TeSys D contactors
Contactor type LC1 D09 DT20 D12 DT25 D18 DT32 D25 DT40
(3P) D098 (3P) D128 (3P) D188 (3P) D258
1 Pole characteristics
Rated operational current (Ie) In AC-3, θ y 60 °C A 9 12 18 25
(Ue y 440 V) In AC-1, θ y 60 °C A 25 (1) 20 25 (1) 25 32 (1) 32 40 (1) 40
Rated operational voltage (Ue) Up to V 690 690 690 690
Frequency limits Of the operational current Hz 25…400 25…400 25…400 25…400
Conventional thermal θ y 60 °C A 25 (1) 20 25 (1) 25 32 (1) 32 40 (1) 40
current (Ith)
2 Rated making capacity (440 V) Conforming to IEC 60947 A 250 250 300 450
Rated breaking capacity (440 V) Conforming to IEC 60947 A 250 250 300 450
Permissible short time rating For 1 s A 210 210 240 380
No current flowing for preceding For 10 s A 105 105 145 240
15 minutes with θ y 40 °C
For 1 min A 61 61 84 120
For 10 min A 30 30 40 50
3 Fuse protection
against short-circuits
Without thermal
overload relay,
type 1 A
type 2 A
25
20
40
25
50
35
63
40
(U y 690 V) gG fuse
With thermal overload relay A See pages 6/20 and 6/21, for aM or gG fuse ratings corresponding to the associated
thermal overload relay
Average impedance per pole At Ith and 50 Hz mΩ 2.5 2.5 2.5 2
Power dissipation per pole for AC-3 W 0.20 0.36 0.8 1.25
4 the above operational currents AC-1 W 1.56 1.56 2.5 3.2
5 50/60 Hz coils
Drop-out
Operation
–
0.8…1.1 Uc on 50 Hz and 0.85…1.1 Uc on 60 Hz at 60 °C
Drop-out 0.3…0.6 Uc at 60 °C
Average consumption a 50 Hz Inrush 50 Hz coil VA –
at 20 °C and at Uc Cos ϕ 0.75
6 Sealed
50/60 Hz coil
50 Hz coil
VA
VA
70
–
Cos ϕ 0.3
50/60 Hz coil VA 7
a 60 Hz Inrush 60 Hz coil VA –
Cos ϕ 0.75
7 Sealed
50/60 Hz coil
60 Hz coil
VA
VA
70
–
Cos ϕ 0.3
50/60 Hz coil VA 7.5
Heat dissipation 50/60 Hz W 2…3
Operating time Closing "C" ms 12…22
(2) ms 4…19
8
Opening "O"
Mechanical durability 50 or 60 Hz coil –
in millions of operating cycles 50/60 Hz coil on 50 Hz 15
9
(1) Versions with spring terminal connections:
16 A for LC1 D093 and LC1 D123 (20 A possible with 2 x 2.5 mm2 in parallel),
25 A for LC1 D183 to LC1 D323 (32 A possible for LC1 D183 connected with 2 x 4 mm2 cables in parallel; 40 A possible for LC1 D253 and LC1 D323 connected
with 2 x 4 mm2 in parallel).
(2) The closing time "C" is measured from the moment the coil supply is switched on to closure of the main poles. The opening time "O" is measured from the
moment the coil supply is switched off to the moment the main poles separate.
10
5/52
D32 D38 D40A DT60A D50A D65A DT80A D80 D95 D115 D150
32 38 40 – 50 65 – 80 95 115 150
1
50 (1) 50 60 60 80 80 80 125 125 200 200
690 690 690 690 690 690 690 1000 1000 1000 1000
25…400 25…400 25…400 25…400 25…400 25…400 25…400 25…400 25…400 25…400 25…400
50 50 60 60 80 80 80 125 125 200 200
550 550 800 800 900 1000 1000 1100 1100 1260 1660 2
550 550 800 800 900 1000 1000 1100 1100 1100 1400
430 430 720 720 810 900 900 990 1100 1100 1400
260 310 320 320 400 520 520 640 800 950 1200
138 150 165 165 208 260 260 320 400 550 580
60 60 72 72 84 110 110 135 135 250 250
63
63
63
63
80
80
80
80
100
100
125
125
125
125
200
160
200
160
250
200
315
250
3
See pages 6/20 and 6/21 for aM or gG fuse ratings corresponding to the associated thermal overload relay
–
0.8…1.1 Uc on 50 Hz and
–
0.8…1.1 Uc on 50 Hz and
0.3…0.6 Uc at 55 °C
0.8…1.1 Uc on 50 Hz and
0.3…0.5 Uc at 55 °C
0.8…1.15 Uc on 50/60 Hz
5
0.85…1.1 Uc on 60 Hz 0.85…1.1 Uc on 60 Hz at 60 °C 0.85…1.1 Uc on 60 Hz at 55 °C
at 60 °C at 55 °C
0.3…0.6 Uc at 60 °C 0.3…0.6 Uc at 60 °C 0.3…0.6 Uc at 55 °C 0.3…0.5 Uc at 55 °C
– – 200 300 –
0.75 0.75 0.75 0.8 0.9
70
–
160
–
245
20
280…350
22
280…350
–
6
0.3 0.3 0.3 0.3 0.9
7 15 26 2…18 2…18
– – 220 300 –
0.75 0.75 0.75 0.8 0.9
70
–
140
–
245
22
280…350
22
280…350
–
7
0.3 0.3 0.3 0.3 0.9
7.5 13 26 2…18 2…18
2…3 4…5 6…10 3…8 3…4.5
12…22 12…26 12…26 12…26 12…26 12…26 20…35 20…35 20…50 20…35
4…19 4…19 4…19 4…19 4…19 4…19 40…75
8
6…20 6…20 6…20
– – – – – – 10 10 8 –
15 6 6 6 6 6 4 4 8 8
3600 3600 3600 3600 3600 3600 3600 3600 2400 1200
10
5/53