Lecturenote - 2227726chap 2
Lecturenote - 2227726chap 2
Transformer
2.1 Introduction
Transformer is a static electromagnetic machine (i.e., it has no moving parts) that
transfers electrical energy from one electrical circuit to another electrical circuit
through the medium of magnetic field and without a change in the frequency.
The electric circuit which receives energy from the supply mains is called primary
winding and the other circuit which delivers electrical energy to the load is called
secondary winding.
𝑉𝑃 𝐼𝑆
Also =
𝑉𝑆 𝐼𝑃
𝑉𝑃 ∗ 𝐼𝑃 10 ∗ 240
𝐼𝑆 = = = 21.81 𝐴
𝑉𝑆 110
𝑉𝑃 𝑁𝑃 𝐼𝑆
= = =𝑎
𝑉𝑆 𝑁𝑆 𝐼𝑃
796 21.82𝐴
𝑎= = = 2.18
365 10𝐴
Note the larger secondary current. The secondary winding would need to have a
larger conductor size than the primary winding to carry this current. If the
transformer were of the step-up type the secondary current would be smaller.
E
Φm =
4.44Nf
Voltage Transformation Ratio(a)
From emf Eqs. we get
𝐸1 𝑁1 𝑉1 𝐼2
= = = =𝑎
𝐸2 𝑁2 𝑉2 𝐼1
The ratio of the primary voltage to the secondary voltage or primary turns to the
secondary turns is called Transformation ratio (Turns ratio) (𝑎)of a transformer.
If N2> N1 i.e., 𝑎 <1, then transformer is step-up transformer.
If N2< N1 i.e., 𝑎 >1, then transformer is step-down transformer.
Example: A single phase transformer has 350 primary and 1050 secondary
turns. The net cross-sectional area of the core is 55 cm2. If the primary
winding be connected to a 400 V, 50 Hz single phase supply, calculate (i)
the maximum value of flux density in the core and (ii) the voltage induced in
the secondary winding.
Solution
𝑉1 = 400𝑉 𝐸1 , 𝑁1 = 350, 𝑁2 = 1050, 𝐴 = 55 𝑐𝑚2 = 55 × 10−4 𝑚2 , 𝑓 = 50𝐻𝑧
Induced emf in the primary is given by
𝐸1 = 4.44𝑓𝛷𝑚 𝑁1 = 4.44𝑓𝐵𝑚 𝐴𝑁1
Maximum value of flux density in the core,
400
𝐵𝑚 = −4
= 0.93𝑇(𝑤𝑏/𝑚2 )
4.44 × 50 × 55 × 10 × 350
Where,
𝑉1 , 𝑉2 = 𝑟𝑚𝑠 𝑣𝑎𝑙𝑢𝑒 𝑜𝑓 𝑡ℎ𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝑣𝑜𝑙𝑡𝑎𝑔𝑒𝑠
𝐸1 , 𝐸2 = 𝑟𝑚𝑠 𝑣𝑎𝑙𝑢𝑒 𝑜𝑓 𝑖𝑛𝑡𝑒𝑟𝑛𝑎𝑙 𝑛𝑑𝑢𝑐𝑒𝑑 𝑣𝑜𝑙𝑡𝑎𝑔𝑒𝑠
𝑋0 = 𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑧𝑖𝑛𝑔 𝑟𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒
𝐼𝑚 = 𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑧𝑖𝑛𝑔 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
𝐼𝑤 = 𝑐𝑜𝑟𝑒 𝑙𝑜𝑠𝑠 𝑐𝑢𝑟𝑟𝑒𝑛𝑡
𝑅1, 𝑅2 = 𝑝𝑟𝑖𝑚𝑎𝑟𝑦 𝑎𝑛𝑑 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑤𝑖𝑛𝑑𝑖𝑛𝑔 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒𝑠
𝐼0 = 𝑁𝑜 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛
1. The first step in the simplification process is to move the shunt magnetization
branch from the middle of the T circuit to either the primary or secondary terminal,
as shown in Fig below. This step neglects the voltage drop across the primary or
secondary winding caused by the exciting current. The voltage drop caused by the
load component of the current is still included, of course.
2.7. Efficiency
Due to the losses describe above the output power of a transformer is always less
than the input power.
𝑂𝑢𝑡𝑝𝑢𝑡 𝑎𝑐𝑡𝑖𝑣𝑒 𝑝𝑜𝑤𝑒𝑟
𝜂= × 100%
𝐼𝑛𝑝𝑢𝑡 𝑎𝑐𝑡𝑖𝑣𝑒 𝑝𝑜𝑤𝑒𝑟
𝑃𝑜
𝜂= × 100%
𝑃𝑖𝑛
𝑃𝑜 = 𝑉2 𝐼2 𝑐𝑜𝑠𝜃2 𝑃𝑖𝑛 = 𝑃𝑜 + 𝑃𝐿𝑜𝑠𝑠
𝜃2 𝑖𝑠 𝑡ℎ𝑒 𝑙𝑜𝑎𝑑 𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟 𝑎𝑛𝑔𝑙𝑒
𝑉2 𝐼2 𝑐𝑜𝑠𝜃2
𝜂= 𝑤ℎ𝑒𝑟𝑒 𝑃𝐿𝑜𝑠𝑠 = 𝑃𝑙(𝑐𝑢) + 𝑃𝑙(𝑖𝑟𝑜𝑛)
𝑉2 𝐼2 𝑐𝑜𝑠𝜃2 +𝑃𝐿𝑜𝑠𝑠
2.8. Auto Transformer
A transformer, having only one winding a part of which acts as a primary winding
and the other as secondary is called an autotransformer. When the primary and
secondary voltage are derived from the same winding, the transformer is called an
autotransformer. In this type of transformer, a single coil is wound on to a steel
core, the primary and secondary windings being part of one winding.
The autotransformer has a low cost, better regulation and low losses. The
autotransformer is not used for interconnecting the high voltage and low voltage
system. It is used in the places where slight variation is required. When 400000V
(400kV) has to be transformed (stepped down) to 132kV, huge transformers are
required.
𝐸1 𝐸𝑎𝑐 𝑁𝑎𝑐
= = =𝑎
𝐸2 𝐸𝑏𝑐 𝑁𝑏𝑐
Step-up autotransformer:
The input voltage V1 is connected to the portion of winding (b-c) and the load is
connected across a the winding (a-c).The voltage V2 is related to V1 as in the
conventional two-winding transformer, that is,
𝑁𝑎𝑐
𝑉2 = 𝑉1 ×
𝑁𝑏𝑐
Where 𝑁𝑎𝑐 and 𝑁𝑏𝑐 are the number of turns on the respective windings.
𝑁𝑏𝑐 𝑉1 𝐼2
𝑎= = =
𝑁𝑎𝑐 𝑉2 𝐼1
with 𝑎<1 for step-up.
When a voltage V1 is applied to the primary of the autotransformer, the induced
voltages are related by
𝐸1 𝐸𝑏𝑐 𝑁𝑏𝑐
= = =𝑎
𝐸2 𝐸𝑎𝑐 𝑁𝑎𝑐
Disadvantage of autotransformers:
The parallel operation of a transformer has some advantages likes it increases the
efficiency of the system, makes the system more flexible and reliable. However, it
increases the short-circuit current of the transformers.
Conditions for parallel operation of Transformers
The two main necessary conditions are
Polarities of the transformers must be same.
Turn Ratio of the transformer should be equal.
Solution:
𝑁1 600 𝑁1 𝑉1 𝑁2 3000
a) 𝑎 = = = 0.2 b) = ⟾ 𝑉2 = × 𝑉1 = × 220 = 1100 𝑉
𝑁2 3000 𝑁2 𝑉2 𝑁1 600
Example 2:
A 200 KVA, 6600/400 V, 50Hz single phase transformer has 80 turns on the
secondary side. Calculate
a) The primary and secondary currents
b) The number of turns of the primary
Solution:
Ignoring losses, the input apparent power equals the output power
𝑆𝑖𝑛 200𝐾𝑉𝐴
a) 𝑆𝑖𝑛 = 𝑉1 𝐼1 = 200 𝐾𝑉𝐴 → 𝐼1 = = = 30.3𝐴
𝑉1 6600
200𝐾𝑉𝐴
𝑆0 = 𝑉2 𝐼2 = 200𝐾𝑉𝐴 → 𝐼2 = = 500𝐴
400
𝑁1 𝑉1 𝑉1 6600
b) = → 𝑁1 = × 𝑁2 = × 80 = 1320 𝑡𝑢𝑟𝑛𝑠
𝑁2 𝑉2 𝑉2 400
Example 3:
A single-phase transformer has the following parameters,
𝑅1 = 0.3Ω 𝑋1 = 2Ω R 2 = 1.5Ω X2 = 4Ω 𝑅𝑐 = 6𝐾Ω
Xm = 150Ω N1 = 400 𝑡𝑢𝑟𝑛𝑠 𝑁2 = 800 𝑡𝑢𝑟𝑛𝑠 & 𝑙𝑜𝑎𝑑 𝑖𝑚𝑝𝑒𝑑𝑎𝑛𝑐𝑒 𝑍𝐿 = 20Ω
a) Draw the complete equivalent circuit without approximation.
b) Draw the approximate equivalent circuit referred to the primary ignoring the
excitation component.
Solution
a)
b)
𝑁1 400
𝑎= = = 0.5
𝑁2 800
Example5:
A 23kVA, 2300/230 V, 60 Hz, step-down transformer has the following resistance
and leakage-reactance values: 𝑅1 = 4Ω, 𝑅2 = 0.04Ω, 𝑋1 = 12Ω and 𝑋2 = 0.12Ω.
The transformer is operating at 75% of its rated load. If the power factor of the
load is 0.866 leading, determine the efficiency of the transformer.
Solution:
Since the transformer is operating at 75% of its rated load, the effective value of
the secondary winding current is
23000
𝐼2 = = 100 𝐴 × 0.75 = 75𝐴
230
The load current at a leading power factor of 0.866, in phasor form, is
𝐼2 = 75∠300 𝐴
The secondary winding impedance is 𝑍2 = 𝑅2 + 𝑗𝑋2 = 0.04 + 𝑗0.12 Ω
The induced emf in the secondary winding is
𝐸2 = 𝑉2 + 𝐼2 𝑍2 = 230 + (75∠300 )(0.04 + 𝑗0.12) = 228.287∠2.330 𝑉
2300
Since 𝑎 = = 10
230
Then 𝐸1 = 𝑎𝐸2 = 10 × 228.287∠2.330 𝑉 = 2282.87∠2.330 𝑉
𝐼2
𝐼1 = = 7.5 ∠300 𝐴
𝑎
The primary winding impedance is 𝑍1 = 𝑅1 + 𝑗𝑋1 = 4 + 𝑗12 Ω
Then 𝑉1 = 𝐸1 + 𝐼1 𝑍1 = 2282.87∠2.330 𝑉 + (7.5 ∠300 )(4 + 𝑗12 )
𝑉1 = 2269.578∠4.70 𝑉
𝑃𝑜 = 𝑉2 𝐼2 𝑐𝑜𝑠𝜃2 = (230)(75∠300 )(0.866) = 14,938.5 𝑊
𝑃𝑖𝑛 = 𝑉1 𝐼1 𝑐𝑜𝑠𝜃1 = (2269.578∠4.70 )(7.5∠−300 )(0.90408) = 15,489.86985 𝑊
𝑃𝑜 14,938.5
η= = × 100% = 96.44%
𝑃𝑖𝑛 15,489.87
Example 6:
The secondary winding of a transformer has a terminal voltage of
𝑉𝑠 (𝑡) = 282.8 sin 377 V. The turn ratio of the transformer is 100:200. If the
secondary current of the transformer is 𝐼𝑠 (𝑡) = 7.07 sin (377t − 36.870 )A, what
is the primary current of this transformer? What are its voltage regulation and
efficiency? The impedances of this transformer referred to the primary side are
𝑅𝑒𝑞1 = 0.20Ω 𝑅𝑐 =300Ω
𝑋𝑒𝑞1 =0.750Ω 𝑋𝑚 = 80Ω
Solution:
The approximate equivalent circuit of transformer referred to the primary side is
The secondary voltage and current are given as
282.8
𝑉𝑠 = ∠00 𝑉 = 200∠00
√2
7.07
𝐼𝑠 = ∠ − 36.870 𝐴 = 5∠ − 36.870 𝐴
√2
The secondary voltage referred to the primary side is
𝑉𝑠′ = 𝑎𝑉𝑠 = 100∠00 𝑉
Then primary voltage is given by
𝑉𝑝 = 𝑉𝑠′ + 𝐼𝑝 (𝑅𝑒𝑞𝑝 + 𝑗𝑋𝑒𝑞𝑝 ) = 𝑎𝑉𝑠 + 𝐼𝑠′ (𝑅𝑒𝑞𝑝 + 𝑗𝑋𝑒𝑞𝑝 )
𝐼𝑠
But, 𝐼𝑠′ = = 10∠ − 36.870
𝑎
10,000
𝐼𝑎𝑏 = = 90.9 𝐴
110
10,000
𝐼𝑏𝑐 = = 22.7 𝐴
440
The performance of a transformer can be calculated on the basis of its equivalent ckt which
contains four main parameters. These are:
The equivalent resistance Ro1 as referred to primary (secondary Ro2)
The equivalent leakage reactance Xo1 and Xo2
The core loss conductance Go (resistance Ro)
The magnetizing susceptance Bo (reactance Xo)
One winding of the transformer is left open while the other is excited by applying the rated voltage.
The frequency of the applied voltage must be the rated frequency of the transformer. Although it
does not matter which side of the transformer is excited, it is safer to conduct the test on the low-
voltage side. Another justification for performing the test on the low-voltage side is the availability
of the low-voltage source in any test facility. Figure 2.11 shows the connection diagram for the
open-circuit test with ammeter, voltmeter, and wattmeter inserted on the low-voltage side.
Fig 2.11.A two-winding transformer wired with instruments for open-circuit test
This test is designed to determine the winding resistances and leakage reactances. The short-circuit
test is conducted by placing a short circuit across one winding and exciting the other from an
alternating-voltage source of the frequency at which the transformer is rated. Since the short circuit
constrains the power output to be zero, the power input to the transformer is low. The low power
input at the rated current implies that the applied voltage is a small fraction of the rated voltage.
Therefore, extreme care must be exercised in performing this test. In this case, the wattmeter
records the copper loss at full load.
Transformer power levels range from low-power applications, such as consumer electronics power
supplies to very high power applications, such as power distribution systems. For higher power
applications, three-phase transforms are commonly used. The typical construction of a three-phase
transformer is shown in Figure. The detailed analysis of this circuit is not straightforward since
there are numerous combinations of flux paths linking various windings. For this reason, the three-
phase transformer will be modeled as three independent single-phase transformers herein.
Fig 2.16 Three phase transformer
For practical calculations, it is reasonable to model the three-phase transformer as three ideal
transformers as shown in Figure 2.17. Since these transformers are ideal, the secondary voltages
are related to the primary voltages by the turn‘s ratio:
Fig 2.17Three phase transformer ideal model
Considering the individual transformers of Figure 2.17 and that both delta and wye connections
are possible for the primary and secondary windings, there are four possible combinations of
transformer connections. The most straightforward combinations are the wye-to-wye connection
and the delta-to-delta connections shown in Figures 2.20 (S) and (B) respectively. In these cases,
the line to-line voltages on the secondary side are directly proportional to those on the primary
side through the turn‘s ratio. Therefore, the following relationship holds for both connections.
The delta-to-wye connection is shown in Figure 2.20 (C). From the ideal transformer equations, it
can be determined that
In this analysis A-B-C sequence is assumed. If a source does not have this sequence the input lines
can be relabeled so that it does. With this sequence, (5) is equivalent to
As can be seen, the secondary line-to-line voltage leads the primary by 30o. A factor of 3 is also
inserted in the magnitude calculation as well. The wye-to-delta connection is shown in Figure 6.