SDongleA-05 MODBUS TCP Guide

This document provides instructions on enabling and disabling MODBUS TCP on Huawei SDongleA-05 devices and connected inverters. It outlines the minimum software versions required, networking diagram, and step-by-step procedures to configure MODBUS TCP settings using a mobile phone app. Troubleshooting tips are also provided to assist with resolving potential issues.

Uploaded by

Surca Andrei
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views15 pages

SDongleA-05 MODBUS TCP Guide

This document provides instructions on enabling and disabling MODBUS TCP on Huawei SDongleA-05 devices and connected inverters. It outlines the minimum software versions required, networking diagram, and step-by-step procedures to configure MODBUS TCP settings using a mobile phone app. Troubleshooting tips are also provided to assist with resolving potential issues.

Uploaded by

Surca Andrei
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

SDongleA-05

MODBUS TCP Guide

Issue 01
Date 2021-11-07

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. i


SDongleA-05
MODBUS TCP Guide Preface

Preface

Purpose
This document describes how to enable/disable Modbus TCP and provides the
common-fault rectification methods, operations, and tool use guide.

Intended Audience
This document is intended for Modbus TCP personnel. Operator must:
● Be familiar with the product networking and related NEs' versions.
● Have device maintenance experience and be familiar with device operation
and maintenance.

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. ii


SDongleA-05
MODBUS TCP Guide Preface

Symbol Description

Indicates a hazard with a high level of risk which,


if not avoided, will result in death or serious
injury.

Indicates a hazard with a medium level of risk


which, if not avoided, could result in death or
serious injury.

Indicates a hazard with a low level of risk which,


if not avoided, could result in minor or moderate
injury.

Indicates a potentially hazardous situation which,


if not avoided, could result in equipment damage,
data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to
personal injury.

Supplements the important information in the


main text.
NOTE is used to address information not related
to personal injury, equipment damage, and
environment deterioration.

Change History
Issue Date Description

01 2021-11-07 This issue is the first official release.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. iii


SDongleA-05
MODBUS TCP Guide Contents

Contents

Preface........................................................................................................................................... ii
1 Before You Start....................................................................................................................... 1
1.1 Software of Device.................................................................................................................................................................. 1
1.2 Precautions................................................................................................................................................................................ 1

2 Networking Diagram.............................................................................................................. 2
3 Operations.................................................................................................................................3
3.1 Enable/Disable MODBUS TCP............................................................................................................................................. 3
3.1.1 Environment Setup.............................................................................................................................................................. 3
3.1.2 Procedure................................................................................................................................................................................ 3
3.1.3 Troubleshooting................................................................................................................................................................. 10

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. iv


SDongleA-05
MODBUS TCP Guide 1 Before You Start

1 Before You Start

1.1 Software of Device


1.2 Precautions

1.1 Software of Device


To properly use the Modbus TCP function, each device subcomponent has a
minimum version number. The following table lists the minimum version number
requirements

Device Minimum version number

SDongleA-05 V100R001C00SPC124

SUN2000L V200R001C00SPC115

SUN2000MA V100R001C00SPC139

1.2 Precautions
Before enable/disable Modbus TCP, pay attention to the following:
● During the configuration, ensure that the Dongle is not powered off.
● After the configuration is complete, you do not need to perform the
configuration again after the device is powered off and then powered on.
● After the inverter is replaced, reconfigure the inverter.
● After the Dongle is replaced, you do not need to reconfigure the inverter.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 1


SDongleA-05
MODBUS TCP Guide 2 Networking Diagram

2 Networking Diagram

NOTE

The Dongle and the customer's device must be in the same LAN. The access mode is not
limited (either network cable or Wi-Fi).

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 2


SDongleA-05
MODBUS TCP Guide 3 Operations

3 Operations

3.1 Enable/Disable MODBUS TCP

3.1 Enable/Disable MODBUS TCP


3.1.1 Environment Setup
[Required Devices]
● Mobile phone
● The Dongle is powered on and running properly.
[Device requirements]
● Mobile phone operating system: Android 4.0 or later.
● Recommended mobile phones: Huawei and Samsung.
● The mobile phone supports the web browser and can connect to the Internet.
● The mobile phone supports the Wi-Fi function.

3.1.2 Procedure
Step 1 Downloading and Installing the App
Search for SUN2000 in the following app market, download the app installation
package (the version number must be 3.2.00.015 or later), and install the app by
following the instructions.
● Baidu Mobile Assistant (Android)
● Huawei AppGallery (Android)
After the installation is complete, the SUN2000 icon is displayed.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 3


SDongleA-05
MODBUS TCP Guide 3 Operations

Step 2 Downloading the Inverter Upgrade Package


Download the update package from http://e.huawei.com and copy the update
package to the root directory of your phone's internal storage or microSD card.
Step 3 Connects to the inverter. The app supports the following connection mode.
● Method 1: Connect the mobile phone to the inverter through the inverter
Wi-Fi hotspot.
Open the SUN2000 APP, touch Connect, and select the device type you want
to connect. Here, select WLAN.
Select the WiFi name of the inverter and enter the WiFi password of the
inverter. Use the initial password Changeme for the first login and change the
password as soon as possible to ensure account security.
NOTE

The WiFi name of the connected inverter is SUN2000-SN, which can be obtained from the
inverter label.

Figure 3-1 Connect to inventor

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 4


SDongleA-05
MODBUS TCP Guide 3 Operations

If you log in to the SUN2000 for the first time and do not change the WiFi
password, you can scan the WiFi QR code of the SUN2000 to connect to the WiFi
network.

Figure 3-2 Scan to upgrade

Step 4 Select a user name and enter the password (select installer, and enter the correct
password, which is 00000a by default) to log in to the operation console.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 5


SDongleA-05
MODBUS TCP Guide 3 Operations

Figure 3-3 Log in

Step 5 On the home page, select Settings.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 6


SDongleA-05
MODBUS TCP Guide 3 Operations

Figure 3-4 Home page

Step 6 On the Settings page, click Communication configuration. The Communication


configuration page is displayed.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 7


SDongleA-05
MODBUS TCP Guide 3 Operations

Figure 3-5 Settings

Figure 3-6 Communication configuration

Step 7 On the Communication configuration page, click Dongle parameter settings. The
Dongle parameter settings page is displayed.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 8


SDongleA-05
MODBUS TCP Guide 3 Operations

Figure 3-7 Dongle parameter settings

Step 8 On the Dongle parameter settings page, click Modbus-TCP.

Figure 3-8 Modbus TCP

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 9


SDongleA-05
MODBUS TCP Guide 3 Operations

NOTE

If the MODBUS TCP function is disabled, customer devices cannot access the network.
If the restriction function is enabled, you must configure a trustlist IP address (currently,
only one trustlist IP address is supported) so that only the client devices with the trustlist IP
address can access the network.
If unrestricted is enabled, all client devices on the same LAN can access the network, but
only one client device can access the network at a time.

----End

3.1.3 Troubleshooting
If Modbus TCP is not found in step 6, check whether the inverter version and app
version meet requirements.
If MODBUS TCP still cannot be used after the configuration is complete, check
whether the SDongle version meets the requirements.
.

Issue 01 (2021-11-07) Copyright © Huawei Technologies Co., Ltd. 10