Chapter

PLC Communications
6
In This Chapter...
Introduction................................................................................................................ 6–2
DirectLOGIC PLCs Password Protection.................................................................... 6–2
PLC Communication Cables & Wiring Diagrams....................................................... 6–5
AutomationDirect PLCs RS-232C Serial:..................................................................... 6–7
AutomationDirect PLCs RS-422A/RS-485A:.............................................................. 6–10
Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON:....................... 6–16
Direct LOGIC Universal Converter, p/n F2-UNICON:............................................... 6–17
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples........................................ 6–18
Allen-Bradley:.......................................................................................................... 6–22
GE:.......................................................................................................................... 6–27
GE VersaMax Micro:................................................................................................ 6–27
Mitsubishi:.............................................................................................................. 6–27
Omron:................................................................................................................... 6–29
Modicon ModBus RS-232:....................................................................................... 6–30
Modicon Micro Series:............................................................................................ 6–30
Modicon ModBus with RJ45:................................................................................... 6–30
Siemens:.................................................................................................................. 6–31
Chapter 6: PLC Communications

Introduction
1 The C-more family of touch panels is capable of communicating with a wide variety of
Programmable Logic Controllers. C-more is capable of communicating over RS232,
2 RS422 and RS485 serial networks as well as Ethernet networks. It communicates with all
AutomationDirect PLC’s utilizing various protocols. C-more also communicates with other
brands of PLCs by their different protocols. The table on the next page lists all of the various
3 PLCs and protocols that can be configured. The page after the protocol table lists the various
serial communication cables that are available to purchase. The rest of this chapter is devoted
4 to show the pin to pin connections of all the available cables plus wiring diagrams that the user
can refer to in order to construct their own cables, along with wiring diagrams of cables that
are not available for purchase. To simplify RS422/RS485 wiring schemes, we have included
5 wiring diagrams showing connections for available terminal connectors such as our ZIPLink
Communication Adapter Module, p/n ZL-CMA15, used for example with our DL-06 and
6 D2-260 PLCs and C-more D-Sub 15-pin to Terminal Block Adapter p/n EA-COMCON-3.
If you have difficulty determining whether the particular PLC and/or protocol you are using
7 will work with the C-more series of touch panels, please contact our technical support group
at 770-844-4200

8 DirectLOGIC PLCs Password Protection


9 NOTE: Many DirectLogic PLCs support multi-level password protection of the ladder program. This allows
password protection while not locking the communication port to an operator interface. The multilevel
10 password can be invoked by creating a password with an upper case “A” followed by seven numeric
characters (e.g. A1234567). Please refer to the specific PLC user manual for further details.

11 C-more
Touch Panel
12
DL-06 PLC
13
14
C-more to
A Direct LOGIC
VGA 15-pin port
Port 2
B serial cable
p/n EA-2CBL-1

C
D

6-2 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

PLC Protocol & Cables


Compatibility Table
Model Protocols
1
Productivity3000
P3000 Serial
P3000 Ethernet 2
CLICK Modbus (CLICK)

all
K-Sequence
Direct NET
3
DL05/DL06

H0-ECOM/H0-ECOM100
Modbus (Koyo addressing)
Direct LOGIC Ethernet
4
DL105 all K-Sequence
D2-230 K-Sequence 5
K-Sequence
D2-240
Direct NET
K-Sequence
6
DL205 D2-250/D2-250-1/D2-260 Direct NET
Modbus (Koyo addressing)
7
Direct NET
D2-240/D2-250-1/D2-260
Using DCM Modbus (Koyo addressing) 8
H2-ECOM/H2-ECOM100 Direct LOGIC Ethernet
D3-330/330P (Requires the use of a Data Communications Unit)
D3-340
Direct NET
Direct NET
9
AutomationDirect
DL305 D3-350
K-Sequence
Direct NET
10
Modbus (Koyo addressing)

D3-350 DCM
Direct NET 11
Modbus (Koyo addressing)

D4-430
K-Sequence
Direct NET
12
D4-440
K-Sequence
Direct NET
13
K-Sequence
DL405
D4-450 Direct NET 14
Modbus (Koyo addressing)

All with DCM


Direct NET
Modbus (Koyo addressing)
A
H4-ECOM/H4-ECOM100
H2-WinPLC (Think & Do) Live V5.2 or later and Studio any version
Direct LOGIC Ethernet
Think & Do Modbus RTU (serial port)
B
H2-WinPLC (Think & Do) Live V5.5.1 or later and Studio V7.2.1 or later Think & Do Modbus TCP/IP (Ethernet port)

GS Drives
GS Drives Serial C
GS Drives TCP/IP (GS-EDRV)
SOLO Temperature Controllers SOLO Temperature Controller D
PLC Compatibility Table continued on the next page.

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-3
Chapter 6: PLC Communications

PLC Protocol & Cables (cont’d)


1 Compatibility Table (cont’d)
Model Protocols
2 MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-01/02/03 DH485/AIC/AIC+
MicroLogix 1000, 1100, 1200, 1400 and 1500
3 SLC 5-03/04/05 DF1 Half Duplex; DF1 Full Duplex
ControlLogix™, CompactLogix™, FlexLogix™
4 Allen-Bradley
PLC-5 DF1 Full Duplex
ControlLogix, CompactLogix, FlexLogix - Tag Based DF1 Half Duplex; DF1 Full Duplex

5 ControlLogix, CompactLogix, FlexLogix - Generic I/O Messaging EtherNet/IP Server


ControlLogix, CompactLogix, FlexLogix - Tag Based

6 MicroLogix 1100, 1400 and SLC 5/05, via native Ethernet port EtherNet/IP Client
MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5-03/04/05, all via ENI adapter

7 GE 90/30, 90/70. Micro 90, VersaMax Micro


FX Series
SNPX
FX Direct

8 Mitsubishi
Q02, Q02H, Q06H, Q12H, Q25H
Q, QnA Serial
Q CPU
QnA Serial

9 Q, Qna Ethernet
984 CPU, Quantum 113 CPU, AEG Modicon Micro Series 110 CPU: 311-xx, 411-xx,
QnA Ethernet
Modbus RTU
512-xx, 612-xx
10 Modicon
Other devices using Modicon Modbus addressing
Modbus RTU
Modbus TCP/IP

11 Omron
C200 Adapter, C500
CJ1/CS1 Serial
Host Link

FINS
12 CJ1/CS1 Ethernet
S7-200 CPU, RS-485 Serial PPI
Siemens
13 S7-200 CPU, S7-300 CPU, S7-1200 CPU; Ethernet Ethernet ISO over TCP

14
A
B
C
D

6-4 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams


Purchased Cable
Description
Cable
Part Number
1
AutomationDirect Productivity Series, CLICK,
Direct LOGIC PLC RJ-12 port, DL05, DL06, DL105, EA-2CBL
DL205, D3-350, D4-450 & H2-WINPLC (RS-232C)
2
Direct LOGIC (VGA Style) 15-pin port
DL06, D2-250 (250-1), D2-260
(RS-232C)
EA-2CBL-1 3
Direct LOGIC PLC RJ-11 port, D3-340
(RS-232C) EA-3CBL Part No. EA-2CBL 4
Direct LOGIC DL405 PLC 15-pin D-sub
port, DL405 (RS-232C)
Direct LOGIC PLC 25-pin D-sub port,
EA-4CBL-1
5
DL405, D3-350, DL305 DCU and EA-4CBL-2
all DCM’s (RS-232C) 6
Allen-Bradley MicroLogix 1000, 1100,
EA-MLOGIX-CBL
1200, 1400, 1500 (RS-232C)
Allen-Bradley SLC 5-03/04/05,
7
ControlLogix, CompactLogix, FlexLogix, MicroLogix EA-SLC-232-CBL
DF1 port (RS-232C)
Allen-Bradley PLC-5 DF1 port
8
(RS-232C) EA-PLC5-232-CBL Part No. EA-2CBL-1

Allen-Bradley MicroLogix, SLC 5-01/02/03, PLC5


DH485 port (RS-232C) EA-DH485-CBL
9
GE 90/30, 90/70, Micro 90, VersaMax Micro
15-pin D-sub port (RS-422A) EA-90-30-CBL 10
MITSUBISHI FX Series 25-pin port
(RS-422A) EA-MITSU-CBL
11
MITSUBISHI FX Series 8-pin mini-DIN
EA-MITSU-CBL-1
(RS-422A)
OMRON Host Link
12
C200 Adapter, C500 EA-OMRON-CBL
(RS-232C) Part No. EA-3CBL
13
NOTE 1: The above list of pre-made communications cables may be purchased. See further in this chapter
14
for wiring diagrams of additonal user constructed cables. This chapter also includes wiring diagrams for the
pre-made cables. A
NOTE 2: EZTouch serial PLC communication cables are compatible with C-more touch panels. B
C-more PLC Serial
Communications Port
8 1
D-Sub 15-pin female C
on rear of touch panel
15 9
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-5
Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams


1
2
3
Part No. EA-4CBL-1
4 Part No. EA-4CBL-1

5
6
7 Part No. EA-MLOGIX-CBL Part No. EA-SLC-232-CBL

8
9
10
11 Part No. EA-PLC5-232-CBL Part No. EA-DH485-CBL

12
13
14
A Part No. EA-90-30-CBL Part No. EA-MITSU-CBL

B
C
D Part No. EA-MITSU-CBL-1 Part No. EA-OMRON-CBL

6-6 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

PLC Communication Cables & Wiring Diagrams (cont’d)


The following series of wiring diagrams show the connectors and wiring details for the
communication cables that are used between the C-more touch panels and various PLC
1
controllers. Part numbers are included with the pre-made cables that can be purchased from
AutomationDirect. The information presented will allow the user to construct their own cables 2
if so desired.
EA-2CBL 3
Productivity Series, Do-more, CLICK and Direct Logic PLC RJ12 port:
To PLC
RJ12 Port
DL05, DL06, DL105, DL205, DL350, DL450, H2-WINPLC
To C-more Touch
Panel PLC Port 4
RS-232C (p/n EA-2CBL)

RJ12 6-pin 15-pin


5
Phone Plug D-sub
1 = Sig GND
2 = do not use
(6P6C)

TXD 4
Wiring Diagram

3 RXD
8 = do not use
7 = do not use
6 = do not use
(male)
15
15 = do not use
14 = do not use
13 = do not use
6
3 = RXD 5 = Logic GND
7
3 2 12 = do not use
4 = TXD RXD TXD
4 = do not use 11 = do not use
5 = do not use GND 1 5 3 = RXD (232C) 10 = do not use
123456
6 = do not use 1 2 = TXD (232C) 9 = do not use
shield 1
1 = Frame GND
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable. 8
AutomationDirect PLCs RS-232C Serial: EA-2CBL-1 9
Direct Logic PLC (VGA style) 15-pin HD port:
To PLC
15-Pin HD Port
D2-250, D2-250-1, D2-260, DL06
RS-232C (p/n EA-2CBL-1)
To C-more Touch Panel
Serial Port2 10
15-pin Wiring Diagram
11
15-pin
HD D-sub
8 = do not use
7 = Sig GND
(male)
15
15 = do not use
14 = do not use
TXD
RXD
2
3
3 RXD
2 TXD
8 = do not use
7 = do not use
D-sub
(male) 15 = do not use
15 14 = do not use
12
6 = do not use 13 = do not use GND 7 5 6 = donot use 13 = do not use
5 = CTS
4 = RTS
3 = RXD 1 6
12 = do not use
11 = do not use RTS
10 = do not use CTS
4
5
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
13
2 = TXD 9 = do not use 2 = TXD (232C) 1 9 = do not use
1 = +5 VDC - N/C
HD = High Density shield 1 1 = Frame GND

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
14
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-7
Chapter 6: PLC Communications

AutomationDirect PLCs RS-232C Serial (cont’d):


1 EA-3CBL
Direct Logic PLC RJ11 port: D3-340 To C-more Touch

2 To PLC
RJ11 Port
RS-232C (p/n EA-3CBL) Panel PLC Port

3 RJ11 4-pin
Phone Plug
15-pin
D-sub
(4P4C) Wiring Diagram 8 = do not use (male) 15 = do not use
4 1 = RXD
2 = TXD
TXD 2
1
3
2
RXD
7 = do not use
6 = do not use
5 = Logic GND
14 = do not use
15 13 = do not use
12 = do not use
RXD TXD
3 = do not use 4 = do not use 11 = do not use
5 4 = Sig ground 1234
GND 4
shield
5
1
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
1
10 = do not use
9 = do not use

6 Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

7
8
9
10
11
12
13
14
A
B
C
D

6-8 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

AutomationDirect PLCs RS-232C Serial (cont’d):


EA-4CBL-1 1
To PLC Direct Logic PLC 15-pin D-sub port: DL405, To C-more Touch
15-Pin Port
RS-232C (p/n EA-4CBL-1) Panel PLC Port
2
TXD 2
Wiring Diagram
3 RXD
3
15-pin 15-pin
4
RXD 3 2 TXD
D-sub D-sub
8 = YOM Sense (male) 15 = Logic GND online 4 5 8 = do not used (male) 15 = do not use
7 = CTS 14 = Logic GND 7 = do not used 14 = do not use
6 = do not use
15
13 = Logic GND GND 13 15
6 = do not used 13 = do not use
5 = do not use
4 = Online
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
GND 14
GND 15
5 = Logic GND
4 = do not used
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
5
2 = TXD (232C) 9 = do not use YOP 1

6
2 = TXD (232C) 1 9 = do not use
1 = YOP Sense 1 7 1 = Frame GND
CTS
See PLC user manual YOM 8
for pin out details.
1
shield
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable. 7
8
EA-4CBL-2
To PLC
25-Pin Port
Direct Logic PLC 25-pin D-sub port:
DL405, D3-350, DL305 DCU, and all DCMs,
To C-more Touch
Panel PLC Port
9
RS-232C (p/n EA-4CBL-2)
10
11
25-pin Wiring Diagram 15-pin
D-sub D-sub
13 = do not use (male) 25 = do not use TXD 2 3 RXD 8 = do not use
12 = do not use (male) 15 = do not use
25 24 = do not use 3 2 7 = do not use 14 = do not use
23 = do not use RXD
12
11 = do not use TXD 15 13 = do not use
10 = do not use 6 = do not use
22 = do not use GND 7 5
5 = Logic GND 12 = do not use
9 = do not use 21 = do not use
8 = do not use 4 4 = do not use 11 = do not use
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
13
19 = do not use CTS 5
6 = do not use 2 = TXD (232C) 1 9 = do not use
5 = CTS 18 = do not use 1 = Frame GND
4 = RTS 17 = do not use shield 1
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
14
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-9
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A:


When using the RS-422A/RS-485A capabilities of the C-more PLC communications port, the
1 termination resistor is placed between the RXD– and RXD+ terminals on the PLC side of the
connection between the touch panel and PLC. The Termination Resistor value is based on the
2 characteristic impedance of the cable being used. To enable the built-in 120 Ohm Termination
Resistor, jumper pin 13 to pin 9 (RXD+) on the C-more 15-pin PLC communications port.

3 To PLC Direct LOGIC DL-06, D2-250, D2-250-1, D2-260 (all Port 2) To C-more Touch
Panel PLC Port
15-Pin Port RS-422A
User Constructed
4
5
Wiring Diagram 13
15-pin Term. 15-pin
HD D-sub D-sub
TXD+ 9 9 RD+
(male) 8 = do not use (male) 15 = do not use
TXD– 10 10 RD– 7 = do not use 14 = do not use
6 8 = do not use
7 = Sig GND
6 = RXD–
15
15 = CTS–
14 = CTS+
RXD+
RXD–
13
6
11
12
SD+
6 = do not use
5 = Logic GND
SD– 4 = do not use
15
13 = Termination
12 = SD– (RS422)
11 = SD+ (RS422)
5 = do not use 13 = RXD+
7 5 3 = do not use 10 = RD– (RS422)
7 4 = do not use
3 = do not use
2 = do not use
1 6
12 = RTS-
11 = RTS+
10 = TXD–
GND
RTS– 12
15
2 = do not use 1
1 = Frame GND
9 = RD+ (RS422)

9 = TXD+ CTS–
1 = do not use
8 RTS+
CTS+
11
14
shield 1

9 Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

10 To PLC
25-Pin Port
Direct LOGIC D2-DCM*, D3-DCM* & D4-DCM* To C-more Touch
RS-422A Panel PLC Port

11 User Constructed
12 13 = CTS–
25-pin
D-sub
(male)
25 = do not use
24 = do not use TXD+ 14
Wiring Diagram 13 Term.
9 RD+
15-pin
D-sub
8 = do not use (male) 15 = do not use
12 = CTS+ 23 = do not use

13 11 = RTS–
10 = RTS+
9 = do not use
25 22 = do not use TXD–
21 = do not use RXD+ 17
20 = do not use
15 10 RD– 7 = do not use
11 SD+ 6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
8 = do not use 16 12 SD– 4 = do not use
19 = do not use RXD– 11 = SD+ (RS422)

14 7=0V
6 = do not use
5 = do not use
18 = do not use
17 = RXD+
(RS422)
0V
RTS–
7
11
5 3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422)
4 = do not use 13
16 = RXD–
A 3 = do not use CTS–
2 = do not use (RS422)
RTS+ 10 * Note: The DCM modules must be set for:
1 = do not use 1 15 = TXD–
CTS+ 12 Direct NET Slave, HEX mode.
(RS422)

B 14 = TXD+
(RS422)
shield 1

Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

C NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more

D than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel.

6-10 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


User Constructed 1
To PLC Direct LOGIC D4-430/D4-440/D4-450 Port 1 and D3-350 Port 2
25-Pin Port To C-more Touch
RS-422A Panel PLC Port

2
25-pin
D-sub
14
Wiring Diagram 13
9
Term. 15-pin
D-sub
3
13 = do not use (male) 25 = do not use TXD+ RD+
12 = do not use 8 = do not use (male) 15 = do not use
11 = CTS+
10 = RXD–
(RS422)
24 = do not use
25 23 = CTS–
22 = do not use
TXD–
RXD+
16
9
10
11
RD– 7 = do not use
SD+
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
4
21 = do not use 10 12
9 = RXD+ RXD– SD– 4 = do not use 11 = SD+ (RS422)
(RS422)
8 = do not use
7=0V
20 = do not use
19 = RTS+
18 = RTS–
0V
RTS–
7
18
5 3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) 5
6 = do not use 17 = do not use
23
5 = do not use
4 = do not use
3 = do not use 1
16 = TXD–
(RS422)
15 = do not use
CTS–
RTS+ 19
11
6
2 = do not use 14 = TXD+ CTS+
1 = do not use (RS422) shield 1

Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
7
8
User Constructed
To PLC
25-Pin Port
Direct LOGIC D4-450 Port 3 To C-more Touch 9
RS-422A Panel PLC Port
RTS and CTS are not present on this port.
10
13 = TXD–
25-pin
D-sub
(male)
25 = RXD–
(RS422) TXD+ 12
Wiring Diagram 13
9
Term.
RD+
15-pin
D-sub 11
(RS422) 8 = do not use (male) 15 = do not use
12 = TXD+ 24 = RXD+ 13 10
(RS422)
11 = do not use
10 = do not use
25 (RS422)
23 = do not use
22 = do not use
TXD–
RXD+ 24
25
11
12
RD– 7 = do not use
SD+
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
12
9 = do not use RXD– SD– 4 = do not use 11 = SD+ (RS422)
21 = do not use
8 = do not use
7=0V
6 = do not use
20 = do not use
19 = do not use
18 = do not use
0V 7
shield
5
1
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) 13
5 = do not use

14
4 = do not use 17 = do not use
3 = do not use 16 = do not use
2 = do not use 1 15 = do not use
1 = do not use 14 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
A
NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
B
than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
connected to a panel. C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-11
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


User Constructed
1 To PLC Direct LOGIC DL-06, D2-260 (both Port 2) To C-more Touch
Panel PLC Port
15-Pin Port RS-485A
2
3 15-pin
HD D-sub
(male) RXD+ 13
Wiring Diagram 13
9
Term.
RD+
8 = do not use
15-pin
D-sub
(male) 15 = do not use
9 11 SD+ 7 = do not use 14 = do not use
4
TXD+
8 = do not use 15
10 10 6 = do not use 13 = Termination
7 = Sig GND 15 = CTS– TXD– RD–
15 5 = Logic GND 12 = SD– (RS485)
6 = RXD– 14 = CTS+ 6 12 SD– 4 = do not use
RXD– 11 = SD+ (RS485)
5 = do not use 13 = RXD+

5
7 5 3 = do not use 10 = RD– (RS485)
4 = do not use 12 = RTS- GND
2 = do not use 1 9 = RD+ (RS485)
3 = do not use 1 6 11 = RTS+ RTS– 12
1 = Frame GND
2 = do not use 10 = TXD– 15
9 = TXD+ CTS–
1 = do not use
6 RTS+
CTS+
11
14
shield 1

7 Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.

8 NOTE: The RS-485 wiring diagram shown above is not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram example on page 6-18 if more than one PLC will be
9 connected to a panel.

10
11
12
13
14
A
B
C
D

6-12 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-485A – PLC D2-260 or DL06 only – Port 2
1
Terminal Block Adapter
RS-232 RXD
RS-232 TXD Wiring Diagram
plugs into C-more 15-pin
PLC Serial Comm. Port 2
3
TERMINATE +5V
SIGNAL GND GND
ZL-CMA15L
RS-422/485 RX– RD–

RS422/485
RXD

TXD
232
RS-422/485 TX–
RS-422/485 RX+
SD–
SD+ 4
TX+
RX+

TXD
RXD
+5V
TX-
RX-

RS-422/485 TX+ RD+


SG

ZL-CMA15L
shield
See ZL-CMA15L specifications on
TERM EA-COMCON-3
5
termination resistor jumper.

Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent. 6
7
Direct LOGIC ZIPLink ZL-CMA15L Adapter Module to EA-COMCON-3 Terminal Block Adapter
RS-422A – PLC D2-250 (-1), D2-260 or DL06 – Port 2
Terminal Block Adapter
8
plugs into C-more 15-pin

9
RS-232 RXD
PLC Serial Comm. Port
RS-232 TXD Wiring Diagram
TERMINATE +5V

ZL-CMA15L

RXD
SIGNAL GND
RS-422/485 RX–
GND
SD–
10
RS-422/485 RX+ SD+

RS422/485
TXD
232
RS-422/485 TX– RD–
11
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

RS-422/485 TX+ RD+


EA-COMCON-3
12
shield TERM

ZL-CMA15L See ZL-CMA15L specifications on


termination resistor jumper.

Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
13
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving
connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if
14
more than one PLC will be connected to a panel.
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-13
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):


1
Productivity3000 PAC RS485 Port to EA-COMCON-3 Terminal Block Adapter
2 Wiring Diagram
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port

3 SIGNAL GND
TXD / RXD –
GND
RD –
*
4 TXD / RXD +

Productivity3000
SD –
SD +
PS485 Port RD +

5 * 120 Ω resistor
shield TERM

EA-COMCON-3
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
6
7
8
AutomationDirect Productivity PAC
9 Removable Connector
included with
Productivity3000 CPU
RS-485
To C-more Touch
Panel Serial Port2

10
Wiring Diagram 13 15-pin
11
Term.
D-sub
TXD+ / RXD+ 3 9 RD+
8 = do not use (male) 15 = do not use
TXD+ / RXD+ + Term. 11 SD+ 7 = do not use 14 = do not use
15

12 8 10 6 = do not use 13 = Termination


TXD- / RXD- - TXD- / RXD- RD–
5 = Logic GND 12 = SD– (RS485)
12 SD– 4 = do not use
Ground G 11 = SD+ (RS485)
Ground 5 5 3 = do not use 10 = RD– (RS485)

13 shield 1
2 = do not use 1
1 = Frame GND
9 = RD+ (RS485)

Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
14
A
B
C
NOTE: The RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more
D than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC
will be connected to a panel.

6-14 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

AutomationDirect PLCs RS-422A/RS-485A (cont’d):

AutomationDirect CLICK PLC


1
CLICK To C-more Touch
Analog CPU
Com Port 3
RS-485
Panel Serial Port2
2
Wiring Diagram 13 Term. 15-pin
3
D-sub
RS-485 3 9

4
RD+
Signal A 8 = do not use (male) 15 = do not use
RS-485 Signal A + Term. 11 SD+ 7 = do not use 14 = do not use
15
RS-485 8 10 6 = do not use 13 = Termination
RS-485 Signal B - Signal B
RD–
5 = Logic GND 12 = SD– (RS485)

5
12 SD– 4 = do not use
Logic Ground LG 11 = SD+ (RS485)
Logic 5 5 3 = do not use 10 = RD– (RS485)
Ground 2 = do not use 1 9 = RD+ (RS485)
shield 1 1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
6
7
8
9
10
11
12
13
14
A
B
C
NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving
connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if
more than one PLC will be connected to a panel.
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-15
Chapter 6: PLC Communications

Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON:


1 FA-ISOCON Universal Isolated Network Adapter
RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
2 Wiring Diagram Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
A COM B GND

3 RX–
RX+
SD–
SD+
RXD

4 TXD
TXD EN
TX–
TX+
RD–
RD+
B TXD shield TERM

5
RXD
CTS Ground the shield only at the equipment
C-A end where the FA-ISOCON is located. EA-COMCON-3
C +V
C-A
D

6
TX+
TX–
RX– See FA-ISOCON specificaitons to
RX+ properly configure the adapter. Note: When using multiple PLCs
C-B connected to one C-more touch
panel, only jumper the Term

7 FA-ISOCON
terminal to the RD+ terminal
when the panel is the last device
at one end of the network.

8 Port 2

9
10 Modular cable included
with the FA-ISOCON
PW
RU
CP
TX1
RX
1
R
N
U
DL05 PLC
TX2

11
2
RX

12 Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

13
14
A
B
C
D

6-16 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

Direct LOGIC Universal Converter, p/n F2-UNICON:

F2-UNICON Universal Converter 1


RS-422A to RS-232C – PLC DL05 or D2-240 – Port 2 only
Wiring Diagram Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
2
GND GND
RXD–
RXD+
SD–
SD+
3
TXD–
TXD+
RD–
RD+ 4
shield TERM
Ground the shield only at the equipment
end where the F2-UNICON is located. EA-COMCON-3 5
F2-UNICON
See F2-UNICON specificaitons to
properly configure the converter.
Note: When using multiple PLCs
connected to one C-more touch
panel, only jumper the Term
6
terminal to the RD+ terminal
when the panel is the last device
at one end of the network.
PWR
BATT
RUN
CPU
7
DL240
RUN

8
CPU TERM

D2-240 PLC CH 1

CH 2

9
CH 3

CH 4

10
PORT 1

PORT 2

Modular cable included


with the F2-UNICON
11
Note: Use the above wiring diagram to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
12
13
14
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-17
Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples


1 DL06 and DL205 used for illustration purposes

2 (example device communicating


DirectLOGIC
DL06 PLC
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave) RXD
DL205 PLC
Cable Adapter
5
TXD
RS422/485 232

(example device communicating

TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)

Port 2
6 ZL-CMA15L

Shielded Cable
When connecting to a DirectLogic PLC
RXD

Cable Adapter
7
TXD

use connector ZL-CMA15L or ZL-CMA15


RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable

8
9
10 Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
To DL06 PLC port 2 To D2-250-1 PLC port 2
11 (example RS-422 connection) (example RS-422 connection)
RXD+

RXD+
RXD–

RXD–
TXD+

TXD+
RTS+

CTS+

RTS+

CTS+
TXD–

TXD–
RTS–
CTS–

RTS–

CTS–
GND

GND

12 7 10 9 6
*
13 11 14 12 15 7 10 9 6 13 11 14 12 15

13 7 = Sig GND
15-pin
HD D-sub
8 = do not use (male)
15
15 = CTS–
14 = CTS+
6 = RXD– 13 = RXD+

14
5 = do not use 12 = RTS-
4 = do not use 11 = RTS+
3 = do not use 10 = TXD–
2 = do not use 1 9 = TXD+
1 = do not use 6

A
HD = High Density

RXD+ RXD+

RXD– RXD–

B TXD+

TXD–
TXD+

TXD–
Signal GND Signal GND

C * Termination resistors required at both ends of the


network receive data signals to match the impedance
shield

of the cable (between 100 and 500 ohms).


Typical RS-422 Multi-Drop Wiring Diagram
D using DirectLogic pin numbers to illustrate

6-18 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


DL06 and DL205 used for illustration purposes
1
C-more

(example device communicating


DirectLOGIC
DL06 PLC
Touch Panel
2
across RS-422 connection)
3
4
(Slave)
(Master)
5
Port 2
6
e
e cod
Dat Origin
of
ntry
Cou .
., LTD
S CO
RIE

TERM
N-3
UST
IND
ICS
CO

RD+
ON

-COM
CTR

RD–
ELE
O
EA

SD+
KOY

SD–
GND
ZL-CMA15L

RXD

Cable Adapter
7
TXD
RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L) 10
To DL06 PLC port 2 To C-more Touch Panel
(example RS-422 connection)
11

* Term.
RXD+
RXD–
TXD+

RTS+

CTS+
TXD–

RTS–
CTS–

SHD
RD+
RD–

SD+
GND

SD–
GND

EA-COMCON-3
7 10 9 6 13 11 14 12 15 5 10 9 12 11 13 1
12
6 = RXD–
15-pin
HD D-sub
8 = do not use (male)
7 = Sig GND
15
15 = CTS–
14 = CTS+
13 = RXD+
8 = do not use
15-pin
D-sub 15 = do not use
13
7 = do not use (male) 14 = do not use
5 = do not use 12 = RTS-

14
6 = do not use 15 13 = Termination
4 = do not use 11 = RTS+ 5 = Logic GND 12 = SD– (RS422)
3 = do not use 10 = TXD– 4 = do not use 11 = SD+ (RS422)
2 = do not use 1 9 = TXD+ 3 = do not use 10 = RD– (RS422)
1 = do not use 6
2 = do not use 9 = RD+ (RS422)
HD = High Density 1 = Frame GND 1

RXD+ RXD+ A
RXD– RXD–

TXD+

TXD–
TXD+

TXD–
B
Signal GND Signal GND
shield
* Termination resistors required at both ends of the
network receive data signals to match the impedance
shield
C
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-422 Multi-Drop Wiring Diagram (cont-d)
using DirectLogic pin numbers to illustrate
13 to 9 on the C-more Touch Panel 15-pin connector
to place the 120 internal resistor into the network. If
the cable impedance is different, then use an external
resistor matched to the cable impedance.
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-19
Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


1 DL06 and DL205 used for illustration purposes

2 (example device communicating


DirectLOGIC
DL06 PLC
across RS-422 connection) (Slave)
3
Port 2
4 ZL-CMA15L DirectLOGIC
(Slave) RXD
DL205 PLC
Cable Adapter
5
TXD
RS422/485 232

(example device communicating

TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown) across RS-422 connection)

Port 2
6 ZL-CMA15L

Shielded Cable
When connecting to a DirectLogic PLC
RXD

Cable Adapter
7
TXD

use connector ZL-CMA15L or ZL-CMA15


RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable

8
9
10 Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)

11 To DL06 PLC port 2 To D2-250-1 PLC port 2


(example RS-485 connection) (example RS-485 connection)

12
RXD+

RXD+
RXD–

RXD–
TXD+

RTS+

CTS+

TXD+

RTS+

CTS+
TXD–

RTS–
CTS–

TXD–

RTS–

CTS–
GND

GND

7 6 10 13 9 11 14 12 15 7 6 10 13 9 11 14 12 15

13 *

15-pin
HD D-sub

14 8 = do not use (male)


7 = Sig GND
6 = RXD–
5 = do not use
15
15 = CTS–
14 = CTS+
13 = RXD+
12 = RTS-
4 = do not use 11 = RTS+

A
3 = do not use 10 = TXD–
2 = do not use 1 9 = TXD+
1 = do not use 6
HD = High Density

B TXD– / RXD–

TXD+ / RXD+
TXD– / RXD–

TXD+ / RXD+

Signal GND Signal GND

C
shield

* Termination resistors required at both ends of


the network to match the impedance of the cable
(between 100 and 500 ohms).
Typical RS-485 Multi-Drop Wiring Diagram
D using DirectLogic pin numbers to illustrate

6-20 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

RS-422A/RS-485A Multi-Drop Wiring Diagram Examples (cont’d)


DL06 and DL205 used for illustration purposes
1
C-more

(example device communicating


DirectLOGIC
DL06 PLC
Touch Panel
2
across RS-422 connection)
3
4
(Slave)
(Master)
5
Port 2
6
e
e cod
Dat Origin
of
ntry
Cou .
., LTD
S CO
RIE

TERM
N-3
UST
IND
ICS
CO

RD+
ON

-COM
CTR

RD–
ELE
O
EA

SD+
KOY

SD–
GND
ZL-CMA15L

RXD

Cable Adapter
7
TXD
RS422/485 232
TX+
RX+

TXD
RXD
+5V
TX-
RX-
SG

(ZL-CMA15L shown)

Shielded Cable
Shielded Cable
8
9
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L) 10
To DL06 PLC port 2 To C-more Touch Panel
11
(example RS-485 connection)

* Term.
12
RXD+
RXD–

TXD+

RTS+

CTS+
TXD–

RTS–
CTS–

SHD
RD+
RD–

SD+
GND

GND

SD–
EA-COMCON-3
7 6 10 13 9 11 14 12 15 5 10 12 9 11 13 1

15-pin
13
HD D-sub
15-pin

14
8 = do not use (male) 15 = CTS–
7 = Sig GND 14 = CTS+ 8 = do not use D-sub 15 = do not use
6 = RXD– 15 13 = RXD+ 7 = do not use (male) 14 = do not use
5 = do not use 12 = RTS- 6 = do not use 15 13 = Termination
4 = do not use 11 = RTS+ 5 = Logic GND 12 = SD– (RS485)
3 = do not use 10 = TXD– 4 = do not use 11 = SD+ (RS485)
2 = do not use 1
1 = do not use 6
9 = TXD+

HD = High Density
3 = do not use
2 = do not use
1 = Frame GND 1
10 = RD– (RS485)
9 = RD+ (RS485)
A
TXD– / RXD–

TXD+ / RXD+
TXD– / RXD–

TXD+ / RXD+ B
Signal GND Signal GND

C
shield shield

* Termination resistors required at both ends of the


network receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-485 Multi-Drop Wiring Diagram (cont-d)
using DirectLogic pin numbers to illustrate
13 to 9 on the C-more touch panel 15-pin connector
to place the 120 internal resistor into the network. If
the cable impedance is different, then use an external
resistor matched to the cable impedance.
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-21
Chapter 6: PLC Communications

Allen-Bradley:
EA-MLOGIX-CBL
1 Allen-Bradley MicroLogix™ 1000/1100/1200/1400/1500 To C-more Touch
To AB MicroLogix RS-232
RS-232C (p/n EA-MLOGIX-CBL) Panel PLC Port

2 communication channel

3 1 = do not use
2 = Sig GND
Mini Din
8-pin Male Wiring Diagram 8 = do not use
15-pin
D-sub
(male) 15 = do not use
7 = do not use 14 = do not use

4
3 = do not use TXD 7 3 RXD 6 = do not use 15 13 = do not use
0.290”
4 = RXD 6 7 8
5 = Logic GND 12 = do not use
3 4 5
RXD 4 2
5 = do not use 1 2
TXD
4 = do not use 11 = do not use
6 = do not use GND 2 5 3 = RXD (232C) 10 = do not use
0.35”

5 7 = TXD
8 = do not use
DIA. Nonstandard
keying shield 1 2 = TXD (232C) 1
1 = Frame GND
9 = do not use

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6
EA-SLC-232-CBL
7 To PLC
9-Pin Port
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix,
FlexLogix, MicroLogix, DF1, RS-232C (p/n EA-SLC-232-CBL)
To C-more Touch
Panel PLC Port

8
9 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
1 = do not use 1 3 3
10
6 = do not use TXD RXD 6 = do not use 15 13 = do not use
2 = RXD 7 = do not use 5 = Logic GND
2 2 12 = do not use
3 = TXD 8 = do not use RXD TXD
4 = do not use 11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9

11 shield 1 2 = TXD (232C) 1


1 = Frame GND
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
9 = do not use

12
EA-PLC5-232-CBL
13 To PLC
25-Pin Port
Allen-Bradley PLC5 DF1
RS-232C (p/n EA-PLC5-232-CBL)
To C-more Touch
Panel PLC Port

14
Wiring Diagram
A 25-pin
D-sub
13 = do not use (male) 25 = do not use TXD 2
12 = do not use
3 RXD 8 = do not use
15-pin
D-sub
(male) 15 = do not use
25 24 = do not use 3 2 TXD 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD
B 10 = do not use
9 = do not use
8 = do not use
22 = do not use GND 7
21 = do not use
shield
5
1
6
5
=
=
do not
Logic
use
GND
4 = do not use
15 13 = do not use
12 = do not use
11 = do not use
7 = Signal GND 20 = do not use 3 = RXD (232C) 10 = do not use

C 6 = do not use
5 = do not use
4 = do not use
19 = do not use
18 = do not use
17 = do not use
2 = TXD (232C) 1
1 = Frame GND
9 = do not use

3 = RXD 16 = do not use

D 2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6-22 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

Allen-Bradley (cont’d): EA-DH485-CBL


To AB SLC500
DH-485 Port
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485
Point-to-Point
To C-more Touch
Panel PLC Port 1
RS-485A (p/n EA-DH485-CBL)

Wiring Diagram 2
RJ45 8-pin

1 = TXD/RXD+
2 = TXD/RXD–
Phone Plug
(8P8C)
TXD/RXD+ 1
13
9
Term.
RD+
15-pin
D-sub
8 = do not use (male) 15 = do not use
3
3 = do not use 2 10 7 = do not use 14 = do not use
4 = Signal GND
5 = LE
6 = do not use
TXD/RXD–
11
12
RD–
SD+
6 = LE
5 = Logic GND
4 = do not use
15 13 = Termination
12 = SD– (RS485)
11 = SD+ (RS485)
4
SD– 3 = do not use 10 = RD– (RS485)
5
7 = Signal GND
5 6 LE * 2 = do not use 1 9 = RD+ (RS485)
8 = do not use LE *
4 1 = Frame GND
GND
7 5 * Note: The LE signal is wired in the cable

6
GND
as shown, but not required for
shield 1 point-to-point communications.
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 9842 shielded cable or equivalent.

Allen-Bradley SLC500™, 5/01, /02, /03 DH-485/AIC to Multiple C-more Touch Panels 7
RS-485A (using C-more cable p/n EA-DH485-CBL)

Allen-Bradley DH-485 Link


8
SLC 500 Modular (See manufacturer’s litature for details.)
PLC Controller

DH-485 DH-485
9
10
Peripheral Peripheral
J2 J2

CPU CPU
J1 J1

Channel 1 must be Power Power


set to DH485.

AB 1747-AIC
DH485 Link Coupler
AB 1747-AIC
DH485 Link Coupler
11
AB 1747-C11 A
Cable 12
13
14
C-more
Touch Panel
C-more
Touch Panel
A
B
C-more
EA-DH485-CBL
Cable
C-more
EA-DH485-CBL
Cable
C
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network
using the AB DH485 Link Coupler, p/n 1747-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-23
Chapter 6: PLC Communications

Allen-Bradley (cont’d):
1 Allen-Bradley SLC500™ 5/03 DH-485/AIC to Multiple C-more Touch Panels
(using C-more cables p/n EA-MLOGIX-CBL, EA-SLC-232-CBL)

2 Allen-Bradley DH-485 Link


SLC 5/03 Modular (See manufacturer’s litature for details.)

3 PLC Controller

4 Channel 0 must be
set to DH485.

5 AB 1761-NET-AIC
AIC + Advanced
Interface Converter
AB 1761-NET-AIC
AIC + Advanced
Interface Converter

6 C-more
EA-MLOGIX-CBL
Cable

7 AB 1747-CP3
RS-232 Cable

8 To additional
C-more
Touch Panel

9 C-more
Touch Panel
C-more
Touch Panel

10
C-more
11 EA-MLOGIX-CBL
Cable
C-more
EA-SLC-232-CBL
Cable

12 Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the
AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.

13
14
A
B
C
D

6-24 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

Allen-Bradley (cont’d):
Multiple Allen-Bradley PLCs connected to multiple C-more Touch Panels
(using AB Ethernet Network Interface p/n 761-NET-ENI with EtherNet/IP protocol)
1
Allen-Bradley
SLC 5/03 Modular
Allen-Bradley
MicroLogix 1000
Allen-Bradley
MicroLogix 1500
PLC Controller
2
PLC Controller PLC Controller

3
4
5
AB mini DIN to D-shell AB mini DIN to mini DIN
cable p/n 1761-CBL-AP00 cable p/n 1761-CBL-AM00

6
ETHERNET
RS232
FAULT

Ethernet
TX/RX ETHERNET
RS232
FAULT

Hub or Switch
IP

10/100 Base-T
TX/RX
PWR

7
ETHERNET CABLE IP
RS232
FAULT
EXTERNAL
PWR

TX/RX CABLE

EXTERNAL

IP
AB 1761-NET-ENI

8
PWR

AB 1761-NET-ENI
CABLE

EXTERNAL

Ethernet/IP
Network
AB 1761-NET-ENI

9
C-more
Touch Panel 10
C-more
Touch Panel
11
12
13
14
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-25
Chapter 6: PLC Communications

Allen-Bradley (cont’d): User Constructed


1 To PLC
25-Pin Port
Allen Bradley PLC5 DF1
RS-422
To C-more
PLC Port

2
25-pin Wiring Diagram

3
15-pin
D-sub D-sub
13 = do not use (male) 25 = do not use TXD + 2 10 RD – 8 = do not use
12 = do not use (male) 15 = do not use
25 24 = do not use 3 12 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD + SD – 15 13 = do not use

4 10 = do not use
9 = do not use
8 = do not use
22 = do not use GND
21 = do not use
20 = do not use
TXD – 14
7 5
6 = do not use
5 = Logic GND
9 RD + 4 = do not use
12 = SD –
11 = SD +
7 = Signal GND 11 SD + 3 = do not use 10 = RD –
19 = do not use RXD – 16
5 6 = do not use
5 = do not use
4 = do not use
3 = RXD +
18 = do not use
17 = do not use
16 = RXD –
shield 1
2 = do not use 1
1 = Frame GND
9 = RD +

2 = TXD +
6 1 15 = do not use
1 = do not use 14 = TXD –
Notes:
1. Polarities must be swapped.

7 2. Handshaking is turned off


3. Use the above wiring diagram if you need to make your own cable. We recommend using 8103 shielded cable or equivalent.
4. Refer to the PLC-5 Programmable Controllers User Manual Switch Setting Reference for details on switch settings to define
the controller's serial port electrical interface.

8
9
10
11
12
13
14
A
B
C
D

6-26 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

GE: EA-90-30-CBL
To PLC
15-Pin Port
GE 90/30 and 90/70 15-pin D-sub port,
RS-422A (p/n EA-90-30-CBL)
To C-more Touch
Panel PLC Port 1
2
Wiring Diagram 13
15-pin Term. 15-pin
8 = CTS(B’)
7 = Logic GND
D-sub
(male)
15
15 = CTS(A’)
14 = do not use
SD(B)
SD(A)
13
12
9
10
RD+
D-sub
8 = do not use (male) 15 = do not use
RD– 7 = do not use 14 = do not use
3
6 = do not use 13 = SD(B) 15
11 11 SD+ 6 = do not use
4
5 = +5V 12 = SD(A) RD(B’) 13 = Termination
5 = Logic GND 12 = SD– (RS422)
4 = do not use 11 = RD(B’) RD(A’) 10 12 SD– 4 = do not use
3 = do not use 10 = RD(A’) 11 = SD+ (RS422)
GND 7 5 3 = do not use 10 = RD– (RS422)
2 = do not use 9 = do not use

5
2 = do not use 1 9 = RD+ (RS422)
1 = do not use 1 CTS(B’) 8
1 = Frame GND
CTS(A’) 15
+5V 5
shield 1

Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
6
GE VersaMax Micro: User Constructed 7
GE VersaMax Micro Port 1 To C-more Touch
To PLC
RJ45 Port 1 RS-232C
Panel PLC Port
8
RJ45 8-pin
Phone Plug Wiring Diagram
15-pin
D-sub
9
1 = RTS (8P8C) (male)
10
2 = CTS 8 = do not use 15 = do not use
TXD 4 3 RXD 7 = do not use
3 = RXD 15 14 = do not use
4 = TXD RXD 3 2 TXD 6 = donot use 13 = do not use
5 = DCD 8 5 5 = Logic GND 12 = do not use

11
6 = DTR GND 4 = do not use 11 = do not use
7 = +5V shield 1 3 = RXD (232C) 10 = do not use
8 = GND 2 = TXD (232C) 1 9 = do not use
1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
12
Mitsubishi: EA-MITSU-CBL
To PLC
25-Pin Port
Mitsubishi FX Series 25-pin D-sub port,
RS-422A (p/n EA-MITSU-CBL)
To C-more Touch
Panel PLC Port
13
14
13 = do not use
25-pin
D-sub
(male) 25 = do not use SD+ 3
Wiring Diagram 13 Term.
9 RD+
8 = do not use
15-pin
D-sub
(male) 15 = do not use
A
12 = do not use 25 24 = do not use SD– 16 10 RD– 7 = do not use

B
11 = do not use 23 = do not use 14 = do not use
15
10 = do not use 22 = do not use RD+ 2 11 SD+ 6 = do not use 13 = Termination
9 = do not use 21 = do not use RD– 15 5 = Logic GND 12 = SD– (RS422)
8 = do not use 12 SD–
20 = do not use 4 = do not use 11 = SD+ (RS422)
7 = Signal GND
C
7 5 3 = do not use 10 = RD– (RS422)
6 = do not use 19 = do not use GND
18 = do not use GND 4 2 = do not use 1 9 = RD+ (RS422)
5 = do not use 1 = Frame GND
4 = Signal GND 17 = do not use 1
3 = SD+ (RS422) 16 = SD– (RS422) shield
2 = RD+ (RS422) 1
1 = do not use
15 = RD– (RS422)
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-27
Chapter 6: PLC Communications

Mitsubishi(cont’d): EA-MITSU-CBL-1
1 To PLC
8-Pin Port
Mitsubishi FX Series 8-pin MINI-DIN,
RS-422A (p/n EA-MITSU-CBL-1)
To C-more Touch
Panel PLC Port

2 Mini Din Wiring Diagram 13 15-pin


Term.
8-pin Male D-sub
3 1 = RD– (RS-422)
2 = RD+ (RS-422)
3 = Sig GND 6 7 8
SD+
SD–
7
4
9
10
RD+
RD–
8 = do not use
7 = do not use
6 = do not use
(male)

15
15 = do not use
14 = do not use
13 = Termination
4 = SD– (RS-422) RD+ 2 11 SD+ 5 = Logic GND
4
12 = SD– (RS422)
3 4 5

5 = do not use 1 2
1 12
RD– SD– 4 = do not use 11 = SD+ (RS422)
6 = do not use
3 5 3 = do not use 10 = RD– (RS422)
7 = SD+ (RS-422) GND 2 = do not use 9 = RD+ (RS422)
8 = do not use 1 1

5 shield 1 = Frame GND


Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.

6 User Constructed
7 Mitsubishi Q02 / Q02H / Q06H / Q12H / Q25H Serial Driver
and QnA Serial Driver with Direct Connection to To C-more Touch
Panel PLC Port
To PLC the Serial Port on Q00 and Q01 CPU’s
6-Pin Port
8 RS-232C

9 1 = RXD (232C)
2 = TXD (232C)
Mini Din
6-pin Male Wiring Diagram
8 = do not use
15-pin
D-sub
(male) 15 = do not use
TXD 2 3 RXD 7 = do not use
3 = Logic GND 15 14 = do not use
10 4 = do not use
5 = do not use
6 = do not use
5
3
6
4
RXD
GND
1
3
2
5
TXD 6 = donot use
5 = Logic GND
4 = do not use
13 = do not use
12 = do not use
11 = do not use
1 2 1 3 = RXD (232C) 10 = do not use
11 shield
2 = TXD (232C) 1
1 = Frame GND
9 = do not use

Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

12 User Constructed
13 To PLC
9-Pin Port
Mitsubishi Q / QnA Serial PLC
QJ71C24N
To C-more Touch
Panel PLC Port
RS-232C
14
Wiring Diagram

A 9-pin
CD 1
15-pin
DTR 4
D-sub D-sub
B 1 = CD 1
(female)

6 = DSR RS
DSR 6
7
8 = do not use (male)
7 = do not use
6 = do not use 15
15 = do not use
14 = do not use
13 = do not use
2 = RXD 7 = RS 8 5 = Logic GND 12 = do not use
C 3 = TXD CS
8 = CS 3 3 4 = do not use 11 = do not use
4 = DTR 9 = do not use TXD RXD
3 = RXD (232C) 10 = do not use
5 = Signal GND 9 2 2
RXD TXD 2 = TXD (232C) 9 = do not use
1
1 = Frame GND
D GND 5 5
shield 1

Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

6-28 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

Omron:
EA-OMRON-CBL
To PLC
25-Pin Port
Omron Host Link (C200 Adapter, C500),
RS-232C (p/n EA-OMRON-CBL)
To C-more Touch
Panel PLC Port
1
2
25-pin Wiring Diagram

3
15-pin
D-sub D-sub
13 = do not use (male) 25 = do not use TXD 2 3 RXD 8 = do not use
12 = do not use (male) 15 = do not use
25 24 = do not use 3 2 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD TXD 15 13 = do not use
10 = do not use
9 = do not use
8 = do not use
22 = do not use GND 7
21 = do not use
20 = do not use RTS
4
5
6 = do not use
5 = Logic GND
4 = do not use
12 = do not use
11 = do not use
4
7 = Signal GND 3 = RXD (232C) 10 = do not use
19 = do not use CTS 5
6 = do not use
5 = CTS
4 = RTS
18 = do not use
17 = do not use shield 1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
5
3 = RXD 16 = do not use

6
2 = TXD 1 15 = do not use
1 = do not use 14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.

User Constructed 7
To PLC
9-Pin Port
Omron FINS (CQM1, CPM1, CPM2, C200, CJ1 & CS1)
RS-232C
To C-more Touch
Panel PLC Port 8
9-pin 15-pin
9
D-sub D-sub

1 = do not use
(male)
9
6 = do not use TXD 2
Wiring Diagram

3 RXD
8 = do not use (male)
7 = do not use
6 = do not use 15
15 = do not use
14 = do not use
13 = do not use
10
2 = TXD 7 = do not use 5 = Logic GND 12 = do not use

11
3 = RXD 3 2
8 = do not use RXD TXD 4 = do not use 11 = do not use
4 = RTS 9 = Signal GND SG 9 5 3 = RXD (232C) 10 = do not use
5 = CTS 1 2 = TXD (232C) 9 = do not use
RTS 4
1 = Frame GND 1
CTS 5
shield 1
12
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
13
User Constructed
To Peripheral Omron Host Link CQM1 using CQM1-CIF02 Peripheral Port Connecting Cable To C-more Touch
Panel PLC Port
14
Port Cable RS-232C
A
9-pin
D-sub
(male) Wiring Diagram 8 = do not use
7 = do not use
15-pin
D-sub
(male) 15 = do not use
14 = do not use
B
1 = do not use 9 6 = do not use
C
6 = do not use TXD 3 3 RXD 15 13 = do not use
2 = RXD 7 = do not use 5 = Logic GND 12 = do not use
3 = TXD 2 2
8 = do not use RXD TXD 4 = do not use 11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 1
D
2 = TXD (232C) 9 = do not use
shield 1 1 = Frame GND 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-29
Chapter 6: PLC Communications

Modicon ModBus RS-232:


User Constructed
1 To PLC
9-Pin Port
Modicon™ ModBus™, 984 CPU, Quanum 113 CPU
RS-232C
To C-more Touch
Panel PLC Port

2
9-pin 15-pin

3 1 = do not use
D-sub
(male)
9
Wiring Diagram
7 = do not use
D-sub
8 = do not use (male) 15 = do not use
14 = do not use
6 = DSR TXD 3 3 RXD 6 = do not use 15 13 = do not use

4
2 = RXD 7 = RTS 5 = Logic GND
2 2 12 = do not use
3 = TXD 8 = CTS RXD TXD
4 = do not use 11 = do not use
4 = DTR 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 1 2 = TXD (232C) 1
4 9 = do not use

5 DTR
DSR 6
7
1 = Frame GND

RTS

6 CTS 8
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

7 Modicon Micro Series:


User Constructed
8 To PLC
9-Pin Port
AEG Modicon™ Micro Series:
110 CPU 311-xx, 110 CPU 411-xx, 110 CPU 512-xx, 110 CPU 612-xx
To C-more Touch
Panel PLC Port

9 RS-232C

10 9-pin
D-sub
(female) Wiring Diagram
15-pin
D-sub
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
1 = do not use 1 2 3 6 = do not use 13 = do not use
11 6 = do not use TXD RXD 15
2 = TXD 7 = do not use 5 = Logic GND 12 = do not use
3 = RXD 3 2
8 = do not use RXD TXD 4 = do not use 11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 9 2 = TXD (232C)
12
9 = do not use
shield 1 1 = Frame GND 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

13 Modicon ModBus with RJ45: User Constructed


14 To PLC
RJ45 Port
Modicon™ ModBus™ with RJ45
RS-232C
To C-more Touch
Panel PLC Port

A RJ45 8-pin Wiring Diagram 15-pin


Phone Plug
B 1 = do not use
2 = do not use
3 = TXD
(8P8C) TXD
RXD
3
4
3
2
RXD
8 = do not use
TXD 7 = do not use
D-sub
(male) 15 = do not use
15 14 = do not use
4 = RXD GND 5 5 6 = donot use 13 = do not use

C 5 = Logic GND
6 = RTS
7 = CTS
RTS
CTS
6
7
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
8 = do not use 2 = TXD (232C) 1 9 = do not use

D shield 1 1 = Frame GND

Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.

6-30 ®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20
Chapter 6: PLC Communications

Siemens:
User Constructed
To PLC
9-Pin Port
Siemens S7-200 CPU Port 0 or 1
RS-485A
To C-more Touch
Panel PLC Port 1
2
Wiring Diagram 13
9-pin Term. 15-pin
D-sub
(male)
9
RS-485
Signal B
3 9
11
RD+
SD+
D-sub
8 = do not use (male) 15 = do not use
7 = do not use 14 = do not use
3
1 = Logic Com 6 = +5 VDC 15
6 = do not use 13 = Termination
4
2 = Logic Com RS-485 8 10 RD–
7 = +24 VDC Signal A 5 = Logic GND 12 = SD– (RS485)
3 = RS485 Sig B 8 = RS485 Sig A 12
4 = do not use SD– 4 = do not use 11 = SD+ (RS485)
9 = do not use Logic 5 5 3 = do not use 10 = RD– (RS485)
5 = Logic Com 1 Common

5
2 = do not use 1 9 = RD+ (RS485)
shield 1 1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect L19954 shielded cable or equivalent.

6
7
8
9
10
11
12
13
14
A
B
C
D

®
EA-USER-M Hardware User Manual, 3rd Ed, Rev A, 06/20 6-31

You might also like