AIB Instruction Book GHS1300 1900VSD 6996022310 Issue B ENG
AIB Instruction Book GHS1300 1900VSD 6996022310 Issue B ENG
AIB Instruction Book GHS1300 1900VSD 6996022310 Issue B ENG
Atlas Copco
Oil-sealed rotary screw vacuum pumps
GHS 1300 VSD+, GHS 1600 VSD+,
GHS 1900 VSD+, GHS 1300 VSD+ Turbo,
GHS 1600 VSD+ Turbo
Instruction Book
6996 0223 10
Issue B
1
Atlas Copco
Oil-sealed rotary screw vacuum pumps
Instruction book
Original instructions
Copyright notice
Any unauthorized use or copying of the contents or any part thereof is prohibited. This applies in
particular to trademarks, model denominations, part numbers and drawings.
This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as identified in the
Declaration of Conformity.
2019 - 07
Table of contents
1 Safety precautions ...................................................................................................................................... 7
4 Installation.................................................................................................................................................. 65
6996 0223 10 5
Instruction book
5 Options ....................................................................................................................................................... 74
7 Maintenance ............................................................................................................................................... 89
11 Disposal.................................................................................................................................................... 121
6 6996 0223 10
Instruction book
1 Safety precautions
Warning
Important note
1. The operator must employ safe working practices and observe all related work safety requirements
and regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter of the two
shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized, trained,
specialized personnel.
4. The vacuum pump is designed for handling atmospheric air only. No other gases, vapours or fumes
should be exposed to the vacuum pump intake or processed by the vacuum pump.
5. Before any maintenance, repair work, adjustment or any other non-routine checks:
• Stop the vacuum pump
• Press the emergency stop button
• Switch off the voltage
• Make sure that the pump system is at atmospheric pressure level.
• Lock Out - Tag Out (LOTO):
• Open the power isolating switch and lock it with a personal lock
• Tag the power isolating switch with the name of the service technician.
• On units powered by a frequency converter, wait 10 minutes before starting any electrical
repair.
• Never rely on indicator lamps or electrical door locks before maintenance work, always
disconnect and check with measuring device.
If the machine is equipped with an automatic restart after voltage failure function
and if this function is active, be aware that the machine will restart automatically
when the power is restored if it was running when the power was interrupted.
In a domestic environment, this product may cause radio interference in which case
supplementary mitigation measures are required.
6996 0223 10 7
Instruction book
1. The machine must only be lifted using suitable equipment in accordance with the applicable safety
regulations. Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to
dwell or stay in the risk zone under a lifted load. Lifting acceleration and deceleration must be kept
within safe limits. Wear a safety helmet when working in the area of overhead or lifting equipment.
2. The unit is designed for indoor use. If the unit is installed outdoors, special precautions must be taken;
consult Atlas Copco.
3. Place the machine where the ambient air is as cool and clean as possible. Never obstruct the cooling
air inlet. Water handling capacity is detailed in the specification.
4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting the pipes.
5. Vacuum connection and discharge pipes must be of correct size and suitable for the working pressure
and temperature. Never use frayed, damaged or worn hoses. Distribution pipes and connections must
be of the correct size and suitable for the working pressure.
6. The aspirated air must be free of flammable fumes, vapors and particles, e.g. paint solvents that can
lead to internal fire or explosion. Follow the material safety guidelines.
7. The external force extended on the inlet and outlet connection is limited to 30 kg; the connection pipes
must be free of strain. No supports may be fixed to the canopy of the machine.
8. If remote control is installed, the machine must bear a clear sign stating:
DANGER: This machine is remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and that the isolating switch is open and
locked before any maintenance or repair. As a further safeguard, persons switching on remotely
controlled machines shall take adequate precautions to ensure that there is no one checking or
working on the machine. To this end, a suitable notice shall be affixed to the starting equipment.
9. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is available
and that the exhausted air does not recirculate to the vacuum pump air inlet or cooling air inlet.
10. The electrical connections must correspond to the applicable codes. The machines must be earthed
and protected against short circuits by fuses in all phases. A lockable power isolating switch must be
installed near the vacuum pump.
11. On machines with automatic start/stop system or if the automatic restart function after voltage failure is
activated, a sign stating, "This machine may start without warning" must be affixed near the instrument
panel.
12. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
13. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be accidentally
touched by personnel in normal operation must be guarded or insulated. Other high temperature piping
must be clearly marked.
14. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
8 6996 0223 10
Instruction book
15. Pump outlet air contains traces of oil mist. Ensure compatibility with the working environment.
16. Any vacuum pump placed in an application with inlet gas stream temperatures above the published
maximum temperature should be approved by Atlas Copco prior to start-up.
17. For water-cooled machines, the cooling water system installed outside the machine has to be
protected by a safety device with set pressure according to the maximum cooling water inlet pressure.
Also consult sections Safety precautions during operation and Safety precautions
during maintenance or repair.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment;
hence some statements may not apply to your machine.
1. Never touch any piping or components of the vacuum pump during operation.
2. Use only the correct type and size of hose end fittings and connections. Make sure that a hose is fully
depressurized before disconnecting it.
3. Persons switching on remotely controlled machines shall take adequate precautions to ensure that
there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to
the remote start equipment.
4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes, vapours or
particles.
5. Never operate the machine below or in excess of its limit ratings.
6. Keep all bodywork doors shut during operation. The doors may be opened for short periods only, e.g.
to carry out routine checks. Wear ear protectors when opening a door.
7. People staying in environments or rooms where the sound pressure level reaches or exceeds 80 dB(A)
shall wear ear protectors.
8. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not rubbing
• There are no leaks
• All fasteners are tight
• All electrical leads are secure and in good order
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in good repair,
free of wear or abuse
9. If warm cooling air from vacuum pumps is used in air heating systems, e.g. to warm up a workroom,
take precautions against air pollution and possible contamination of the breathing air.
10. Do not remove any of, or tamper with, the sound-damping material.
11. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
12. The oil separator tank can be slightly pressurized. Do not open and do not leave oil filler or drain plugs
open during operation.
6996 0223 10 9
Instruction book
Also consult sections Safety precautions during installation and Safety precautions
during maintenance or repair. These precautions apply to machinery processing or
consuming air or inert gas. Processing of any other gas requires additional safety
precautions typical to the application which are not included herein.
Some precautions are general and cover several machine types and equipment;
hence some statements may not apply to your machine.
10 6996 0223 10
Instruction book
16. Every time the separator element is renewed, examine the discharge and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
17. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering
them, e.g. when steam cleaning.
18. Make sure that all sound damping material and vibration dampers, e.g. damping material on the
bodywork and in the air inlet and outlet systems of the vacuum pump are in good condition. If
damaged, replace it by genuine material from the manufacturer to prevent the sound pressure level
from increasing.
19. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
20. Faults or wearing of seals may cause oil lubricant leaks. Avoid dispersion in soil and pollution of other
materials.
Also consult sections Safety precautions during installation and Safety precautions
during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment;
hence some statements may not apply to your machine.
6996 0223 10 11
Instruction book
2 General description
Reference Designation
1 Pressure
2 Absolute vacuum
3 Typical GHS pump working range (400 mbar(a) – 10 mbar(a))
4 Atmospheric pressure
Atmospheric pressure at sea level is roughly 1 bar or 1000 mbar. A typical working range for the GHS pumps
is 400 mbar(a) to 10 mbar(a). From the illustration it can be seen clearly that this range is also equivalent to
-600 mbar(e) and -990 mbar(e).
It is important to understand which type of reference is required before selecting a pressure instrument for
measuring the vacuum. It must be noted that the distinction doesn't matter for a pressure difference (delta P;
e.g. pressure loss), since it is always the result of subtracting 2 pressures (whether stated as absolute or
effective pressures).
12 6996 0223 10
Instruction book
2.2 Introduction
The GHS 1300 VSD+ up to GHS 1900 VSD+ are single-stage, oil-sealed screw vacuum pumps driven by
an electric motor.
The vacuum pumps are controlled by the Atlas Copco Elektronikon® Graphic regulator (5).
The regulator is fitted to the front door. An electric cabinet (7) comprising fuses, transformers, relays, etc. is
located behind this door.
The vacuum pumps use VSD (Variable Speed Drive) technology. This means: automatic adjustment of the
motor speed, depending on the process demand.
The vacuum pumps are air-cooled and are enclosed in a sound-insulated bodywork.
Front view
6996 0223 10 13
Instruction book
Reference Name
1 Discharge connection
2 Inlet connection
3 Oil cooler
4 Cable entry
5 Elektronikon® graphic controller
6 Emergency stop button
14 6996 0223 10
Instruction book
Reference Name
7 Electric cabinet
8 Air intake filter
9 Oil filter
10 Thermostatic bypass valve
11 Oil separator tank
12 Vacuum control valve
13 Element
14 Drive motor
15 Cooling fan
6996 0223 10 15
Instruction book
Air flow
Air comes in through air intake filter (8) and vacuum control valve (12) and is displaced by the vacuum pump
element (13).
A mixture of air and oil flows into the oil separator tank (11).
After passing the air/oil separator filter, clean air, conditioned to a few parts per million, is discharged
through the outlet.
Oil system
The oil separator tank (11) removes most of the oil from the air/oil mixture by centrifugal action. The oil
separator (OS) removes the remaining oil. The oil collects in the lower part of the oil separator tank (11)
which serves as oil tank.
The oil system has a thermostatic bypass valve (10). When the oil temperature is below 80 °C (176 °F)
(87°C (189° F) for optional high-water handling capacity versions), the bypass valve shuts off the oil
supply from the oil cooler (3).
Air pressure forces the oil from oil separator tank through the oil filter (9). The oil cooler (3) is bypassed.
When the oil temperature has increased up to 80°C (176 °F) (87°C (189° F) for optional high-water
handling capacity versions), bypass valve (BV) starts opening the supply from the oil cooler (3). At
approx. 95°C (203 °F) (104°C (219° F) for optional high water handling capacity versions), all the oil
flows through the oil cooler. The filtered oil flows into the vacuum pump element (13).
Cooling
The cooling system has an oil cooler (3).
The fan (15) blows air over the coolers. This fan is set to run on or off, depending on the operating
conditions, according to a specific algorithm.
When discharge piping is used, water in the discharge air can condense in the piping and is accumulated
in the collector of the outlet pipe, where a drain point (Dr) is available.
When the pump leaves the factory, this drain point is connected with the external valve (EV). Preventing
condensate collection in the oil separator will extend oil life.
Consult local regulations, which are applicable for water drainage.
16 6996 0223 10
Instruction book
Electrical diagrams
You can find the complete electrical diagram inside the electric cabinet.
6996 0223 10 17
Instruction book
Introduction
18 6996 0223 10
Instruction book
Shut-down
Several sensors are provided on the vacuum pump. If one of the measurements succeeds the
programmed shut down level, the vacuum pump will be stopped. This will be indicated on display (1) and
general alarm LED (2) will blink.
Remedy the trouble and reset the message. See also the Inputs menu.
Shut-down warning
Warning
Service warning
A number of service operations are grouped (called Service Plans). Each service plan has a programmed
time interval. If a time interval is exceeded, a message will appear on display (1) to warn the operator to
carry out the service actions belonging to that service plan.
The regulator has a built-in function to automatically restart the vacuum pump if the voltage is restored
after voltage failure. For vacuum pumps leaving the factory, this function is made inactive. If desired, the
function can be activated. Consult the Atlas Copco customer center.
If activated and provided the regulator was in the automatic operation mode, the
vacuum pump will automatically restart if the supply voltage to the module is
restored.
6996 0223 10 19
Instruction book
Elektronikon regulator
Elektronikon regulator
20 6996 0223 10
Instruction book
Status icons
Motor stopped
Local start/stop
Network control
Emergency stop
Warning
6996 0223 10 21
Instruction book
Not valid
Input icons
Icon Description
Pressure
Temperature
Digital input
Special protection
System icons
Icon Description
Fan
Frequency converter
Motor
Network problem
General alarm
22 6996 0223 10
Instruction book
Menu icons
Icon Description
Inputs
Outputs
Counters
Test
Settings
Service
Saved data
Network
Regulation
Info
General
Navigation arrows
Icon Description
Up
Down
6996 0223 10 23
Instruction book
Function
The Main screen is the screen that is shown automatically when the voltage is switched on and one of the
keys is pushed. It is switched off automatically after a few minutes when no keys are pushed.
Typically, 5 different main screen views can be chosen:
1. Two value lines
2. Four value lines
3. Chart (High resolution)
4. Chart (Medium resolution)
5. Chart (Low resolution)
24 6996 0223 10
Instruction book
• Section A shows information regarding the vacuum pump operation (e.g. the Inlet pressure or the
temperature at the vacuum pump outlet). On Vacuum pumps with a frequency converter, the load
degree (flow) is given in % of the maximum flow at the actual inlet pressure.
6996 0223 10 25
Instruction book
• Section B shows Status icons. Following icon types are shown in this field:
• Fixed icons
These icons are always shown in the main screen and cannot be selected by the cursor (e.g.
vacuum pump stopped or running, vacuum pump status (running, running unloaded or motor
stopped).
• Optional icons
These icons are only shown if their corresponding function is activated (e.g. week timer,
automatic restart after voltage failure, etc.)
• Pop up icons
These icons pop up if an abnormal condition occurs (warnings, shutdowns, service)
To call up more information about the icons shown, select the icon concerned using the scroll
keys and press the enter key.
• Section C is called the Status bar.
This bar shows the text that corresponds to the selected icon.
• Section D shows the Action buttons. These buttons are used:
• To call up or program settings
• To reset a motor overload, service message or emergency stop
• To have access to all data collected by the regulator
The function of the buttons depends on the displayed menu. The most common functions are:
Designation Function
Menu To go to the menu
Modify To modify programmable settings
Reset To reset a timer or message
To activate an action button, highlight the button by using the Scroll keys and press the Enter key. To go
back to the previous menu, press the Escape key.
Chart views
Instead of viewing values, it is also possible to view a graph of one of the input signals (see section Inputs
menu) in function of the time.
When Chart (High Resolution) is selected, the chart shows the variation of the selected input (in this case
the pressure) per minute. Also, the instantaneous value is displayed. The screen shows the last 4 minutes.
The switch button (icon) for selecting other screens is changed into a small Chart and is highlighted
(active). When the Chart (Medium Resolution) is selected, the chart shows the variation of the selected
input per hour. The screen shows the last 4 hours.
When the Chart (Low Resolution) is selected, the chart shows the variation of the selected input per day.
The screen shows the evolution over the last 10 days.
26 6996 0223 10
Instruction book
To change between the different screen layouts, select the far-right icon in the control icons line (see value
lines display icon or chart display icon in section Icons used) and press the Enter key. A screen similar to
the one below opens:
Select the layout required and press the Enter key. See also section Inputs menu.
Control panel
When the voltage is switched on, the main screen is shown automatically.
6996 0223 10 27
Instruction book
• The screen shows a number of icons. Each icon indicates a menu item. By default, the pressure
settings (Regulation) icon is selected. The status bar shows the name of the menu that corresponds
with the selected icon.
• Use the Scroll keys to select an icon.
• Press the Escape key to return to the Main screen.
Function
• To display the actual value of the measured data (analog inputs) and the status of the digital inputs
(e.g. emergency stop contact, motor overload relay, etc.).
• To select the digital input to be shown on the chart in the main screen.
28 6996 0223 10
Instruction book
Procedure.
• Move the cursor to the action button menu and press the enter key, following screen appears:
(i) Menu
(ii) Regulation
• Using the scroll keys, move the cursor to the inputs icon (see above, section Menu icon)
• Press the enter key, a screen similar to the one below appears:
(i) Inputs
(ii) Pump discharge
(iii) Inlet pressure
(iv) Emergency stop
(v) Pressure setting selection
• The screen shows a list of all inputs with their corresponding icons and readings.
• If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown icon
respectively (i.e. the Stop icon and the Warning icon in the screen shown above).
6996 0223 10 29
Instruction book
A small chart icon, shown below an item in the list means that the input signal is shown on the chart
at the main screen. Any analog input can be selected.
With the Modify button active (light grey background in above screen), press the Enter button on the
controller. A screen similar to the one below appears:
The first item in the list is highlighted. In this example, the inlet pressure is selected (chart icon). To
change, press the Enter button again: a pop-up window opens:
Press Enter again to remove this input from the chart. Another confirmation pop-up opens:
30 6996 0223 10
Instruction book
(i)
Function
To call up information regarding the actually measured data and the status of some outputs such as the
motor overload protection.
Procedure
Starting from the Main screen (see Main screen):
• Move the cursor to the action button Menu and press the enter key (2), following screen appears:
6996 0223 10 31
Instruction book
(i) Menu
(ii) Regulation
• Move the cursor to the outputs icon (see above, section Menu icon, using the scroll keys (1)
• Press the enter key (2), a screen similar to the one below appears:
(i) Outputs
• The screen shows a list of all output switches and their corresponding icons and readings.
• If an input is in warning or shut down, the original icon is replaced by the warning or shut down
icon respectively.
32 6996 0223 10
Instruction book
3.8 Counters
Control panel
Function
To call up:
• The running hours
• The number of motor starts
• The number of hours that the regulator has been powered up
• Fan starts
• Emergency stops
Procedure
• Starting from the Main screen (see Main screen):
• Move the cursor to the action button menu and press the enter key (2), following screen appears:
(i) Menu
(ii) Regulation
• Using the scroll keys, move the cursor to the counters icon (see above, section Menu icon)
• Press the enter key, following screen appears:
6996 0223 10 33
Instruction book
(i) Counters
(ii) Running hours
(iii) Motor starts
(iv) Load relay
VSD 1-20 % rpm in % (the percentage of the time during which the motor speed was
(v)
between 1 and 20 %)
• The screen shows a list of all counters with their actual readings.
Function
To select the control mode, i.e. whether the vacuum pump is in local control, remote control or controlled
via a local area network (LAN).
34 6996 0223 10
Instruction book
Procedure
Starting from the main screen, make sure the button menu (iv) is selected:
Next, use the scroll buttons to go to the regulation icon (ii) and press the enter button:
After selecting the required regulation mode, press the enter button on the controller to confirm your
selection. The new setting is now visible on the main screen. See section Icons used for the meaning of
the icons.
6996 0223 10 35
Instruction book
Function
• To reset the service plans which are carried out.
• To check when the next service plans are to be carried out.
• To find out which service plans were carried out in the past.
• To modify the programmed service intervals.
Procedure
Starting from the Main screen,
• Move the cursor to the action button menu and press the Enter key. Following screen appears:
• Using the Scroll keys, move the cursor to the Service icon (see above, section Menu icon).
• Press the Enter key. Following screen appears:
36 6996 0223 10
Instruction book
(i) Service
(ii) Overview
(iii) Service plan
(iv) Next service
(v) History
• Scroll through the items to select the desired item and press the Enter key to see the details as
explained below.
Overview
(i) Overview
(ii) Running hours
(iii) Real time hours
(iv) Reset
6996 0223 10 37
Instruction book
Service plans
A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a
number of service actions to be carried out at the time intervals programmed in the Elektronikon®
controller. When a service plan interval is reached, a message will appear on the screen. After carrying out
the service actions related to the indicated levels, the timers must be reset.
From the Service menu above, select Service plan (3) and press Enter. Following screen appears:
Dependent on the operating conditions, it can be necessary to modify the service intervals. (By default, the
service plan in Elektronikon controller is for normal application and needs to be changed when running in
medium or harsh applications). To do so, use the Scroll keys to select the value to be modified. A screen
similar to the one below appears:
Modify the value as required using the arrow or scroll key and press the Enter key to confirm.
38 6996 0223 10
Instruction book
Next service
In the example above, the A Service level is programmed at 4000 running hours, of which 0 hours have
passed.
History
The History screen shows a list of all service actions done in the past, sorted by date. The date at the top
is the most recent service action. To see the details of a completed service action (e.g. service level,
running hours or real-time hours), use the Scroll keys to select the desired action and press the Enter key.
6996 0223 10 39
Instruction book
Function
On vacuum pumps with a frequency converter driven main motor, it is possible to program two different set
points. This menu is also used to select the active set point.
Procedure
Starting from the Main screen,
• Highlight the action key Menu using the Scroll keys and press the Enter key. Following screen
appears:
(i) Menu
(ii) Regulation
• Activate the menu by pressing the enter key. A screen similar to the one below appears:
Text on figures
(i) Regulation
(ii) setpoint 1
(iii) Indirect stop level 1
(iv) setpoint
(v) Indirect stop level 2
(vi) Modify
• The screen shows the actual settings.
To modify the settings, move the cursor to the action button modify and press the Enter key. Following
screen appears:
40 6996 0223 10
Instruction book
• The first line of the screen is highlighted. Use the Scroll keys (1) to highlight the setting to be modified
and press the Enter key (2). Following screen appears:
The upper and lower limit of the setting is shown in grey, the actual setting is shown in black. Use the
Scroll keys to modify the settings as required and press the Enter key to accept. If necessary, change the
other settings as required in the same way as described above.
Indirect stop: occurs when the pressure decreases to the pre-set Indirect stop setpoint (= setpoint minus
Indirect stop level). The motor will decelerate to minimum speed and the inlet valve will close.
Both settings (Indirect stop level and direct stop level) are programmable, see section Programmable
settings.
6996 0223 10 41
Instruction book
Function
• Using the Scroll keys, move the cursor to the Event History icon (see section Menu icon)
• The list of last shut-down and emergency stop cases is shown.
• Scroll through the items to select the desired shut-down or emergency stop event.
• Press the Enter key to find the date, time and other data reflecting the status of the vacuum pump
when that shut-down or emergency stop occurred.
42 6996 0223 10
Instruction book
Control panel
Function
Procedure
• Next, move the cursor to the Settings icon (see above, section menu icon). using the Scroll keys.
• Press the Enter key. Following screen appears:
6996 0223 10 43
Instruction book
This screen shows again a number of icons. By default, the User Password icon is selected. The status bar
shows the description that corresponds with the selected icon. Each icon covers one or more items, such
as:
• Access level
• Elements
• Fan
• Converter(s)
• Motor/Starter
• General
• Automatic restart after voltage failure (ARAVF)
• Network
• Regulation
• Remote
For adapting certain parameters, a password may be necessary.
Example: Selecting the General Settings icon gives the possibility to change e.g. the language, the date,
the date format, etc.
(i) General
(ii) Language used
(iii) Time
(iv) Date
(v) Date format
(vi) Modify
• To modify, select the modify button using the Scroll keys and press the Enter key.
• A screen similar to the one above is shown, the first item (Language) is highlighted. Use the arrow key
or the Scroll key to select the setting to be modified and press the Enter key.
44 6996 0223 10
Instruction book
• A pop-up screen appears. Use the arrow key to select the required value and press the Enter key to
confirm.
In the setting menu, it is possible to adjust:
- Runtime at minimum pressure- gas ballast (automatic - manual)
For Humid version pumps:
- Maximum pre- purge time
- Maximum pre- purge time during Operation
- Post purge time
- Manual purge time
Control panel
6996 0223 10 45
Instruction book
Function
Procedure
• Using the Scroll keys, move the cursor to the Info icon (see above, section Menu icon).
• Press the Enter key. The Atlas Copco internet address appears on the screen.
Control panel
46 6996 0223 10
Instruction book
Function
Important remark:
In the Elektronikon you can select different timers on one day. (up to 8 actions). It is
however not possible to program 2 actions at the same time. The solution: leave at
least 1 minute in between 2 actions.
Example: Start vacuum pump: 5.00 a.m., Pressure setpoint 2: 5.01 a.m. (or later).
Procedure
Starting from the Main screen (see Main screen),
• Move the cursor to the action button Menu and press the Enter key. Use the Scroll buttons to select
the Timer icon.
(1) Menu
(2) Week Timer
• Press the Enter key on the controller. Following screen appears:
6996 0223 10 47
Instruction book
The first item in this list is highlighted in red. Select the item requested and press the Enter key on the
controller to modify.
• A new window opens. The Modify action button is selected. Press the enter button on the controller to
create an action.
(1) Monday
(2) Modify
• A new pop-up window opens. Select an action from this list by using the Scroll keys on the controller.
When ready press the Enter key to confirm.
48 6996 0223 10
Instruction book
(1) Monday
(2) Actions
(3) Remove
(4) Start
(5) Stop
(6) Pressure setpoint 1
(7) Modify
• A new window opens. The action is now visible in the first day of the week.
(1) Monday
(2) Start
(3) Save
(4) Modify
• A pop-up window opens. Use the or key of Scroll keys to modify the values of the hours. Use the
or Scroll keys to go to the minutes.
(1) Monday
(2) Start
(3) Save
(4) Modify
6996 0223 10 49
Instruction book
• A new pop-up window opens. Use the Scroll keys on the controller to select the correct actions. Press
the Enter key to confirm.
(1) Monday
(3) Are you sure?
(4) No
(5) Yes
(6) Save
(7) Modify
50 6996 0223 10
Instruction book
6996 0223 10 51
Instruction book
• A new window opens. Select Week 1 to set the Week Timer active.
• Press the Escape key on the controller to leave this window. The status shows that week 1 is active.
52 6996 0223 10
Instruction book
• This timer is used when the week timer is set and for certain reasons the Vacuum pump must
continue working, for example, 1 hour, it can be set in this screen. This timer is prior to the Week
Timer action.
6996 0223 10 53
Instruction book
Function
If the password option is activated, it is impossible for not authorized persons to modify any setting.
Procedure
• Using the Scroll keys, select the Settings icon (see section Modifying general settings)
• Press the Enter key. Following screen appears:
54 6996 0223 10
Instruction book
• Move the cursor to the Password icon (see above, section Menu icon)
• Select Modify using the Scroll keys and press the Enter key. Next, modify the password as required.
6996 0223 10 55
Instruction book
56 6996 0223 10
Instruction book
• After selecting TCP/IPv4 click on the properties button to change the settings.
6996 0223 10 57
Instruction book
• Go to ‘Settings
58 6996 0223 10
Instruction book
• Go to ‘Network’
• Go to ‘Ethernet
• Adapt IP address
• Adapt Gateway address
• Adapt Subnet mask
• Switch ‘On’ the Ethernet communication again
• Wait some minutes so the LAN network can connect to the Elektronikon Mk5.
6996 0223 10 59
Instruction book
All screen shorts are indicative. The number of displayed fields depends on the
selected.
Navigation options
The banner shows the compressor type and the language selector
In this example three languages are installed on the controller
60 6996 0223 10
Instruction book
On the left site of the interface you can find the navigation menu.
If a license for ESi is foreseen, the menu contains 3 buttons.
• Compressor: shows all compressor settings.
• Es: shows the ESi status if a license is provided.
• Preferences: Change temperature and pressure unit.
Compressor settings
All compressor settings can be displayed or hidden. Put a mark in front of each point of interest and it will
be displayed.
Only the machine status is fixed and cannot be removed from the main screen.
Analog Inputs
Counters
Counters give an overview of all actual counters from controller and compressor.
Info Status
Machine status is always shown on the web interface
6996 0223 10 61
Instruction book
Digital Inputs
Digital Outputs
Special Protections
Service Plan
62 6996 0223 10
Instruction book
Parameters
Minimum Factory Maximum
Units
setting setting setting
Run time a minimum pressure sec 0 5 10
Maximum pre- purge time min 1 15 20
Maximum post-purge time min 1 30 180
Maximum pre- purge time during
sec 1 120 600
operation
Manual purge time min 1 30 120
Fan motor starts per day (air-
- - -
cooled vacuum pumps)
ES post purge time min 1 30 180
Protections
Minimum Maximum
Units Warning Shutdown
setting setting
Vacuum pump element outlet
temperature (shut-down warning °C 110 112 120 120
level)
Vacuum pump element outlet
temperature (shut-down warning °F 230 234 248 248
level)
Service plan
The built-in service timers will give a Service warning message after their respective pre-programmed time
interval has elapsed.
For specific data, see section Preventive Maintenance.
6996 0223 10 63
Instruction book
Consult Atlas Copco if a timer setting needs to be changed. The intervals must not exceed the nominal
intervals and must coincide logically. See section modifying general settings.
Terminology
Term Explanation
Automatic Restart After Voltage Failure. See section Elektronikon graphic
ARAVF
controller.
The period within which the voltage must be restored to have an automatic restart.
Power recovery
Accessible if the automatic restart is activated.
time
To activate the automatic restart function, consult Atlas Copco.
This parameter allows to programme that not all vacuum pumps are restarted at the
Restart delay
same time after a power failure (ARAVF active).
The recommended minimum setting is 110 °C (230 °F). For testing the temperature
sensor, the setting can be decreased to 50 °C (122 °F). Reset the value after
Vacuum pump testing. The regulator does not accept inconsistent settings, e.g. if the warning level
element outlet is programmed at 95 °C (203 °F), the minimum limit for the shut-down level
changes to 96 °C (204 °F). The recommended difference between the warning level
and shut-down level is 10 °C (18 °F).
The time period during which the warning signal must exist before the warning
Delay at signal
message appears.
The time period after starting, which must expire before generating a warning. The
Delay at start
setting should be less than the setting for the delay at signal.
Minimum stop Once the Vacuum pump has automatically stopped, it will remain stopped for the
time minimum stop time, whatever happens with the system pressure.
Proportional band The settings for the proportional band and integration time are determined by
and integration experiment. Altering these settings may damage the vacuum pump. Consult Atlas
time Copco.
64 6996 0223 10
Instruction book
4 Installation
6996 0223 10 65
Instruction book
66 6996 0223 10
Instruction book
1) Location:
Locate the vacuum pump on a level surface that is clean, well lit, well ventilated and capable taking the
weight of the pump. The entire length of the frame base must be supported. Shim where necessary (do not
use wood).
Ambient temperature should not exceed temperatures listed on the specifications.
All models are intended for indoor installation.
Do not locate the unit where the hot exhaust air from other vacuum pumps or heat generating equipment
may be drawn into the unit. Never restrict the flow of exhaust air from the fluid cooler.
The heated exhaust air must be exhausted to the outside to prevent high ambient conditions in the room.
Allow sufficient space (1 m of clearance on all sides and top of the vacuum pump) for safe installation,
inspection and maintenance.
2) Piping connections:
The vacuum distribution and piping system, including the vacuum pump and all related components, must
be designed in accordance with generally accepted engineering practices. For instance, inlet pipe work
should slope away from the vacuum pump. Improperly designed distribution systems can cause damage to
the vacuum pump. Exhaust piping should be installed in such a manner as to not create additional back
pressure on the vacuum pump. Also, the exhaust piping should be installed sloping away from the vacuum
pump.
A drip leg with drain point provision is foreseen available inside the vacuum pump, to prevent condensate
from running back into the fluid reservoir.
Care must be taken to avoid assembling the piping in a strain with the vacuum pump.
It is very important to use adequate pipe diameter for the vacuum network. The combination of restrictive
pipe diameter and long pipe runs can create significant pressure drop. A rule of thumb on single vacuum
pump installations: maintain the diameter of the vacuum pump inlet as far into the process as possible.
It is recommended to install an isolation valve at the inlet of the vacuum pump, to isolate the pump from
vacuum distribution and piping system before performing maintenance.
The discharge air can run up to 120 °C (248 °F), piping should be suitable to handle this temperature.
3) Ventilation:
The inlet grid(s) and ventilation fan should be installed in such a way that any recirculation of cooling air to
the inlet grating of the vacuum pump is avoided. The air velocity to the grid(s) has to be limited to 5m/s.
The maximum air temperature at intake opening is 46°C (115°F), (minimum 0°C / 32°F)
6996 0223 10 67
Instruction book
Ventilation alternative 1 and 3: The required ventilation to limit vacuum pump room temperature can be
calculated from:
Qv = SF * Pnom / (1.21 * dT)
Where:
Qv = Required cooling air flow (m³/s)
SF= Service factor of Motor (-)
Pnom = Nominal motor power of vacuum pump (kW)
dT= Temperature increase in vacuum pump room (°C)
Ventilation alternative 2 and 4: The fan capacity should match the vacuum pump fan capacity at a
pressure head equal to the pressure drop caused by cooling air ducts.
Maximum allowable pressure drop in ducting before or after the vacuum pump = 10 Pa.
Safety
Apply all relevant safety precautions, including those mentioned in this book.
Outdoor/altitude operation
The vacuum pumps are designed according to IP2X classification. The electrical cabinet and motor are
designed according to IP54 classification. If the unit is installed outdoors, special precautions must be
taken; consult Atlas Copco.
The vacuum pumps can only be used in temperatures above 0 °C (+32 °F). If frost might occur, the
appropriate measures should be taken to avoid damage to the machine and its ancillary equipment. In this
case, consult Atlas Copco.
Also, if operating above 1000 m (3300 ft.), consult Atlas Copco.
Moving/lifting
The vacuum pumps can be moved by a lift truck using the slots in the frame. Take care not to damage the
bodywork during lifting or transport.
68 6996 0223 10
Instruction book
Lifting slots
Before lifting, reinstall the transport securing bolts. Make sure that the forks protrude from the other side of
the frame. The vacuum pumps can also be lifted after inserting beams in the slots.
Make sure that the beams cannot slide and that they protrude from the frame equally. The chains must be
held parallel to the bodywork by chain spreaders in order not to damage the Vacuum pump. The lifting
equipment must be placed in such a way that the vacuum pump is lifted perpendicularly. Lift gently and
avoid twisting.
It is not allowed to lift the Vacuum pump if the canopy parts or lifting supports are
not completely installed. When the vacuum pump is being lifted, it is also forbidden
to come under the load or to perform maintenance activities to it.
Acclimatization
When moving the vacuum pump into an installation room, condensation can occur on
some components.
To avoid the dew from harming the electrical components, ensure at least 2 hours of
acclimatization before switching on the vacuum pump.
Most vacuum pump are designed for use in TT/TN networks and are intended for
industrial environments where the electrical supply is separated from the
residential/commercial supply network.
To use the machine in light industrial, commercial or residential environments with a
shared supply network or in an IT network, extra measures can be required: contact
Atlas Copco.
6996 0223 10 69
Instruction book
Reference Designation
1 Customer’s installation
2 Vacuum pump motor
70 6996 0223 10
Instruction book
Note
The complete electrical diagram can be found in the electrical cubicle.
Description
You find the correct position for the electrical connection on the Dimension
drawings.
To preserve the protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper cable
gland when connecting the supply cable to the vacuum pump.
Mount the transformer bridge on the primary winding side of the transformer, mounted inside the electrical
cubicle, according to the scheme indicated on the transformer (also shown here) for the applicable supply
voltage. GHS pumps leave the factory with 400V supply voltage setting.
6996 0223 10 71
Instruction book
Have the modifications checked by Atlas Copco. Stop the vacuum pump and switch
off the voltage before connecting external equipment.
Only potential-free contacts are allowed.
• LAN control: The vacuum pump is controlled via a local network. Consult Atlas Copco.
Vacuum pump status indication
The Elektronikon controller is provided with potential-free auxiliary NO contacts (NO = normally open)
(K07, K08 and K09) for remote indication of:
• Manual or automatic operation (K07)
• Warning condition (K08)
• Shut-down condition (K09)
Maximum contact load: 10 A / 250 V AC.
Stop the vacuum pump and switch off the voltage before connecting external equipment. Consult Atlas
Copco.
72 6996 0223 10
Instruction book
4.4 Pictographs
Pictographs
Reference Designation
1 Switch off the voltage and depressurize the vacuum pump before starting maintenance
or Repairs
2 Lightly oil the gasket of the oil filter, screw it on and tighten by hand (approx. half a turn)
3 Warning, hot surface
4 Stop the vacuum pump before cleaning the coolers
5 Warning, voltage
6 Switch off the voltage and wait at least 10 minutes before maintenance
7 If the rotation direction is wrong, open the isolating switch in the voltage supply line and
reverse two incoming electric lines
6996 0223 10 73
Instruction book
5 Options
74 6996 0223 10
Instruction book
Reference Description
1 Water inlet pipe
2 Water outlet pipe
3 Oil drain valve
4 Oil line from vacuum pump oil separator vessel to ER unit
5 Oil line from ER unit to oil filter housing
BV2 Location of heat exchanger by-pass valve (BV2)
HE Heat exchanger
AR Oil separator vessel
Field installation
The main components are assembled ex-factory as a compact unit which fits inside the bodywork of the
vacuum pump. Consult Atlas Copco for installing and connecting the energy recovery unit.
6996 0223 10 75
Instruction book
5.3 Operation
Description
The vacuum pump oil flow is controlled by two thermostatic valves (BV1 and BV2), ensuring reliable
vacuum pump operation and optimum energy recovery.
Bypass valve (BV1) is integrated in the oil filter housing of the vacuum pump and controls the oil flow to the
heat exchanger (HE) and the main oil cooler (Co) of the vacuum pump. Bypass valve (BV2) controls the oil
flow through the oil/water heat exchanger (HE) of the ER unit. Both valves consist of an insert (thermostat)
mounted in a housing.
76 6996 0223 10
Instruction book
BV1 starts closing the bypass line over the oil cooling circuit at the lower limit of its temperature range. At
the upper limit of its temperature range, the bypass line is completely closed and all the oil flows through
the oil cooling circuit.
BV2 starts closing the bypass line over the ER heat exchanger (HE) at the lower limit of its temperature
range. At the upper limit of its temperature range, the bypass line is completely closed and all the oil flows
through the main oil cooler (Co).
Bypass valve BV1 starts opening at 80 ºC (176 ºF) and is completely open at 95 ºC (203 ºF). Bypass valve
BV2 starts opening at 87 ºC (189 ºF) and is completely open at 102 ºC (216 ºF). The ER system can be
provided with bypass valves at the water side.
BV2 must have a higher opening temperature (set point) than BV1 in order to prevent the heat from being
dissipated in the vacuum pump oil cooler (Co) rather than in the oil/water heat exchanger (HE) when using
the compression heat as source for energy recovery.
6996 0223 10 77
Instruction book
5.4 Maintenance
Vacuum pump oil
For references used consult section Energy recovery unit.
Oil change:
1. Run the unit until warm. Stop the unit, switch off the isolating switch and close the air outlet valve of
the vacuum pump.
2. Depressurize the vacuum pump and drain the oil by opening the drain valve. Also drain the oil from
the heat exchanger by opening the drain plug on the heat exchanger (HE). Close the plug after
draining.
3. Resume oil change as described in section Oil and Oil Filter Change.
Thermostatic bypass valves
Change the thermostat of the ER system at the same interval as the thermostat of the unit.
No general recommendation can encompass the effects of all combinations of the various compounds,
solids and gases typically found in cooling water in interaction with different materials. Therefore, the
recommendations formulated in our Cooling Water Specifications are a general guide line for acceptable
coolant quality. However, where strict limits apply, a statement is made in the specification.
The water requirements refer to untreated water. When water is treated, some parameters will change.
Water treatments should be carried out by a specialized water treatment company, taking the responsibility
for the performance of the treated cooling water and the compatibility with the materials in the cooling
circuit. This includes not only the selection of the appropriate additives, but also the correct application,
monitoring of concentrations and properties, prevention of sludge formation and maintenance of the
system. This applies also to treatment with antifreeze products. They must be provided with suitable
stabilizers and inhibitors. Specifications are also depending on the type of cooling circuit (open, once
through / recirculating with tower / closed) and on the application (Standard - max 65 °C cooling water
temperature at the outlet) or Energy Recovery (water temperature up to 95 °C).
In case water is not in line with recommended values or if any doubt, consult the manufacturer.
78 6996 0223 10
Instruction book
pH
Energy
Type of cooling system Materials Standard
recovery
Containing copper 6.8 - 9.3 6.8 - 9.3
Stainless steel with carbon
Single pass 6.8 - 9.3 6.8 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3 6 - 9.3
Containing copper 6.8 - 9.3 not applicable
Stainless steel with carbon
Recirculating (with tower) 6.8 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3
Containing copper 7.5 - 9.3 7.5 - 9.3
Stainless steel with carbon
Closed loop 7.5 - 9.3 7.5 - 9.3
steel and / or cast iron
Stainless steel only 6 - 9.3 6 - 9.3
3. Hardness
Different types of hardness are in relation with each other and together with the pH and the alkalinity of the
water they determine the equilibrium situation of the water, determined and specified by the RSI.
In addition, the calcium hardness must be limited to:
Ca (ppm CaCO3)
Type of cooling system Standard Energy recovery
Single pass < 500 <2
Recirculating (with tower) < 500 not applicable
Closed loop < 1000 < 50
6996 0223 10 79
Instruction book
80 6996 0223 10
Instruction book
As a general rule, the RSI index should be between 5.6 and 7.5. If that is not the
case, contact a specialist.
6. Chlorides (Cl-)
Chloride ions will create pitting corrosion on stainless steel. Their concentration should be limited,
depending from the RSI value.
RSI < 5.5 5.6 < RSI < 6.2 6.3 < RSI < 6.8 6.9 < RSI < 7.5 7.6 < RSI
Cl- (ppm) 200 350 500 350 200
9. Copper
6996 0223 10 81
Instruction book
Copper (ppm)
Type of cooling system Standard Energy recovery
Single pass <1 < 0.2
Recirculating (with tower) <1 not applicable
Closed loop <1 < 0.2
10. Ammonium
The limit of 0.5 ppm is a rejection limit.
The limitation only applies for copper containing systems.
13. Biology
If biology is present, it must be aerobic. Anaerobic biology (in closed systems) must be avoided.
Biology (CFU/ml)
Type of cooling system Standard Energy recovery
Single pass < 105 / < 107 < 103 / < 105
Recirculating (with tower) < 105 / < 107 not applicable
Closed loop < 103 / < 105 < 103 / < 105
If additives are used in the cooling water, take into account that the cooling capacity
will change.
Δm = ((Cpw - Cpa) * X) / (Cpw *(1-X) + X*Cpa) * 100 %
with
Δm: change of mass flow of the coolant
Cpw: specific heat capacity of water
Cpa: specific heat capacity of the additives
X: the percentage of additives
82 6996 0223 10
Instruction book
Reading settings
In addition to other data, the following temperatures can be read on the Elektronikon display: For air-cooled
units:
1. The water inlet temperature of the energy recovery system
2. The water outlet temperature of the energy recovery system
Modifying settings
If the programmed warning settings for the water temperatures are exceeded, a warning indication is
shown on the Elektronikon:
Minimum Maximum
Temperature input Nominal setting
setting setting
Water inlet temperature of energy recovery ºC 0 50 99
Water inlet temperature of energy recovery ºF 32 122 210
Depends on
Energy recovery water outlet temperature ºC 0 99
application
Depends on
Energy recovery water outlet temperature ºF 32 210
application
To modify a setting, consult the relevant section in the description of the Elektronikon controller.
Recoverable energy
6996 0223 10 83
Instruction book
84 6996 0223 10
Instruction book
6 Operating instructions
The operator must apply all relevant Safety precautions. Also consult section
Problem solving.
1. Remove the red transport spacers and the related bolts under element (1) and oil separator tank (2).
2. Remove the service canopy panel(s) in order to get access to the internal components.
3. Check that the electrical connections correspond to the local codes and that all wires are clamped tight
to their terminals.
4. The installation must be earthed and protected against short circuits by fuses of the inert type in all
phases. It is advised to install an isolating switch near the vacuum pump.
5. Check the process lines for the correct size to prevent high pressure drop and for cleanliness to protect
the vacuum pump. Also check for leaks.
6. Make sure the pump outlet is not obstructed.
7. Fit the inlet isolation valve; see section Installation proposal for the position of the valve.
6996 0223 10 85
Instruction book
6.2 Starting
Step Action
1 Switch on the voltage. Check that voltage on LED (6) lights up.
Press start button (1) on the control panel. The vacuum pump starts running and the
2
automatic operation LED (8) lights up.
3 Open the inlet isolation valve (IV).
86 6996 0223 10
Instruction book
When the motors are stopped and LED (8) (automatic operation) is a light, the
motors may start automatically.
When the automatic operation LED (8) is lit, the regulator is automatically
controlling the vacuum pump, i.e. loading, purging, stopping of the motors and
restarting.
A few minutes after stopping, the oil level should reach the top of the oil sight glass (Gl).
If the oil level is too low, wait until the vacuum pump has vented. Push the emergency stop button (10) to
avoid the vacuum pump to start unexpectedly. Next, close the inlet isolation valve (IV).
Remove the oil filler plug (FC) and add oil until the level reaches the top of the oil sight glass. Fit and
tighten the plug (FC).
Unlock the emergency stop button (S3), select the STOP icon on the display and press reset before
restarting.
6996 0223 10 87
Instruction book
6.5 Stopping
1. Press stop button (13). Automatic operation LED (7) goes out and the vacuum pump stops.
2. To stop the vacuum pump in the event of an emergency, press emergency stop button (S3). Alarm LED
flashes (4).
3. Remedy the problem cause, unlock the button by pulling it out.
4. Navigate to the Stop icon on the display by means of the navigation keys or scroll keys (12) and press the
Select key.
5. Press the Reset icon.
88 6996 0223 10
Instruction book
7 Maintenance
Control panel
Use only authorised parts. Any damage or malfunction caused by the use of unauthorised parts is not
covered by Warranty or Product Liability.
Service kits
For overhauling or carrying out preventive maintenance, service kits are available (see section Service
kits).
Service contracts
Atlas Copco offers several types of service contracts, relieving you of all preventive maintenance work.
Consult your Atlas Copco Customer Center.
General
Intervals
The local Atlas Copco Customer Center may overrule the maintenance schedule, especially the service
intervals, depending on the environmental and working conditions of the vacuum pump.
The longer interval checks must also include the shorter interval checks.
Service plans for vacuum pump with an Elektronikon® Graphic controller. Besides the daily and 3-monthly
checks, preventive service operations are specified in the schedule below.
Each plan has a programmed time interval at which all service actions belonging to that plan are to be
carried out. When reaching the interval, a message will appear on the screen indicating which service
plans are to be carried out. After servicing, the intervals must be reset, see section Service menu.
6996 0223 10 89
Instruction book
Period Operation
Check oil level and condition. (see section During operation).
Daily Check readings on display.
Drain outlet collector.
Remove the air filter elements and inspect. Replace damaged or heavily
Monthly (1) contaminated elements.
Check for possible air and oil leakages.
Check coolers, clean if necessary.
3-monthly (1) Check the filter elements of the electric cabinet. Replace if necessary
Check the silencer of the blow off valve, clean if necessary.
(1) Depending on type of application (normal, medium, harsh) this needs to be done more frequently.
Consult your Atlas Copco Customer Center for more information on your application.
Type of application
Action Normal Medium Harsh
Check oil level and condition
Daily Daily Daily
Check readings on display
Remove the air filter elements and inspect
Replace damaged or heavily contaminated
elements Monthly Monthly Weekly
Check for possible air and oil leakages
90 6996 0223 10
Instruction book
Type of application
Action Normal Medium Harsh
Change oil * (for vacuum fluid premium and
vacuum fluid ultra
Change oil filter (for vacuum fluid premium and
vacuum fluid ultra)
Replace the oil separator elements
Replace the filter element of electric cabinet 8000 hrs. (2) 6000 hrs. (2) 4000 hrs. (2)
Motor overhaul
Working pressure, P < 200 mbar 64000 hrs. 48000 hrs. 36000 hrs.
Working pressure, P > 200 mbar(a) 72000 hrs. 64000 hrs. 48000 hrs.
Working pressure, P > 300 mbar(a) 96000 hrs. 72000 hrs. 64000 hrs.
Working pressure, P < 200 mbar 48000 hrs. 32000 hrs. 24000 hrs.
Working pressure, P > 200 mbar(a) 64000 hrs. 48000 hrs. 32000 hrs.
Working pressure, P > 300 mbar(a) 72000 hrs. 64000 hrs. 48000 hrs.
6996 0223 10 91
Instruction book
Vacuum pumps with optional high-water handling capability (humid version) are
recommended for use with Atlas Copco vacuum Synthetic fluid only.
Important
• Always consult Atlas Copco if a timer setting has to be changed.
• For the change interval of oil and oil filter in extreme conditions of temperature,
humidity or cooling air, consult your Atlas Copco Customer Center.
• Any leakage should be attended to immediately. Damaged hoses or flexible
joints must be replaced.
Avoid mixing lubricants of different brands or types as they may not be compatible
and the oil mix may have inferior properties. A label, indicating the type of oil filled
ex-factory, is stuck on the air receiver/oil tank.
92 6996 0223 10
Instruction book
Recommended grease:
Use 2901 0338 03 Amber
Quantity: 16g (0.56 oz) per bearing (@2000 rpm)
6996 0223 10 93
Instruction book
Air filter
Procedure
When placing the air filter element, verify that the seal is present and in good
condition.
94 6996 0223 10
Instruction book
3. Open the oil drain valves (Do1 and Do2). Do1 drains the vessel and Do2 drains the vacuum pump
element and the injection hose. Insert the tubes, delivered as loose parts, into the drain couplings.
4. Collect the oil in a collector and deliver it to the local collection service. Refit the vent plugs after
draining.
5. Close the oil drain valves (Do1 and Do2).
6. Clean the seat on the manifold. Lubricate the gasket of the new oil filters and screw them into place.
Tighten firmly by hand.
6996 0223 10 95
Instruction book
•
Unscrew the plug (Dp) in the outlet element housing and drain the oil from the vacuum pump
element and outlet housing. Collect the oil in a collector and deliver it to the local collection service.
Refit the vent plugs after draining.
7. Remove filler plug (FC).
• Fill the oil seperator vessel with oil until the level reaches the top of the oil sight glass.
OT
• Take care that no dirt drops into the system. Refit and tighten filler plug (FC).
8. Run the vacuum pump loaded for a few minutes. Stop the vacuum pump.
9. Close the isolation valve and switch off the voltage.
• Wait a few moments for the Vacuum pump to vent the vessel.
• Unscrew the oil filler plug (FC) just one turn to permit any remaining pressure in the system to
escape.
10. Fill the oil separator tank (OT) with oil until the level reaches the top of the oil sight glass.
(see Operating instructions /During operation)
• Refit and tighten filler plug (FC).
• When the oil level is too low, go back to step 7.
7.6 Coolers
General
Keep the coolers clean to maintain their efficiency.
Procedure
1. Stop the vacuum pump, close the isolation valve and switch off the voltage.
2. Cover all parts under the coolers.
3. Remove the service plate (1) at the fan compartment.
96 6996 0223 10
Instruction book
4. Remove dirt from the coolers with a fiber brush. Brush in the direction of the cooling fins.
5. Clean with an air jet in the reverse direction to normal flow.
6. If it is necessary to wash the coolers with a cleaning agent, consult Atlas Copco.
Procedure
1. Stop the vacuum pump, close the isolation valve and switch off the voltage.
2. Wait a few moments for the vacuum pump to vent the vessel.
3. Open the required service panels.
4. Unscrew the bolts of the cover (1 and 2) of the oil separator tank.
5. Slide one cover (1) of the oil separator tank backwards.
6. Remove the oil separator elements (OS) by turning one quarter counter-clockwise.
7. Clean the seat on the shield. Lubricate the gasket of the new oil separator using vacuum pump oil
and screw it into place. Tighten by hand.
6996 0223 10 97
Instruction book
Make sure all separator elements are assembled in the correct position. An arrow is
printed on the cover of the separator elements and the bottom of the shield; all
arrows should be pointing in the same direction after assembly.
8. Slide one cover (1) of the oil separator tank back in position. Make sure not to squeeze the O-ring.
9. Tighten bolts.
10. Slide the other cover (2) of the oil separator tank backwards
11. Remove the oil separator elements (OS) by turning one quarter counter-clockwise
12. Clean the seat on the shield. Lubricate the gasket of the new oil separator using vacuum pump oil
and screw it into place. Tighten by hand.
Make sure all separator elements are assembled in the correct position. An arrow is
printed on the cover of the separator elements and the bottom of the shield; all
arrows should be pointing in the same direction after assembly.
13. Slide the cover (2) of the oil separator tank back in position. Caution not to squeeze the O-ring.
14. Tighten bolts.
Testing
The pressure switch test can only be performed by authorized personnel and is
protected by a security code.
If the pressure switch does not open at the set pressure of 1500 mbar(a), it needs to be replaced.
Warning
98 6996 0223 10
Instruction book
No adjustments are allowed. Never run the vacuum pump without pressure switch.
Service kits
For overhauling and for preventive maintenance, a wide range of service kits is available. Service kits
comprise all parts required for servicing the component and offer the benefits of genuine Atlas Copco parts
while keeping the maintenance budget low.
Also, a full range of extensively tested lubricants, suitable for your specific needs is available to keep the
vacuum pump in excellent condition.
Consult the Spare Parts List for part numbers.
Procedure
Run the vacuum pump regularly, e.g. twice a week, until warm.
If the vacuum pump is going to be stored without running from time to time,
protective measures must be taken. Consult your supplier.
6996 0223 10 99
Instruction book
8 Problem solving
Warning
Before carrying out any maintenance, repair work or adjustment, stop vacuum pump,
close the isolation valve and wait 3 minutes.
Press the emergency stop button and switch off the voltage.
Vent the vacuum pump by opening the plug on the cover of the air inlet filter.
For location of components, see sections:
• Introduction
• Operation instructions
• Maintenance
Open and lock the isolating switch.
Lock the isolation valve during maintenance or repair.
The operator must apply all relevant Safety precautions.
Wait for at least 10 minutes before starting any electrical repairs as dangerous high
voltage remains on the capacitors of the start and speed regulation unit during some
minutes after switching off the voltage.
(1) Shutdown
Navigate to the Stop icon or to the Protections icon and press Enter.
(1) Protection
(1) General
The display shows the problem (Main Motor Converter Alarm) and a fault code (31 in this case).
Neos:
If a problem is detected by the Neos converter, a specific code (Main motor converter alarm) will appear on
the Elektronikon display, together with a fault code and a fault description.
Convertor
If a problem is detected by the converter, a specific code (Main motor converter alarm) will appear on the
graphic regulator display, together with a fault code and a fault description.
Typical display, Main Motor Converter Alarm (1), Fault (2) Code (0x7130) and description (Motor over
temperature (3)) in this case.
Below table lists the most important error codes. If another code appears, please contact Atlas Copco.
Fault
Fault
code Fault
code Cause Actions
(Hexade description
(Decimal)
cimal)
0x1111 4369 Under voltage Main Power supply voltage too
low or missing links in the Check if main supply voltage
control panel is within specs. Check main
fuses.
Check for loose connectors
at the control unit of the
converter and Elektronikon.
Check for tripped fuses at
the secondary of the
transformer T1 in the
electrical panel.
Fault
Fault
code Fault
code Cause Actions
(Hexade description
(Decimal)
cimal)
0x4311 17169 Drive over Over temperature detected in an
temperature IGBT
0x4312 17170 Drive over Over temperature detected in
temperature the heatsink
0x4314 17172 Drive over Over temperature detected in
temperature IGBT junction UH
Fault
code Fault
Fault
(Hexade code Cause Actions
description
cimal) (Decimal)
0x6103 24835 Drive failure General fault detected Try to reset the error.
(hardware) If error returns, contact
Atlas Copco.
0x6104 24836 Drive failure Internal checksum error detected
(hardware)
0x6105 24837 Drive failure Internal communication timeout
(hardware)
0x6106 24838 Drive failure Internal checksum error detected
(hardware)
0x6107 24839 Drive failure Internal communication timeout
(hardware)
0x6108 24840 Drive failure Internal communication timeout
(hardware)
0x6109 24841 Drive failure Internal checksum error detected
(hardware)
0x610A 24842 Drive failure Internal communication overload
(hardware)
0x610B 24843 Drive failure Internal control overload
(hardware)
0x610C 24844 Drive failure CAN communication time-out
Check CAN-cable
(hardware)
connection between
Elektronikon and
converter.
Check position of the
CAN termination switch
at both sides of the
CAN cable. Both should
be OFF.
Fault
Fault
code Fault
code Cause Actions
(Hexade description
(Decimal)
cimal)
0x8402 33794 Overvoltage Motor startup unsuccessful; Wait until the vessel
requested speed not depressurizes by blow off.
reached (by not resetting the fault
immediately).
If the problem persists,
contact Atlas Copco.
0x9001 36865 Hardware run Hardware enable signal missing Check for loose connectors
enable missing at the control unit of the
converter and Elektronikon.
Check for tripped fuses at
the secondary of the
transformer T1 in the
electrical panel.
0x9065 36965 to Drive failure Failure on attempt to write Try to reset the error.
to 91F4 37364 (software) parameter Pyyy out of If error returns, contact
range Atlas Copco.
9 Technical data
Important
The readings mentioned below are valid under the reference conditions (see
section Reference conditions and limitations).
Reference Reading
V Hz A A A A
GHS1300 380 60 IEC 46.3 - 51.4 -
GHS1300 400 50 IEC 43.6 - 48.4 -
GHS1300 460 60 IEC/CSA/UL 38.3 - 42.6 -
GHS1300 200 50 IEC 87.1 43.6 96.8 48.4
GHS1300 230 60 CSA/UL 76.7 38.3 85.2 42.6
GHS1300 500 50 IEC 34.9 43.6 38.7 48.4
GHS1300 575 60 CSA/UL 30.7 38.3 34.1 42.6
GHS1600 380 60 IEC 56.9 - 63.2 -
GHS1600 400 50 IEC 53.6 - 59.6 -
GHS1600 460 60 IEC/CSA/UL 47.1 - 52.3 -
GHS1600 200 50 IEC 107.2 53.6 119.1 59.6
V Hz A A A A
GHS1600 230 60 CSA/UL 94.2 47.1 104.6 52.3
GHS1600 500 50 IEC 42.9 53.6 47.7 59.6
GHS1600 575 60 CSA/UL 37.7 47.1 41.8 52.3
GHS1900 380 60 IEC 69.8 - 77.5 -
GHS1900 400 50 IEC 65.9 - 73.2 -
GHS1900 460 60 IEC/CSA/UL 57.7 - 64.1 -
GHS1900 200 50 IEC 131.7 65.9 146.4 73.2
GHS1900 230 60 CSA/UL 115.5 57.7 128.3 64.1
GHS1900 500 50 IEC 52.7 65.9 58.6 73.2
GHS1900 575 60 CSA/UL 46.2 57.7 51.3 64.1
GHS1300 Turbo 380 60 IEC 56.9 - 63.2 -
GHS1300 Turbo 400 50 IEC 53.6 - 59.6 -
GHS1300 Turbo 460 60 IEC/CSA/UL 47.1 - 52.3 -
GHS1300 Turbo 200 50 IEC 107.2 53.6 119.1 59.6
GHS1300 Turbo 230 60 CSA/UL 94.2 47.1 104.6 52.3
GHS1300 Turbo 500 50 IEC 42.9 53.6 47.7 59.6
GHS1300 Turbo 575 60 CSA/UL 37.7 47.1 41.8 52.3
GHS1600 Turbo 380 60 IEC 69.8 - 77.5 -
GHS1600 Turbo 400 50 IEC 65.9 - 73.2 -
GHS1600 Turbo 460 60 IEC/CSA/UL 57.7 - 64.1 -
GHS1600 Turbo 200 50 IEC 131.7 65.9 146.4 73.2
GHS1600 Turbo 230 60 CSA/UL 115.5 57.7 128.3 64.1
GHS1600 Turbo 500 50 IEC 52.7 65.9 58.6 73.2
GHS1600 Turbo 575 60 CSA/UL 46.2 57.7 51.3 64.1
Q1 1A
Q15 (as fuse) 6.3 A
Fuse calculations for IEC are done according to 60364-4-43 electrical installations of buildings, part 4:
protection for safety- section 43: protection against over current. Fuse sizes are calculated in order to
protect the cable against short circuit.
Fuse calculations for cUL and UL: The indicated fuse size is the maximum fuse size in order to protect
the motor against short circuit. For cUL fuse HRC form II (200-230, 500-575V) / class T (380-460V), for UL
fuse class K5 (200-230, 500-575V) / class T (380-460V).
Earthing
The earthing cable connected to the vacuum pump (PE) should be minimum according to EN 60204-1
section 828.
The tables below indicate the current carrying capacities of cables for 3 commonly used installation
methods, calculated according to standard 60364-5-52 - electrical installations of buildings part 5 -
selection and erection equipment and section 52 - current carrying capacities in wiring systems.
The allowed currents are valid for PVC insulated cables with three loaded copper conductors (maximum
conductor temperature 70 °C).
Maximum allowed current in function of the ambient temperature for installation method B2.
Maximum allowed current in function of the ambient temperature for installation method C.
Maximum allowed current in function of the ambient temperature for installation method F
• For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5% of the nominal voltage is recommended).
Example: Itot= 89 A, maximum ambient temperature is 45 °C, recommended fuse = 100 A
• Single supply cables (3 phases + PE - configuration (1)):
• I = 89 A + 10% = 89 x 1.1 = 97.9 A
• The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93 A for a 50 mm²
cable. For a cable of 70 mm², the maximum allowed current is 118 A, which is sufficient. Therefore,
use a 3 x 70 mm² + 35 mm² cable. If method C is used, 50 mm² is sufficient. (35 mm² for method F)
=>cable 3 x 50 mm² + 25 mm².
• Parallel supply cable (2 x 3 phases + PE - configuration (2)):
• I = (89 A + 10%)/2 = (89 x 1.1)/2 = 49 A
• For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So, 2 parallel
cables of 3 x 25 mm² + 25 mm² are sufficient.
• Install 50 A fuses on each cable instead of 100 A.
Cable sizing according UL/cUL
Calculation method according UL 508A, table 28.1 column 5: allowable ampacities of insulated copper
conductors (75°C (167°F)). Maximum allowed current in function of the wire size
Reference conditions
Relative humidity % 0
°C 20
Air inlet temperature
°F 68
mbar(g) 0
Exhaust back pressure
psi 0
mbar(a) 1013
Ambient barometric pressure
psi 14.7
Limitations
ºC 0
Minimum ambient temperature
ºF 32
ºC 46
Maximum ambient temperature
ºF 115
ºC -10
Minimum allowable inlet temperature
ºF 14
ºC 70
Maximum allowable inlet temperature
ºF 158
mbar(a) 1050
Maximum (absolute) inlet pressure
psi 0.73
mbar(a) 1500
Maximum vessel pressure (mbar(g))
psi 7.3
All data specified below apply under reference conditions, see section Reference
conditions and limitations.
Unit
Number of compression stages 1
mbar(a) 0.35
Ultimate pressure
Torr 0.4
Maximum exhaust back pressure mbar(g) 100
°C 83
Temperature of the air leaving the discharge (approx.)
°F 181
L 40 40
L 40 40
L 40 40
kW 37 37
Nominal motor power
HP 50 50
L 40 40
kW 37 37
Nominal motor power
HP 50 50
L 40 40
General
24V AC/16 VA 50/60Hz (+40%/-30%)
Supply voltage
24V DC/0.7 A
IP54 (front)
Type of protection
IP21 (back)
Ambient and temperature condition IEC60068-2
Operating temperature range -10°C.....+60°C (14°F.....140°F)
Storage temperature range -30°C.....+70°C (-22°F.....158°F)
Permissible humidity Relative humidity 90% No condensation
Digital outputs
9(Elektronikon® Graphic controller - p.n. 1900 5200
Number of outputs
10.....1900 5200 19)
Type Relay (voltage free contacts)
Digital inputs
10(Elektronikon® Graphic controller - p.n. 1900 5200
Number of inputs
10.....1900 5200 19)
Supply by regulator 24 V DC
Analog inputs
- This vessel can contain pressurised air; this can be potentially dangerous if the equipment is misused.
- This vessel must only be used as an air/oil separator and must be operated below 0.5bar(g).
- No alterations must be made to this vessel by welding, drilling or any other mechanical methods without
the written permission of the manufacturer.
- Use only oil as specified by the manufacturer.
- This vessel has been designed and built to guarantee an operational lifetime in excess of 20 years. The
vessel needs a yearly visual inspection.
11 Disposal
DIRECTIVE 2012/19/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL
on waste electrical and electronic equipment (WEEE)
This equipment falls under the provisions of the European Directive 2012/19/EU on waste electrical and
electronic appliances (WEEE) and may not be disposed as unsorted waste
The equipment is labelled in accordance with the European Directive 2012/19/EU with
the crossed-out wheelie bin symbol.
At the end of life-time of the electric and electronic equipment (EEE) it must be taken to
separate collection.
For more information check with your local waste authority, customer center or distributor.
On the Declaration of Conformity / Declaration by the Manufacturer, the harmonized and/or other
standards that have been used for the design are shown and/or referred to.
The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that is
supplied with this vacuum pump.
Local legal requirements and/or use outside the limits and/or conditions as specified by the manufacturer
may require other inspection periods as mentioned below.
13 Declaration of conformity
Sustainable Productivity
We stand by our responsibilities towards our customers,
towards the environment and the people around us.
We make performance stand the test of time.
This is what we call - Sustainable Productivity.
Atlas Copco AB
(publ) SE-105 23 Stockholm, Sweden Phone: +46 8 743 80 00
Reg. no: 556014-2720 www.atlascopco.com