S LV SWG Aux - 00
S LV SWG Aux - 00
S LV SWG Aux - 00
Group: Auxiliaries
Subject: Main LV AC Auxiliary Distribution Board
2 APPLICATION FIELD
This specification refers to Main LV AC Auxiliary Distribution Boards to be installed in the
distribution network of TAQA/ADDC/AADC.
3 REFERENCE DOCUMENTS
The list of the reference documents is indicated in the following paragraphs.
In case of discrepancy between these Specifications and any of the applicable Codes and
Standards, the following order of precedence shall apply:
1) TAQA/ADDC/AADC specifications
2) applicable reference standards
3) other documents.
The Supplier shall note that compliance of the Manufacturer with the provision of these
specifications does not relieve him from his responsibility to supply the equipment and accessories
of proper design, electrically and mechanically suited to meet the operating guarantees at the
specified service conditions.
3.1 TAQA/ADDC/AADC specifications
Table 1 - List of TAQA/ADDC/AADC specifications
S-GEN-NET Network Parameters
S-GEN-SER Service Conditions
S-GEN-COR Corrosion protection
S-GEN-ID Component Marking & Identification
S-GEN-ENC Cubicles & Enclosures
Three-phase CT operated static energy meters Class 1 for circuit categories
S-MET-STEM-CT-3P-1
E4 and E5
Current transformer for CT energy meters of circuit categories E3, E4 and
S-MET-CT
E5
S-AUX-DCNC DC system with Nickel Cadmium Batteries
3.2 Reference standards
The last edition of the standards mentioned in Table 2 that shall be take in consideration.
4 SERVICE CONDITIONS
The service conditions are specified in TAQA/ADDC/AADC specification S-GEN-SER.
6.1 General
The Main LV AC Auxiliary Distribution Board - hereinafter referred to as MDB - is a secondary
selective switchgear (e.g. fitted with two redundant incomers and a normally open tie breaker)
meant to feed substation auxiliary equipment as well as the lighting and other services via the
relevant AC boards.
The MDB shall provide the following voltages:
• 400V, 50 Hz, 3-phase, 50 Hz, for power supply to auxiliaries
• 230V, 50 Hz, single phase, 50 Hz, for lighting, outlets, etc.
The MDB shall be of metal-enclosed, indoor floor-mounted, front access, free-standing type and
shall meet requirements as specified in the Technical Data Sheet (D-LV-SWG-AUX). The MDB
will be installed in indoor substations without air conditioning (but with natural ventilation).
The MDB shall be of sealed version and vermin, corrosion, dust and damp proof to comply with
degree of protection IP 43 as defined by IEC 60529.
Provision shall be made for top, or bottom entries for cables as appropriate. Same option to be
specified in the Technical Data Sheet (D-LV-SWG-AUX).
The MDB shall be supplied complete with all instruments, meters, indicators, control switches or
pushbuttons, indicating lamps, terminal blocks, wiring, circuit breakers, miniature circuit breakers
and miscellaneous devices, etc.
MDB’s Cubicles shall be fitted with LED lights controlled by door-operated switches. The lights
shall be combined with an accumulator-cum-charger and shall be installed in such a position to
illuminate the whole compartment.
6.3.1 General
The MDBs shall be dust & vermin proof construction and metal enclosed to FORM 4b of IEC
61439-2. The cubicles shall be partitioned internally to form individual metal enclosed
compartments.
The MDBs shall be divided into distinct vertical sections, each comprising of:
• A completely enclosed bus bar compartment for running horizontal and vertical bus bars.
• Completely enclosed compartment(s), one for each circuit, for housing the
circuit breaker. Each compartment shall have an individual hinged door with locking facilities (of
an approved type of lock) and door interlock. The individual hinged door shall be operated from
outside. It shall be possible to open the door only after the breaker is switched-off.
• A compartment for power and control cables.
• A compartment for relays and other control devices associated with a circuit breaker.
All internal separations to achieve the above compartments shall comply with IP2X requirement
as per IEC 61439-1 standard. Sheet steel barriers shall be provided between two adjacent vertical
panels running to the full height of the distribution board, except for the horizontal bus bar
compartment.
After isolation of power and control circuits connections it shall be possible to safely carryout
maintenance in a compartment/cubicle with the bus bar and adjacent live circuit. All live parts
shall be covered using IP2X barriers.
Wherever it is not possible to maintain the required clearance, sleeves or barriers shall be used to
provide sufficient insulation. However, for horizontal run of bus bar minimum clearance as
specified in Technical Data Sheets (D-LV-SWG-AUX) should be maintained even if they are
sleeved.
6.4.1 General
The normal incoming feeders and the tie breaker shall be connected to an automatic changeover
device (ATS). Parallel operation of both incomers is not permitted. The automatic changeover
power and control device shall be fed from DC system at the rated voltage specified in the
Technical Data Sheet (D-LV-SWG-AUX).
In the event any of the two incoming sources is lost, the automatic device shall change over from
the double ended to the single ended configuration of the MDB (i.e. the incoming breaker relevant
to faulty incoming section shall be open, while the tie breaker shall be closed).
The changeover shall be indicated on the alarm panel.
The secondary circuit breakers of the two main power supplies feeding the main 400V switchboard
shall have selector switch with two positions:
• Position 1: off duty
• Position 2: automatic.
Any tripping, either from sub-distribution protection or manually operated, shall block the
automatic changeover system. The blocking shall be indicated visually.
Automatic and manual interlocking scheme shall be provided between the two incoming circuit
breakers in order to prevent their parallel operation
1
Depending on the Switchgear rating
Client: ADDC/ AADC
STANDARD TECHNICAL SPECIFICATIONS FOR ELECTRICITY DISTRIBUTION WORKS
Title: SPECIFICATION FOR MAIN LV AC AUXILIARY DISTRIBUTION BOARDS
DOCUMENT NO: S-LV-SWG-AUX_00.DOCX Rev: 0-2022 Sheet: 21 of: 35
Notes:
• The above-mentioned CT features are preliminary, it is Supplier responsibility to select the CTs
according to the protection schemes developed for the project
• It is supplier responsibility to adapt CT rating to the requirement of the selected relays (burden,
current rating, etc.)
• The thermal rating of the current transformer shall allow, at site conditions, a minimum of continuous
overloading referred to nominal rating of the feeder:
o 20% incoming feeder
o 50 % for transformer feeders
• Where multiple ratios are to be implemented, this shall be achieved by changing of the secondary
connection only. Primary switching is not acceptable
• The magnetizing curves for each CT, marking the points on the curve at which, knee-point voltage is
obtainable and also the corresponding excitation current, shall be submitted for approval by
TAQA/ADDC/AADC
• Supplier shall present CT rating selection calculations, both in steady state and transients, to
TAQA/ADDC/AADC for approval before CT manufacturing.
6.9.8 Indicating Instruments for Main LV AC Auxiliary Distribution Boards
The incoming sections of MDBs shall be fitted with 3-phase digital ammeters with instantaneous
elements plus maximum current demand and a reversible dial. The maximum demand indicator
shall be compensated for the site ambient temperature. One voltmeter of range 0-500V with
necessary connections and selector switch to provide all phase to neutral and phase to phase
voltage readings shall also be provided.
Ammeters provided on motor feeders shall have a compressed scale at the upper current region to
cover the starting current.
6.9.9 Control & Selector Switches
For control & selector switches requirements, reference shall be made to Standard Technical
Specification S-GEN-ENC.
6.9.10 Push Buttons
For push buttons requirements, reference shall be made to Standard Technical Specification S-
GEN-ENC.
All pushbuttons shall have one normally open and one normally closed contact, unless specified
otherwise. All push buttons shall be provided with integral escutcheon plates marked with its
function.
6.9.14.1 General
Provision for cable termination of LV Cables up to 240 mm2 Cu or 400 mm2 Al conductor
(selection of cable material to be specified in the Technical Data Sheet) shall be made for each
outgoing feeder. Outgoing MCCBs shall have built-in terminal to allow cable connection without
use of lugs.
Adequate separation (at least 10mm) between MCCB’s shall be maintained for ease of cable
connection.
The neutral conductor of each outgoing cable shall be terminated onto the neutral busbar.
Identification for LV outgoing cables shall be marked permanently above or below the respective
feeder according to Standard Technical Specification S-GEN-ID.
7.1 General
All MDB components shall be tested. The Supplier may be required to carry out any one or all of
the tests stated in this Specification under witness of TAQA/ADDC/AADC or their
representatives.
Testing Boards’ components assembly shall be performed in line with this General Specification
and in accordance with IEC 61439-2.
Acceptance by TAQA/ADDC/AADC’s representative of any unit shall not relieve the
manufacturer from any of his performance guarantees or from any other obligations.
Test certificates for each unit shall be submitted prior to delivery of the unit.
TAQA/ADDC/AADC reserve the right to perform checks during manufacturing process at any
time or all the times. It shall be at the discretion of TAQA/ADDC/AADC to witness tests on 100%,
or any percentage quantity of each lot for routine tests, apart from the type tests, wherever called
for. Testing of MDB assemblies shall include the factory and site tests.
7.2 Factory test
The bus riser interconnection with the low voltage switchboard shall be type tested.
MDBs shall be tested to minimize the risk associated with the propagation of an internal arc fault
of 50 kA for 0.3 sec. Internal arc tests as per IEC TR 61641 for internal arc protection with
certification covering criteria 1 to 7 / classes C. As per IEC TR 61641 during the test the points of
initiation shall be chosen to that the effects of the resultant arc provide the highest stresses on the
assembly.
If deemed necessary, TAQA/ADDC/AADC will decide whether additional tests are necessary to
be performed by the Supplier.
The Supplier shall submit certified copies of type test certificates of the Boards’ main components
(circuit breakers, etc.).
Type tests certificates/reports shall be considered acceptable if they are in compliance with the
relevant Standards and the following:
• Verification Tests conducted at an internationally recognised laboratory acceptable to
TAQA/ADDC/AADC. The Test laboratory shall be accredited to ISO 17025 standard. The final Type
test certificates shall be issued by an independent Certification body accredited to ISO 17065 standard
• Verification Tests conducted at the manufacturer’s laboratory and witnessed by representatives from
an internationally recognised laboratory acceptable to TAQA/ADDC/AADC.
If the presented verification test reports are not in accordance with the above requirements,
TAQA/ADDC/AADC may decide to ask for the verification tests to be carried out in the
manufacturer’s premises or other places subject to the approval of TAQA/ADDC/AADC and at
no additional cost. These tests shall be performed in the presence of an internationally recognised
laboratory, which should issue the relevant type test certificates upon successful test.
With reference to the afore mentioned table D.1, under all those circumstances where more than
one design verification option applies for a given characteristic of the assembly, then verification
testing shall apply.
7.2.2 Routine tests
MDBs shall be subjected to routine tests as per the relevant IEC recommendations (ref. chapter 11
of IEC 61439-1).
Routine test certificates shall be submitted for TAQA/ADDC/AADC’s review and approval before
shipment of assembly.
The following site tests, but not limited to, shall be carried out after installation and prior to putting
in service:
10 EXCEPTIONS
Possible exceptions to the present prescriptions, concerning the adoption of technical and/or
manufacturing aspects different from the ones prescribed in the present specification, can be
evaluated by TAQA/ADDC/AADC.
In such a case, TAQA/ADDC/AADC will take into account the opportunity to require additional
tests with regard to the technical/manufacturing proposed solutions.
Such exceptions can be approved by TAQA/ADDC/AADC.
2
The drawing shows a general layout for the sake of representing typical MDB configuration, dimensions and
arrangement. It shall be the Manufacturer’s/Supplier’s responsibility to provide with the actual general arrangement
drawing of the purchased MDB;
3
Dimensions and arrangement shall be confirmed prior the civil drawings are finalized.
Client: ADDC/ AADC
STANDARD TECHNICAL SPECIFICATIONS FOR ELECTRICITY DISTRIBUTION WORKS
Title: SPECIFICATION FOR MAIN LV AC AUXILIARY DISTRIBUTION BOARDS
DOCUMENT NO: S-LV-SWG-AUX_00.DOCX Rev: 0-2022 Sheet: 35 of: 35