MOV Rotork
MOV Rotork
IQ Multi-turn
Electric Valve Actuators
1. Introduction___________________________3
This manual provides instruction on the
ACTUATOR
1.1 Using the Rotork Setting Tool____________4 setup and analysis of the actuator.
SETTING TOOL
The Setting Tool is used to connect to the actuator, navigate Pages, Functions and Index
through menus, change settings and view information presented
on the actuator display. The display indicates the number of each function as it is
highlighted along with the total number of functions on that
page. In the example below, Action is function 2 out of a total of
1
12 functions on that page: 2/12
9 4
This manual uses the display function number as reference
7 for instructions.
8
5 11
3
6
10
Action (highlighted) is function 2 out of a total 12
on the LIMITS page.
Selection
The key is used to select a main menu item, menu items or
Name General Operation instruction buttons. For a setting, is used to select when a
change is required. The first time this occurs in a communication
1. Key Scroll up. session, a password will be requested (refer to 1.3). Subsequent
changes within the same session will not require the entry of
2. Key Scroll down / Connect a password. When selected, a menu item will be opened or a
setting or function will be highlighted.
3. Key Decreases value / Toggle setting / Scroll left.
Information, instruction and the password entry page screens
4. Key Increase value / Toggle setting / Scroll right.
require a or button to be selected. Navigate
5. Key Select the highlighted item. to highlight the required button using or and press to
Save the highlighted setting. select.
Stops actuator running (when Setting Tool
control is enabled, see section 2.3.1).
Setting controls
6. Key Return to previous menu.
There are four types of setting control used. When a function is
7. Key Cycle between standard and zoom view on data selected, the ability to change the function, setting or value is
logger torque graphs. made available using drop down list boxes, check boxes, slider
8. Key Actions the pre-configured mission stored on controls or number values.
the Rotork Bluetooth® Setting Tool Pro.
9. Infra-red transmitter window. Drop down list boxes
10. Key Sends a close command to the connected Drop down list boxes are indicated by .
actuator (when enabled see section 2.3.1).
11. Key Sends an open command to the connected Contacts
Monitor Relay
actuator (when enabled see section 2.3.1).
Mode Available
S1
Navigation Function Closed Limit
Contact N/O N/C
To navigate through screens, menus and pages, the
Position 0%
and keys are used. A single key press results in one
S2
movement. Holding the key will result multiple movements in
Function Open Limit
succession. Menus, pages and dropdowns wrap round. This
Contact N/O N/C
means that that an item at the bottom of a screen can be
Position 0%
accessed by pressing while at the top.
2/37
is highlighted. Press to select. The drop down list box will Function Open Limit
be closed and the selected function is saved and shown on the Contact N/O N/C
page. Position 0%
4/37
To exit the drop down list without saving a new setting
press to return to the page.
The example of the S1 indication position value is shown
above. For the S contact function of Pos.% Open indication, this
Checkboxes is the position opening at which the contact will change state.
Check boxes are indicated by or . Press (and enter password if applicable – refer to 1.3).
Use or to decrease or increase the value.
Contacts Slider controls wrap round so a key press on a minimum value
Monitor Relay will wrap round and indicate the maximum value. The value step
Mode Available changes increase as or is held down.
S1
Function Closed Limit
Once the required value is set press to select. The selected
value will be saved and shown on the page.
Contact N/O N/C
Position 0%
S2
To exit the slider control without saving a new setting,
Function Open Limit
press to return to the page.
Contact N/O N/C
Position 0%
Number values
3/37
Number values relate to values such as time or address - shown
in the example below.
The example of the S1 indication contact type check box is
shown above.
Stopped
Pakscan
Contacts Address 3
Monitor Relay
Baud Rate 2400
Mode Available
Position
S1
Update Times (s) 1
Function Closed Limit
Deviation 5%
Contact N/O N/C
Torque
Position 0%
Update Times (s) 5
S2
Function Open Limit
1/8
Contact N/O N/C
Position 0%
Press (and enter the password if applicable – refer to 1.3).
3/37
The Rotork Bluetooth® Setting Tool Pro incorporating Bluetooth Connecting to the actuator using Bluetooth
wireless technology is shown below. It is identified by the key
symbols and a clear seal between the top and bottom casings The actuator must be powered up to connect using Bluetooth. The
being transparent. default security set in the actuator for Bluetooth connection is by
initiation using an infra-red command. This means that the user
The Rotork Infra-red Setting Tool Pro is identified by solid yellow must be in close proximity and in direct line of sight of the actuator.
keys and a yellow band between casings:
Point the Setting Tool at the infra-red sensor located at the lower
right of actuator display window within a range of 0.25 m (10 in)
and press until the key flashes blue.
The screen will change to the Main Menu screen.
Rotork Setting Tool Pro The Setting Tool will automatically connect using
Bluetooth which takes up to 5 seconds.
Connection is indicated by steady blue lights on the tool and in
the actuator display window. Once connected, the tool can be
used without pointing it at the actuator display window.
Bluetooth connection will be maintained while Setting Tool key
commands are made. After a period of 6 minutes with no key
commands, Bluetooth connection will be turned off and the
Setting Tool and display blue lights will go out. To manually
disconnect Bluetooth at any time, press and together.
Menus, pages and settings may be viewed when the actuator is Navigate to the OK button using . Press . The setting page
set to Remote, Stop or Local. To change a setting, the actuator from which the function was selected will be displayed
must be selected to Local or Stop using the red selector and the with the function highlighted.
correct password must be entered.
The example below shows Settings – Limits – Close Settings
The password will be requested the first time a function with the function Action highlighted:
is selected. Once correctly entered, other changes can be
made without re-entering the password for the duration
of the Setting Tool session with the actuator.
If the actuator is selected to Remote and a setting is selected, the
following information screen will be displayed:
Press to select.
The highlight will return to the function name only and its stored
setting will be displayed:
Settings Settings
Limits Limits
Indication Indication
Control Control
ESD ESD
Security Security
Defaults Defaults
Close Settings
The value of torque available to close the valve can be limited The actuator can be configured to open on torque for back-
between 40% and 100% of its nameplate rated torque. If the seating valve types or limit for non back-seating valve types.
actuator develops the set torque when closing it will stop -
“torque trip” and must then be reversed before it will move Refer to valve manufacturer for recommended setting.
closed again. Operational torque can be monitored using the In the absence of valvemaker instruction set open action
datalogger (refer to 3) and using the torque-position home to “Limit”.
screen (refer to 2.2.2). Limit (default) – The actuator will move the valve to the set
The default setting for closed torque limit is 40%. If a Open Limit position and stop.
value of torque was specified at time of order, the % value Torque – The actuator will move the valve to the set Open Limit
equating to the specified torque will have been set by position and then apply the set torque (6/12) to back-seat the
Rotork. valve.
If the actuator was delivered complete with valve, the To change, . The checkbox will indicate the set
valvemaker may have set the closed torque limit based on opening action.
testing and/or design requirements.
In the absence of valvemaker instruction, set the minimum
6/12 Open Torque
value required to close the valve under process conditions.
To change, . The slider will indicate the set The value of torque available to open the valve can be limited
closing torque value. between 40% and 100% of its nameplate rated torque. If the
actuator develops the set torque when opening it will stop -
“torque trip” and must then be reversed before it will move
4/12 Close Limit open again. Operational torque can be monitored using the
datalogger (refer to 2.2.2) and using the torque- position home
Limits must only be set when the actuator is coupled to the valve. screen (refer to 2.2.2).
The minimum number of output turns between set Closed The default setting for open torque limit is 40%. If a value
and Open Limits is 2.5. A Closed Limit position cannot be set of torque was specified at time of order, the % value
if the actuator is at its set Open Limit or within 2.5 turns of an equating to the specified torque will have been set by
Open Limit position. Should a condition arise where this occurs, Rotork.
for example where an actuator at its “closed” limit position is
coupled to a valve at its open position, refer to 2.6 Defaults - If the actuator was delivered complete with valve, the
Limits. valvemaker may have set the closed torque limit based on
testing and/or design requirements.
If the actuator was delivered complete with valve, the
valvemaker should have set the closed and Open Limit In the absence of valvemaker instruction, set the minimum
positions, refer to testing below. value required to open the valve under process conditions
but higher than that set for closed torque.
The Closed Limit position must be set by moving the actuator to
the valve Closed Limit position and pressing . To change, . The slider will indicate the set limit
of opening torque value.
The actuator will display the following Instruction:
Settings Settings
Limits Limits
Indication Indication
Control Control
ESD ESD
Security Security
Defaults Defaults
Analogue
2.3.3 Interrupter timer
Analogue
Invert On Off The interrupter timer is an optional extra, check circuit
diagram for inclusion. If it is not enabled it will not be
included in the display menu. It is used to control
closing and/or opening operating time under both
local and remote control.
1/1
1/1 Invert
3/5 Maintained
Remote – Actuator selected for Remote control. Setting Tool HMI – Human Machine Interface consists of the actuator display
control keys are inactive and the actuator responds only to and red and black selectors. If for any reason the HMI stops
remote control signals. responding, the response of the actuator can be set.
To change, . The drop down list will close and Stayput (default) – The actuator will stayput and alarm using
the selected control mode will be indicated. the monitor relay. It will not respond to remote control signals.
Remote – The actuator will alarm using the monitor relay. It will
continue to respond to remote control signals.
Settings The Remote Control menu is shown left listing all possible
Limits entries. Some menu items shown are optional remote control
Indication
forms requiring additional hardware to be fitted in the actuator
Control
(see table below). The menu list displayed on the actuator will
show only the option(s) fitted. Options not fitted will not be
ESD
included in the menu list, check wiring diagram for option
Security
inclusion.
Defaults
Instruction is provided on the setup of standard hardwired Note: When any of the analogue or network remote
and remote control options. control options are fitted, Auxiliary Mask and Positioning are
automatically included in the remote control menu. These items
allow access to settings that are common to all fitted options.
See Examples below.
Remote Control
Hardwired
Control Source
Partial Stroke
Remote Control
Hardwired
Control Source
Positioning
Partial Stroke
Auxiliary Mask
Profibus
Remote Control Conditional – Close and open interlock inputs are enabled,
Hardwired interlocking is available and will be active in remote control
Control Source only. The actuator will not run under remote control unless
Partial Stroke
interlock signals are applied to the closed control and closed
interlock input or the open control and open interlock input.
Remote control is conditional on 2 signals being applied
simultaneously and therefore integrity of operation due to
spurious control signals is increased. Local control is available
without interlock inputs.
Remote Control
Partial Stroke – Partial stroke testing demonstrates the
2-Wire Priority Stop operational integrity of the valve and actuator by moving them
Interlocks for a set portion of stroke. A remote "partial stroke" hardwired
Mode Disabled signal applied to the open interlock input is used to initiate a
partial stroke test. For setting the partial stroke test parameters,
refer to 2.3.2-4. When set to partial stroke, the closed interlock
is disabled. Partial stroke initiated via a network command (with
a network option fitted), does not require the interlocks to be
1/2
configured for partial stroke.
Sets the action the actuator will take when a closed and open
signal are applied simultaneously. Hardwired remote control
form C uses the priority action (open or closed) to set the
actuator response when 2 signals are applied. Refer to the
circuit diagram and its referenced RWS control diagram.
On applying hardwired closed and open signals together, the
actuator will:
Open – the actuator will move open .
Stop (default) – the actuator will not move, or will stop if running.
Closed – the actuator will move closed.
2/2 Interlocks
Sets the mode for the interlock inputs, refer to wiring diagram.
External interlocks can be used to prevent operation of the
actuator until a certain process condition is met. An example is a
main and bypass valve system. The main valve is interlocked with
the bypass valve such that it cannot be opened until the bypass
valve is fully open.
Disabled (default) – the interlock inputs are disabled –
interlocking is not available .
Enabled – Close and open interlock inputs are enabled –
interlocking is available and will be active in both local and
remote control. The actuator will not run in local or remote
control unless interlock signals are applied to the closed or the
open interlock input. If only one interlock is required, for example
an interlock to prevent closed operation, the open interlock must
be linked out.
Options Control
KEY: For "Network", display will indicate the fitted option(s): Pakscan/Profibus/Modbus/Foundation Fieldbus (FF)/HART.
Control Source 1 will be set by Rotork for the fitted remote Sets the actuator response for when the analogue signal
Analogue or Network control option(s). Refer to Table: Control or Network communications of the source controlling
Source Settings. are lost.
There are 3 settings for determining the actuator response on
2/19 Control Source 2 loss of signal and these are common for all option types fitted.
Each group of 3 will be headed with the applicable option
Control Source 2 will be set by Rotork for standard hardwired type - example Analogue. For actuators including one control
control and/or the fitted remote Analogue or Network control option, settings 8/19 to 10/19 will be available and settings 11/19
option(s). Refer to Table: Control Source Settings. to 19/19 will be greyed out. For 2 options fitted, 8/19 to 13/19
will be available and so on up to 4 options. This instruction is
therefore common for as many options as are fitted.
3/19 Ctrl Selection
Control Selection is used to select the control source and if 8/19 Lost Signal Time
required for Analogue Option or Analogue with Network
options, allow hardwired switching between sources using the Sets the amount of time in seconds that a signal must be lost
Manual/Auto input before the set lost signal action takes place. Range 0 to 65
second:
Disabled – All remote control disabled. The actuator can only be
operated using the local controls. For the analogue option, time must be set to 0 seconds.
Hardwired – Remote control by hardwired inputs only. This To change, . The time set after which Lost signal
setting is the default for actuators with no option cards fitted. action will be implemented will be indicated.
If a Network option is fitted but is not required for
control, to select Hardwired. 9/19 Lost Signal Action
Source1 – Control by the option listed for Control Source 1 and
if a Network option, by its auxiliary mask control inputs if used, Sets the action implemented when the signal is lost:
refer to 2.3.2-5. Off (default) – The lost signal feature is disabled. An actuator
Hardwired/Source1 – Control available only when Analogue with Analogue control will run to the set low signal position. An
option is fitted. This mode enables the user to select between actuator with Network Control will stay at its current position
control by hardwired inputs or source 1 (Analogue) control by when communication is lost.
applying or removing a signal to the Manual/Auto input, refer to Stayput – If the actuator is not moving it will Stayput, if it is
wiring diagram. Manual will enable hardwired control and Auto moving it will Stop.
will enable Source1 control.
Close – The actuator will run to the Close Limit.
If an Analogue option is fitted and Manual/Auto switching
is required, to select Hardwired/Source 1. Open – The actuator will run to the Open Limit.
Source 1/Source 2 – Control by Analogue and a Network Position – The actuator will run to the mid-travel position set for
option only. This mode enables the user to select between Signal Loss Position, refer to 10/19.
Source1 (Analogue) and Source 2 (Network) control, by applying
To change, . The drop down list will close and
or removing a signal to the Manual/Auto input available with the
the selected action will be indicated.
Analogue option, refer to wiring diagram. Manual will enable
Source2 and Auto will enable Source1 control.
If an Analogue and Network options are fitted and 10/19 Lost Signal Position
Manual/Auto switching is required, to select
Source 1/Source 2. When the lost signal action is set to Position the actuator will
run to the mid-travel position set. Range is 0% (Closed Limit) to
100% (Open Limit). This control should be used if a lost signal
4/19 to 7/19 Options Fitted position in mid-travel is required.
Whenever the actuator is running under positioning mode, the
Not editable. Factory set for the Control options fitted. Up to
parameters in the Positioning menu will apply. Refer to 2.3.2-3.
4 options can be fitted and will be indicated in the list. Unused
allocations will be set to Disabled. To change, . The slider control will indicate the
mid-travel position the actuator will move to when the
If a control option is fitted after manufacture, the allocation will control/network signal is lost.
be set to the fitted option type by Rotork Service. Where the
user upgrades an actuator to include a new control option using
a kit supplied by Rotork, this must be set before the Control
mode settings can be made. Contact Rotork for access.
The Positioning option settings page with its default 2/5 Hysteresis
settings is shown above.
Range 0% - 25.5%. Default setting: 2%.
Applicable for Analogue and HART control options
and for all Network control options where positioning Affects positioning accuracy as a response to the process control
control is required. Settings are used to tune the actuator system desired value (DV) signal position. A larger Hysteresis
positioning response. setting will increase accuracy but the value set must not be
greater than that set for Deadband.
• Deadband and Hysteresis are combined to set positioning
Hysteresis setting should be combined with 1/5 Deadband
accuracy.
setting. The actuator will run towards the DV position until the
• Inhibit Time is used to set a dwell in the actuators response. actual position is within the set deadband minus the hysteresis
setting. This has the effect of the actuator stopping nearer to the
• Low/High Signal Position sets the range of the valve stroke DV position. The actuator will not restart unless it overshoots and
where positioning is required. runs outside the deadband or a new command places the new
desired position outside the deadband. Refer to figure 2.3-1.
DV
Hysteresis = 1%
Deadband = 3%
Example: An actuator set with a 3% deadband and a 1% The Deadband setting will be determined by the accuracy of
hysteresis and a control system new Desired Value (DV) of 50% control required and valve overrun. Overrun is a factor of valve
will come to rest between 48% and 53% when moving from and actuator inertia dependent on mass, speed, valve stiffness
a position less than 47%, and between 52% and 47% when and friction
moving from a position greater than 53%.
To change, . The checkbox will indicate partial To initiate a partial stroke test using the Setting Tool, the
stroke test status. actuator must be set to Local control using the red selector and
at the limit position set for 2/6 From Limit.
Analogue When Analogue and Network options are fitted and Auto is
Signal Type mA Volts selected, the Network option fitted will continue to report
Signal Range 20mA actuator status.
Invert On Off
Manual-Auto On Off
Hardwired ESD is available in both Manual and Auto.
When applied, ESD will override all other control signals.
Set Low Signal
Refer to 2.4 ESD.
Set High Signal
1/6 Signal Type The actuator must be calibrated to the Low analogue signal
value. By measuring this signal it will then be able to control the
actuator by moving it to the Set Low Signal position, refer to
mA (default) – Set for current (mA) analogue control signal.
2.3.2-3 Positioning.
Volts – Set for voltage analogue control signal.
APPLY THE LOW ANALOGUE SIGNAL and select .
To change, . The checkbox will indicate the set The signal will be measured and set as the Low signal
analogue signal type. position value.
Available ranges: 5 mA, 10 mA or 20 mA (default) or 5 V, 10 V The actuator must be calibrated to the High analogue signal
or 20 V range for voltage control. For analogue signal using a value. By measuring this signal it will then be able to control the
4 mA to 20 mA range, set 20 mA. actuator by moving it to the Set High Signal position, refer to
2.3.2-3 Positioning.
To change, . The drop down list will close and
the selected range will be indicated. APPLY THE HIGH ANALOGUE SIGNAL and select .
The signal will be measured and set as the High signal
position value.
3/6 Invert
Deviation Disabled
Position
Filter Manual Auto
Torque
6/8 Deviation
7/8 Filter
Profibus
Address 126 5/6 Redundancy
GSD Param. Yes No
Termination1 On Off Used for dual Profibus option (redundant) only. Refer to wiring
Termination2 On Off diagram.
Redundancy Flying System System (default) - System redundancy implies that there are 2
Extended Diag. Yes No completely separate Profibus highways in the network system
1/6 and that each highway is connected to one of the Profibus
channels, in this mode the address of both Profibus channels are
identical.
The Profibus Control option settings page is shown above
with its default settings. Profibus is a control option and Flying - Flying redundancy implies that there is 1 highway that
is available in single or dual versions – refer to wiring is connected to both channels, in this mode the addresses of the
diagram. channels must be different to avoid both channels responding to
the same message. In flying redundancy channel 2 address will
Depending on the Profibus control scheme, other related settings be channel 1 address plus 64.
may be required, refer also to:
To change, . The checkbox will indicate the set
2.3.2-3 Positioning redundancy.
2.3.2-5 Auxiliary Mask
6/6 Extended Diagnostics
1/6 Address
Used for dual Profibus option (redundant) only. Refer to wiring
diagram.
The actuator Profibus module must be allocated an address
unique in the Profibus system. Changes made to the address will The slave redundancy specification from the PNO describes
take effect immediately. The range of address is 01 – 126 (default Extended diagnostics that are available in the redundant card.
126). Refer also to 5/6 Redundancy. These messages describe (for example) the state of the backup
channel. Diagnostics messages can be turned on and off
To change, . The set address will be indicated. depending on the capabilities of the PLC to which the module is
connected.
2/6 GSD Parameter No (default) - Diagnostic messages turned off.
If the user parameterisation data is to be setup using FDT, EDDL Yes - Diagnostic messaging turned on.
or the actuators menu, setting this menu item to ‘No’ will ensure To change, . The checkbox will indicate the set
that the user parameterisation data sent to the Profibus card extended diagnostic mode.
during the parameterisation of the Profibus network with the
GSD file will be ignored and settings previously made will not be
overwritten. As default this is ‘Yes’ to ensure that the Profibus
card will be parameterised by the GSD user parameterisation
data.
Yes (default) – Parameterisation by GSD file is enabled.
No – Parameterisation by GSD file is disabled.
1/5 Address
4/6 Parity/Stop
Modbus
Address 247
Termination On Off
Where Modbus parity bit detection is used, the module must
Baud Rate 9600
be set with the same parity settings as the host. The choices of
parity are None, Even, Odd. This item also allows selection for
Parity/Stop None/1 stop
the number of stop bits as 1 or 2. The choices for stop bits are 1
Second Address 247
or 2. The drop down box requires selection of the parity and stop
Control CH1 Ctrl Ch2 Ctrl
bits together.
1/6
To change, . The drop down list will close and
the selected parity and stop bit will be indicated.
The Modbus Control option settings page is shown above
with its default settings. Modbus is a control option and
5/6 Second Address
is available in single or dual versions – refer to wiring
diagram.
Used for dual Modbus option (redundant) only. Refer to wiring
diagram.
Depending on the Modbus control scheme, other related settings
may be required, refer also to: A dual Modbus card has 2 channels available for connection to
separate or the same highway(s). The second channel address is
2.3.2-3 Positioning
setup with this setting. It may be identical or different to the first
2.3.2-5 Auxiliary Mask channel depending on the requirement of the system.
The Modbus option must be allocated an address unique in the 6/6 Control
system to which it is attached. Changes made to this parameter
will take effect immediately. The address range is 01 – 247
Not editable. For dual Modbus option (redundant) Only.
(default 247).
Refer to wiring diagram.
To change, . The set address will be indicated.
Setting will indicate that control is available on both channels
1 and 2.
2/6 Termination
Remote Control
Hardwired
Control Source
Positioning
Partial Stroke
Auxiliary Mask
Analogue
Pakscan
Profibus
HART
Modbus
Extra I/O
2/6 Pos1
ESD Override
ESD can be set to override local Stop selection, active interlocks,
Interrupter Timer and motor thermostats.
4/7 Stop
External interlocks can be used to prevent operation of the The IQ motor includes two embedded thermostats. Should
actuator until a certain process condition is met. Refer to 2.3.2-1 the duty cycle of the actuator be exceeded and the motor
If interlocks are being used, ESD can be set to override them. temperature rises to that that of the thermostat trip temperature,
the motor will be de-energised and the actuator will stop. On
No (default) – ESD action cannot override active interlocks. cooling, the thermostats will automatically reset and the actuator
Yes – ESD action will override active interlocks. can be returned to operation.
WARNING: In this mode, when under ESD control, WARNING - Actuators certified for use in Hazardous
the process or safety interlocks may be overridden. Areas. If the thermostats are bypassed during ESD,
Consideration should be given to providing warning signs hazardous area certification is invalid. Users must carry
and control system information. In all circumstances, active out their own risk assessment. Due to this requirement,
interlocks on cannot be considered as a safety lockout – an internal physical link must also be set to bypass
always isolate the electrical supply to the actuator during thermostats. Setting 7/7 alone to Yes will not bypass the
valve or actuator maintenance. thermostats. Contact Rotork.
To change, . The checkbox will indicate ESD ESD action can be set to override tripped thermostats
override interlock status. providing an internal physical link is also set:
No (default) – ESD action cannot override the thermostats.
6/7 Timer Yes – ESD overrides tripped thermostats. Under ESD control,
should the motor temperature rise and trip the thermostats, ESD
ESD override the interrupter time (if enabled). operation will continue.
The Interrupter timer option allows the valve operating time
To change, . The checkbox will indicate ESD
to be increased. This is used, for example, to prevent hydraulic
override thermostats status.
shock (water hammer) when closing or to prevent surges when
opening a valve. The interrupter Timer is active in both local and
remote control, refer to 2.3.3.
No (default) – ESD action cannot override the interrupter Timer.
Under ESD control, the timer will remain active and the valve
operating time as controlled by the Interrupter Timer is set.
Yes – ESD overrides the interrupter Timer. Under ESD control, the
timer will be overridden and the actuator will run continuously to
the set ESD position at normal speed.
Bluetooth
High: Infra Red Initiation only
Password
Change Password Default
Re-Enter Password
Lost Code L81L18
Medium: Discover in Local and Stop – The actuator is The Lost Code characters will change. Refer to 4/4 Lost Code.
available and searchable for Bluetooth communication using a
PC running Insight2 when it is selected to Local or Stop using 3/4 Re-Enter Password
the red selector. Connection is unavailable in Remote. The Local/
Stop/Remote selector can be padlocked in all three positions. The Re-enter Password control is used when high level access
Communication with the Bluetooth Setting Tool is available. is required by Rotork Service or by a user requiring a high level
High: Infra Red Initiation only (default) – The actuator is not access in order to make other settings available. Contact Rotork
available or searchable for Bluetooth communication using a PC for user high level password.
running Insight2. Communication with the Bluetooth Setting Tool Enter the provided higher access level password, refer to 1.3
is available using the quick connect method. Refer to 1.2.
Once correctly entered, access to high level settings as indicated
Very High: Disabled. Infra Red only – All Bluetooth in this manual will be made available.
communication is disabled. Communication is by infra-red
commands from the Setting Tool only. Refer to 1.2.
4/4 Lost Code
Note. If requested, the user required Bluetooth security
level can be set and made non-editable by Rotork. Non editable. Lost Code is used if a user password has been set
Contact Rotork. and then lost or forgotten.
To change, . The drop down list will close and Contact Rotork quoting the code as read from the display. After
the selected Bluetooth security level will be indicated. caller verification, Rotork can then provide the user set password.
3/3 Restore
3/3
This setting will restore the factory set limit positions and
position the actuator at 50% open. Factory limits: 25 output
turns between Closed and Open Limit positions.
Allows default settings and factory set limits to be To restore the default Limits, . A warning will be given,
restored. to continue .
Open Limit
Control
Local
Remote Hardwired
Remote Source 1
Remote Source 2
1/6 Open
Displays the current Local Open signal status. When active this
indicates the local controls have been turned to open and a local
control open signal is being received.
2/6 Close
Displays the current Local Close signal status. When active this
indicates the local controls have been turned to close and a local
control close signal is being received.
3/6 Stop
Displays the current Local Stop signal status. When active this
indicates the local controls have been set to stop and a local
control stop signal is being received.
When the local controls have been set to stop the actuator will
not move to position regardless of the local or remote control
signals it receives.
4/6 Local
1/6 Open
2/6 Close
3/6 ESD
Control Control
Local Local
Remote Hardwired Remote Hardwired
Remote Source 1 Remote Source 1
Remote Source 2 Remote Source 2
Displays the current Remote Source 1 Open signal status. When Displays the current Remote Source 2 Open signal status. When
active this indicates that an open signal is being received from active this indicates that an open signal is being received from
remote source 1. remote source 2.
Displays the current Remote Source 1 Close signal status. When Displays the current Remote Source 2 Close signal status. When
active this indicates that a close signal is being received from active this indicates that a close signal is being received from
remote source 1. remote source 2.
Displays the current Remote Source 1 Stopped signal status. Displays the current Remote Source 2 Stopped signal status.
When active this indicates that remote source 1 has been set to When active this indicates that remote source 2 is set to stop.
stop.
4/4 ESD
4/4 ESD
Displays the current Remote Source 2 ESD signal status. When
Displays the current Remote Source 1 ESD signal status. When active this indicates that an ESD (Emergency Shut Down) signal is
active this indicates that an ESD (Emergency Shut Down) signal is being received from remote source 2.
being received from remote source 1.
ESD can be set to open, close or stayput. ESD signals are higher
ESD can be set to open, close or stayput. ESD signals are higher priority than local or remote signals and will operate under
priority than local or remote signals and will operate under both local and remote control selection. ESD can also be set to
both local and remote control selection. ESD can also be set to operate an actuator selected to local stop.
operate an actuator selected to local stop.
Actuator Alarms
This screen displays the current status of the actuator alarms; the
checkbox indicates that the alarm is currently active.
To scroll through this information use .
Displays the Motor stall alarm status. When active this alarm
indicates that the actuator has received a valid command, but
has not detected any movement within 5 seconds.
Displays the Valve Jammed alarm status. When active this alarm
indicates that the valve has jammed in either the open or closed
position. Check valve operation by hand.
Movement
Displays the inhibit timer status. When active this status indicates
that the inhibit timer is counting to the set time. Range 0-255
Moving Open
seconds, default 5 seconds.
Moving Closed
Contactor CW The inhibit timer sets a delay after the actuator stops as a
Contactor ACW result of reaching a position consistent with a new desired
Open Limit
value position. For the period set, the actuator will not respond
to a change in the desired value. The inhibit timer is used to
Closed Limit
prevent unwanted operation as a result of rapidly oscillating or
PStroke Active
fluctuating desired position signal, or to slow actuator response
Inhibit Timer in order to protect the mechanical valve from excessive wear and/
or maintain actuator within its electrical rating. Refer to section
2.3.2-3 Positioning settings.
Movement status
This screen displays the current movement status of the actuator.
The checkbox indicates that the status is active.
To scroll through this information use .
3/8 Contactor CW
Displays the open limit status. When active this status indicates
that the actuator is at the open limit.
Displays the close limit status. When active this status indicates
that the actuator is at the closed limit.
Status 6/13 S5
Control
Alarms Displays the S5 relay status. When active this indicates that relay
Movement S5 is energised.
Indication
Diagnostics
7/13 S6
Displays the S6 relay status. When active this indicates that relay
S6 is energised.
8/13 S7
Displays the S7 relay status. When active this indicates that relay
Indication S7 is energised.
Monitor Relay
S1
9/13 S8
S2
S3 Displays the S8 relay status. When active this indicates that relay
S4 S8 is energised.
S5
S6
10/13 S9
Displays the S9 relay status. When active this indicates that relay
S9 is energised.
Indication status
This screen displays the indication relays statuses. The checkbox 11/13 S10
indicates that the relay is energised.
Displays the S10 relay status. When active this indicates that relay
The monitor relay and relays S1-S4 are provided as standard, S10 is energised.
relays S5-S8 and relays S9-S12 are available options that are
greyed out if the options are not present.
12/13 S11
To scroll through this information use .
Displays the S11 relay status. When active this indicates that relay
S11 is energised.
1/13 Monitor Relay
Displays the monitor relay status. When the monitor relay is used 13/13 S12
to monitor the remote control status; the checkbox indicates
that the actuator is set to remote control, there are no detected Displays the S12 relay status. When active this indicates that relay
internal failures and the actuator is powered. When the monitor S12 is energised.
relay is used in fault mode the checkbox indicates that there are
no detected internal failures and the actuator is powered.
For each relay function, please refer to section 2.2.1 for
indication contacts settings.
2/13 S1
Displays the S1 relay status. When active this indicates that relay
S1 is energised.
3/13 S2
Displays the S2 relay status. When active this indicates that relay
S2 is energised.
4/13 S3
Displays the S3 relay status. When active this indicates that relay
S3 is energised.
5/13 S4
Displays the S4 relay status. When active this indicates that relay
S4 is energised.
Diagnostics status
This screen displays the actuators diagnostics status. The
checkbox indicates that the fault is present.
To scroll through this information use .
Displays the power supply failure status. When active this status
indicates a power supply failure has occurred. If the backlight is
still present it is likely that the third phase has been lost. Check
all incoming phases.
Displays the phase loss status. When active this status indicates
that one or more phases have been lost. Only the third phase
is monitored so if the backlight is present then check the third
phase is present. If the backlight is not present, check all phases.
Displays the fault status of the torque sensor. When active this
status indicates that a fault has occurred with the torque sensor.
Check the torque sensor and loom.
www.rotork.com
A full listing of our worldwide sales and
service network is available on our website.
As part of a process of on-going product development, Rotork reserves the right to amend
and change specifications without prior notice. Published data may be subject to change.
For the very latest version release, visit our website at www.rotork.com
The name Rotork is a registered trademark. Rotork recognises all registered trademarks.
PUB002-040-00 The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG,
Inc. and any use of such marks by Rotork is under license. Published and produced in the
Issue 07/13 UK by Rotork Controls Limited. POWTG0713