3RT25261BB40 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Data sheet 3RT2526-1BB40

Power contactor, AC-3 25 A, 11 kW / 400 V 2 NO + 2 NC 24 V DC 4-pole


size S0 screw terminals 1 NO + 1 NC integrated

product brand name SIRIUS


product designation contactor
product type designation 3RT25
General technical data
size of contactor S0
product extension
● function module for communication No
● auxiliary switch Yes
insulation voltage
● of main circuit with degree of pollution 3 rated value 690 V
● of auxiliary circuit with degree of pollution 3 rated 690 V
value
surge voltage resistance
● of main circuit rated value 6 kV
● of auxiliary circuit rated value 6 kV
maximum permissible voltage for safe isolation between 400 V
coil and main contacts according to EN 60947-1
shock resistance at rectangular impulse
● at DC 10g / 5 ms, 7,5g / 10 ms
shock resistance with sine pulse
● at DC 15g / 5 ms, 10g / 10 ms
mechanical service life (switching cycles)
● of contactor typical 10 000 000
● of the contactor with added electronically optimized 5 000 000
auxiliary switch block typical
● of the contactor with added auxiliary switch block 10 000 000
typical
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 10/01/2009
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 95 %
maximum
Main circuit
number of poles for main current circuit 4
number of NO contacts for main contacts 2

3RT25261BB40 Subject to change without notice


3/29/2022
Page 1/7 © Copyright Siemens
number of NC contacts for main contacts 2
operational current
● at AC-1 up to 690 V
— at ambient temperature 40 °C rated value 40 A
— at ambient temperature 60 °C rated value 35 A
● at AC-2 at AC-3 at 400 V
— per NO contact rated value 25 A
— per NC contact rated value 20 A
minimum cross-section in main circuit at maximum AC-1 10 mm²
rated value
operational current
● at 1 current path at DC-1
— at 24 V rated value 35 A
— at 110 V rated value 4.5 A
— at 220 V rated value 1A
— at 440 V rated value 0.4 A
● with 2 current paths in series at DC-1
— at 24 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 5A
— at 440 V rated value 1A
● at 1 current path at DC-3 at DC-5
— at 24 V per NC contact rated value 20 A
— at 24 V per NO contact rated value 20 A
— at 110 V per NC contact rated value 1.25 A
— at 110 V per NO contact rated value 2.5 A
— at 220 V per NC contact rated value 0.5 A
— at 220 V per NO contact rated value 1A
— at 440 V per NC contact rated value 0.045 A
— at 440 V per NO contact rated value 0.09 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V per NC contact rated value 35 A
— at 24 V per NO contact rated value 35 A
— at 110 V per NC contact rated value 7.5 A
— at 110 V per NO contact rated value 15 A
— at 220 V per NC contact rated value 1.5 A
— at 220 V per NO contact rated value 3A
— at 440 V per NC contact rated value 0.135 A
— at 440 V per NO contact rated value 0.27 A
operating power at AC-2 at AC-3
● at 230 V per NC contact rated value 5.5 kW
● at 230 V per NO contact rated value 5.5 kW
● at 400 V per NC contact rated value 7.5 kW
● at 400 V per NO contact rated value 11 kW
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum 200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum 200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum 200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum 128 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum 106 A; Use minimum cross-section acc. to AC-1 rated value
power loss [W] at AC-3 at 400 V for rated value of the 1.6 W
operational current per conductor
no-load switching frequency
● at AC 5 000 1/h
● at DC 1 500 1/h
operating frequency at AC-1 maximum 1 000 1/h
Control circuit/ Control
type of voltage of the control supply voltage DC
control supply voltage at DC
● rated value 24 V

3RT25261BB40 Subject to change without notice


3/29/2022
Page 2/7 © Copyright Siemens
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value 0.8
● full-scale value 1.1
closing power of magnet coil at DC 5.9 W
holding power of magnet coil at DC 5.9 W
closing delay
● at DC 50 ... 170 ms
opening delay
● at DC 15 ... 18 ms
arcing time 10 ... 10 ms
Auxiliary circuit
number of NC contacts for auxiliary contacts 1
instantaneous contact
number of NO contacts for auxiliary contacts 1
instantaneous contact
operational current at AC-12 maximum 10 A
operational current at AC-15
● at 230 V rated value 10 A
● at 400 V rated value 3A
● at 500 V rated value 2A
● at 690 V rated value 1A
operational current at DC-12
● at 24 V rated value 10 A
● at 48 V rated value 6A
● at 60 V rated value 6A
● at 110 V rated value 3A
● at 125 V rated value 2A
● at 220 V rated value 1A
● at 600 V rated value 0.15 A
operational current at DC-13
● at 24 V rated value 10 A
● at 48 V rated value 2A
● at 60 V rated value 2A
● at 110 V rated value 1A
● at 125 V rated value 0.9 A
● at 220 V rated value 0.3 A
● at 600 V rated value 0.1 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
yielded mechanical performance [hp]
● for single-phase AC motor at 230 V rated value 3 hp
● for 3-phase AC motor at 460/480 V rated value 15 hp
contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required gG: 63 A (690 V, 100 kA)
— with type of assignment 2 required gG: 35 A (690 V, 50 kA)
● for short-circuit protection of the auxiliary switch fuse gG: 10 A
required
Installation/ mounting/ dimensions
mounting position +/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 50022
● side-by-side mounting Yes
height 85 mm
width 61 mm
depth 107 mm
required spacing

3RT25261BB40 Subject to change without notice


3/29/2022
Page 3/7 © Copyright Siemens
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— at the side 6 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
● at contactor for auxiliary contacts Screw-type terminals
● of magnet coil Screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— solid or stranded 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— finely stranded with core end processing 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
● at AWG cables for main contacts 2x (16 ... 12), 2x (14 ... 8)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— solid or stranded 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
AWG number as coded connectable conductor cross 16 ... 8
section for main contacts
Safety related data
product function
● mirror contact according to IEC 60947-4-1 Yes
● positively driven operation according to IEC 60947- No
5-1
protection class IP on the front according to IEC IP20
60529
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
Certificates/ approvals
General Product Approval EMC

Confirmation

Functional
Safety/Safety of Declaration of Conformity Test Certificates Marine / Shipping
Machinery

3RT25261BB40 Subject to change without notice


3/29/2022
Page 4/7 © Copyright Siemens
Type Examination UK Declaration of Type Test Certific- Special Test Certific-
Certificate Conformity ates/Test Report ate

Marine / Shipping other

Confirmation

other Dangerous Good

Transport Informa-
tion

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2526-1BB40
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2526-1BB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2526-1BB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2526-1BB40&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2526-1BB40/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2526-1BB40&objecttype=14&gridview=view1

3RT25261BB40 Subject to change without notice


3/29/2022
Page 5/7 © Copyright Siemens
3RT25261BB40 Subject to change without notice
3/29/2022
Page 6/7 © Copyright Siemens
A1 (+)

R1

R3

21
13
1

3
-Q

2
A2 (-)

14
R2

R4

22
4

last modified: 12/1/2021

3RT25261BB40 Subject to change without notice


3/29/2022
Page 7/7 © Copyright Siemens

You might also like