Chapter-3 - Analysis of Earthquake Load Lecture-One
Chapter-3 - Analysis of Earthquake Load Lecture-One
STRUCTURAL DESIGN
CEng5123
Chapter Three: Analysis of Earthquake Load
Lecture One
Duresa Dubale (MSc.)
Contents
Introduction:
• A structure is a system of connected parts used to support a load.
• Safety • Economy
• Aesthetic • Environmental
• Serviceability
a) Building configuration
b) Construction materials
• That is, the distribution of masses and stiffness in the building and the
choice of load paths by which lateral loads will eventually reach the
ground.
1) Plan Irregularities
• The diaphragm acts as a wide flat beam that develops tension and
compression on its edges.
1) Plan Irregularities
2) Vertical Irregularities
2) Vertical Irregularities
• Thus, the upper storeys move as a single unit together and most of the
horizontal displacement of the building occur in the ground storey.
16-Jan-23 By: Duresa Dubale 27
Cont.
3.2.3.1 Building configuration
2) Vertical Irregularities
2) Vertical Irregularities
• A mass irregularity exists where the effective mass of any storey exceeds
150% of the effective mass of the adjacent storey.
• Massive roofs and heavy equipments rooms at upper floors are not
advisable as they may induced large inertia forces and cause collapse of
the structure during earthquake.
2) Vertical Irregularities
2) Vertical Irregularities
2) Vertical Irregularities
• The structure should have a complete and continuous path for transfer
of seismic forces i.e., floor- beams-columns and walls-foundation-
ground.
2) Vertical Irregularities
Fundamental Requirements
No collapse requirement
3) Special measures
• The shape of the elastic response spectrum is taken as being the same for
the two levels of seismic action for the no-collapse requirement (ultimate
limit state – design seismic action) and for the damage limitation
requirement.
• If the earthquakes that contribute most to the seismic hazard defined for the
site for the purpose of probabilistic hazard assessment have a surface-wave
magnitude, Ms, not greater than 5.5, it is recommended that the Type 2
spectrum is adopted.
• For the five ground types A, B, C, D and E the recommended values of the
parameters S, TB, TC and TD are given in Table 3.2 for the Type 1 Spectrum
and in Table 3.3 for the Type 2 Spectrum in ES EN 1998-1:2015.
𝑇𝐶 ≤ 𝑇 ≤ 𝑇𝐷
• 𝑎𝑔 = 𝛾𝐼 ∗ 𝑎𝑔𝑅
Where
𝛾𝐼 = Importance class
𝑎𝑔𝑅 = Reference peak ground acceleration which depends on seismic hazard map
𝒒 = 𝒒0 ∗ 𝒌𝒘 ≥ 1.5
Where;
• qo is the basic value of the behavior factor, dependent on the type of
the structural system and on its regularity in elevation.
• kw is the factor reflecting the prevailing failure mode in structural
systems with walls.
• Where:
• α1 is the value by which the horizontal seismic design action is
multiplied in order to first reach the flexural resistance in any
member in the structure, while all other design actions remain
constant;
• αu is the value by which the horizontal seismic design action is
multiplied, in order to form plastic hinges in several sections
sufficient for the development of overall structural instability, while
all other design actions remain constant. The factor αu may be from
a nonlinear static (pushover) global analysis.
• Where;
• αo is the prevailing aspect ratio of the walls of the structural
system.
• Where
✓TC is the upper limit of the period of the constant spectral
acceleration branch
✓T1 is fundamental period of time.
16-Jan-23 By: Duresa Dubale 72
Cont.
3.3.7 Lateral force method of analysis
a) The “lateral force method of analysis” for buildings meeting the
conditions
• For buildings with heights of up to 40 m the value of T1 (in s) may
be approximated by the following expression:
Example-1:
On Roof Slab
𝑇𝐶 ≤ 𝑇 ≤ 𝑇𝐷