valves, etc.
- The ISA S5.3 and ANSI Y32.11 in addition to any other symbols which are used in the
graphics shall be made available as insertable block symbols in "system graphical library"
for system modifications and future expansions.
5.4.2.10 Alarm summary displays shall present the latest plant alarms and their respective operator
reset activation to the operator chronologically.
- Each line of the alarm list display page shall show one specific alarm. This alarm line shall
minimally contain the following information:
a) Alarm occurrence and the time when the acknowledge command has been
issued by the operator showing hours, minutes, and seconds.
c) Alarm description showing the alarm group page number and the group display
and control configuration page numbers which the alarm is associated with.
- The following separate lists with time stamp shall be provided for the system:
19
Mar. 2004 IPS-M-IN- 250(1)
5.4.2.11 Alarm display pages shall be provided for alarm handling by the operator. The alarms shall
be grouped into the pages according to alarm groupings provided to the vendor in DCS alarm lists.
The system shall manage the alarms and provide the following performance:
-The system shall provide at least four measurement and two deviation alarm levels for
each control variable. The level of these alarms shall be definable by the process
supervisor.
-The possibility of displaying the alarm status for discrete variables with their pertinent
status or value.
-The alarm message shall show the point tag identification and description of the alarm.
-Alarms shall be prioritized by color. They shall preferably be prioritized by position as well.
5.4.2.12 The occurrence of any alarm within the control system and shutdown system shall result
the following responses:
1) A change in color of the alarm point status indication in all displays in which it is present;
3) Audible annunciation;
4) Print out of the alarms in order of occurrence with details such as; tag number, alarm
state indicator, alarm description, trip point value (if applicable), time and date of;
occurrence, reset and return to normal.
The MMI shall provide suitable means to document the reports and alarm listings with presentation
of the time of occurrence of each item and pertinent designation of sequential events and operator
entries. The following process record keeping features shall be provided in the system, as a
minimum:
A list of all entries actions initiated by the operator affecting control of the process,
including; changes in control mode set-point, manual output or logic commands, with the
identification of the console which the changes have been made from, with time stamp.
- Event List
A documentary list which presents all discrete events within the system, indicating the time
and description of the events. The time stamp resolution of the events shall be less than
100 m Sec. The alarm messages shall be user definable and the length of them shall be
minimally 80 characters. The system shall support 10 separate lists minimally.
20
Mar. 2004 IPS-M-IN- 250(1)
All custom reports shall be stored on the console hard discs, to be recalled at any suitable time. All
reports shall be made available by the system printer on operator request and/or on eight hour
cyclic shift basis. The following type of reports shall be made available on the system:
These reports shall be user configurable with ability to include any selected information
from any log, event or alarm list. This type of report shall be printable on-demand or
periodically.
These reports shall be user configurable with ability to include any system data, such as;
data stored in historical trend files or controller inputs/outputs. It is required that
manipulation and calculation to be allowed to generate time-based averages, totalization,
minimum values, minimum times, maximum values and maximum times.
5.4.3.1 All engineering parameters pertinent to the loop configuration, control strategies, and control
algorithms shall be accessible by engineering console for engineering modifications interactively.
5.4.3.2 The console shall be either a dedicated engineering console or a multitask MMI console as
specified in attached project data sheets, and shall be capable to perform the following tasks:
a) Customizing the system to meet any specific control objectives at start-up or at any time
during operation and initial configuration generation;
b) Assigning tag-numbers to I/O channel to make them addressable by the control system;
5.4.3.3 The engineering display shall provide the following types of displays, in fill-in-the-blank
forms preferably or by a menu page selection; to be configured on-line:
21
Mar. 2004 IPS-M-IN- 250(1)
- Configuring inputs to the system by filling the tag number, tag descriptor, system terminal
number, type of signal characterizer, input alarm limits, alarm deadband and engineering
units. Multiplexed inputs shall use a single configuration display format.
- Configuring output functions by filling the tag number, function description, system
terminal number, output valve (including manual over-ride capability), reverse or direct
acting selection and output fail-safe action selection.
- Configuring discrete output functions by filling the tag-number, function description, output
status, contact type, output hold option, fail-safe action selection and system terminal
number.
5.4.3.4 The console shall provide on-screen forms to configure points and devices in the system by
filling-in-the-blank. The spaces provided in front of data description headers generated by the
system for all variety of control algorithms and strategies.
5.4.3.5 The engineering console shall provide an on-line Help facility to provide enough information
to facilitate the programming and auditing tasks at any level encountered in the control system.
5.4.3.6 The auditing software shall be provided in the engineering console to perform checking of all
configuration data entered and alert any missing information or any other potential errors made by
Engineer.
5.4.3.7 The console shall preferably provide a special auditing software for specialized complex
control strategies to recognize the type of instructions entered and prompts for information needed.
This program shall also check the data entered for their correctness. Such an auditor shall provide
on-line Help messages pertinent to all types of instructions on Engineer demand.
5.4.3.8 Graphic display elements shall be drawn by using library of symbols provided in the system-
data base. The graphic software shall provide facilities for symbol rotation, size selection and ability
to create new symbols.
5.4.3.9 The engineering console software library shall include a global data-base software to handle
all points data, configurations, and adjustment parameters on hard disc.
5.4.3.10 All information entered shall be saved by engineering console in a global data-base.
5.4.3.11 The system shall be equipped with a relational data-base to store each type of data in a
designated area, in a manner that, data retrieval and manipulation can be performed efficiently. The
data-base shall permit incorporation of new types of data after original database is set-up at system
operation time. The system shall be capable to import/ export ASCII formatted data from
commercially available data base and spread-sheet programs.
5.4.3.12 The system shall be equipped with necessary softwares to transfer configuration data to
control system after completion of all configuration data in system data base or after auditing of the
configuration data is completed and saved.
5.4.3.13 A menu selection shall be provided letting the Engineer to choose whether to download
specific configuration data to several devices or only to a specific one. In addition, the system shall
provide the Engineer with facilities to down-load the entire configuration data for a device or just the
configuration changes since the last down-load at his own discretion.
5.4.3.14 In performing the down-loading operation, the system shall preferably extract pertinent
information for the device concerned from relational data base and generate a separate file to be
down-loaded to the device with all requested options.
5.4.3.15 A language editor software shall be provided in the engineering console to facilitate data
22
Mar. 2004 IPS-M-IN- 250(1)
base generation by cutting, joining, and copying the existing information for use in other parts of the
database. The editor shall also provide the Search and Search-and-Replace functions to find and
update data.
5.4.3.16 When modified configuration data is saved by the Engineer, the system shall store it as the
current version. The previously downloaded version shall be still stored and made available on hard
disk by the system. At downloading time of the new version, the system shall preferably be capable
to compare the old and new configurations and to send only the changes along the Highway to the
devices, in order to decrease the data highway occupation time for on-line engineering applications.
5.4.3.17 The engineering console system shall be provided with an automatic tuning program
residing on the hard disc unit. The program shall be capable to be run on-line by the Engineer
request to tune individual control loops optimally.
5.4.3.18 The controller tuning parameter changes that have been made by automatic tuning
program shall be uploaded to be visible on the monitory the Engineer and used to keep the data
base up-to-date.
5.4.3.19 In addition to the automatic tuning software, a Trace-and-Tune software shall be provided
in the system to allow off-line tuning of individual control loops and testing the performance of the
pertinent control strategy without affecting the process control operations. Such a task shall be
performed by entering simulated analog or discrete inputs for an on-line controller to the Trace-and-
Tune routine and observe the controller output. All the key points within a complex strategy shall
also be capable to be observed by this Trace-and-Tune program.
5.4.3.20 The system shall also be provided with a diagnostic software to perform the system
diagnostics, identifying specific device errors and helping trace the source of intermittent faults.
Diagnostic display pages provided by this diagnostic software shall provide extensive coverage of
system conditions. The following features shall be provided by this software, minimally:
- A Communication overview display page to show the communication status of all data
highway devices. (primary and back-up communication links).
- Indication of malfunctions that occurs, on the; primary and backup control devices, primary
and backup power supplies, peripherals, and continuous indication of throughput traffic on
the communication link.
5.4.3.21 To prevent unauthorized access to the console, it shall be equipped with passwords to
protect the process from unauthorized configuration changes. The security functions shall
preferably provide the following features:
- Approved user passwords shall be provided for maintenance personnel’s. Such level of
users can use only the functions specified by the Engineer supervisor using administration
password. The extent of the approved user functions shall cover all available functions
which some are listed bellow;
23
Mar. 2004 IPS-M-IN- 250(1)
5.4.4.1 Each console shall be equipped with an alphanumeric keyboard plus necessary functional
keyboards. The following requirements shall be foreseen in the keyboards minimally:
- The keyboard shall have a retractable cable to provide the user the capability to position
the keyboard wherever he wishes for maximum comfort.
5.4.4.2 The keyboard shall be partitioned in the following distinct functional zones:
d) Control area.
5.4.5.1 Color video-copier shall minimally fulfill the following technical requirements:
- The copier shall have acceptable quality and reliability and shall be accessible from any
operator console.
- The copier shall provide addressability of 154 dots per inch both horizontally and vertically
with enough color composition.
- The copier shall use the A4 non-sensitized papers for picture production.
- The copier shall perform the copying in a time interval not more than 5 seconds.
5.4.5.2 A color printer shall be provided to log events and alarms. The printer shall meet the
following requirements minimally:
- The printer shall be microprocessor type, high speed and with excellent letter quality.
- The device shall preferably use parallel, nine wire array, matrix print heads to provide bi-
directional printing.
- Connection of the printer to the system shall be by an integral serial interface port
conforming to RS-232C standard.
24
Mar. 2004 IPS-M-IN- 250(1)
- The printer shall support printing of block, character, and line graphics, by means of four
color ribbon.
- The device shall accept all types of ribbons such as four color, red/black and black only
type.
5.4.5.3 The Bid documents shall identify any capability of generating customized format printouts, if
included.
5.4.6.1 The hard disc unit shall be industrial state of drive type. The hard disc shall be permanently
sealed into the drive and shall not be removable, to be unaffected by environmental dust and
smoke.
5.4.6.2 The spindle driving of the disc shall be preferably of direct drive motor type to reduce the
number of bearings and provide the drive with more reliable mechanism.
5.4.6.3 An automatic seek truncation shall be provided at inner/outer tracks of the hard disc.
5.4.6.4 The Storage device magnetic medium shall be preferably 3½" aluminum platter, coated with
a smooth, polished metallic oxide and shall provide 40 Gbyte minimally formatted storage capacity.
5.4.6.5 A full shock protection counter-arm mounting shall be provided for the device to eliminate
head/carriage damage during transportation.
5.4.6.6 The following data must be provided for the Bulk Storage System:
5.4.7.1 Removable diskette drives shall be used primarily to store and down-load the programs that:
- Store the configuration of operating information used by the remote electronic units
(controllers)
- To organize the programs that set-up the operator station group overview display
5.4.7.2 The magnetic media employed shall be 3½" double high density diskette type preferably.
5.4.7.3 The diskette drives employed, shall be capable to support 1.44 Mega-bytes of formatted
storage. And 650 MB, CD drive 40X.
25
Mar. 2004 IPS-M-IN- 250(1)
5.5.1 General
5.5.1.1 The DCS consoles and cabinets shall be according to the following unless otherwise
specified.
5.5.1.2 The cabinets and consoles shall be complete with all instruments, terminals, equipment,
etc., ready for site installation. The Vendor shall provide all parts, components, and modules,
necessary to provide tidy, complete workstations and cabinetry.
The consoles shall be complete with all modules, systems, and sub-systems in full accordance with
the intent of this specification.
5.5.2.3 The height of the console shall be around 1500 mm, at the front and around 1300 mm, at
the back side.
5.5.2.4 The console shall be equipped with a cabinet to accommodate the electronics with a
nominal height of 800 mm, measured from the floor. The cabinet shall have two access doors, one
from the front of the console and the other from the back, to accommodate the following modules;
- An EIA 19 inch card file rack to accommodate all electronic circuits of the console, such
as; keyboard interface card, recorders interface card or printer interface card, display
generator card, Direct Memory Access (CPU) card, memory cards, Highway logic cards,
Highway driver/ receiver cards, microprocessor (CPU) card, diskette interface card, etc.
5.5.2.5 The station shall have a writing surface to accommodate the keyboard and function keys
with nominal depth of 300 mm at height of 800 mm measured from the floor.
5.5.2.6 By the side or under the monitor, floppy and CD drives shall be installed.
5.5.2.7 The steel-work shall be painted by stove enameled method with texture finish in sea green
according to BS- 381C, shade 217.
5.5.2.8 The power and control cables shall enter from the bottom of the consoles.
5.5.2.9 The vendor shall provide standard filler plates to make the consoles uniform and integrated
as a complete operator station.
5.5.2.11 The console for electronic circuits and controller cards shall be provided with a suitable
capacity circulation fan for cooling and thermostically anticondensation heater.
26
Mar. 2004 IPS-M-IN- 250(1)
5.5.3.2 The cabinets shall house remote mounting auxiliary equipment, controller cards, plus any
kind of rear panel mounted equipment, as well as, interconnecting wiring and instrument power
supplies. Marshaling racks shall be housed in the cabinets, when requested in purchase order.
5.5.3.3 The components inside the cabinets shall be located in an optimum position for operation
and servicing.
5.5.3.4 The Cabinets housing the electronic circuits and controller cards shall be provided with a
suitable capacity, circulation fan.
5.5.3.5 The Cabinets shall be equipped with EIA 19" racks for housing electronic circuit cards.
5.5.3.6 The Cabinets shall have standard arrangement and the following nominal dimensions:
Height 2000 mm
Width 600 mm
Depth 600 mm
- The height and width of the enclosure doors shall be at least fifteen millimeters (15 mm)
greater than corresponding height and width of the enclosure opening.
- A permanent metal drawing pocket shall be welded to the inside surface of the door. The
drawing pocket shall be 300 mm wide with 70 mm depth.
- Doors of the enclosure shall be designed to have sufficient rigidity to conserve alignment
between mating parts.
- Opposite access doors (if required), shall be provided for cabinets, for ease of
maintenance.
- Doors swing shall be minimally 165° and shall be attached to the enclosure body with a
continuous hinge.
- Neoprene door gaskets shall be attached to the doors with oil resistant adhesive materials
and held in place by means of steel restraining strips to increase enclosure protection
against dust and water.
5.5.3.8 Cable entrance shall be incorporated at the bottom of the panel by means of gland plate,
made of steel plate minimally 5 mm thick and shall be removable with suitable screws.
5.5.3.9 All cabinets shall be provided with suitable temperature sensor with DCS alarm for detecting
abnormal temperature inside the cabinets.
5.5.3.10 Terminals shall be mounted on sides of the enclosure to be connected to field instruments.
Minimum distance of terminals from floor shall be suitable for ease of maintenance.
5.5.3.11 Terminals on the terminal block shall be plainly and permanently marked with the
identification tags shown on electrical diagrams correspondingly. Only two terminations per side of a
terminal is permissible.
5.5.3.12 Conductors shall be identified at each termination by the same tag as the terminal by
means of wire sleeves, made of oil resistant material.
27
Mar. 2004 IPS-M-IN- 250(1)
5.5.3.13 Conductors and cables shall be run from terminal to terminal without splices.
5.5.3.15 Terminal blocks shall be mounted and wired so that the internal and external wirings do not
cross over the terminals.
5.5.3.16 The conductors used shall be all of extra-flexible, stranded copper, PVC insulated, 75°C
type.
5.5.3.18 At least 40% of terminals and 20% of card files shall be considered as spare for future
expansion in each enclosure.
5.5.3.19 The cabinets shall be provided with louvers and removable anti-dust filters, and shall have
a sealed bottom in order to avoid dust infiltration in final arrangement.
5.5.3.20 The cabinets shall be painted by stove enameled method with texture finish in Sea Green
Color according to BS 381C shade 217.
5.5.3.23 The cabinet for electronic circuits and controller cards shall be provided with a suitable
capacity circulation fan for cooling and thermostically anticondensation heater.
5.6.1 The DCS shall be capable to be interconnected in higher level automation network by data
highway interface. The interface shall be capable to perform the following functions minimally:
- The communication between computer and DCS shall be based on DCS master/computer
slave principle.
- The DCS shall allow for the full transfer of the data bases resident in the system to the
computer system without any limitations.
- DCS shall be capable to accept the computer system messages and commands in a
separate dedicated data-base to be further evaluated and transferred to the control system
by specialized softwares; (reference shall be made to pertinent project requirements)
5.6.2.1 The DCS data highway computer interface shall use either Ethernet TCP/IP, synchronous
X.25 or asynchronous ASCII or as specified the company, to interface to any type of computer
supporting an ASCII terminal driver at minimum 31.2 K baud rate. The system shall support
interface to any commercially available automation computers. This general computer interface
shall be configured from the DCS console, so there is no need for two separate operator consoles.
5.6.2.2 In order to simplify the establishing of communication links between the computer and the
DCS, the DCS vendor shall provide an extensive list of instructions, easily implemented in standard,
C Language statements, or BASIC program statements. A sample program and a list of instructions
shall be included in the vendor’s proposal to be evaluated by Company.
28
Mar. 2004 IPS-M-IN- 250(1)
5.7.1 General
The purpose of the PLC interface is to provide operator with the required data from the PLC. This
feature shall be accomplished by displaying the data, primarily in the form of custom-built graphics,
at any DCS console. The DCS shall also be capable of displaying the PLC data in the form of
trends or custom reports.
5.7.2 The PLC interface design and variety of the sub-system shall enable interfacing of the DCS to
the most major manufacturers of the PLC, as listed in Company’s approved vendor list. The
interface shall preferably support MAP/ OSI standard as outlined under ISO codes in section 2 or
Ethernet TCP/IP protocol.
5.7.3 The DCS communication with the PLC shall be implemented by means of RS-232C
connectors. Communication between the interface card and the operator console shall be
established via DCS data highway.
5.7.4 Diagnostic routine alarms of the PLC shall also be transmitted to the DCS and operator
console by the same PLC interface card.
5.7.5 The PLC interface shall have continuous Read and Write capability to maximize throughput
and shall support simple mapping of any PLC registers into the DCS.
5.7.6 A single PLC interface shall be capable of supporting multiple PLC’s on multi-drop basis.
5.8.1.1 The DC power supply system shall be designed to meet the power requirement of the DCS
and all two-wire field instruments. Each power supply shall be sized, such that, not carry more than
75% load of it’s capacity under normal condition. Separate AC circuit breakers shall be provided for
each power supply. The control system will be supplied with 110 V ac power from an Inverter/UPS
system, unless otherwise specified.
5.8.1.2 DC power sub-system, including inputs to the controller and DCS sub-systems shall be dual
redundant. Failed power supplies must be removable without disconnecting power from any part of
the system or affecting control operations.
5.8.1.3 All DC power required to excite external transmitters and drive external transducers shall be
derived from power supplies within the DCS I/O system.
5.8.2.1 Integral battery back-up shall be considered to maintain power for the controllers, I/O signal
conditioning devices and two-wire field instruments for a minimum period of 60 sec., upon loss of all
DCS power.
5.8.3.1 The DCS system shall be capable of monitoring and reporting the status of AC power
supplies and battery back-up conditions to the operator. Output current of the power supplies shall
be indicated, in order, to confirm that supply capacity has exceeded. Blown fuse indication shall be
provided on the face of all system cards if they are equipped with such a feature.
29
Mar. 2004 IPS-M-IN- 250(1)
All DCS electronic circuits shall be internally protected against system errors and hardware
damages resulting from the following causes.
5.8.4.1 Connecting and disconnecting devices, removing and inserting printed circuit boards or
cables including removal of data highway connections while the system is operational shall be
limited to the loss of disconnected equipment only.
5.8.4.2 The Vendor shall quote and specify the following information in his bid proposal, regarding
sensitivity to electromagnetic radiation;
- frequency range,
5.8.4.3 The control system shall not radiate any interference to any other equipment or system
present in the plant.
5.8.5.1 All interconnections between components of the system (including the Data Highway) shall
be via prefabricated (to length) and predetermined cables supplied with the system.
5.8.5.2 All plugs, receptacles and cables must be clearly, uniquely and permanently labeled.
5.8.5.3 All plugs, in cables and devices (including circuit boards) must be keyed to prevent incorrect
connection. A suitable locking device must also be provided to prevent accidental disconnection.
Circuit boards shall be guided for insertion and include permanently attached extraction device to
assist in removing the cards.
6. SOFTWARE REQUIREMENTS
The following software subroutines shall be made available in the system, as a minimum:
A. Control algorithms
- PID (linear)
- PID (non-linear)
- PID (ratio)
- PID (floating)
- Adaptive tuning
30
Mar. 2004 IPS-M-IN- 250(1)
- Motor control
- Supervisory control
B. Computational algorithms
- Summer
- Multiplier
- Function generator
- Dead time
- Median
- Lead/lag
- Mass flow
- Square root
- Log function
- Exponential function
- Accumulator
- Characterizer
C. PID functions
- Output limiting
- Output tracking
- Feed forward
- Set-Point clamping
- Set-Point ramping
- Auto-scaling
- Cascade
D. Input/Output algorithm
- Analog
- Digital
31
Mar. 2004 IPS-M-IN- 250(1)
- Combinational gates
- Sequentional gates
- Mathematical library
- Histogram software
6.3.1 The operating system of the DCS shall be preferably of "Open" type such as UNIX.
6.3.2 Operating system with X-Windows is a privilege in evaluating the vendor proposal since this
OS allows application software and users to interact on "as need" basis.
The Vendor shall supply documents and drawings at different phases of the project engineering
execution with quantity and quality requested in this specification and the particular conditions of the
Contract.
7.1.1 Tender documents shall be carefully studied by the supplier and the requested data marked
as "by Vendor" in data sheets, shall be filled-in and submitted by bid documents. The following
documents and drawings shall be signed and submitted by the tender documents;
- Alarm lists,
- P&ID,
32
Mar. 2004 IPS-M-IN- 250(1)
The above documents shall be completed with the requested data by vendor and submitted as
technical part of the bid documents.
7.1.2 The supplier shall read this Standard specification and attached documents/drawings carefully
and submit his deviations to these documents under the item, "supplier points and deviations to
technical specification". The following documents shall be submitted by the bid proposal for
evaluation;
c) List of components proposed with specification, i.e. type, manufacturer, quantities, etc..
d) Electrical requirements such as; feeding voltages, absorbed power at start-up and at
steady conditions (subdivided per each component), maximum time of electrical failure to
conserve the system operations without shutdown or malfunction,
h) Maximum constructional load per square meter for cabinets and consoles,
- Engineered;
- Manufactured;
33
Mar. 2004 IPS-M-IN- 250(1)
n) Deviation lists.
The following documents shall be submitted after contract award, according to the agreed time-
schedule to be approved by the Company:
The Vendor/Supplier shall prepare the hereunder mentioned documentation in quantity of copies as
requested in contract document/drawing schedule and contractual purchase order. All these
documents shall be numbered according to the project documents numbering criteria.
7.3.1 Documents
Minimally five copies and one reproducible of the following Vendor documents shall be provided:
- Final loop diagrams developed on the basis of the tender documents incorporating all
Company’s comments, indicating all elements and information pertinent to field instruments
and system’s equipment.
- Recommended spare parts list with their pertinent manufacturer’s stock number for
commissioning period and two years of operation.
7.3.2 Softwares
7.3.2.1 Minimally 6 (six) copies of the following information shall be provided on CD:
34
Mar. 2004 IPS-M-IN- 250(1)
7.3.3 Manuals
7.3.3.1 Minimally five copies and one reproducible of the following Manuals shall be provided;
a) Operator’s manual, including operating guide for the system’s softwares (both operating
and application softwares),
b) Engineering and user’s manual describing how the work may be modified in the future,
and how the work is presently configured. This manual shall include all system components
technical specifications,
7.3.3.2 The above manuals shall be provided for each component of the DCS, including operator’s
consoles, process control units, communication devices, peripheral devices, etc.:
- Installation procedure,
- Parts lists,
7.3.3.3 All Manuals shall be well-organized and easily understood, and shall contain comprehensive
tables of contents and alphabetical indices. Topics for each of the hardware components shall
include, but not limited to the following:
35
Mar. 2004 IPS-M-IN- 250(1)
- Operation procedures,
7.3.4 Drawings
7.3.4.1 Minimally five copies and one reproducible of the following drawings shall be provided:
This shall illustrate the central control configuration, the communications configuration, and
the controller configurations, on one drawing, if possible;
This shall be scale drawing of the operator’s console, showing front, side, and top
perspectively. Locations of the various components (i.e. video displays, keyboards,
communication panels etc.), shall also be shown with dimensions.
Electrical connections and wiring shall be illustrated and described on separate drawings.
Cabinet layout and construction drawings shall be provided for all cabinets supplied by the
Vendor. This shall include each controller cabinet, computer, disk, communications, and
terminations cabinet. The drawings shall be to scale, and shall illustrate all components in
each cabinet and their electrical interconnections, and cabinet mechanical mounting
specifications;
d) Termination Schedule
This drawing shall list and illustrate all terminations, indicating; terminal/connector numbers,
tag names, voltages, currents, polarities, and grounding/shielding requirements. This
drawing shall be provided for terminal strips and for any cable supplied by the Vendor.
7.3.4.2 System Vendor shall provide reproducible CAD generated "as-built" mechanical and system
interconnection drawings. These drawings shall identify I/O assignments by tag number in a tabular
format.
7.3.5 The above Vendor documentation and drawings shall be provided after completion of Factory
Acceptance Test before shipment.
8. TRAINING
8.1 The system supplier shall provide Company’s personnel with adequate training for equipment
maintenance and operation, in order to get them familiar with the system. The Vendor shall provide
a description of the training courses available for his system with the duration and cost of each
course by his bid quotation for evaluation. The training courses shall minimally provide the following
courses:
8.2 The training shall be provided before DCS installation on site. The courses shall be scheduled
36
Mar. 2004 IPS-M-IN- 250(1)
- Location,
- Duration,
- Schedule,
- Prerequisites,
8.4 The cost for training shall be included in the contract price but itemized separately.
9.1 The system Vendor/Supplier shall have spare parts stock in Iran or guarantee to provide the
required parts not later than 4 days from the date of request, by Telex or Fax.
The Vendor shall have qualified service personnel which can promptly assign them to the job site
for repairs, adjustments, assistance in problem determination and trouble-shooting at a reasonable
cost. The price of such a service shall be quoted in Bid proposal for evaluation and economical
considerations by the Company, on the man-day basis.
9.2 The Vendor shall be technically responsible for all installation, commissioning, and start-up
work.
9.3 The Vendor shall provide such on-site services as may be required during installation. Qualified
Vendor personnel shall be on call and available immediately for telephone consultation 12 hours per
day, 7 days per week, and shall arrive on site within one working day after having been so
requested by the Company.
The DCS Vendor shall submit his own test procedures for all hardware and software supplied based
on the requirements specified herein. No material or equipment shall be shipped, unless all required
tests successfully conducted and so certified by the Company’s assigned inspector. Vendor shall
include heat soak test in his test procedure, as well.
10.1.1 General
The tests shall demonstrate the functional integrity of all hardwares and softwares. Company
assigned inspectors shall inspect the performance of all tests and they shall have access right to all
facilities involved in the manufacturing of the equipment purchased under this specification. The
Vendor shall maintain and/or replace any hardware or modify the softwares, if the specified
functions are not satisfactorily performed in (FAT) on the Company’s inspector judgment. A
detailed, scheduled factory test (FAT) procedure shall be submitted in the bid proposal by vendor.
Vendor shall provide all necessary personnel and test equipment to perform the tests as, and when
required with the costs included in the bid prices and separately indicated.
10.1.2.1 Quality control shall be as per manufacturer’s quality control standards to assure good
performance of components/ modules used in the system.
37
Mar. 2004 IPS-M-IN- 250(1)
10.1.2.2 The sampling procedure for the tests will be defined by Company’s assigned inspectors.
The Vendor shall check the workmanship and shall perform all his routine tests on the system prior
to power-up of the system.
10.1.2.4 Vendor shall check all the functions of the DCS hardware and software including diagnostic
software, at system and sub-system level by simulating the inputs and outputs.
The second check will be the calibration check of all signal conditioners, alarm setters, and other
components which affect the accuracy of the loops for their correct calibration according to the
requirements. All of these calibrations shall be performed and logged in the record book of power
test to be reviewed by the Company.
The Company’s assigned inspectors will supervise this phase of the tests to be performed on all
hardware and software of the system. The necessary manpower and co-operation shall be provided
by the Vendor, as well as, all measuring instruments. All sub-systems shall be interconnected as
"per actual" interconnecting configuration in the field. DCS vendor shall use simulators to simulate
the various inputs and measure the outputs through proper approved measuring instruments.
Followings are details of testings to be performed by the vendor and witnessed by the Company’s
assigned inspectors. The Company’s inspectors shall have the right to perform any of these tests
themselves, ask for re-performing any test, or ask for additional test as included in the Vendor’s test
procedure proposal.
Company’s inspectors will carry out visual and mechanical testing in principle to assure correct,
proper and good workmanship of the equipment.
Functional test shall include simulation of each type of input/output to testify the proper function and
response of the equipment. The following tests shall be included, as a minimum:
- Checking of all monitoring systems for their conformity to the drawings and proper quality.
- Checking the function keys to include all functions required and specified.
- Checking monitoring refresh time, data-base update rate, and display changing time to be
adequate. The Vendor shall trim the configuration to meet the requirements, in case that,
the above mentioned times are inadequate to meet the requirements.
38
Mar. 2004 IPS-M-IN- 250(1)
-Checking of diagnostic routines for all sub-systems with the faults simulated by Company’s
inspectors request, and reviewing the diagnostic alarms at console level and alarm log
level.
- Checking of interfacing software for foreign devices, such as; tank gaging, packaged units,
automation computer system, etc., by means of simulation of these instruments.
- Checking of spare capacity in terms of hardware, memory, and software to meet the
requirements stated in the contract final specification.
- Checking of special control strategies and advanced control by connecting the DCS to the
process automation computer (if applicable).
After completion of checkings mentioned here-above, the entire system shall be remained
energized for 72 hours continuously, with hands-off from the system. The system performance for
given simulated I/O’s shall be only observed during this 72 hour period.
Any malfunction of any kind shall be noted as "Observations" in the final acceptance test report to
the Company. If any fault is observed in performance test, the test shall be reconducted after
maintaining of the fault.
All the latest configurations and data-base, as performed during acceptance test shall be
transferred on floppy diskettes (two copies) and shipped with the DCS.
Each test carried out shall be formally recorded. Any deficiency or problem found in equipment shall
be corrected by the Vendor with replacing brand-new tested parts. Any change in configuration or
data shall be clearly recorded in Test log books.
10.4 Conclusion
All FAT reports shall be presented to the Company’s assigned inspectors for his signature and
issuance of certificate of shipment on satisfactory completion of witnessing the tests. Vendor shall
properly pack the system according to shipping instructions and packaging specifications IPS-G-
GN-210 and forward the equipment to the Company’s site.
39
Mar. 2004 IPS-M-IN- 250(1)
APPENDICES
APPENDIX A
40
Mar. 2004 IPS-M-IN- 250(1)
APPENDIX B
The measurement for reliability estimation shall be expressed in terms of Availability, Failure rate,
Mean Time Between Failure and repair duration time (Mean Time To Repair). The data used to
calculate the above mentioned terms shall be universally accepted predictions (i.e. Mil-STD-
Handbook 217 predictions), which quantifies expected useful life of components, utilized under real
service conditions.
1
MTBF =
R1 + R2 + ... + Rn
R1 through Rn are the failure rates of components used in the equipment or system.
The MTBF calculation for each equipment used and the whole components shall be
submitted for evaluation in each bid proposal.
R = e-rt
Where R is the probability that the system operates without failure in a duration indicated by
time t, and r is the failure rate for the class of device as extracted from generally accepted
predictions (i.e. Mil-STD. HDBK 217).
The DCS vendor shall provide his certified (MTTR) which will be the measure of repair
duration time. Such a document shall indicate the skills, test instruments and repair spare
stocks required to achieve the stated MTTR.
d) availability
Steady state availability shall be calculated as a fraction of time which the system is
operational and shall be expressed as:
A = MTBF/(MTBF + MTTR)
For serial subsystems the overall availability shall be calculated by the equation:
A = A1.A2 ................An
and for parallel subsystems the net availability will be estimated by the equation:
A = 1 - [(1-A1) (1-A2).....(1-An)]
41
Note to Users
The IPS Standards reflect the views of the Iranian Ministry of Petroleum and are intended for use in
the oil and gas production facilities, oil refineries, chemical and petrochemical plants, gas handling
and processing installations and other such facilities.
IPS publications are based on internationally acceptable standards and include selections from the
options stipulated in the referenced standards. They are also supplemented by additional
requirements and/or modifications based on the experience acquired by the Iranian Petroleum
Industry and the local market availability. The options which are not specified in the text of the
standards are itemized in data sheet/s, so that, the user can select his appropriate preferences
therein.
The IPS standards are therefore expected to be sufficiently flexible so that the users can adapt
these standards to their requirements. However, they may not cover every requirement or diversity
of conditions of each project or work.
For such cases, an addendum to IPS Standard shall be prepared by the user which elaborates the
particular requirements of the user. This addendum together with the relevant IPS shall form the job
specification for the specific project or work.
The users of IPS publications are therefore requested to send their views and comments, including
any addendum prepared for particular cases to the Ministry of Petroleum, Standards and Research
Organization. These comments and recommendations will be reviewed by the relevant technical
committee and will be incorporated in the formal revision of the relevant IPS. The IPS publications
are reviewed and revised approximately every five years.