Prepared Document no.

Svein Arild Hagnæss Type 500 to DCU 305 R3 (LT)


Approved Date Revision
Anders Waal 2016-10-29 PA1

Re-wiring engine panels


Type 500 to DCU 305 R3 (LT)

Introduction
It is possible to re-wire from an existing installation that uses the type 500 series of
the Auto-Maskin engine panel to the newer DCU 305 R3 (LT) panel.
This document outlines the necessary steps for a successful transfer. It should
however not be seen as a complete guide.
Careful consideration must be taken with all wiring changes and all new sensor
configurations.
Carefully consult the installation manual for the DCU 305 R3 (LT) panel.

The type 500 engine panel The DCU 305 R3 (LT) engine panel

Page 1 (4)
Wiring changes
The three right-most columns advises wiring and configuration in the
DCU 305 R3 (LT) panel.
Note!​ The number in parenthesis ( ) reference the components 0V wire terminal
reference.

500 Panel DCU 305 Description and comments Configuration tip1


wire ref. wire ref.

1 1 24 VDC supply from start bat.


Configure low voltage setting
to 23.2 V
2 2 0 VDC supply from start bat.

N/A 3 24 VDC aux supply


(if available)

N/A 4 0 VDC aux supply


(if available)

3 (2) 5
Connect the two wires from the MPU Configure the correct
to wire terminals 5 and 6. flywheel teeth count
6

4 7 Shutdown switch 1 Configure all these as NO


(normally open) contacts.
5 8 Shutdown switch 2 If the wire break detection
feature is selected, then add
6 9 Shutdown switch 3 a 10k resistor across the
switch.
7 ​ 10 Shutdown switch 4
All ​pressure sensors shall be
configured with “On run only”.
N/A 11 All sensors shall be
Shutdown switch 5
referenced to terminal 29
(0V).
N/A 12 Shutdown switch 6 Channels not used for
shutdown can be configured
and used as alarm channels.

8 21-22 Oil Pressure gauge.


The sensor in use on the 500 panel
AI 1 is ​resistive, and cannot be used
directly for the DCU 305.
Change the sensor into a 4-20 mA
type, and connect as advised.

9 23-24 Coolant Temp. gauge.


The sensor in use on the 500 panel
AI 2 is ​resistive, and cannot be used
directly on the DCU 305.
Change the sensor into a 4-20 mA
type, and connect as advised.

10 41 Crank output.
24 VDC output to auxiliary relay.

1
Helpful information for the configuration in the Rudolf R3 configuration tool.

Page 2 (4)
11 42 Stop output.
24 VDC output to auxiliary relay.

43 Energize to Run.
This 24 VDC channel is active when
the engine shall run.

12 44 Emergency Stop.
24 VDC output to auxiliary relay.
and

48-49 Also, relay K6 activates for


Relay K6 shutdown.

13-14 34 (33) Automatic Start input Note that the DCU 305 panel
must be in Standby mode for
15-16 35 (33) Automatic Stop input these to be enabled.
The time before the stop
sequence activates can be
configured.

17-18 54-55-56 Ready for Power Management Start.


Relay K8 Relay K8 is pre-configured for this.

19-20 Any Disconnect Gen. Breaker This function is available to


configurable be configured to relay K7 or
relay K9.

21 13 Alarm switch 1

22 14 Alarm switch 2 Configure all these as NC


(normally closed) contacts.
23 15 Alarm switch 3 All ​pressure sensors shall be
configured with “On run only”.
24 16 Alarm switch 4 All sensors shall be
referenced to terminal 29
25 17 Alarm switch 5 (0V).

26 18 Alarm switch 6

27 29 The common 0V wire terminal.


Reference all alarm- and shutdown
switches here.

28-29-30 45-46-47 Common Alarm relay


Relay K5 - Active if no alarm
- Inactive if alarm

31-32 N/A All power supply is on terminals 1-2


(start battery) and 3-4 (aux supply)

33-34-35 31 (30) Remote Start Configure pre-glow or


pre-lube as needed.

36-37 32 (30) Remote Stop

38-39 Any Running This function is available to


configurable be configured to relay K7 or
relay K9.

40-41-42-43 N/A Glow plugs Configure pre-glow as

Page 3 (4)
-44-45 needed, and configure an
output relay.

Magnetic Pickup Unit


The DCU 305 R3 must have an RPM signal from a magnetic pick-up, preferrably
installed on the flywheel.
The pickup used on the 500 panel may be used with the DCU 305 R3 (LT).

Example configuration
Below is an example of configuration of a switch channel, made in the Rudolf R3 for
the DCU 305 R3 (LT), for the Autostop channel ​Oil Press.
The sensor wires shall be moved from wire terminals 4 (27) on the 500 panel, to
terminals 7 (29) on the DCU 305 R3 (LT) panel. Terminal 7 is the switch channel #1
input, and terminal 29 is the 0 V reference for the sensor.

Note!​ The Broken Wire Detection option requires a 10k ohm ¼ watt resistor installed
over the NO switch.

Configuration software
The Rudolf R3 software can be downloaded ​here​.

Page 4 (4)